Abb REM611, REB611, REU611, REF611 User Manual

Page 1
RELION® PROTECTION AND CONTROL
611 series
Operation Manual
Page 2
Page 3
Document ID: 1MRS757453
Issued: 2019-04-10
Revision: C
Product version: 2.0
Page 4
Copyright
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/relion
Page 5
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and information via a network interface which should be connected to a secure network. It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures (such as, but not limited to, installation of firewalls, application of authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the product and the network, its system and interface included, against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not liable for any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.
Page 7
Safety information
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected.
Non-observance can result in death, personal injury or substantial property damage.
Only a competent electrician is allowed to carry out the electrical installation.
National and local electrical safety regulations must always be followed.
The frame of the protection relay has to be carefully earthed.
When the plug-in unit has been detached from the case, do not touch the inside of the case. The relay case internals may contain high voltage potential and touching these may cause personal injury.
The protection relay contains components which are sensitive to electrostatic discharge. Unnecessary touching of electronic components must therefore be avoided.
Whenever changes are made in the protection relay, measures should be taken to avoid inadvertent tripping.
Page 8
Page 9

Table of contents

Table of contents
Section 1 Introduction.......................................................................7
This manual........................................................................................ 7
Intended audience.............................................................................. 7
Product documentation.......................................................................8
Product documentation set............................................................8
Document revision history............................................................. 8
Related documentation..................................................................9
Symbols and conventions...................................................................9
Symbols.........................................................................................9
Document conventions.................................................................. 9
Functions, codes and symbols.................................................... 10
Section 2 Environmental aspects...................................................15
Sustainable development................................................................. 15
Disposal of a protection relay........................................................... 15
Section 3 611 series overview........................................................17
Overview...........................................................................................17
Local HMI......................................................................................... 17
Display.........................................................................................18
LEDs............................................................................................19
Keypad........................................................................................ 20
Local HMI functionality................................................................ 22
Protection and alarm indication.............................................. 22
Parameter management ........................................................23
Front communication..............................................................24
Web HMI...........................................................................................24
Command buttons....................................................................... 26
Authorization.....................................................................................27
Audit trail......................................................................................28
Communication.................................................................................30
Self-healing Ethernet ring............................................................ 30
Ethernet redundancy................................................................... 31
Secure communication................................................................ 33
PCM600 tool.....................................................................................34
Connectivity packages.................................................................34
PCM600 and relay connectivity package version........................34
Section 4 Using the HMI.................................................................37
Using the local HMI.......................................................................... 37
611 series 1 Operation Manual
Page 10
Table of contents
Logging in....................................................................................37
Logging out..................................................................................38
Turning the display backlight on.................................................. 38
Selecting local or remote use...................................................... 39
Identifying the device...................................................................39
Identifying relay's IEC 61850 version..................................... 40
Adjusting the display contrast......................................................40
Changing the local HMI language............................................... 41
Changing display symbols...........................................................41
Changing setting visibility............................................................ 41
Navigating in the menu................................................................42
Menu structure....................................................................... 42
Scrolling the display............................................................... 43
Changing the default view...................................................... 43
Browsing setting values...............................................................43
Editing values.............................................................................. 44
Editing numerical values........................................................ 44
Editing string values............................................................... 46
Editing enumerated values.....................................................46
Committing settings..................................................................... 46
Clearing and acknowledging....................................................... 47
Using the local HMI help..............................................................48
Using the Web HMI.......................................................................... 48
Logging in....................................................................................48
Logging out..................................................................................49
Identifying device.........................................................................49
Navigating in menus.................................................................... 50
Menu structure....................................................................... 51
Showing parameters....................................................................52
Editing values.............................................................................. 55
Committing settings..................................................................... 58
Clearing and acknowledging....................................................... 60
Selecting programmable LEDs view............................................61
Selecting event view....................................................................62
Selecting disturbance records view............................................. 64
Saving disturbance records....................................................64
Triggering disturbance recorder manually..............................65
Deleting disturbance records..................................................66
Selecting phasor diagrams.......................................................... 66
Selecting fault records................................................................. 69
Selecting signal configuration......................................................71
Import and export of settings....................................................... 76
Exporting settings ..................................................................76
2 611 series
Operation Manual
Page 11
Table of contents
Importing settings .................................................................. 77
Exporting report summary........................................................... 79
Using Web HMI help....................................................................80
Section 5 IED operation ................................................................ 83
Normal operation.............................................................................. 83
Disturbance identification................................................................. 83
Disturbance recording triggering................................................. 84
Disturbance record analysis........................................................ 84
Disturbance reports..................................................................... 84
Relay self-supervision................................................................. 84
Relay parametrization.......................................................................85
Settings for relay functionality......................................................85
Settings for different operating conditions................................... 85
Section 6 Operating procedures.....................................................87
Monitoring.........................................................................................87
Indications................................................................................... 87
Monitoring indication messages............................................. 87
Monitoring an internal relay fault ........................................... 87
Monitoring condition monitoring data..................................... 88
Measured and calculated values................................................. 88
Measured values.................................................................... 88
Using the local HMI for monitoring......................................... 89
Recorded data............................................................................. 89
Creating disturbance recordings............................................ 89
Monitoring disturbance recorder data.....................................90
Controlling and reading of disturbance recorder data............ 90
Monitoring fault records..........................................................91
Monitoring events................................................................... 91
Remote monitoring...................................................................... 92
Monitoring protection relays remotely.................................... 92
Controlling........................................................................................ 92
Controlling via the control menu.................................................. 92
Controlling with the closing delay................................................ 93
Resetting IED................................................................................... 94
Clearing and acknowledging via the local HMI............................94
Changing the IED functionality......................................................... 95
Defining the setting group............................................................95
Activating a setting group....................................................... 95
Copying a setting group......................................................... 96
Browsing and editing setting group values.............................96
Activating programmable LEDs................................................... 97
Setting autoscroll delay............................................................... 98
611 series 3 Operation Manual
Page 12
Table of contents
Section 7 Troubleshooting .............................................................99
Fault tracing......................................................................................99
Identifying hardware errors..........................................................99
Identifying runtime errors.............................................................99
Identifying communication errors.................................................99
Checking front communication link operation.........................99
Checking time synchronization.............................................100
Running the display test............................................................ 100
Indication messages.......................................................................100
Internal faults.............................................................................100
Warnings................................................................................... 102
Correction procedures.................................................................... 103
Rebooting the software..............................................................103
Restoring factory settings.......................................................... 103
Setting passwords..................................................................... 104
Identifying relay application problems....................................... 104
Inspecting wiring...................................................................105
Sample data interruptions.................................................... 105
Section 8 Commissioning.............................................................107
Commissioning checklist................................................................ 107
Checking the installation.................................................................107
Checking of the power supply................................................... 107
Checking CT circuits..................................................................108
Checking VT circuits..................................................................108
Checking binary input and output circuits..................................109
Checking binary input circuits...............................................109
Checking binary output circuits............................................ 109
Authorizations.................................................................................110
User authorization..................................................................... 110
Setting IED and communication..................................................... 111
Setting the communication between protection relays and
PCM600.....................................................................................111
Communication link options between PCM600 and
protection relays................................................................... 111
Communication settings............................................................ 112
Serial communication ports and drivers............................... 113
Serial link diagnostics and monitoring.................................. 114
Defining Ethernet port settings............................................. 116
Defining serial port settings.................................................. 116
Setting communication protocol parameters........................ 117
Connecting jumper connectors.............................................117
Setting the local HMI................................................................. 117
4 611 series
Operation Manual
Page 13
Table of contents
Changing the local HMI language........................................ 117
Adjusting the display contrast...............................................117
Changing display symbols....................................................118
Changing the default view.................................................... 118
Setting the system time and time synchronization............... 118
Setting IED parameters............................................................. 120
Defining setting groups.........................................................120
Relay parametrization.......................................................... 122
Defining disturbance recorder channel settings................... 123
Configuring analog inputs.....................................................123
Testing protection relay operation.................................................. 123
Selecting the IED test mode...................................................... 123
Testing the digital I/O interface..................................................124
Testing functions....................................................................... 124
Selecting the internal fault test.................................................. 125
Selecting the IED blocked or IED test and blocked mode......... 125
ABB Product Data Registration...................................................... 126
Section 9 Glossary....................................................................... 127
611 series 5 Operation Manual
Page 14
6
Page 15
1MRS757453 C Section 1

Introduction

Section 1 Introduction

1.1 This manual

The operation manual contains instructions on how to operate the protection relay once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the relay. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault.

1.2 Intended audience

This manual addresses the operator, who operates the protection relay on a daily basis.
The operator must be trained in and have a basic knowledge of how to operate protection equipment. The manual contains terms and expressions commonly used to describe this kind of equipment.
611 series 7 Operation Manual
Page 16
Planning &
purchase
Engineering
Installation
Commissioning
Operation
Maintenance
Decommissioning,
deinstallation & disposal
Quick start guide Quick installation guide Brochure Product guide Operation manual Installation manual Connection diagram Engineering manual Technical manual Application manual Communication protocol manual IEC 61850 engineering guide Point list manual Cyber security deployment guideline
Section 1 1MRS757453 C Introduction

1.3 Product documentation

1.3.1 Product documentation set

1.3.2 Document revision history

8 611 series
GUID-0777AFDA-CADF-4AA9-946E-F6A856BDF75E V1 EN
Figure 1: The intended use of manuals in different lifecycles
Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion.
Document revision/date
A/2011-11-18 1.0 First release
B/2016-02-22 2.0 Content updated to correspond to the
C/2019-04-10 2.0 Content updated
Product series version History
product series version
Download the latest documents from the ABB Web site
http://www.abb.com/substationautomation.
Operation Manual
Page 17
1MRS757453 C Section 1
Introduction

1.3.3 Related documentation

Product series- and product-specific manuals can be downloaded from the ABB Web
http://www.abb.com/substationautomation.
site

1.4 Symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazard which could result in electrical shock.
The warning icon indicates the presence of a hazard which could result in personal injury.
The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.

1.4.2 Document conventions

A particular convention may not be used in this manual.
Abbreviations and acronyms are spelled out in the glossary. The glossary also contains definitions of important terms.
Push button navigation in the LHMI menu structure is presented by using the push button icons.
611 series 9 Operation Manual
Page 18
Section 1 1MRS757453 C Introduction
To navigate between the options, use and .
Menu paths are presented in bold. Select Main menu/Settings.
WHMI menu names are presented in bold. Click Information in the WHMI menu structure.
LHMI messages are shown in Courier font. To save the changes in nonvolatile memory, select Yes and press
.
Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting.
Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off".
Input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE.
This document assumes that the parameter setting visibility is "Advanced".

1.4.3 Functions, codes and symbols

All available functions are listed in the table. All of them may not be applicable to all products.
Table 1: Functions included in the relays
Function
Protection
Three-phase non-directional overcurrent protection, low stage, instance 1
Three-phase non-directional overcurrent protection, high stage, instance 1
Three-phase non-directional overcurrent protection, high stage, instance 2
Three-phase non-directional overcurrent protection, instantaneous stage, instance 1
Non-directional earth-fault protection, low stage, instance 1
Non-directional earth-fault protection, low stage, instance 2
Non-directional earth-fault protection, high stage, instance 1
Non-directional earth-fault protection, instantaneous stage
Three-phase directional overcurrent protection, low stage, instance 1
Three-phase directional overcurrent protection, low stage, instance 2
Table continues on next page
IEC 61850 IEC 60617 IEC-ANSI
PHLPTOC1
PHHPTOC1
PHHPTOC2
PHIPTOC1
EFLPTOC1 Io> (1) 51N-1 (1)
EFLPTOC2 Io> (2) 51N-1 (2)
EFHPTOC1 Io>> (1) 51N-2 (1)
EFIPTOC1 Io>>> 50N/51N
DPHLPDOC1 3I> -> (1) 67-1(1)
DPHLPDOC2 3I> -> (2) 67-1(2)
3I> (1) 51P-1 (1)
3I>> (1) 51P-2 (1)
3I>> (2) 51P-2 (2)
3I>>> (1) 50P/51P (1)
10 611 series
Operation Manual
Page 19
1MRS757453 C Section 1
Introduction
Function IEC 61850 IEC 60617 IEC-ANSI
Three-phase directional overcurrent protection, high stage, instance 1
Directional earth-fault protection, low stage, instance 1
Directional earth-fault protection, low stage, instance 2
Directional earth-fault protection, high stage
Transient/intermittent earth-fault protection
Non-directional (cross-country) earth fault protection, using calculated Io
Negative-sequence overcurrent protection, instance 1
Negative-sequence overcurrent protection, instance 2
Negative-sequence overcurrent protection for machines, instance 1
Negative-sequence overcurrent protection for machines, instance 2
Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD
Residual overvoltage protection, instance 1
Residual overvoltage protection, instance 2
Residual overvoltage protection, instance 3
Three-phase undervoltage protection, instance 1
Three-phase undervoltage protection, instance 2
Three-phase undervoltage protection, instance 3
Three-phase overvoltage protection, instance 1
Three-phase overvoltage protection, instance 2
Three-phase overvoltage protection, instance 3
Positive-sequence undervoltage protection, instance 1
Positive-sequence undervoltage protection, instance 2
Negative-sequence overvoltage protection, instance 1
Negative-sequence overvoltage protection, instance 2
Frequency protection, instance 1 FRPFRQ1 f>/f<,df/dt (1) 81(1)
Table continues on next page
DPHHPDOC1 3I>> -> (1) 67-2(1)
DEFLPDEF1 Io> -> (1) 67N-1 (1)
DEFLPDEF2 Io> -> (2) 67N-1 (2)
DEFHPDEF1 Io>> -> 67N-2
INTRPTEF1 Io> -> IEF 67NIEF
EFHPTOC1 Io>> (1) 51N-2 (1)
NSPTOC1 I2> (1) 46 (1)
NSPTOC2 I2> (2) 46 (2)
MNSPTOC1 I2>M (1) 46M (1)
MNSPTOC2 I2>M (2) 46M (2)
ROVPTOV1 Uo> (1) 59G (1)
ROVPTOV2 Uo> (2) 59G (2)
ROVPTOV3 Uo> (3) 59G (3)
PHPTUV1 3U< (1) 27(1)
PHPTUV2 3U< (2) 27(2)
PHPTUV3 3U< (3) 27(3)
PHPTOV1 3U> (1) 59(1)
PHPTOV2 3U> (2) 59(2)
PHPTOV3 3U> (3) 59(3)
PSPTUV1 U1< (1) 47U+(1)
PSPTUV2 U1< (2) 47U+(2)
NSPTOV1 U2> (1) 47O-(1)
NSPTOV2 U2> (2) 47O-(2)
611 series 11 Operation Manual
Page 20
Section 1 1MRS757453 C Introduction
Function IEC 61850 IEC 60617 IEC-ANSI
Frequency protection, instance 2 FRPFRQ2 f>/f<,df/dt (2) 81(2)
Three-phase thermal protection for feeders, cables and distribution transformers
Loss of load supervision LOFLPTUC1 3I< 37
Motor load jam protection JAMPTOC1 Ist> 51LR
Motor start-up supervision STTPMSU1 Is2t n< 49,66,48,51LR
Phase reversal protection PREVPTOC1 I2>> 46R
Thermal overload protection for motors
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
High-impedance differential protection for phase A, instance 1
High-impedance differential protection for phase B, instance 2
High-impedance differential protection for phase C, instance 3
Switch onto fault CBPSOF1 SOTF SOTF
Other
Input switch group ISWGAPC ISWGAPC ISWGAPC
Output switch group OSWGAPC OSWGAPC OSWGAPC
Selector SELGAPC SELGAPC SELGAPC
Minimum pulse timer (2 pcs) TPGAPC TP TP
Minimum pulse timer (2 pcs, second resolution), instance 1
Move (8 pcs), instance 1 MVGAPC MV (1) MV (1)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Emergency start-up ESMGAPC1 ESTART ESTART
Autoreclosing DARREC1 O -> I 79
Condition monitoring and supervision
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Runtime counter for machines and devices
Phase segregated CT supervision function for phase A, instance 1
Phase segregated CT supervision function for phase B, instance 2
Phase segregated CT supervision function for phase C, instance 3
Table continues on next page
T1PTTR1
MPTTR1 3Ith>M 49M
HIAPDIF1 dHi>(1) 87(1)
HIBPDIF1 dHi>(2) 87(2)
HICPDIF1 dHi>(3) 87(3)
TPSGAPC TPS (1) TPS (1)
MDSOPT1 OPTS OPTM
HZCCASPVC1 MCS 1I(1) MCS 1I(1)
HZCCBSPVC1 MCS 1I(2) MCS 1I(2)
HZCCCSPVC1 MCS 1I(3) MCS 1I(3)
3Ith>F 49F
12 611 series
Operation Manual
Page 21
1MRS757453 C Section 1
Introduction
Function IEC 61850 IEC 60617 IEC-ANSI
Logging
Disturbance recorder RDRE1 DR (1) DFR(1)
Fault recorder FLTRFRC1 - FR
Measurement
Three-phase current measurement, instance 1
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 1
Three-phase voltage measurement, instance 1
Three-phase voltage measurement, instance 2
Sequence voltage measurement, instance 1
Residual voltage measurement RESVMMXU1 Uo Vn
Frequency measurement, instance 1 FMMXU1 f f
Three-phase power and energy measurement, instance 1
1)
CMMXU1 3I 3I
RESCMMXU1 Io In
VMMXU1 3U 3U
VMMXU2 3U(B) 3U(B)
VSMSQI1 U1, U2, U0 U1, U2, U0
PEMMXU1 P, E P, E
1) In REB611, CMMXU is used for measuring differential phase currents
611 series 13 Operation Manual
Page 22
14
Page 23
1MRS757453 C Section 2

Environmental aspects

Section 2 Environmental aspects

2.1 Sustainable development

Sustainability has been taken into account from the beginning of the product design including the pro-environmental manufacturing process, long life time, operation reliability and disposing of the protection relay.
The choice of materials and the suppliers have been made according to the EU RoHS directive (2002/95/EC). This directive limits the use of hazardous substances which are the following:
Table 2: Maximum concentration values by weight per homogeneous material
Substance Proposed maximum concentration
Lead - Pb 0.1%
Mercury - Hg 0.1%
Cadmium - Cd 0.01%
Hexavalent Chromium Cr (VI) 0.1%
Polybrominated biphenyls - PBB 0.1%
Polybrominated diphenyl ethers - PBDE 0.1%
Operational reliability and long life time have been assured with extensive testing during the design and manufacturing processes. Moreover, long life time is supported by maintenance and repair services as well as by the availability of spare parts.
Design and manufacturing have been done under a certified environmental system. The effectiveness of the environmental system is constantly evaluated by an external auditing body. We follow environmental rules and regulations systematically to evaluate their effect on our products and processes.

2.2 Disposal of a protection relay

Definitions and regulations of hazardous materials are country-specific and change when the knowledge of materials increases. The materials used in this product are typical for electric and electronic devices.
All parts used in this product are recyclable. When disposing of a protection relay or its parts contact a local waste handler who is authorized and specialized in disposing of electronic waste. These handlers can sort the material by using dedicated sorting processes and dispose of the product according to the local requirements.
611 series 15 Operation Manual
Page 24
Section 2 1MRS757453 C Environmental aspects
Table 3: Materials of the protection relay parts
Protection relay Parts Material
Case Metallic plates, parts and screws Steel
Plastic parts
Electronics plug in module Various
Plug-in unit Electronics plug in modules Various
Electronics LHMI module Various
Plastic parts
Metallic parts Aluminium
Package Box Cardboard
Attached material Manuals Paper
1) Polycarbonate
2) Liquid crystal polymer
3) Polybutylene terephthalate
4) Polyamide
PC1), LCP
PC, PBT3), LCP, PA
2)
4)
16 611 series
Operation Manual
Page 25
1MRS757453 C Section 3

611 series overview

Section 3 611 series overview

3.1 Overview

The 611 series is part of ABB’s Relion® product family. The 611 series protection relays offer functionality within basic protection and control configurations. There are product variants for feeder, motor, busbar and voltage protection applications. The relays, characterized by their compactness and withdrawable-unit design, are designed for most utility substations and industrial power systems including radial, looped and meshed distribution networks that may also involve distributed power generation.
The 611 series relays support the Edition 1 and Edition 2 versions of the IEC 61850 standard for communication and interoperability of substation automation devices, including fast GOOSE messaging. The 611 series relays are able to use IEC 61850 and Modbus® communication protocols simultaneously. The relays also support the parallel redundancy protocol PRP and the high-availability seamless redundancy HSR protocol. IEEE 1588 v2 is available for high-accuracy time synchronization in all variants with an optional redundant Ethernet communication module.

3.2 Local HMI

The LHMI is used for setting, monitoring and controlling the protection relay. The LHMI comprises the display, buttons, LED indicators and communication port.
611 series 17 Operation Manual
Page 26
REF611
Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure
Section 3 1MRS757453 C 611 series overview
GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN
Figure 2: Example of the LHMI

3.2.1 Display

The LHMI includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size.
Table 4: Small display
Character size
Small, mono-spaced (6 × 12 pixels) 5 20
Large, variable width (13 × 14 pixels) 3 8 or more
1) Depending on the selected language
The display view is divided into four basic areas.
1)
Rows in the view Characters per row
18 611 series
Operation Manual
Page 27
1
3
4
2
1MRS757453 C Section 3
611 series overview
GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN
Figure 3: Display layout
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
The header area at the top of the display view shows the current location in the menu structure.
The icon area at the upper right corner of the display shows the current action or user level. Current action is indicated by the following characters.
U: Font/Firmware is being updated
S: Parameters are being stored
!: Warning and/or indication
Current user level is indicated by the following characters.
V: Viewer
O: Operator
E: Engineer
A: Administrator
The content area shows the menu content.
If the menu contains more rows than the display can show at a time, a scroll bar is displayed on the right.
The display is updated either cyclically or based on changes in the source data such as parameters or events.

3.2.2 LEDs

The LHMI includes three protection indicators above the display: Ready, Start and
611 series 19 Operation Manual
Trip.
Page 28
Section 3 1MRS757453 C 611 series overview
There are also 8 programmable LEDs on front of the LHMI. The LEDs can be configured with the LHMI, WHMI or PCM600.

3.2.3 Keypad

The LHMI keypad contains push buttons which are used to navigate in different views or menus. With the push buttons you can give open or close commands to one object in the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The push buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.
GUID-A9613A2B-0084-4D1D-A4E3-D04E72A1728E V1 EN
Figure 4: LHMI keypad with object control, navigation and command push
buttons and RJ-45 communication port
1
Close
2 Escape
3 Up
4 Enter
5 Uplink LED
6 Communication LED
7 Open
8 Left
9 Down
10 Right
11 Remote/Local
12 Help
13 Communication port
20 611 series
Operation Manual
Page 29
1MRS757453 C Section 3
611 series overview
Object control
If the control position of the IED is set to local with the R/L button, the IED can be controlled using the object control buttons.
Table 5: Object control push buttons
Name
Close
Open
Navigation
The arrow buttons are used for navigation. To scroll information, press the arrow button several times or simply keep it pressed down.
Table 6: Navigation push buttons
Name Description
ESC
Description
Closing the object.
Opening the object.
Leaving setting mode without saving the values.
Cancelling certain actions.
• Adjusting the display contrast in combination with or .
• Changing the language in combination with .
• Inserting a space in combination with
Clearing indications and LEDs. The first three-second press clears the indications. The second three-second press clears the programmable LEDs. Requires appropriate user rights.
when editing a string.
Enter
Up
Down
Left
Right
Entering parameter setting mode.
Confirming a new value of a setting parameter.
Moving up and down in menus.
Scrolling active digits of a parameter when entering a new setting value.
Moving left and right in menus.
Changing the active digit of a parameter when entering a new setting value.
• Deleting a character when editing a string by pressing .
• Logging out, when the user is currently logged in. Press for three
seconds in the main menu.
611 series 21 Operation Manual
Page 30
Section 3 1MRS757453 C 611 series overview
Commands
Table 7: Command push buttons
Name
R/L
Description
Changing the control position (remote or local) of the device.
When the R LED is lit, remote control is enabled and local control disabled.
When the L LED is lit, local control is enabled and remote control disabled.
When none of the LEDs are lit, both control positions are disabled.
Help
Showing context sensitive help messages.

3.2.4 Local HMI functionality

3.2.4.1 Protection and alarm indication
Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
Table 8: Ready LED
LED state
Off Auxiliary supply voltage is disconnected.
On Normal operation.
Flashing Internal fault has occurred or the protection relay is in test mode. Internal
Table 9: Start LED
LED state
Off Normal operation.
On A protection function has started and an indication message is displayed.
Description
faults are accompanied by an indication message.
Description
If several protection functions start within a short time, the last start is indicated on the display.
Flashing
22 611 series
A protection function is blocked or the protection relay is in the test and blocked mode.
The blocking indication disappears when the blocking is removed or when the protection function is reset.
Operation Manual
Page 31
1MRS757453 C Section 3
611 series overview
Table 10: Trip LED
LED state Description
Off Normal operation.
On A protection function has tripped and an indication message is displayed.
The trip indication is latching and must be reset via communication.
If several protection functions trip within a short time, the last trip is indicated on the display.
Alarm indicators
The 8 matrix programmable LEDs are used for alarm indication.
Table 11: Alarm indications
LED state Description
Off Normal operation. All activation signals are off.
On Non-latched mode: activation signal is still on.
Latched mode: activation signal is still on, or it is off but has not been acknowledged.
Latched flashing mode: activation signal is still on but has been acknowledged.
Flashing
Non-latched flashing mode: activation signal is still on.
Latched flashing mode: activation signal is still on, or it is off but has
3.2.4.2 Parameter management
The LHMI is used to access the relay parameters. Three types of parameters can be read and written.
Numerical values
String values
Enumerated values
Numerical values are presented either in integer or in decimal format with minimum and maximum values. Character strings can be edited character by character. Enumerated values have a predefined set of selectable values.
Changing the function block on or off affects the visibility of its parameters in the menu.
not been acknowledged.
Changing the value of certain relay parameters affects the visibility or range of other parameters in the menu. This indicates which parameters or parameter values become obsolete due to the change.
611 series 23 Operation Manual
Page 32
2
1
Section 3 1MRS757453 C 611 series overview
The relay changes the visibility or range of these parameters immediately even before the changed values have been committed.
Some parameters may be hidden because the function is off or the setting visibility is set to “basic” instead of “advanced”.
3.2.4.3 Front communication
The RJ-45 port in the LHMI enables front communication. Two LEDs are located above the communication port.
The green uplink LED on the left is lit when the cable is successfully connected to the port.
The yellow communication LED on the right flashes when the protection relay communicates with the connected device.
A070816 V2 EN
Figure 5: RJ-45 communication port and indication LEDs
1
Uplink LED
2 Communication LED
When a computer is connected to the protection relay, the relay's DHCP server for the front interface assigns an IP address to the computer. The fixed IP address for the front port is 192.168.0.254.

3.3 Web HMI

The WHMI allows secure access to the protection relay via a Web browser. When the Secure Communication parameter in the protection relay is activated, the Web server is forced to take a secured (HTTPS) connection to WHMI using TLS encryption.The WHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.
24 611 series
Operation Manual
Page 33
1MRS757453 C Section 3
611 series overview
WHMI is enabled by default. To disable the WHMI, select Main Menu/Configuration/HMI/Web HMI mode via the LHMI. Reboot
the protection relay for the change to take effect.
WHMI offers several functions.
Programmable LEDs and event lists
System supervision
Parameter settings
Measurement display
Disturbance records
Fault records
Phasor diagram
Signal configuration
Importing/Exporting parameters
Report summary
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V2 EN
Figure 6: Example view of the WHMI
The WHMI can be accessed locally and remotely.
Locally by connecting the laptop to the protection relay via the front communication port.
Remotely over LAN/WAN.
611 series 25 Operation Manual
Page 34
Section 3 1MRS757453 C 611 series overview

3.3.1 Command buttons

Command buttons can be used to edit parameters and control information via the WHMI.
Table 12: Command buttons
Name Description
Enabling parameter editing
Disabling parameter editing
Writing parameters to the protection relay
Refreshing parameter values
Printing out parameters
Committing changes to protection relay's nonvolatile flash memory
Rejecting changes
Showing context sensitive help messages
Error icon
Clearing events
Triggering the disturbance recorder manually
Saving values to TXT or CSV file format
Freezing the values so that updates are not displayed
Receiving continuous updates to the monitoring view
Deleting the disturbance record
Deleting all disturbance records
Saving the disturbance record files
Viewing all fault records
Clearing all fault records
Importing settings
Exporting settings
Table continues on next page
26 611 series
Operation Manual
Page 35
1MRS757453 C Section 3
611 series overview
Name Description
Selecting all
Clearing all selections
Refreshing the parameter list view

3.4 Authorization

Four user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords.
The default passwords in the protection relay delivered from the factory can be changed with Administrator user rights.
User authorization is disabled by default for the LHMI and can be enabled with the Local override parameter via the LHMI path Main Menu/Configuration/Authorization/Passwords. WHMI always requires authentication.
Table 13: Predefined user categories
Username
VIEWER Read only access
OPERATOR
ENGINEER
ADMINISTRATOR
User rights
Selecting remote or local state with
Changing setting groups
Controlling
Clearing indications
Changing settings
Clearing event list
Clearing disturbance records
Changing system settings such as IP address, serial baud rate or disturbance recorder settings
Setting the protection relay to test mode
Selecting language
All listed above
Changing password
Factory default activation
(only locally)
For user authorization for PCM600, see PCM600 documentation.
611 series 27 Operation Manual
Page 36
Section 3 1MRS757453 C 611 series overview

3.4.1 Audit trail

The protection relay offers a large set of event-logging functions. Critical system and protection relay security-related events are logged to a separate nonvolatile audit trail for the administrator.
Audit trail is a chronological record of system activities that allows the reconstruction and examination of the sequence of system and security-related events and changes in the protection relay. Both audit trail events and process related events can be examined and analyzed in a consistent method with the help of Event List in LHMI and WHMI and Event Viewer in PCM600.
The protection relay stores 2048 audit trail events to the nonvolatile audit trail. Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit trail and event list work according to the FIFO principle. Nonvolatile memory is based on a memory type which does not need battery backup nor regular component change to maintain the memory storage.
Audit trail events related to user authorization (login, logout, violation remote and violation local) are defined according to the selected set of requirements from IEEE
1686. The logging is based on predefined user names or user categories. The user audit trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.
Table 14: Audit trail events
Audit trail event
Configuration change Configuration files changed
Firmware change Firmware changed
Firmware change fail Firmware change failed
Attached to retrofit test case Unit has been attached to retrofit case
Removed from retrofit test case Removed from retrofit test case
Setting group remote User changed setting group remotely
Setting group local User changed setting group locally
Control remote DPC object control remote
Control local DPC object control local
Test on Test mode on
Test off Test mode off
Reset trips Reset latched trips (TRPPTRC*)
Setting commit Settings have been changed
Time change Time changed directly by the user. Note that this is not used
View audit log
Login Successful login from IEC 61850-8-1 (MMS), WHMI, FTP or
Logout Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP or
Table continues on next page
Description
when the protection relay is synchronised properly by the appropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).
Administrator accessed audit trail
LHMI.
LHMI.
28 611 series
Operation Manual
Page 37
1MRS757453 C Section 3
611 series overview
Audit trail event Description
Password change Password changed
Firmware reset Reset issued by user or tool
Audit overflow Too many audit events in the time period
Violation remote Unsuccessful login attempt from IEC 61850-8-1 (MMS),
Violation local Unsuccessful login attempt from IEC 61850-8-1 (MMS),
PCM600 Event Viewer can be used to view the audit trail events and process related events. Audit trail events are visible through dedicated Security events view. Since only the administrator has the right to read audit trail, authorization must be used in PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data. Audit trail events can be configured to be visible also in LHMI/WHMI Event list together with process related events.
WHMI, FTP or LHMI.
WHMI, FTP or LHMI.
To expose the audit trail events through Event list, define the
Authority logging level parameter via Configuration/ Authorization/Security. This exposes audit trail events to all users.
Table 15: Comparison of authority logging levels
Audit trail event
Configuration change
Firmware change
Firmware change fail
Attached to retrofit test case
Removed from retrofit test case
Setting group remote
Setting group local
Control remote
Control local
Test on
Test off
Reset trips
Setting commit
Time change
View audit log
Login
Table continues on next page
None
Configurati on change
Authority logging level
Setting group
Setting group, control
Settings edit
All
611 series 29 Operation Manual
Page 38
Section 3 1MRS757453 C 611 series overview
Audit trail event Authority logging level
Logout
Password change
Firmware reset
Violation local
Violation remote

3.5 Communication

The protection relay supports a range of communication protocols including IEC 61850 and Modbus®. Operational information and controls are available through
these protocols. However, some communication functionality, for example, horizontal communication between the protection relays, is only enabled by the IEC 61850 communication protocol.
The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC 61850 protocol. Disturbance recordings are available to any Ethernet-based application in the IEC 60255-24 standard COMTRADE file format. The protection relay can send and receive binary signals from other devices (so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile, where the highest performance class with a total transmission time of 3 ms is supported. The protection relay meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard.
The protection relay can support five simultaneous clients. If PCM600 reserves one client connection, only four client connections are left, for example, for IEC 61850 and Modbus.
All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The protection relay can be connected to Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fiber-optic LC connector (100Base-FX). An optional serial interface is available for RS-485 communication.

3.5.1 Self-healing Ethernet ring

For the correct operation of self-healing loop topology, it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches. Otherwise, connecting the loop topology can cause problems to the network. The protection relay itself does not support link-down detection or RSTP. The ring recovery process is based on the aging of the MAC addresses, and the link­up/link-down events can cause temporary breaks in communication. For a better performance of the self-healing loop, it is recommended that the external switch
30 611 series
Operation Manual
Page 39
Managed Ethernet switch with RSTP support
Managed Ethernet switch
with RSTP support
Client A Client B
Network Network
1MRS757453 C Section 3
611 series overview
furthest from the protection relay loop is assigned as the root switch (bridge priority = 0) and the bridge priority increases towards the protection relay loop. The end links of the protection relay loop can be attached to the same external switch or to two adjacent external switches. A self-healing Ethernet ring requires a communication module with at least two Ethernet interfaces for all protection relays.
GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V2 EN
Figure 7: Self-healing Ethernet ring solution

3.5.2 Ethernet redundancy

IEC 61850 specifies a network redundancy scheme that improves the system availability for substation communication. It is based on two complementary protocols defined in the IEC 62439-3:2012 standard: parallel redundancy protocol PRP and high-availability seamless redundancy HSR protocol. Both protocols rely on the duplication of all transmitted information via two Ethernet ports for one logical network connection. Therefore, both are able to overcome the failure of a link or switch with a zero-switchover time, thus fulfilling the stringent real-time requirements for the substation automation horizontal communication and time synchronization.
PRP specifies that each device is connected in parallel to two local area networks. HSR applies the PRP principle to rings and to the rings of rings to achieve cost­effective redundancy. Thus, each device incorporates a switch element that forwards frames from port to port. The HSR/PRP option is available for all 611 series protection relays.
IEC 62439-3:2012 cancels and replaces the first edition published in
2010. These standard versions are also referred to as IEC 62439-3
611 series 31 Operation Manual
Page 40
Managed
Ethernet switch
IEC 61850 PRP
Managed
Ethernet switch
Section 3 1MRS757453 C 611 series overview
Edition 1 and IEC 62439-3 Edition 2. The protection relay supports IEC 62439-3:2012 and it is not compatible with IEC 62439-3:2010.
PRP
Each PRP node, called a double attached node with PRP (DAN), is attached to two independent LANs operated in parallel. These parallel networks in PRP are called LAN A and LAN B. The networks are completely separated to ensure failure independence, and they can have different topologies. Both networks operate in parallel, thus providing zero-time recovery and continuous checking of redundancy to avoid communication failures. Non-PRP nodes, called single attached nodes (SANs), are either attached to one network only (and can therefore communicate only with DANs and SANs attached to the same network), or are attached through a redundancy box, a device that behaves like a DAN.
GUID-AA005F1B-A30B-48F6-84F4-A108F58615A2 V1 EN
Figure 8: PRP solution
In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRP networks, LAN A or LAN B, it is recommended to use a redundancy box device or an Ethernet switch with similar functionality between the PRP network and SAN to remove additional PRP information from the Ethernet frames. In some cases, default PC workstation adapters are not able to handle the maximum-length Ethernet frames with the PRP trailer.
There are different alternative ways to connect a laptop or a workstation as SAN to a PRP network.
32 611 series
Operation Manual
Page 41
IEC 61850 HSR
Ethernet
switch
Redundancy
box
Redundancy
box
Redundancy
box
X
X
Unicast tr affic
Message is recognized as a
duplicat e and is
immediate ly forwarded
X
Sending de vice removes
the mes sage from the ring
Devices not supporting HSR
Sender
Receiver
1MRS757453 C Section 3
611 series overview
Via an external redundancy box (RedBox) or a switch capable of connecting to PRP and normal networks
By connecting the node directly to LAN A or LAN B as SAN
By connecting the node to the protection relay's interlink port
HSR
HSR applies the PRP principle of parallel operation to a single ring, treating the two directions as two virtual LANs. For each frame sent, a node, DAN, sends two frames, one over each port. Both frames circulate in opposite directions over the ring and each node forwards the frames it receives, from one port to the other. When the originating node receives a frame sent to itself, it discards that to avoid loops; therefore, no ring protocol is needed. Individually attached nodes, SANs, such as laptops and printers, must be attached through a “redundancy box” that acts as a ring element. For example, a 615 or 620 series protection relay with HSR support can be used as a redundancy box.
GUID-B24F8609-0E74-4318-8168-A6E7FCD0B313 V1 EN
Figure 9: HSR solution
3.5.3 Secure communication
The protection relay supports secure communication for WHMI and file transfer protocol. If the Secure Communication parameter is activated, protocols require TLS based encryption method support from the clients. In this case WHMI must be

Secure Communication is “ON”.

connected from a Web browser using the HTTPS protocol and in case of file transfer the client must use FTPS.
As a factory default,
611 series 33 Operation Manual
Page 42
Section 3 1MRS757453 C 611 series overview

3.6 PCM600 tool

Protection and Control IED Manager PCM600 offers all the necessary functionality to work throughout all stages of the protection relay life cycle.
Planning
Engineering
Commissioning
Operation and disturbance handling
Functional analysis
The whole substation configuration can be controlled and different tasks and functions can be performed with the individual tool components. PCM600 can operate with many different topologies, depending on the customer needs.
For more information, see the PCM600 documentation.

3.6.1 Connectivity packages

A connectivity package is a software component that consists of executable code and data which enables system tools to communicate with a protection relay. Connectivity packages are used to create configuration structures in PCM600. The latest PCM600 and connectivity packages are backward compatible with older protection relay versions.
A connectivity package includes all the data which is used to describe the protection relay. For example, it contains a list of the existing parameters, data format used, units, setting range, access rights and visibility of the parameters. In addition, it contains code which allows software packages that use the connectivity package to properly communicate with the protection relay. It also supports localization of text even when it is read from the protection relay in a standard format such as COMTRADE.
Update Manager is a tool that helps in defining the right connectivity package versions for different system products and tools. Update Manager is included with the products that use connectivity packages.

3.6.2 PCM600 and relay connectivity package version

Protection and Control IED Manager PCM600 Ver.2.7 or later
REB611 Connectivity Package Ver.2.0 or later
REF611 Connectivity Package Ver.2.0 or later
REM611 Connectivity Package Ver.2.0 or later
REU611 Connectivity Package Ver.2.0 or later
34 611 series
Operation Manual
Page 43
1MRS757453 C Section 3
611 series overview
Download connectivity packages from the ABB Web site
http://www.abb.com/substationautomation or directly with Update
Manager in PCM600.
611 series 35 Operation Manual
Page 44
36
Page 45
1MRS757453 C Section 4

Using the HMI

Section 4 Using the HMI

4.1 Using the local HMI

To use the LHMI, logging in and authorization are required. Password authorization is disabled by default and can be enabled via the LHMI.
To enable password authorization, select Main menu/ Configuration/Authorization/Passwords. Set the Local override parameter to “False”.

4.1.1 Logging in

1.
Press
2.
Press or to select the user level.
GUID-7B40EC73-2324-4E9A-9DF7-CC742744EC1B V1 EN
Figure 10: Selecting access level
3.
Confirm the selection with .
4. Enter the password when prompted digit by digit.
Activate the digit to be entered with and .
Enter the character with and .
or or to activate the login procedure.
GUID-C8BDDF55-EB8B-42AD-8184-3939BF51B4C4 V1 EN
Figure 11: Entering password
5.
Press to confirm the login.
To cancel the procedure, press .
611 series 37 Operation Manual
Page 46
Section 4 1MRS757453 C Using the HMI
GUID-39601B65-8E32-49F7-AE8A-C16B71770D69 V1 EN
Figure 12: Error message indicating wrong password
The current user level is shown on the display's upper right corner in the icon area.

4.1.2 Logging out

An automatic logout occurs 30 seconds after the backlight timeout.
1.
Press for three seconds in the main menu.
2.
To confirm logout, select Yes and press
GUID-65BD2160-B3FF-4FD0-8028-C5F0CB67FE54 V1 EN
Figure 13: Logging out
To cancel logout, press .

4.1.3 Turning the display backlight on

The display backlight is normally off. It turns on during the display test at power up.
To turn on the backlight manually, press any LHMI push button. The backlight turns on and the panel is ready for further operations.
If the panel has not been used for a predefined timeout period, the backlight is switched off. The user is logged out from the current user level 30 seconds after the display backlight has turned off.
.
The display returns to the default view and all unconfirmed operations such as parameter editing and breaker selection are cancelled.
38 611 series
Operation Manual
Page 47
1MRS757453 C Section 4
Using the HMI
Change the backlight timeout period in Main menu/ Configuration/HMI/Backlight timeout.

4.1.4 Selecting local or remote use

The control position of the protection relay can be changed with the R/L button. In local position primary equipment, such as circuit breakers or disconnectors, can be controlled via the LHMI. In remote position, control operations are possible only from a higher level, that is from a control center.
Press for two seconds.
When the L LED is lit, local control is enabled and remote control disabled.
When the R LED is lit, remote control is enabled and local control disabled.
When neither of the LEDs is lit, both control positions are disabled.
When the L and R LEDs are lit, both remote and local control are enabled.
By default, the control position cannot be local and remote simultaneously. See the technical manual for more information on local and remote control.
To control the protection relay, log in with the appropriate user rights.

4.1.5 Identifying the device

The Information menu includes detailed information about the device, such as revision and serial number.
The protection relay information is shown on the display for a few seconds when the device starts. The same information is also found in the protection relay menu.
1. Select Main menu/Information.
2.
Select a submenu with
and .
611 series 39 Operation Manual
Page 48
Section 4 1MRS757453 C Using the HMI
GUID-36916877-1917-4472-AA11-37897C5FD709 V1 EN
Figure 14: Selecting a submenu
3.
Enter the submenu with .
4.
Browse the information with and .
GUID-2437E75E-0B00-4B47-89D2-FD4E5690BCC6 V1 EN
Figure 15: Protection relay information
4.1.5.1 Identifying relay's IEC 61850 version
The relay's IEC 61850 version information identifies if the relay is configured as Edition 1 or Edition 2 device.
1. Select Main menu/Information/System identifiers.
2.
Enter the submenu with .
GUID-D8F6EB65-75D5-4EE6-BC96-1153FC832AB3 V1 EN
Figure 16: Identifying IEC 61850 version

4.1.6 Adjusting the display contrast

Adjust the display contrast anywhere in the menu structure to obtain optimal readability.
To increase the contrast, press simultaneously and .
To decrease the contrast, press simultaneously
40 611 series
and .
Operation Manual
Page 49
1MRS757453 C Section 4
Using the HMI
The selected contrast value is stored in the non-volatile memory if you are logged in and authorized to control the protection relay. After an auxiliary power failure, the contrast is restored.

4.1.7 Changing the local HMI language

1.
Select Main menu/Language and press .
2.
Change the language using or .
3.
Press
4. Commit the changes.
to confirm the selection.
GUID-8588E7BB-6C58-4D6E-8690-27D46738B25F V1 EN
Figure 17: Changing the LHMI language
To change the language using a shortcut, press and simultaneously anywhere in the menu.

4.1.8 Changing display symbols

Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and IEC-ANSI.
1. Select Main Menu/Configuration/HMI/FB naming convention and press .
2.
Change the display symbols with or .
3.
Press
to confirm the selection.
The protection relay has to be rebooted if the WHMI display symbols are changed. With the LHMI, the change takes effect immediately.

4.1.9 Changing setting visibility

The basic settings contain the most used parameters. The advanced settings contain all parameters.
611 series 41 Operation Manual
Page 50
Section 4 1MRS757453 C Using the HMI
1.
Select Main Menu/Configuration/HMI/Setting visibility and press .
2.
Change the setting visibility with shown.
Basic
Advanced
3.
Press to confirm the selection.
GUID-ECF76371-3DF5-4833-966A-447D52FCF492 V1 EN
Figure 18: Viewing basic parameters
or to select which parameters are

4.1.10 Navigating in the menu

Navigate the menus and change the display views on the screen with the keypad.
To move up or down in a menu, press or .
To move downwards in the menu tree, press
To move upwards in the menu tree, press .
To enter setting mode, press .
To leave setting mode without saving, press .
4.1.10.1 Menu structure
The Main menu contains main groups which are divided further into more detailed submenus.
Control
Events
Measurements
Disturbance records
Settings
Configuration
Monitoring
Tests
Information
Clear
Language
.
42 611 series
Operation Manual
Page 51
1MRS757453 C Section 4
Using the HMI
4.1.10.2 Scrolling the display
If a menu contains more rows than the display can show at a time, a scroll bar is displayed on the right.
GUID-3DB7835C-EA13-46C3-AAF5-455C07D454EC V1 EN
Figure 19: Scroll bar on the right
To scroll the view upwards, press .
To scroll the view downwards, press .
To jump from the last row to the first row, press again.
Press to jump from the first row to the last row.
To scroll parameter names and values that do not fit the screen, press . Press
once to return to the beginning.
4.1.10.3 Changing the default view
The default view of the display is Measurements unless set otherwise.
1.
Select Main menu/Configuration/HMI/Default view and press .
2.
Change the default view with or .
3.
Press to confirm the selection.

4.1.11 Browsing setting values

1.
Select Main menu/Settings/Settings and press
2.
Select the setting group to be viewed with or .
.
611 series 43 Operation Manual
Page 52
Section 4 1MRS757453 C Using the HMI
GUID-3A58D472-E755-4244-9B1C-EA18EB6B5709 V1 EN
Figure 20: Selecting a setting group
3.
Press to confirm selection.
4.
To browse the settings, scroll the list with and and to select a submenu
press . To move back to the list, press .
GUID-E1C19F9C-079D-479C-BAF0-71E6E2FAF112 V1 EN
Figure 21: Example of submenus in the Settings menu

4.1.12 Editing values

To edit values, log in with the appropriate user rights.
Changing the function block on or off affects to the visibility of its parameters in the menu. Setting function block off hides the function parameters. When changing function block on or off the parameters' visibility changes immediately. Commit the settings for the activation of the function.
Changing the value of certain relay parameters affects the visibility or range of other parameters in the menu. This indicates which parameters or parameter values become obsolete due to the change. The relay changes the visibility or range of these parameters immediately. Commit the settings for the activation of the function.
4.1.12.1 Editing numerical values
1. Select Main menu/Settings and then a setting. The last digit of the value is active.
44 611 series
Operation Manual
Page 53
1MRS757453 C Section 4
Using the HMI
When the symbol in front of the value is ↑, the active value can only be increased.
When the symbol is ↓, the active value can only be decreased.
When the symbol in front of the value is ↕, the active value can either be increased or decreased.
GUID-91310FC1-E8FB-452E-B9B6-4D65C874278C V1 EN
Figure 22: Last digit is active and it can only be increased
2.
Press to increase or to decrease the value of an active digit. One press increases or decreases the value by a certain step. For integer values, the change is 1, 10, 100 or 1000 (...) depending on the active digit. For decimal values, the change can be fractions 0.1, 0.01, 0.001 (...) depending on the active digit.
For parameters with defined steps, digits smaller than the step value cannot be edited.
3.
Press or to move the cursor to another digit.
4. To select the minimum or maximum value, select the arrow symbol in front of the value.
To set the value to the maximum, press .
To set the value to the minimum, press .
GUID-604A2ED9-E1A7-4986-8CDD-92E43188CA48 V1 EN
Figure 23: Arrow symbol is active, the value is set to the maximum
After pressing , the previous value can be restored by pressing once, and vice versa. Another press of or sets the value to the lower or higher limit.
The symbol in front of the value is ↕, when the previous value is shown.
611 series 45 Operation Manual
Page 54
Section 4 1MRS757453 C Using the HMI
GUID-F65419AD-767F-488E-9915-4BBEB859D15A V1 EN
Figure 24: Restoring the previous value
4.1.12.2 Editing string values
1. Activate the setting mode and select a setting. When editing string values, the cursor moves to the first character.
2.
Press One press changes the value by one step.
3.
Press to move the cursor to the right. Press to delete the character on the left side of the cursor.
or to change the value of an active character.
4.1.12.3 Editing enumerated values
1. Activate the setting mode and select a setting. When editing an enumerated value, the selected value is shown inverted.
2.
Press
or to change the value of an active enumerated value. One press changes the enumerated value by one step in the parameter specific order.

4.1.13 Committing settings

Editable values are stored either in RAM or in non-volatile flash memory. Values stored in flash memory are in effect also after reboot.
Some parameters have an edit-copy. If editing is cancelled, the values with an edit­copy are immediately restored to the original value. The values without an edit-copy, such as string values, are restored to the original value only after a reboot even though the edited value is not stored in the flash memory.
1.
Press
2.
Press to move upwards in the menu tree.
3.
To save the changes in non-volatile memory, select Yes and press .
to confirm any changes.
46 611 series
Operation Manual
Page 55
1MRS757453 C Section 4
Using the HMI
GUID-2366EB35-75C9-48AC-8D11-E2B058BCF996 V1 EN
Figure 25: Confirming settings
To exit without saving changes, select No and press .
If the parameter has an edit-copy, the original parameter value is restored.
If the parameter does not have an edit-copy, the edited parameter value remains visible until the protection relay is rebooted. However, the edited value is not stored in non-volatile memory and the reboot restores the original value.
To cancel saving settings, select Cancel and press
.
After certain parameters are changed, the protection relay has to be restarted.

4.1.14 Clearing and acknowledging

The Clear view is used to reset, acknowledge or clear all messages and indications, including LEDs and latched outputs as well as registers and recordings. Events and alarms assigned to programmable LEDs are cleared in the Clear view as well.
1. Select Main menu/Clear to activate the clear menu.
GUID-6A5EE8B5-5F4B-4F35-958D-645F1134D69B V1 EN
Figure 26: Clear view
2.
Select the item to be cleared with or .
3.
Press , change the value with or and press again. The item is now cleared.
4. Repeat steps 2 and 3 to clear other items.
611 series 47 Operation Manual
Page 56
Section 4 1MRS757453 C Using the HMI
Use the button as a shortcut for clearing. The first three-second press clears the indications. The second three-second press clears the programmable LEDs.

4.1.15 Using the local HMI help

1.
Press
2.
Scroll the text with or if the help text exceeds the display area.
3.
To close the help, press .
to open the help view.

4.2 Using the Web HMI

WHMI is enabled by default. As secure communication is enabled by default, the WHMI must be accessed from a Web browser using the HTTPS protocol.
If the WHMI was previously disabled, it can be enabled again via the LHMI.
1. To enable the WHMI, select Main menu/Configuration/HMI/Web HMI mode via the LHMI.
2. Reboot the relay for the change to take effect.
3. Log in with the proper user rights to use the WHMI.
To establish a remote WHMI connection to the protection relay, contact the network administrator to check the company rules for IP and remote connections.
Disable the Web browser proxy settings or make an exception to the proxy rules to allow the protection relay's WHMI connection, for example, by including the relay's IP address in Internet Options/ Connections/LAN Settings/Advanced/Exceptions.

4.2.1 Logging in

1. Open Internet Explorer.
2. Type the protection relay's IP address in the Address bar and press ENTER.
3. Type the username with capital letters.
4. Type the password.
48 611 series
Operation Manual
Page 57
1MRS757453 C Section 4
Using the HMI
A070923 V5 EN
Figure 27: Entering username and password to use the WHMI
5. Click OK. The language file starts loading and the progress bar is displayed.

4.2.2 Logging out

The user is logged out after session timeout. The timeout can be set in Main menu/ Configuration/HMI/Web HMI timeout.
To log out manually, click Logout on the menu bar.

4.2.3 Identifying device

The Information menu includes detailed information about the device, for example, revision and serial number.
1. Click the Information menu in the left navigation bar.
2. Click a submenu to see the data.
611 series 49 Operation Manual
Page 58
Section 4 1MRS757453 C Using the HMI
GUID-0526D2B8-9C7C-4C29-9E1C-C9DF549B2970 V1 EN
Figure 28: Device information

4.2.4 Navigating in menus

The menu tree structure on the WHMI is almost identical to the one on the LHMI.
Use the menu bar to access different views.
The General view shows the protection relay version and status.
The Events view contains a list of events produced by the application configuration.
The Programmable LEDs view shows the status of programmable LEDs.
The Phasor diagrams view shows phasor diagrams.
The Disturbance records view shows the list of disturbance records.
Signal configuration
Logout ends the session.
50 611 series
Operation Manual
Page 59
1MRS757453 C Section 4
Using the HMI
GUID-C08AA4D5-0F4E-4DC5-9194-8338A19761AC V1 EN
Figure 29: Navigating in Web HMI menus
4.2.4.1 Menu structure
The Main menu contains main groups which are divided further into more detailed submenus.
Control
Events
Measurements
Disturbance records
Settings
Configuration
Monitoring
Tests
Information
Clear
Language
Parameter list
WHMI settings
611 series 51 Operation Manual
Page 60
Section 4 1MRS757453 C Using the HMI

4.2.5 Showing parameters

Some function blocks have a function-specific On/Off setting. When the function setting is “Off”, all settings are hidden and when the function setting is “On”, all settings are visible based on the other visibility and hiding rules.
Switch a function block on or off via the Operation parameter under the required function block.
GUID-F6EDA317-5965-463D-9335-0FD22A315D28 V1 EN
Figure 30: Function block On
52 611 series
Operation Manual
Page 61
1MRS757453 C Section 4
Using the HMI
GUID-9C2AD6B3-594A-4BCC-A2B9-5A875962D368 V1 EN
Figure 31: Function block Off
The Parameter list page offers filtering functionality where only chosen parameters are displayed, saved or printed. There are various options for filtering.
Enabled settings hides settings of disabled function blocks.
Writable settings displays only writable settings. This option is checked by default.
Basic settings displays only basic settings.
Setting group displays only settings of the selected setting group. With “All” selected, all setting groups are displayed.
Options can be combined. For example, with the Enabled settings and Writable settings selected, only enabled and writable settings are displayed. If none of the options is selected, all settings are displayed.
The values “Basic” or "Advanced" of the Setting visibility parameter in Main Menu/Configuration/HMI have no effect on the Parameter list page. This page has its own Basic settings option which can be used to hide or show the advanced settings on the Parameter list page.
GUID-B0106F5F-4798-475B-9DFB-58921B167310 V1 EN
Figure 32: Parameter list filter
1. Click Parameter list in the left navigation bar.
611 series 53 Operation Manual
Page 62
Section 4 1MRS757453 C Using the HMI
GUID-93613E3F-4CD3-4578-9F97-424282B1228B V2 EN
Figure 33: Displaying parameters
2. Select only those settings that are wanted to be shown and click Refresh. If nothing is selected, all settings are shown.
54 611 series
Operation Manual
Page 63
1MRS757453 C Section 4
Using the HMI
GUID-C2331A22-4BC6-4D24-9B8F-A8EB7A22CCCA V1 EN
Figure 34: Enabled settings
3. Select text (.txt) or comma separated values (.csv) file format and click Save to save the settings.
4. Click Print to print all the selected parameters.

4.2.6 Editing values

1. Select a menu in the left navigation bar.
2. Click a submenu to see function blocks.
3. Click a function block to see the setting values.
4. Click Enable Write.
Some parameters, for example the Web HMI mode, cannot be set via the WHMI.
611 series 55 Operation Manual
Page 64
Section 4 1MRS757453 C Using the HMI
GUID-C6FA8F5E-19CC-47AD-A000-8DFF91B3FFE7 V2 EN
Figure 35: Enable writing to edit a value
The selected setting group is shown in the Setting Group drop-down list. The active setting group is indicated with an asterisk *.
5. Edit the value.
The minimum, maximum and step values for a parameter are shown in the Min., Max. and Step columns.
Setting group values are indicated with .
56 611 series
Operation Manual
Page 65
1MRS757453 C Section 4
Using the HMI
GUID-35C049F6-D716-451D-9886-CFC607295675 V2 EN
Figure 36: Editing a value
If the entered value is within the accepted value range, the selection is highlighted in green. If the value is out of range, the row is highlighted in red and a warning dialog box is displayed. Write to IED is unavailable.
GUID-12C28E34-2871-423A-B9D9-A03FB55362AC V2 EN
Figure 37: Warning indicating that the entered value is incorrect
If writing values fails, a warning dialog box is displayed.
611 series 57 Operation Manual
Page 66
Section 4 1MRS757453 C Using the HMI
GUID-E85F77ED-C27F-426B-AAAD-9C6E10994A7C V2 EN
Figure 38: Warning indicating that the values were not written to the
IED
If writing is enabled accidentally, click Disable Write. Disable Write cannot be selected when a value has already been written to the protection relay. After clicking Write to IED, click either Commit or Reject.

4.2.7 Committing settings

Editable values are stored either in RAM or a nonvolatile flash memory. Values stored in the flash memory are in effect also after a reboot.
Some parameters have an edit-copy. If editing is cancelled, the values with an edit­copy are immediately restored to the original value. The values without an edit-copy, such as string values, are restored to the original value only after a reboot even though the edited value is not stored in the flash memory.
1. Click Write to IED after editing parameter values to put the values into protection relay's database for use.
58 611 series
Operation Manual
Page 67
1MRS757453 C Section 4
Using the HMI
GUID-F286D262-E9AB-4168-8BF1-FC37688D91BF V1 EN
Figure 39: Writing values to protection relay
The values are not stored to the flash memory.
2. Click Commit to write the values to the flash memory.
Click Reject to cancel saving settings.
If the parameter has an edit-copy, the original parameter value is restored.
If the parameter does not have an edit-copy, the edited parameter value remains visible until the protection relay is rebooted. However, the edited value is not stored in the nonvolatile memory and thus the reboot restores the original value.
GUID-88F499E6-799A-44D0-869A-1F01E7ED6722 V2 EN
Figure 40: Committing changes
Committing values takes a few seconds.
611 series 59 Operation Manual
Page 68
Section 4 1MRS757453 C Using the HMI
If the values are not committed, they are not taken into use and they are lost after a reboot.

4.2.8 Clearing and acknowledging

All messages and indications, including LEDs and latched outputs as well as registers and recordings, can be reset, acknowledged or cleared using the Clear menu.
1. Click Clear in the left navigation bar.
GUID-BD2CC4E6-6363-4EEA-9402-415901CC74FA V2 EN
Figure 41: Selecting clear menu
2. In the New Value list, select Clear to choose the item to be cleared.
3. Click Write to IED.
60 611 series
Operation Manual
Page 69
1MRS757453 C Section 4
Using the HMI
GUID-3CAE395C-EC4D-409A-99EB-C3434680BB61 V2 EN
Figure 42: Clearing indications and LEDs

4.2.9 Selecting programmable LEDs view

The programmable LEDs view shows the status of the programmable LEDs. These are the same LEDs that are located on the upper right side of the LHMI panel.
Click Programmable LEDs on the menu bar.
611 series 61 Operation Manual
Page 70
Section 4 1MRS757453 C Using the HMI
GUID-20C268F8-B2BA-41E1-A17D-5DBAE8CEFA2F V2 EN
Figure 43: Monitoring programmable LEDs

4.2.10 Selecting event view

The event view contains a list of events produced by the application configuration. When the event page is opened, it displays up to 100 latest events at one time. The event list is updated automatically.
1. Click Events on the menu bar.
62 611 series
Operation Manual
Page 71
1MRS757453 C Section 4
Using the HMI
GUID-4E351C8C-EE76-46F5-B83B-14230676BCE8 V2 EN
Figure 44: Monitoring events
2. Click Freeze to stop updating the event list.
3. Select a page from the drop-down list to view older events or select View all to show all events on the same page.
GUID-4FD2F9CC-D690-4A68-8E17-E6DE420ADED9 V2 EN
Figure 45: Events view
4. To save the events in TXT or CSV file formats, select the file format from the drop-down list and click Save.
611 series 63 Operation Manual
Page 72
Section 4 1MRS757453 C Using the HMI
The CSV file can be opened with a spreadsheet program such as OpenOffice.org Calc or Microsoft Excel.
5. Click Clear events to clear all events from the protection relay.
6. Click Print to print all the selected events.

4.2.11 Selecting disturbance records view

Disturbance records are listed in the disturbance records view.
Click Disturbance records on the menu bar.
GUID-FD3ED365-053B-4613-B290-2F3F46D04A0D V1 EN
Figure 46: Selecting disturbance records view
4.2.11.1 Saving disturbance records
1. Click Disturbance records on the menu bar.
2. To save the disturbance record files, click the icon in the Download Files column of the record.
64 611 series
Operation Manual
Page 73
1MRS757453 C Section 4
Using the HMI
GUID-76B94DE7-6020-4466-833A-2A22DB6A4367 V1 EN
Figure 47: Saving a disturbance record
3. Open the disturbance record files with a suitable program.
4.2.11.2 Triggering disturbance recorder manually
1. Click Disturbance records on the menu bar.
2. Click Manual trigger.
GUID-BD629C96-3A49-47C3-B09B-B2776C9CF467 V2 EN
Figure 48: Manual triggering
611 series 65 Operation Manual
Page 74
Section 4 1MRS757453 C Using the HMI
4.2.11.3 Deleting disturbance records
1. Click Disturbance records on the menu bar.
2. Delete records.
Click Delete all to delete all records.
Select one or more recordings and click Delete to delete selected records.
GUID-9B5D6FB6-68F0-472F-B23D-6369158D6BD7 V2 EN
Figure 49: Deleting disturbance records
3. Click OK to confirm or Cancel to cancel the deletion.

4.2.12 Selecting phasor diagrams

Install or enable the SVG plugin to view the phasor diagrams, if needed.
1. Click Phasor diagrams on the menu bar.
66 611 series
Operation Manual
Page 75
1MRS757453 C Section 4
Using the HMI
GUID-BC13067A-6C27-4532-9BD8-FD9BA724BFFF V1 EN
Figure 50: Monitoring phasors
2. Toggle the diagram visibility by selecting the diagram from the drop-down menu.
GUID-91F00B72-85EE-4577-B828-7B6E158F4CBF V1 EN
Figure 51: Toggling the diagram visibility
611 series 67 Operation Manual
Page 76
Section 4 1MRS757453 C Using the HMI
Visible diagrams are indicated with an asterisk *.
3. Change the size of the diagram by changing the zoom value.
GUID-D1C26F94-FCD1-4A0B-AE94-A3E4DACB8682 V1 EN
Figure 52: Zooming the diagram
4. Click Freeze to stop updating the phasor diagram. No updates are displayed in the diagram.
68 611 series
Operation Manual
Page 77
1MRS757453 C Section 4
Using the HMI
GUID-8BA2E56F-8828-4C5E-807C-F1F780F6E0C8 V1 EN
Figure 53: The arrow extends outside the circle if the current value is too
high

4.2.13 Selecting fault records

1. Fom the main menu, select Monitoring/Recorded data/Fault record or click Fault records on the menu bar to view a list of all available fault records.
2. Click a record from the Fault records list to open the fault record details view.
3. To go back to the list view, click Fault records on the menu bar or click the View all button.
4. To save the records in TXT or CSV file formats, select the format from the File format drop-down list and click Save.
When the fault record details view is shown, only the shown fault record
is saved.
When fault record list view is shown, all fault records are saved.
5. To clear all fault records from the protection relay, click Clear records. This can be done only when the fault record list view is shown.
6. To print all fault records, click Print when the fault record list view is shown.
7. To print only one record, open it in the details view and click Print.
611 series 69 Operation Manual
Page 78
Section 4 1MRS757453 C Using the HMI
GUID-2D4814EC-F4F7-4FF6-9E40-65D8C7F83487 V1 EN
Figure 54: Fault record list view
GUID-0E215160-B6E8-4ACB-B91A-DEAC98501FFC V1 EN
Figure 55: Fault record details view
70 611 series
Operation Manual
Page 79
1MRS757453 C Section 4
Using the HMI

4.2.14 Selecting signal configuration

The signal configuration view provides an easy tool to manage the application configuration, simplifying the configuration work. The signal configuration is done with three switch group functions including input switch group ISWGAPC, output switch group OSWGAPC and selector switch group SELGAPC.
1. Click Signal configuration on the menu bar to open the overview page. The switch groups used in the protection relay are categorized into four logical groups.
Binary inputs
GOOSE
Internal signals
Binary outputs and LEDs
Each group is represented by an area enclosed in a rectangle with a general description text.
GUID-3DC3C22C-ED52-4C1C-A9E8-5559DEA5724D V2 EN
Figure 56: Overview
2. Click the corresponding area to view a specific logical group. The switch groups included in the logical group are shown as a matrix view on the respective page. This view allows to change or map the connections from binary inputs to functions, GOOSE signals to functions, functions to functions, functions to binary outputs and functions to LEDs through corresponding switch group functions.
611 series 71 Operation Manual
Page 80
Section 4 1MRS757453 C Using the HMI
GUID-EAB8BB7D-C914-436D-8DDC-643EDF49ED40 V2 EN
Figure 57: Binary input configuration
GUID-B804DF59-FFE6-42FE-8E41-5A2A125DCD46 V2 EN
Figure 58: GOOSE configuration
72 611 series
Operation Manual
Page 81
1MRS757453 C Section 4
Using the HMI
GUID-4CF3B8E5-F756-4892-AE71-C4AA5895F075 V2 EN
Figure 59: Internal signal configuration
611 series 73 Operation Manual
Page 82
Section 4 1MRS757453 C Using the HMI
GUID-085A93F1-AD8B-42E4-9362-407C7057EA20 V2 EN
Figure 60: Binary outputs and LEDs configuration
3. On the Binary Outputs and LEDs Configuration matrix view, click Expand all to see the expanded page for configuring individual OSWGAPC instances. Use the Expand all and Collapse all buttons to move from the Binary Outputs and LEDs Configuration overview page to the more detailed view and back.
74 611 series
Operation Manual
Page 83
1MRS757453 C Section 4
Using the HMI
GUID-17AA5E7D-88EA-4B1D-AC4E-20EDBAC329F6 V1 EN
Figure 61: Binary outputs and LEDs configuration expanded view
4. Click Enable Write to edit field values.
Figure 62 shows an example view of updating or changing the input signal
configuration. One of the binary input channels has been mapped to one blocking input of a protection function through input switch group ISWGAPC and selector switch group SELGAPC functions.
Click one of the input switch group ISWGAPC connection channel shown
in green.
Click and select the binary input in the selector switch group SELGAPC
function shown in green.
Write the connection setting to IED and refresh values.
611 series 75 Operation Manual
Page 84
Section 4 1MRS757453 C Using the HMI
GUID-B6CE346B-D178-4FD1-B77C-084430E985AF V1 EN
Figure 62: Example view of changing binary input connections
For more information on editing field values, see the corresponding chapter.

4.2.15 Import and export of settings

Protection relay's setting parameters can be imported and exported in the XRIO file format.
4.2.15.1 Exporting settings
Relay setting parameters can be exported in XRIO file format.
1. Click Import/Export on the menu bar.
2. Click Export Settings. The export file includes all parameters except status parameters and parameters writable only in LHMI.
76 611 series
Operation Manual
Page 85
1MRS757453 C Section 4
Using the HMI
GUID-7BF72874-B597-4EB9-B37D-72D58578647D V1 EN
Figure 63: Exporting settings
3. Click Save to export the settings to the computer.
4.2.15.2 Importing settings
The parameter export and import function can be utilized, for example, when the relay parameters are set using the WHMI instead of PCM600. The relay settings engineered with PCM600 can be exported to XRIO files and imported to the WHMI. The WHMI can be used to write the settings to the protection relays. The WHMI can also be used to read the relay setting parameters and to export those to files, which can be used by PCM600. WHMI imports all parameters from the import file except lockable and read only parameters.
The exporting and importing of settings is sensitive to the protection relay contents. Settings are exported and imported for one protection relay at a time. The export files of a specific protection relay can be exchanged between PCM600, WHMI and the actual physical protection relay. To avoid errors and to efficiently manage the exporting and importing of settings, for example, in a substation with several devices, ensure that the names of the export files identify the protection relay to which the file should be imported.
Ensure that the correct settings are imported to the correct protection relay. Wrong settings may cause the protection relay to malfunction.
1. Click Import/Export on the menu bar.
2. Click Browse and choose the file to be imported.
611 series 77 Operation Manual
Page 86
Section 4 1MRS757453 C Using the HMI
GUID-977DDC47-343A-446E-BF59-E06F8330AAD1 V1 EN
Figure 64: Browsing import settings
3. Click Import Settings. Wait until the file transfer is complete.
GUID-9752BEBA-ECEA-4CB9-B77A-A887DBE744BB V1 EN
Figure 65: Importing settings
4. Click OK to commit the imported settings to the protection relay. Wait until the import is complete.
Click Cancel to cancel the importing. Both the WHMI and the protection
relay revert to the settings in use prior to the import.
78 611 series
Operation Manual
Page 87
1MRS757453 C Section 4
Using the HMI
GUID-3F9E3F90-BEC8-40D9-85CF-B837B5F3DE26 V1 EN
Figure 66: Writing parameter settings
GUID-25214819-0E23-4A36-98DE-99B47A63D46A V1 EN
Figure 67: Parameter settings written to protection relay
Only editable parameters are written to the protection relay during the import. If part of the import fails, the faulty parameters are listed separately.

4.2.16 Exporting report summary

The Report summary page allows exporting events, fault records, disturbance records and the parameter list.Events, fault records and the parameter list are saved in TXT format. Saved files contain all events, fault records and settings.Disturbance records are saved in CFG and DAT formats.
1. Click Report summary on the menu bar.
2. Select the items to be exported.
611 series 79 Operation Manual
Page 88
Section 4 1MRS757453 C Using the HMI
Click Select all to select all items and click Clear all to clear all selections.
3. From the Disturbance records drop-down list, select the amount of records to be saved.
All
Last 1
Last 10
4. Click Save to export the ZIP file with the selected files.
GUID-9693E936-E4D0-48CD-B0FE-9F928935198A V1 EN
Figure 68: Report summary page

4.2.17 Using Web HMI help

The context-sensitive WHMI help provides information on a single parameter, for example.
Move the mouse over the
to display the help dialog box.
80 611 series
Operation Manual
Page 89
1MRS757453 C Section 4
Using the HMI
GUID-1769ECA8-EC02-4260-B658-8698D54E89DB V2 EN
Figure 69: Opening the WHMI help
611 series 81 Operation Manual
Page 90
82
Page 91
1MRS757453 C Section 5

IED operation

Section 5 IED operation

5.1 Normal operation

In a normal protection relay use situation, the basic operation includes monitoring and checking procedures.
Monitoring measured values
Checking object states
Checking function setting parameters
Checking events and alarms
All basic operations can be performed via the LHMI, WHMI or with PCM600.
For more information, see the PCM600 documentation.

5.2 Disturbance identification

Disturbances and their causes can be identified by indicator LEDs: Ready, Start and Trip. During normal operation, the Ready LED is steady green.
Table 16: Disturbance indications
LED
Start LED Yellow, steady Protection started
Start LED Yellow, flashing Protection function blocked
Trip LED Red, steady Protection operated
Ready LED Green, flashing Internal fault
State Description
Further actions to be taken to identify the disturbance:
Checking programmable LEDs
Reading event history
Checking fault records
Analyzing disturbance recordings
611 series 83 Operation Manual
Page 92
Section 5 1MRS757453 C IED operation
Document the disturbance before clearing the information from the protection relay.
Only authorized and skilled personnel should analyze possible errors and decide on further actions. Otherwise, stored disturbance data can be lost.

5.2.1 Disturbance recording triggering

Disturbance recordings are normally triggered by protection relay applications when they detect fault events. Disturbance recordings can also be triggered manually or periodically. The manual trigger generates an instant disturbance report. Use this function to get a snapshot of the monitored signals.

5.2.2 Disturbance record analysis

The protection relay collects disturbance records of fault events which are set to trigger the disturbance recorder. Disturbance data is collected and stored for later viewing and analysis. The disturbance recorder data can be read and analyzed with PCM600.
For more information, see the PCM600 documentation.

5.2.3 Disturbance reports

PCM600 can be used for creating reports of disturbance recorder data.
For more information, see the PCM600 documentation.

5.2.4 Relay self-supervision

The relay self-supervision handles internal run-time fault situations.The main indication of an internal fault is a flashing green Ready LED.
Internal faults can be divided to hardware errors, run-time errors in the application or operating system and communication errors. Further actions always depend on the cause of the error.
84 611 series
Operation Manual
Page 93
1MRS757453 C Section 5
IED operation
Only authorized and skilled personnel should analyze the errors and decide on further actions.
The protection relay records system registrations, relay status data and events.
Document all the recorded data from the protection relay before resetting the tripping and relay lockout functions.

5.3 Relay parametrization

Protection relay parameters are set via the LHMI, WHMI or PCM600.
Setting parameters need to be calculated according to the electrical network conditions and the electrical characteristics of the protected equipment. The protection relay's settings need to be verified before the protection relay is connected to a system.
Document all changes to parameter settings.
For more information, see the PCM600 documentation.

5.3.1 Settings for relay functionality

Function settings can be edited one by one by navigating to the individual setting values, for example via the LHMI. The values in other setting groups should be known before editing a certain setting value.
After completing the editing of setting group values, the new values are activated. The user can either commit the edited values or discard them. Setting values can also be copied from one setting group to another.

5.3.2 Settings for different operating conditions

Protection relay settings can be designed for various operation conditions by defining different setting values to different setting groups. The active setting group can be changed by the relay application or manually via the LHMI, WHMI or PCM600.
611 series 85 Operation Manual
Page 94
86
Page 95
1MRS757453 C Section 6

Operating procedures

Section 6 Operating procedures

6.1 Monitoring

6.1.1 Indications

The operation of the protection relay can be monitored via three different indications on the LHMI.
Three indicator LEDs with fixed functionality: Ready, Start and Trip
8 programmable LEDs
Information on the display
6.1.1.1 Monitoring indication messages
Indication messages and tripping data are shown in a dialog box. Only one dialog box can be shown at a time, therefore the relay has internal priority for indication messages and tripping data. Internal fault and warning messages have always higher priority than start or trip information. Trip information has always higher priority than start information.
1. Read the indication message in the dialog box. The message can indicate the starting or tripping of protection functions or an internal fault in the device.
2.
Press activate the Clear view and to clear messages.
GUID-851D3AA9-F22C-49E9-B964-032A24C94B9F V1 EN
Figure 70: Indication message
to close the indication message without clearing it or press to
6.1.1.2 Monitoring an internal relay fault
The flashing green LED indicates an internal relay fault. Internal relay fault messages are shown in a dialog box. Only one dialog box can be shown at a time, therefore the
611 series 87 Operation Manual
Page 96
Section 6 1MRS757453 C Operating procedures
relay has internal priority for indication messages and tripping data. Internal fault has always higher priority than a warning.
See the troubleshooting section for more details.
GUID-216C00ED-ACFF-43AA-A2A6-B53C0FDE8D49 V1 EN
Figure 71: Fault indication
1. Select Main menu/Monitoring/IED status/Self-supervision to monitor the latest fault indication.
2.
Press or to scroll the view.
6.1.1.3 Monitoring condition monitoring data
1. Select Main menu/Monitoring/I/O status/Condition monitoring.
2.
Press or to scroll the view.
3.
Press
to enter or to exit a submenu.
With PCM600 the user can map output signals from condition monitoring related function blocks to the appropriate destinations.

6.1.2 Measured and calculated values

Measurement view in Main Menu/Measurements shows the momentary actual values for various power system measurements.
All values show the momentary measurement value and some include demand values calculated from a set period.
Invalid or questionable measurement values are presented in parentheses.
6.1.2.1 Measured values
Measured values can be accessed through the LHMI, WHMI or PCM600.
88 611 series
Operation Manual
Page 97
1MRS757453 C Section 6
Operating procedures
Table 17: Examples of the measured values
Indicator Description
IL1-A Current measured on phase L1
IL2-A Current measured on phase L2
IL3-A Current measured on phase L3
I0-A
U0-kV
U12-kV Measured phase-to-phase voltage U12
f-Hz Measured frequency
S-MVA Total apparent power
P-MW Total active power
Q-MVar Total reactive power
PF Average power factor
Ng-Seq-A Negative-phase-sequence current
Ps-Seq-A Positive-phase-sequence current
Zro-Seq-A Zero-phase-sequence current
Ng-Seq-kV Negative-phase-sequence voltage
Ps-Seq-kV Positive-phase-sequence voltage
Zro-Seq-kV Zero-phase-sequence voltage
Measured earth-fault current
Measured residual voltage
6.1.2.2 Using the local HMI for monitoring
1. Select Main menu/Measurements to monitor measured and calculated values. The list of protection relay's basic measurements is shown.
2.
Scroll the view with
and .

6.1.3 Recorded data

The protection relay is provided with intelligent and flexible functionality that collects different kinds of data. The recorded data gives substantial information for post fault analysis.
Disturbance records
Fault records
Events
6.1.3.1 Creating disturbance recordings
Normally disturbance recordings are triggered by the protection relay applications but the recording can also be triggered manually.
611 series 89 Operation Manual
Page 98
Section 6 1MRS757453 C Operating procedures
1. Select Main menu/Disturbance records.
2.
Select Trig recording with
3.
Press , change the value with or and press again.
GUID-01F7D531-894B-4D66-A777-4DE7B301EE43 V1 EN
Figure 72: Changing the value
The disturbance recorder is now triggered.
6.1.3.2 Monitoring disturbance recorder data
Upload individual disturbance recordings from the protection relay with the PCM600 software to monitor disturbance recorder data.
or .
1. Select Main menu/Disturbance records. All the disturbance recorder information is listed.
2.
Scroll the view with
or .
The following items are listed in the view:
Number of recordings currently in the protection relay's memory.
Remaining amount of recordings that fit into the available recording
memory.
Recording memory used in percentage.
If the periodic triggering function is used, the time to trigger which
indicates the remaining time to the next periodic triggering of the disturbance recorder.
GUID-42054948-9852-436A-AA73-FCD44FAA2E60 V1 EN
Figure 73: Monitoring disturbance recorder via the LHMI
6.1.3.3 Controlling and reading of disturbance recorder data
Disturbance recorder data can be controlled and read with PCM600. It can also be read via WHMI.
90 611 series
Operation Manual
Page 99
1MRS757453 C Section 6
Operating procedures
For more information, see the PCM600 documentation.
6.1.3.4 Monitoring fault records
Timestamps of the fault records are shown as a list. The first fault record is the newest.
1. Select Main Menu/Monitoring/Recorded data/Fault record.
2.
To navigate between the fault records, press and .
3.
To enter or exit a submenu, press or .
GUID-DE6008BE-30F6-4FD7-A6C3-E65CDC6FCBE0 V1 EN
Figure 74: Monitoring fault records
6.1.3.5 Monitoring events
Event view contains a list of events produced by the application configuration. Each event takes one view area. The header area shows the currently viewed event index and the total amount of the events. The most recent event is always first.
The HMI Event Filtering tool can be used to configure the event visibility in the LHMI.
1. Select Main Menu/Events.
2.
Press to view the first event. Date, time, device description, object description and event text elements of the event are shown.
3.
Press
or to scroll the view.
GUID-6D652E3A-0ECD-4025-9FE2-1535AEA9B1D4 V1 EN
Figure 75: Monitoring events
611 series 91 Operation Manual
Page 100
Section 6 1MRS757453 C Operating procedures

6.1.4 Remote monitoring

The protection relay supports comprehensive remote monitoring.
6.1.4.1 Monitoring protection relays remotely
Use the PCM600 tool and WHMI to operate the protection relay remotely.
Read maintenance record and version log.
Analyze disturbance record data.
Create disturbance records.
Monitor protection relay values.
For more information, see the PCM600 documentation.

6.2 Controlling

6.2.1 Controlling via the control menu

The primary equipment can be controlled via the LHMI with the Open and Close buttons when the protection relay is set to the local-control mode and accessing the control operations is authorized.
1.
Press to open or to close the object.
2. Enter the password when prompted.
3.
To confirm the operation, select Yes and press
GUID-6210E7B8-A5E3-4869-B654-18EB78E9D3DF V1 EN
Figure 76: Opening circuit breaker
.
To cancel the operation, select No and press .
92 611 series
Operation Manual
Loading...