Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
The information in this document is subject to change without notice and should not
be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for
any errors that may appear in this document.
In no event shall ABB Oy be liable for direct, indirect, special, incidental or
consequential damages of any nature or kind arising from the use of this document,
nor shall ABB Oy be liable for incidental or consequential damages arising from
the use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written
permission from ABB Oy, and the contents thereof must not be imparted to a third
party nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied or disclosed only in accordance with the terms of such
license.
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
11
Page 12
12
Page 13
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1.Introduction
1.1.This manual
This manual describes how to use the protection functions available in
REF 542plus.
This manual is addressed to engineering personnel and to anyone who needs to
configure REF 542plus.
1.2.Use of symbols
This publication includes the following icons that point out safety-related conditions
or other important information:
The warning icon indicates the presence of a hazard which could result
in personal injury.
REF 542plusREF 542plus
The caution icon indicates important information or warning related to
the concept discussed in the text. It might indicate the presence of a
hazard which could result in corruption of software or damage to
equipment or property.
The information icon alerts the reader to relevant facts and conditions.
Although warning hazards are related to personal injury, it should be understood
that operation of damaged equipment could, under certain operational conditions,
result in degraded process performance leading to personal injury or death.
Therefore, comply fully with all warning and caution notices.
1.3.Intended audience
This manual is intended for operators, supervisors and administrators to support
normal use of the product.
13
Page 14
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1.4.Product documentation
Name of the ManualDocument ID
Real Time Clock Synchronization, IRIG-B Input Time Master 1MRS755870
Product Guide1MRS756269
Configuration Manual1MRS755871
iButton Programmer User Manual1MRS755863
Manual Part 3, Installation and Commission1 VTA100004
Manual Part 4, Communication1VTA100005
Motor Protection with ATEX Certification, Manual1MRS755862
SCL Tool Configuration Manual1MRS756342
Protection Manual1MRS755860
Technical Reference Manual1MRS755859
Technical Reference Modbus RTU1MRS755868
Web Manual, Installation1MRS755865
Web Manual, Operation1MRS755864
IEC 61850 PIXIT1MRS756360
IEC 61850 Conformance Statement1MRS756361
IEC61850 TISSUES Conformance Statement1MRS756362
Lifecycle Service Tool1MRS756725
1MRS755860
1.5.Document revisions
VersionIED Revision
number
1VTA000215.07.20031
1VTA10002 Rev0210.12.20032
1VTA10002 Rev0301.05.20043
A28.02.2006Document updated
B2.530.9.2006Updated to software version V4E03x
C2.5 SP130.04.2007Updated to software version V4E04x
D2.619.12.2008Updated to software version V4E06x
E3.004.11.2009Updated to software version V4F08x
Applicability
This manual is applicable to REF 542plus Release 3.0, software version V4F08x
and subsequent.
DateHistory
st
release, valid since SW V4C01
nd
release, valid since SW V4D02
rd
release, valid since SW V4D02e
*
language
*
layout
14
Page 15
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
2.Safety Information
The safety warnings should always be observed. Non-observance can result in
death, personal injury or substantial damages to property. Guarantee claims might
not be accepted when safety warnings are not respected.
Do not make any changes to the REF 542plus configuration unless you
are familiar with the REF 542plus and its Operating Tool. This might
result in disoperation and loss of warranty.
REF 542plusREF 542plus
15
Page 16
16
Page 17
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
3.Analog measurement
The 8 available Analog Input channel measures are acquired and processed
according to the following flowchart.
REF 542plusREF 542plus
A050604
Fig. 3.-1Analog measurement
The analog signal entering the Analog Input board goes through two hardware
filters to reduce noise. It is then sampled and converted to digital information by a
sigma-delta Analog/Digital converter with an acquisition rate of 19.2kHz.
The acquisition is performed in parallel on all 8 analogue channels, and therefore the
data samples of the network currents and voltages are contemporary, that is, no
phase shift/time delay is introduced between the network quantities.
The digital data is then processed by a digital filter LP1 to reduce the information
bandwidth to 1,5 kHz.
This information is then provided directly to the DFT/ RMS and Math block,
performing the Discrete Fourier Transformation and RMS value analysis for the
th
protection working on the full RMS harmonic content up to the 25
harmonic
(switching resonance, high harmonic) and to the frequency protection for higher
discrimination of zero crossing.
For all the other protection functions, the digital data is down sampled, that is, one
sample each 4 is used to 4800 samples/s , maintaining the same information
bandwidth.
Furthermore, the signal is digitally filtered by LP2 and LP3 (HSTS function
analogue quantities only) and provided to the DFT/ RMS and math block,
performing the discrete fourier transformation and RMS value analysis.
17
Page 18
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
Almost all protection functions are based on the DFT (Discrete Fourier
Transformation) calculation for the selected network rated frequency. Only the
thermal overload protection performs the temperature calculation by applying the
RMS current values, in which all harmonics are considered.
In addition the following functions use:
*
Overcurrent instantaneous
To function the peak value of the measured current under transient condition for a
faster response. This is when the instantaneous peak value is over three times higher.
SQRT (2) the RMS value:
II
xpeakxRMS__
*
Inrush harmonic
The function evaluates the ratio between the current values at 2
23>⋅
nd
harmonic and at
fundamental frequency.
*
Differential protection
The function evaluates the measured amount of differential current at the
nd
fundamental, 2
and 5thharmonic frequencies.
(1)
18
Page 19
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
4.Analog Inputs
The Analog Inputs dialog allows the user to configure:
*
Analog input channels
*
Network characteristics (REF 542plus can handle currents or voltages from two
different networks)
*
Calculated values (power, THD, mean and maximum current values over the
desired time interval)
4.1.Analog Inputs
REF 542plusREF 542plus
Fig. 4.1.-1Analog Inputs
A050606
To ease the input of analog input channels, the user can push the Get group data
button in the Inputs tab of Analog Inputs dialog and then select the used board from
the list. This automatically configures the used analog input channels to the proper
sensor type and sets default values for each sensor type.
19
Page 20
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
4.1.1.Analog board selection
Fig. 4.1.1.-1Analog board selection
1MRS755860
A050695
To complete the configuration of each analog input channel, that is, to set the
appropriate Rated Primary and Secondary Values, the user must double-click the
line in the Inputs tab of Analog Inputs dialog.
20
Page 21
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
4.1.2.Current transformer
REF 542plusREF 542plus
A050607
Fig. 4.1.2.-1Current transformer
Board Input Rated Value (IRV) at present can be 0.2, 1 or 5 A only depending on the
type of CT mounted on Analog Input board.
In case of a mismatch between Rated Secondary Value (RSV) and Board Input
Rated Value, REF 542plus automatically compensates the protection function
thresholds.
Default direction of the polarity for the CT is Line. If Bus is selected, the polarity of
analog signal will be inverted to preserve directions in directional protections. The
amplitude and phase corrections can be introduced.
21
Page 22
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
4.1.3.Current Rogowski
1MRS755860
A050608
Fig. 4.1.3.-1Current Rogowski
The current sensors usually cover a rated primary current range, for example the
type KEVCD 24 A covers the primary current range 80 – 1250A.
One value should be chosen as Rated Primary Value (RPV), usually the value
matching through the current sensor rated transformation ratio the Rated Secondary
Value (RSV) and Board Input Rated Value (IRV). For example, with a
transformation ratio 80 A/0.150 V and RSV, IRV value of 0.150 V a RPV of 80 A
can be chosen. The RPV value introduced will be used as the rated current in
protection functions.
The rated transformation ratio of current sensors, typically 80 A/0.150
V, shall always be correctly introduced to avoid incorrect
measurements. Such ratio shall equal the ratio of RPV over RSV.
IRV at present can be only 0.150 V depending on the Rogowski sensor input on
Analog Input board. In case of a mismatch between RSV and IRV, REF 542plus
automatically compensates the protection function thresholds.
22
Page 23
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Default direction for the polarity of the Rogowski current sensors is Line. If Bus is
selected, the polarity of analog signal will be inverted to preserve directions in
directional protections. The amplitude and phase corrections can be introduced.
4.1.4.Voltage transformer
Voltage transformers can be phase, line or residual (open delta) voltage
transformers.
Phase-voltage transformer
REF 542plusREF 542plus
A050609
Fig. 4.1.4.-1Phase-voltage transformer
Phase-voltage transformers normally refer the rated phase-voltage at primary side
with rated phase voltage on the secondary side, for example:
20
This is shown below RSV line in the Transformer ratio dialog. When
entering the VT rated voltage data, it is not necessary to perform division by:
100
kVV
:
3
3
(2)
23
Page 24
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
3
(3)
IRV at present can be 100 V only depending on the input transformer mounted on
Analog Input Board.
In case of a mismatch between RSV and IRV, REF 542plus automatically
compensates protection function thresholds. If Invert phase is selected, the polarity
of analog signal will be inverted. The amplitude and phase corrections can be
introduced.
Line voltage transformer
24
A050612
Fig. 4.1.4.-2Line voltage transformer
Line voltage transformers normally refer rated line voltage at primary side with
rated voltage on secondary side, for example 20 kV:100 V. This is shown below the
RSV line in Transformer ratio dialog.
IRV at present can be 100 V only depending on the input transformer mounted on
Analog Input Board.
Page 25
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
In case of a mismatch between RSV and IRV, REF 542plus automatically
compensates protection function thresholds. If Invert phase is selected, the polarity
of analog signal will be inverted. The amplitude and phase corrections can be
introduced.
REF 542plusREF 542plus
Residual voltage transformer (open delta)
A050683
Fig. 4.1.4.-3Residual voltage transformer (open delta)
Residual voltage transformers normally refer rated phase-voltage at the primary side
with secondary side rated voltage of each winding in the open delta, for example:
20
This is shown below RSV line in Transform ratio dialog.
When entering VT rated voltage data, it is not necessary for the user to perform any
division. The user must simply select in the VT type dialog the corresponding
secondary winding denominator.
kV
3
100
:
3
(4)
25
Page 26
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
IRV at present can be 100 V only depending on the input transformer mounted on
Analog Input Board.
In case of a mismatch between RSV and IRV, REF 542plus automatically
compensates the protection function thresholds. If Invert phase is selected, the
polarity of analog signal will be inverted. The amplitude and phase corrections can
be introduced.
4.2.General constraints
*
Channels 1... 6 can be used only for phase currents, phase voltages or line
voltages
*
Channels 7 and 8 can be used also either for neutral current, residual voltage or
line voltage for synchronism check function.
*
Current and voltage sensors inside the triples 1 ... 3 and 4 ... 6 must have the
same characteristics (RPV, RSV and IRV)
1MRS755860
4.3.Network characteristics
Fig. 4.3.-1Networks tab
REF 542plus can handle two different networks or network parts having the same
frequency. By default only one network is used.
If the second network is needed, it must be enabled in the Networks tab of Analog
Inputs dialog.
A050687
26
For each network the rated nominal voltage and current can be configured. These
values are used by HMI led bars to scale the displayed quantities.
All the protection functions refer to Analog Input RPV as In, Un to
scale Start values.
Page 27
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
4.4.Calculated values
The three-phase power or the Aaron power calculation scheme can be applied for
the power calculation. Also active and reactive energies are calculated. Thereby, the
preferred reference system for the calculation can either be load or generator.
REF 542plusREF 542plus
Fig. 4.4.-1Calculated values
For monitoring purposes, the following values are calculated:
*
*
Demand and maximal demand current
The demand current is calculated as the mean value within a certain demand
value period up to 30 min. The maximal demand current is the maximal of the
demand currents from the last reset command.
The equation used to calculate the demand current is (IIR filter):
()
+×
4095
()( )
−
1
4096
(5)
I
mean t
II
value tmean t
=
()
The calculation period is 2.5 ms and the refresh time is 1 min.
Demand and maximal demand active and reactive power
The demand power is calculated as the mean value within a certain demand
values period up to 30 min. The maximal demand power is the maximal of the
demand powers from the last reset command.
A080144
The equation used to calculate the demand power is (IIR filter):
27
Page 28
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
()
+×
4095
()( )
−
1
4096
P
mean t
PP
value tmean t
=
()
1MRS755860
(6)
The calculation period is 2.5 ms and the refresh time is 1 min.
*
Minimum/maximum voltage calculation
Minimum/maximum voltages are the minimum/maximum of the measured line
voltages (RMS on fundamental component) from the last reset command.
*
Maximum current calculation
Maximum current is the maximum of the measured phase currents (RMS on
fundamental component) belonging to a network from the last reset command.
*
Maximum active and reactive power calculation
Maximum active and reactive power is the maximum measured active and
reactive power (negative, positive and absolute values) from the last reset
command.
The following calculated values are shown on the HMI and available for
transmission to remote control center:
*
Demand and maximal demand current
*
Demand and maximal demand active and reactive power
The reset of the maximal demand values can be done by the related command from
the HMI or from the remote control center. The following calculated values are not
shown on the HMI and they are available only for transmission to the remote control
center:
*
Minimum/maximum voltage
*
Maximum current
*
Maximum active and reactive power
The reset of the remote calculated values is selectable:
*
After reading
The measurements are reset automatically by REF 542plus after the values are
read out. This mode is used when the measurement values are read only by the
remote control center and not polled for periodic reading by the communication
module.
*
By command
28
The measurements are reset by the related reset command. This mode is used
when the measurement values are polled for periodic reading by the
communication module. This mode is mandatory when selecting the IEC61850
protocol.
The following calculated values are saved at power-down:
Page 29
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
*
Maximal demand current
*
Maximal demand active and reactive power
*
Minimum/maximum voltage
*
Maximum current
*
Maximum active and reactive power
REF 542plusREF 542plus
The THD (Total Harmonic Distortion) is calculated, only on voltages, as percentage
of the RMS voltage of the harmonics excluding the fundamental component:
22
VV
−
THD
(%) =×
100
RMSFUND
V
RMS
(7)
29
Page 30
30
Page 31
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
5.Control and monitoring
5.1.Measurement supervision NPS and PPS
REF 542plus provides two types of measurement supervision functions. Each of
them can be independently activated:
*
Positive Phase Sequence (PPS)
*
Negative Phase Sequence (NPS)
Fig. 5.1.-1Measurement supervision
REF 542plusREF 542plus
A050689
5.1.1.Input/output description
Table 5.1.1.-1Input
NameTypeDescription
BSDigital signal (active high)Blocking signal
When the BS signal becomes active, the measurement supervision function is reset
no matter its state. This means that all the output pins go low generating the required
events (if any), and all the internal registers and timers are cleared. The protection
function will then remain in idle state until the BS signal goes low.
Table 5.1.1.-2Output
NameTypeDescription
WarningDigital signal (active high)Warning signal
FailingDigital signal (active high)Failing signal
Warning is the start signal. Warning signal will be activated when the start
conditions are true. The negative phase sequence value exceeds the setting threshold
value for NPS , and the positive phase sequence value falls below the setting
threshold value for PPS.
Failing signal will be activated when the start conditions are true and the operating
time has elapsed.
31
Page 32
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
5.1.2.Configuration
1MRS755860
Fig. 5.1.2.-1General
Fig. 5.1.2.-2Sensors
A050690
A050691
32
The measurement supervision functions operate on all sensors in a triple. The analog
channels 1-3 or 4-6 can be used to supervize the phase currents, phase voltages or
line voltages.
Page 33
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A050692
Fig. 5.1.2.-3Parameters
Start Value:Positive/Negative phase sequence threshold for Start condition detection.
Time:Time delay for Trip condition detection.
Fig. 5.1.2.-4Events
A050693
33
Page 34
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
Fig. 5.1.2.-5Pins
5.1.3.Measurement mode
Measurement supervision functions evaluate the measured amount of positive and
negative phase sequence values at the fundamental frequency.
5.1.4.Operation criteria
If the negative phase sequence value exceeds the setting threshold value (Start
value) in the NPS based functions, or if the positive phase sequence value falls
below the setting threshold (Start value) the function enters the START status and
raises the warning. After the preset operating time (Time delay) has elapsed, the
failing signal is generated.
The measurement function will come back in passive status and the warning signal
will be cleared, if the negative phase sequence value falls below 0.95 the setting
threshold value for NPS , or if the positive phase sequence value exceed 1.05 the
setting threshold value for PPS.
The measurement function will exit the failing status and the failing signal will be
cleared when the negative phase sequence value falls below 0.4 the setting threshold
value for NPS, or if the positive phase sequence value exceed 1.05 the setting
threshold value for PPS.
A050694
5.1.5.Setting groups
Two parameter sets can be configured for each of the measurement supervision
functions.
34
Page 35
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
5.1.6.Parameters and events
Table 5.1.6.-1Setting values
ParameterValuesUnitDefaultExplanation
Start value
(PPS)
Time delay30 ... 30000ms1000Time delay from start condition
Start value
(NPS)
Time delay30 ... 30000ms1000Time delay from start condition
Table 5.1.6.-2Events
CodeEvent reason
E0Warning signal is active
E1Warning signal cancelled
E6Failing signal is active
E7Failing signal is back to inactive state
E18Function block signal is active
E19Function block signal is back to inactive state
0.30 ... 0.90In or Un0.85PPS threshold to undergo.
0.05 ... 0.40In or Un0.10NPS threshold to be exceeded.
REF 542plusREF 542plus
(warning signal) to failing
signal.
to failing signal.
By default all events are disabled.
5.2.Power factor controller
The power factor controller is designed to control reactive power compensation in
power systems. The magnitude of the reactive power in the network is derived from
the measured power factor. Consequently, the power factor controller permanently
monitors the power factor, which is defined as the ratio of the effective power to the
active power. The PFC then controls the switching ON/OFF the available capacitors
banks to reach the set power factor target.
Fig. 5.2.-1Power factor controller
A050697
35
Page 36
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
5.2.1.Input/output description
Table 5.2.1.-1Input
NameTypeDescription
BLDigital signal (active high)Blocking signal
DISCONNECTDigital signal (active high)Disconnect all capacitor
RESETDigital signal (active high)Reset the function
OVERTEMP.Digital signal (active high)Overtemperature
VMIN / VMAXDigital signal (active high)Voltage out of range
VA MAXDigital signal (active high)Overload due to overvoltage
MODE: MAN.Digital signal (active high)Mode manual
SET NIGHTDigital signal (active high)Set night parameter
MANUAL CONTROL BANK 0 Digital signal (active high)Switch bank 0 manually
MANUAL CONTROL BANK 1 Digital signal (active high)Switch bank 1 manually
MANUAL CONTROL BANK 2 Digital signal (active high)Switch bank 2 manually
MANUAL CONTROL BANK 3 Digital signal (active high)Switch bank 3 manually
CHECKED BACK BANK 0Digital signal (active high)Status on indication bank 0
CHECKED BACK BANK 1Digital signal (active high)Status on indication bank 1
CHECKED BACK BANK 2Digital signal (active high)Status on indication bank 2
CHECKED BACK BANK 3Digital signal (active high)Status on indication bank 3
1MRS755860
banks
When the BS signal becomes active, the protection function is reset no matter its
state. This means that all the output pins go low generating the required events (if
any), and all the internal registers and timers are cleared. The protection function
will then remain in idle state until BS signal goes low.
Table 5.2.1.-2Output
NameTypeDescription
Q ALARMDigital signal (active high)Alarm indication Q
COS ФALARMDigital signal (active high)Alarm indication cos Ф
OPERAT. ALARMDigital signal (active high)Operation Alarm (reset only
by power off)
GENERAL ALARMDigital signal (active high)General alarm
SWITCH ON/OFF BANK 0Digital signal (active high)Bank 0 on (high), off (low)
SWITCH ON/OFF BANK 1Digital signal (active high)Bank 1 on (high), off (low)
SWITCH ON/OFF BANK 2Digital signal (active high)Bank 2 on (high), off (low)
SWITCH ON/OFF BANK 3Digital signal (active high)Bank 3 on (high), off (low)
36
Page 37
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
5.2.2.Configuration
REF 542plusREF 542plus
Fig. 5.2.2.-1General
Fig. 5.2.2.-2Capacitor banks
A050698
A050699
37
Page 38
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
Fig. 5.2.2.-3Control data
Fig. 5.2.2.-4Time
A050700
A050701
38
Page 39
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
Fig. 5.2.2.-5Events
By default all events are disabled.
A050702
Fig. 5.2.2.-6Pins
5.2.3.Measurement mode
When a reactive power consumer is switched into the network, the current variable
increases. Simultaneously, the phase displacement increases in relation to the related
voltage quantity. As a result, the reactive power increases and the power factor is
reduced correspondingly. Because of the increase in the current measured quantity
A050750
39
Page 40
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
and the angle of the phase displacement, an increased voltage drop in the power
system must be taken into account. For more detailed information please refer to the
corresponding application notes.
5.2.4.Parameters and events
Table 5.2.4.-1Setting values
ParameterValuesUnitDefaultExplanation
Neutral zone105 … 200% Q
Pickup zone0 … 100% Q
Reactive power of
smallest Q
Number of banks1 … 41
Maximum switching
cycles
Set point cos phi0.7 ... 1.0Ind/cap0.9 ind
Limiting value cos phi0 … 1Ind/cap0
Discharge blocking
time
Dead Time1 … 120s10
Power on delay1 … 7200s900
Duration of
integration
CO
1 … 20000kVA100
1 … 100002500
1 … 7200s900
1 … 7200s900
CO
CO
1MRS755860
115
0
Table 5.2.4.-2Events
CodeEvent reason
E0Bank 0 on
E1Bank 1 on
E2Bank 2 on
E3Bank 3 on
E4Bank 0 off
E5Bank 1 off
E6Bank 2 off
E7Bank 3 off
E8Overtemperature started
E9Overtemperature back
E10Va max started
E11Va max back
E12Vmin/Vmax started
E13Vmin/Vmax back
E14Command DISCONNECT started
E15Command DISCONNECT back
E16Cos phi warning started
E17Cos phi warning back
E18Alarm Q started
E19Alarm Q back
40
Page 41
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
CodeEvent reason
E20Warning switching cycle
E21Alarm reset
E22Block signal started
E23Block signal back
E24Manual operating mode
E25Automatic operating mode
E26Night mode
E27Day mode
5.3.Circuit breaker monitoring
Circuit breaker monitoring can be used to supervise the contact wear condition by
calculating the switched current and to help to analyze faults by storing all
configured measurements in case of a CB trip.
REF 542plusREF 542plus
5.3.1.Configuration
Fig. 5.3.1.-1Currents
A080170
Current sensors used for CB Switched Currents calculation.
41
Page 42
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
A080172
Fig. 5.3.1.-2Settings
Circuit Breaker
CB Open channel:Number of the output channel used to open
the circuit breaker. In case a Switching
Object 2-2 configured as CB or the PTRC
General are installed, the REF 542plus
Configuration Tool will take automatically
the configured CB open channel and
disable the edited channel of this setting.
CB Switched Currents
Enable Switched Currents recording:If enabled, the values of the last six CB
Switched Currents are stored in the nonvolatile memory with the date and time of
switching.
Switched Currents break time:Switched Currents break time is the time
between the start of the switching and the
breaking of the circuit breaker main contact
for recording the switched current.
CB Contact Wear
Parameters (A, B, C, K):These parameters are used for the internal
Contact Wear calculation done with the
equation presented in the dialog box.
CB Trip Context
Enable Trip Context recording:If enabled, the values of the last six CB Trip
Contexts are stored in the non-volatile
memory with the date and time of tripping.
42
Page 43
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
Fig. 5.3.1.-3Events
5.3.2.Measurement mode
The switched current is calculated as the maximum RMS value at the fundamental
frequency until the moment of contact separation.
The trip context is represented by all the configured measurements at the instant of
CB Trip. Maximum six switched current/trip context values are stored in order to
cover system operation using auto-reclose with up to five multi-shots.
5.3.3.Operation criteria
The switched currents are recorded each time the circuit breaker is opened. The trip
context is recorded each time the circuit breaker is opened due to a protection trip.
A080174
43
Page 44
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
5.3.4.Parameters and events
Table 5.3.4.-1Setting values
ValuesUnit DefaultExplanation
CB Switched Currents
recording
0 … 500ms 30CB contact separation time
1.0 … 1.61.0Parameter for contact wear calculation
2.8 … 3.33.000Parameter for contact wear calculation
1.0 … 1.01.000Parameter for contact wear calculation
0… 6500010000Parameter for contact wear calculation
The function for reading of the circuit breaker monitoring data can be used for:
*
Uploading data from the connected REF 542plus
*
Reset data in the connected REF 542plus
*
Save uploaded data to a recorded file (text format)
*
Uploading data from the recorded file
44
Page 45
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A080146
Fig. 5.3.5.-1Settings
Click the Settings tab to select the location of the CB Monitoring recording files and
file prefixes. The recording file name is automatically composed by the REF
542plus Configuration Tool with the following items:
*
User editable prefix
*
Feeder name
*
Device communication address
An example of a CB Switched Currents recording file name:
SC_Feeder_98.txt
Where:
SCThe prefix of the recorded file
FeederThe feeder name from the device configuration. In case the feeder name is
empty, the default (Feeder) is used.
98The device communication address (SPA, IEC103, LON, and so on) read from
the device configuration. In case the address is an IP address (ETHERNET
board), the standard dot separator is replaced by dash to avoid confusion on
file extension (for example 198-162-2-112).
The file name is unique in a project, because two devices cannot have
the same feeder name and communication address.
45
Page 46
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
1MRS755860
Protection Functions: Configuration and Settings
Protection manual
Click the CB Switched Currents or the CB Trip Context tab to upload the
information relating to the circuit breaker switched currents or circuit breaker trip
context from file or from REF 542plus.
Fig. 5.3.5.-2CB Switched Currents
A080148
46
A080150
Fig. 5.3.5.-3CB Trip Context
Page 47
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Fig. 5.3.5.-4Upload from file
REF 542plusREF 542plus
A080152
Fig. 5.3.5.-5Upload from REF 542plus
*
Device information
Device information displays data regarding REF 542plus and its configuration.
*
File information
When uploading from REF 542plus, File information displays the location and
the file name where the data is saved when clicking Save To File. When
uploading from file, it displays the location and the file name of the uploaded
file.
A080154
47
Page 48
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
The data table displays the CB Monitoring data type (CB Switched Currents or
CB Trip Context) and the upload source (device/file). The information is
presented in a table where each row contains the data relevant to one record.
The time stamp contains also its quality. It is set to "Good” in case the
record has been time-stamped when the device time was synchronized;
otherwise it is set to “Bad”.
*
Save To File
You can use Save To File after a successful upload from REF 542plus. In case
the file does not exist, the file is created. Otherwise the file is saved into a backup
file (*.bak) and the new uploaded records are appended to the file. In order to
save the file, the uploaded and the saved file has to be compatible. The files are
compatible when they have the same device information and the same record
format (number of data and measurements name). In case the files are not
compatible the existing file is replaced by the uploaded one. In case a new
configuration has been downloaded to REF 542plus, the user can choose to
append the new records to the saved file or to save only the new ones.
*
Reset Device Data
You can use Reset Device Data after a successful upload from REF 542plus.
After a requested confirmation, the CB Monitoring data stored in REF 542plus is
reset.
48
Page 49
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.Protection functions
6.1.Current protection functions
6.1.1.Inrush blocking
REF 542plus has one inrush blocking protection function. This function is
appropriate for application in motor protection scheme in order to block the
corresponding overcurrent protection.
The following current protection functions are blocked by the inrush blocking
protection function without the need of additional wiring in the FUPLA (that is, the
block to the protection functions is implicit).
*
Overcurrent instantaneous
*
Overcurrent high
*
Overcurrent low
*
Directional overcurrent high
*
Directional overcurrent low
*
IDMT
*
Earthfault IDMT
REF 542plusREF 542plus
Fig. 6.1.1.-1Inrush blocking
6.1.1.1.Input/output description
Table 6.1.1.1.-1Input
NameTypeDescription
BSDigital signal (active high)Blocking signal
When the BS signal becomes active, the protection function is reset (no matter its
state). This means that all the output pins go low generating the required events (if
any) and all the internal registers and timers are cleared. The protection function will
then remain in idle state until the BS signal goes low.
A050769
49
Page 50
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
Table 6.1.1.1.-2Output
NameTypeDescription
S L1Digital signal (active high)Start signal of IL1
S L2Digital signal (active high)Start signal of IL2
S L3Digital signal (active high)Start signal of IL3
TRIPDigital signal (active high)Trip signal
S L1-3 are the start signals phase selective. The phase starting signal will be
activated when the respective phase current start conditions are true and the
overcurrent protection will be implicitly blocked until the operating time (Time)
has elapsed.
The TRIP signal will be activated when the start conditions are true (inrush
detection), the maximum measured current exceeds the threshold (limit N•I>>) and
the relevant overcurrent protection operating time has elapsed.
6.1.1.2.Configuration
Fig. 6.1.1.2.-1General
A050770
50
Page 51
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A090004
Fig. 6.1.1.2.-2Fast I/O
Output Channel different from 0 means a direct execution of the trip or the general
start command, that is, skipping the FUPLA cyclic evaluation.
Input Channel different from 0 means a direct execution of the block command,
skipping the FUPLA cyclic evaluation.
51
Page 52
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
A050811
Fig. 6.1.1.2.-3Sensors
The protection function operates on any combination of current phases in a triple,
for example, it can operate as single phase, double phase or three-phase protection
on phase currents belonging to the same system.
52
A050812
Fig. 6.1.1.2.-4Parameters
Page 53
1MRS755860
Multifunction Protection and Switchgear Control
Unit
REF 542plusREF 542plus
Protection Functions: Configuration and Settings
Protection manual
N:Threshold I>> multiplier for fault detection and inrush protection trip
M:Threshold I> multiplier for inrush detection
Time:Overcurrent protection blocking Time at inrush detection
Fig. 6.1.1.2.-5Events
Fig. 6.1.1.2.-6Pins
A050813
A050814
53
Page 54
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.1.3.Measurement mode
Inrush blocking function evaluates the current at the fundamental frequency.
6.1.1.4.Operation criteria
An inrush is detected if the maximum measured current exceeds the threshold M•I>
within 60 ms after it exceeded 10% of current threshold I>.
Here I> is the threshold (Start value I>) of the overcurrent low protection
function. If this protection function is not installed, the threshold of IDMT
protection function (Base current Ieb:, if installed) is used or a standard value
of 0.05•I
If an inrush is detected, the above-listed protection functions are blocked until the
end of inrush has been detected or the maximum preset inrush duration (that is,
Time) has elapsed.
(if IDMT also is not installed).
N
1MRS755860
The end of inrush condition is detected when the maximum measured current falls
below M•0.65•I>. A counter is then started and 100 ms later the end of inrush is
assumed. The current protection functions are then released from the block.
At feeder start-up, with current zero, the implicit block of the
overcurrent protection function is already active. Only as the current
increases, the inrush condition is evaluated and the block can be
released if an inrush is not present.
The inrush blocking itself becomes a protection function, if the maximum measured
current exceeds the limit N•I>> after the inrush detection. The operating time is that
of the overcurrent instantaneous (if installed) or 80 ms.
Here I>> is the threshold (Start value I>>) of the overcurrent high protection
function. If this protection function is not installed, the threshold of overcurrent
instantaneous protection function (if installed) is used or a standard value of 0.10•I
(if overcurrent instantaneous also is not installed).
The following three diagrams are not scaled, but they are provided solely for a better
understanding of the explanations of how the inrush blocking works.
Tesb is the operation counter that is compared to the set overcurrent protection
blocking time (that is, Time).
N
54
In Fig. 6.1.1.4.-1 inrush is detected within the 60 ms window. Then the end of
inrush condition is detected and the block released before protection-blocking time
expires.
Page 55
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A050815
Fig. 6.1.1.4.-1Current-time characteristic of the detected inrush process
In Fig. 6.1.1.4.-2 inrush is detected within the 60 ms window. Then the end of
inrush condition is detected and the block released before protection-blocking time
expires. The current value is over the I> threshold and that protection function will
start timing and trip in due time.
Fig. 6.1.1.4.-2Current-time characteristic of the detected overload
A050816
55
Page 56
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
In Fig. 6.1.1.4.-3 inrush is detected within the 60 ms window, no end of inrush
condition is detected and the protection-blocking time expires. The current value is
over the I>> threshold and that protection function will start timing and trip in due
time.
Fig. 6.1.1.4.-3Current-time characteristic when no inrush condition is detected
6.1.1.5.Setting groups
Two parameter sets can be configured for the inrush blocking protection function.
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Table 6.1.1.6.-2Events
CodeEvent reason
E0Start L1 started
E1Start L1 back
E2Start L2 started
E3Start L2 back
E4Start L3 started
E5Start L3 back
E6Trip started
E7Trip back
E18Protection block started
E19Protection block back
By default all events are disabled.
6.1.2.Inrush harmonic
REF 542plusREF 542plus
REF 542plus has an inrush harmonic function which can be used to temporarily
block protection functions.
The following current protection functions are blocked by the inrush harmonic
protection function without the need of additional wiring in the FUPLA, that is, the
block to the protection functions is implicit.
*
Overcurrent instantaneous
*
Overcurrent high
*
Overcurrent low
*
Directional overcurrent high
*
Directional overcurrent low
*
IDMT
*
Earthfault IDMT
Other protection functions, such as distance protection, can be blocked by wiring
them to FUPLA.
Fig. 6.1.2.-1Inrush harmonic
A050818
57
Page 58
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.2.1.Input/output description
Table 6.1.2.1.-1Input
NameTypeDescription
BSDigital signal (active high)Blocking signal
When the BS signal becomes active, the protection function is reset (no matter its
state). This means that all the output pins go low generating the required events (if
any) and all internal registers and timers are cleared. The protection function will
then remain in idle state until the BS signal goes low.
Table 6.1.2.1.-2Output
NameTypeDescription
StartDigital signal (active high)Start signal
Start signal can be wired in FUPLA to signal inrush condition status or to the
protection functions BS input pins (different from those listed above and implicitly
blocked) to temporarily block during an inrush transient. This means that the block
to the protection functions is explicit.
1MRS755860
6.1.2.2.Configuration
Fig. 6.1.2.2.-1General
A050819
58
Output Channel different from 0 means direct execution of the trip command, that
is, skipping FUPLA cyclic evaluation.
Page 59
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
Fig. 6.1.2.2.-2Sensors
The protection function operates on any set of phase currents in a triple.
A050820
Fig. 6.1.2.2.-3Parameters
A050821
59
Page 60
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
1MRS755860
Protection Functions: Configuration and Settings
Protection manual
Minimum current threshold:Current threshold for inrush detection.
Fault current threshold:Current threshold for fault detection.
Harmonic ratio threshold:2nd/fundamental current ratio threshold for inrush
detection.
Fig. 6.1.2.2.-4Events
Fig. 6.1.2.2.-5Pins
A050822
A050823
60
Page 61
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.2.3.Measurement mode
Inrush harmonic protection function evaluates the ratio between current values at
2nd harmonic and at fundamental frequency.
6.1.2.4.Operation criteria
If for at least one phase current:
the current is not in steady-state condition,
AND the current value at fundamental frequency is above the preset minimum
current threshold (that is, Min current threshold),
AND the current value is below the preset maximum current threshold (that is,
Fault current threshold),
REF 542plusREF 542plus
AND the harmonic ratio between the current values at 2
nd
harmonic and at
fundamental frequency exceeds the preset threshold (that is, Harmonic ratiothreshold)
then the protection function is started and the start signal will be activated.
The start criteria is illustrated in the following flowchart:
A050824
The protection function will remain in START status until at least for one phase the
above conditions (steady state excluded) are true. It will come back in passive status
with a 10ms delay when:
61
Page 62
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
for all the phases at least one condition falls below 0.95 the setting threshold value
(that is, Min Current threshold or Harmonic ratio threshold
respectively),
OR at least for one phase the current value exceeds the preset maximum current
threshold (that is, Fault current threshold).
6.1.2.5.Steady-state detection
Steady-state condition is detected if:
the current value at fundamental frequency falls below the preset minimum current
threshold (that is, Min current threshold) for at least 10 ms,
OR the current value at fundamental frequency is between 95% and 105% of the
previous period for at least one period.
1MRS755860
6.1.2.6.Setting groups
Two parameter sets can be configured for the harmonic inrush protection function.
6.1.2.7.Parameters and events
Table 6.1.2.7.-1Setting values
ParameterValuesUnitDefaultExplanation
Minimum current
threshold
Fault current
threshold
Harmonic ratio
threshold
Table 6.1.2.7.-2Events
CodeEvent reason
E0Protection has started
E1Start is cancelled
E18Protection block signal is active started
E19Protection block signal is back to inactive state
0.05 ... 40.00ln0.5Current threshold for inrush
0.05 ... 40.00ln2Current threshold for fault
5 ... 50%102
detection, if exceeded the inrush
conditions are evaluated.
detection, if exceeded the inrush
start is set to low.
nd
/fundamental current ratio
threshold for in-rush detection.
By default all events are disabled.
6.1.3.Non-directional overcurrent protection
In the non-directional overcurrent protection can up to eight instances be applied.
62
Page 63
1MRS755860
Multifunction Protection and Switchgear Control
Unit
When the BS signal becomes active, the protection function is reset (no matter its
state). This means that all the output pins go low generating the required events (if
any) and all internal registers and timers are cleared. The protection function
remains in idle state until the BS signal goes low.
REF 542plusREF 542plus
A080156
Table 6.1.3.1.-2Outputs
NameTypeDescription
START L1Digital signal (active high)Start signal of IL1
START L2Digital signal (active high)Start signal of IL2
START L3Digital signal (active high)Start signal of IL3
GEN.STARTDigital signal (active high)General start signal (logical OR combination
of all start signal inclusive reset time)
TRIPDigital signal (active high)Trip signal
The START signal is activated when the respective phase current start conditions are
true. START L1 – L3 are the phase selective start signals. The GEN. START is a
logical OR combination of the start signal START L1 – L3 and remains active until
the reset time, if used, is expired. The TRIP signal is activated when the start
conditions are true and the operating time has elapsed at least for one phase current.
63
Page 64
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.3.2.Configuration
1MRS755860
Fig. 6.1.3.2.-1General
A080158
64
Page 65
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A090006
Fig. 6.1.3.2.-2Fast I/O
Output channel different from 0 means a direct execution of the trip command or
general start command, that is, skipping the FUPLA cyclic evaluation.
Input channel different from 0 means a direct execution of the block command, that
is, skipping the FUPLA cyclic evaluation.
65
Page 66
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
A080160
Fig. 6.1.3.2.-3Sensors
The protection function operates on any combination of the phase current in a triple,
for example, it can operate as single-phase, double-phase or three-phase protection
on the phase currents belonging to the same network.
66
Page 67
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A080162
Fig. 6.1.3.2.-4Mode
Status:Mode of the operating status on or off
Mode:Mode for the overcurrent, instantaneous,
definite or inverse time
IDMT (IEEE):Free programmable inverse time curve
according to equation
A,P,B, Td:Parameter for the free programmable
inverse time curve
t-I Diagram:Diagram of the inverse time operation
characteristic
Reset type:Mode of the reset time
Reset time:Timer resets after start current condition is
not valid anymore
67
Page 68
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
Fig. 6.1.3.2.-5Parameter
Start Value:Current threshold for start
Def. operate time:Operation time in mode definite time
A080164
68
Page 69
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
Fig. 6.1.3.2.-6Events
A080166
Fig. 6.1.3.2.-7Pins
A080168
69
Page 70
⎝
⎠
⎝
⎠
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.3.3.Measurement mode
All overcurrent functions evaluate the current RMS value at the fundamental
frequency. In case of the overcurrent definite time instantaneous, the peak value of
the measured current is also used under transient condition for a faster response.
When the instantaneous peak value is higher than three times the peak value, in
relation to the RMS value, a trip is generated.
6.1.3.4.Operation criteria
If the measured current exceeds the setting threshold value (Start Value), the
overcurrent protection function is started. The start signal is phase selective, that is,
when at least a value of one phase current is above the setting threshold value the
relevant start signal is activated. The protection function remains in START status
until there is at least one phase started. It returns to passive status and the start signal
is cleared if for all the phases the current falls below 0.95 the setting threshold value.
1MRS755860
After the protection has entered the start status and the preset operating time (Time)
has elapsed, function goes in TRIP status and the trip signal is generated. The
protection function exits the TRIP status and the trip signal is cleared when the
measured current value falls below 0.4 the setting threshold value. The tripping can
be applied according to definite time or inverse time characteristic, which is defined
according to an equation.
A
⎛
t
=
⎜
P
−
M
Where:
t:Operation time to trip
A:Curve parameter for the time value (according to IEC 60255-3)
P:Value for the exponent
M:Ratio of actual current to the pickup current I/In
B:Additional offset time
td:Time-dial to adapt the operation time
The inverse time characteristic (IDMT) is applied after the condition M > 1 is valid.
The operation range is, as defined in the IEC 60255-3 standard, from 1.2 to 20 In.
Each time the protection is started due to a system fault condition (M>1.2), the
IDMT operating counter is incremented according to the equation. When it reaches
the operation time to trip the function operates activating the trip output signal. If
required, a reset type with Inverse time characteristic can be set according to an
equation.
1
+
Btd
⎞
⎟
(8)
tr
⎛
t
=
⎜
M
Where:
70
⎞
td
⎟
P
1
−
(9)
Page 71
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
t:Operation time to reset
tr:Reset time (for M = 0)
M:Ratio of actual current to the pickup current I/In
td:Time-dial to adapt the operation time additionally
REF 542plusREF 542plus
The reset type inverse time characteristic is valid for 0 < M < 1. In this case the
inverse-time overcurrent protection enters the reset state and decrements the
operating counter according to equation above. If the condition is 1 ≤ M < 1.2, the
counter remains unchanged.
Instead of inverse time reset type a definite time can also be selected. The purpose of
the definite reset time is to enable fast clearance of intermittent faults, for example
self-sealing insulation faults, and severe faults, which may produce high
asymmetrical fault currents that partially saturate the current transformers. It is
typical for an intermittent fault that the fault current contains so called drop-off
periods during which the fault current falls below the set start current including
hysteresis. Without the reset time function, the operating counter would be stopped,
when the current has dropped off. In the same way, an apparent drop-off period of
the secondary current of the saturated current transformer might also reset the
operating counter.
The reset type inverse time can only be applied in conjunction with
inverse time overcurrent protection. For definite time overcurrent
protection only reset type definite time may be used.
6.1.3.5.Setting groups
Two parameter sets can be configured for the non-directional overcurrent protection.
A switch over between the parameter sets can be performed in dependency of the
network configuration. If this is not required, set 1 and set 2 can be parameterized
identically to avoid wrong setting if switch over of parameters has happened
accidentally.
71
Page 72
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.3.6.Parameters and events
Table 6.1.3.6.-1Setting values
ParameterValuesUnitDefaultExplanation
StatusOn/OffOnOperating status
ModeInstantaneous/
IDMT
A (ratio multiplier) 0.005 … 200.00013.500Parameter for
P (ratio
exponent)
B (offset time)0.000 … 50.000s0.000Parameter for
Td (time dial)0.050 … 5.000s0.5000Parameter for
Reset typeNot used/Definite
Reset time (Tr)0.020 … 100.000 s1.000Parameter for reset
Start Value0.050 … 40.000In0.5000Current threshold for
Def. operate time 0.015 … 300.000 s0.080Time delay for trip
0.005 … 3.0001.000Parameter for
time/Inverse time
1MRS755860
InstantaneousOperation
characteristic
operation
characteristic
operation
characteristic
operation
characteristic
operation
characteristic
Not usedReset Characteristic
characteristic
start condition
condition
Table 6.1.3.6.-2Events
CodeEvent reason
E0Protection start on phase L1
E1Start on phase L1 cancelled
E2Protection start on phase L2
E3Start on phase L2 cancelled
E4Protection start on phase L3
E5Start on phase L3 cancelled
E6Trip signal is active
E7Trip signal is back to inactive state
E8Protection general start (logical OR combination of all start signal)
E9General start is cancelled (after expiration of the reset time)
E18Protection block signal is active
E19Protection block signal is back to inactive status
By default all events are disabled.
6.1.4.Directional overcurrent protection
In the directional overcurrent protection can up to eight instances be applied.
72
Page 73
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Fig. 6.1.4.-1Directional overcurrent protection
6.1.4.1.Input/output description
Table 6.1.4.1.-1Input
NameTypeDescription
BSDigital signal (active high)Blocking signal
When the BS signal becomes active, the protection function is reset (no matter its
state). This means that all the output pins go low generating the required events (if
any) and all internal registers and timers are cleared. The protection function
remains in idle state until the BS signal goes low.
REF 542plusREF 542plus
A080176
Table 6.1.4.1.-2Output
NameTypeDescription
START L1Digital signal (active high)Start signal of IL1 (fault in set direction)
START L2Digital signal (active high)Start signal of IL2 (fault in set direction)
START L3Digital signal (active high)Start signal of IL3 (fault in set direction)
GEN.STARTDigital signal (active high)General start signal (logical OR combination
of all starts including reset time)
TRIPDigital signal (active high)Trip signal
BODigital signal (active high)Block output signal (fault in opposite direction)
START L1 to L3 are the phase selective start signals. The phase starting signal is
activated when respective phase current start conditions are true (current exceeds the
setting threshold value and the fault is in the specified direction).
GEN. START is a logical OR combination of the start signal START L1 to L3 and
remains active until the reset time, if used, has expired.
The TRIP signal is activated when at least for a phase current the start conditions are
true and the operating time has elapsed.
Block Output (BO) signal becomes active when the protection function detects a
current exceeding the preset value and the fault direction opposite to the specified
direction.
73
Page 74
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.4.2.Configuration
1MRS755860
Fig. 6.1.4.2.-1General
A080178
74
Page 75
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A090008
Fig. 6.1.4.2.-2Fast I/O
Output Channel different from 0 means a direct execution of the trip or general start
command, that is, skipping the FUPLA cyclic evaluation.
Input Channel different from 0 means a direct execution of the block command, that
is, skipping the FUPLA cyclic evaluation.
75
Page 76
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
A080180
Fig. 6.1.4.2.-3Sensors
The protection function operates on any combination of current phases in a triple,
for example, it can operate as single-phase, double-phase or three-phase protection
on the phase currents belonging to the same network. The faulty phase current is
combined with the voltage of the corresponding sound phases. The required voltage
measure is automatically selected and displayed in the General dialog box.
76
Page 77
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A080182
Fig. 6.1.4.2.-4Mode
Status:Mode of the operating status on or off
Mode:Mode for the directional overcurrent, definite or inverse time
IDMT (IEEE):Free programmable inverse-time curve according to equation
A,P,B, Td:Parameter for the free programmable inverse-time curve
t-I Diagram:Diagram of the inverse time operation characteristic
Reset type:Mode of the reset time
Reset time:Timer resets after the start current condition not valid any more
77
Page 78
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
Fig. 6.1.4.2.-5Parameter
Direction:Directional criteria to be accessed together to overcurrent
condition for the start detection
Start Value:Current threshold for start
Def. operate time:Operation time in mode definite time
A080184
78
Page 79
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
Fig. 6.1.4.2.-6Events
A080186
Fig. 6.1.4.2.-7Pins
A080188
79
Page 80
⎝
⎠
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.4.3.Measurement mode
All overcurrent directional protection functions evaluate the current RMS value at
the fundamental frequency.
6.1.4.4.Operation criteria
If the measured current exceeds the setting threshold value (Start Value), the
overcurrent directional protection function is started, if at least the value of one
phase current is above the setting threshold value. At the same time the general start
signal is activated.
If the general start condition exists and the fault is in a specified direction
(backward/forward), the timer for the operation time is started. The start signal
is phase selective. In case of fault in the opposite direction to the specified one, the
Block Output signal becomes active. The protection function remains in START
status if there is at least one phase started. It comes back in passive status and the
start signal is cleared if for all the phases the current falls below 0.95 the setting
threshold value (or the fault current changes direction).
1MRS755860
When the protection has entered the start status and the preset operating time
(Time) has elapsed, the function goes in TRIP status and the trip signal is
generated. The protection function exits the TRIP status and the trip signal is cleared
when the measured current value falls below 0.4 the setting threshold value.
To determine the fault direction, REF 542plus must be connected to the three-phase
voltages. The protection function has a voltage memory, which allows a directional
decision to be produced even if a fault occurs in the close-up area of the voltage
transformer/sensor (when the voltage falls below 0.1 Un).
The inverse time tripping characteristic is defined according to an equation.
A
⎛
t
=
⎜
P
M
−
Where:
t:Operation time to trip
A:Curve parameter for the time value (according to IEC 60255-3)
P:Value for the exponent
M:Ratio of actual current to the pickup current I/In
B:Additional offset time
td:Time dial to adapt the operation time
1
Btd
+
⎞
⎟
(10)
The inverse time characteristic (IDMT) is applied after the condition M > 1 is valid.
The operation range is, as defined in the IEC 60255-3 standard, from 1.2 to 20 In.
80
Page 81
⎝
⎠
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Each time the protection function is started due to a system fault condition (M>1.2)
the IDMT operating counter is incremented according to the equation (1). When it
reaches the operation time to trip, the function will operate activating the trip output
signal.
If required, a reset type with Inverse time characteristic can be set according to an
equation.
tr
⎛
t
=
⎜
M
Where:
t:Operation time to reset
tr:Reset time
M:Ratio of actual current to the pickup current I/In
td:Time dial to adapt the reset time
⎞
td
⎟
P
1
−
REF 542plusREF 542plus
(11)
The reset type inverse time characteristic is valid for 0 < M < 1. In this case the
inverse time overcurrent protection enters the reset state and decrements the
operating counter according to above equation. If the condition is 1 ≤ M < 1.2, the
counter remains unchanged.
Instead of inverse time reset type a definite time can also be selected. The purpose of
the definite reset time is to enable fast clearance of intermittent faults, for example
self-sealing insulation faults, and severe faults, which may produce high
asymmetrical fault currents that partially saturate the current transformers. It is
typical for an intermittent fault that the fault current contains so called drop-off
periods during which the fault current falls below the set start current including
hysteresis. Without the reset time function, the operating counter would be stopped,
when the current has dropped off. In the same way, an apparent drop-off period of
the secondary current of the saturated current transformer might also reset the
operating counter.
The reset type inverse time can only be applied in conjunction with
inverse time overcurrent protection. For definite time overcurrent
protection only reset type definite time may be used.
6.1.4.5.Current direction
Detection of the current direction is obtained by calculating the reactive power,
which is computed combining the faulty phase current with the voltage of the
corresponding sound phases. The reactive power calculation uses voltage and
current measurements at the fundamental frequency. Before the calculations, the
voltages are shifted to a lagging angle of 45°.
81
Page 82
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
QIUIUIU
=××
()
LLL
12312312 3123
sinsinsin
+××
ϕϕϕ
()
××
()
(12)
Where:
QReactive power
IL
1,2,3
U
12,23,31
φ
1,2,3
Current of phase 1, 2 and 3
Line voltages between phases 1-2, 2-3 and 3-1 after shifting -45°
Angles between the currents and the corresponding voltages
Only the phases in which the current exceeds preset threshold are used in the
calculation. If the result of the calculation leads to a negative reactive power, which
is greater than 5% of the nominal apparent power, the fault is in forward direction.
Otherwise, the fault is in backward direction.
A directional signal can be sent to the opposite station using the output (trip) and/or
the Block Output (BO) signal. The content of a directional signal from the opposite
station (BO output) can be used to release tripping of its own directional protective
function. This enables a directional comparison protection to be established.
Fig. 6.1.4.5.-1Forward and backward direction in the impedance plane in case of a
balanced three-phase fault
Because the application of the fault current is in combination with the sound
voltages, the directional decision area can change. This change depends on the
power system parameters in case of nonsymmetrical fault condition. The criteria for
forward and backward direction are derived from the calculated reactive power.
6.1.4.6.Voltage memory
The directional overcurrent protection function includes a voltage memory feature.
This allows a directional decision to be produced even if a fault occurs in the closeup area of the voltage transformer/sensor. At a sudden loss of voltage, a fictive
voltage is used for direction detection. The fictive voltage is the voltage measured
82
Page 83
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
before the fault has occurred, assuming that the voltage is not affected by the fault.
The memory function enables the function block to operate up to 300 seconds after
a total loss of voltage.
When the voltage falls below 0.1 x Un, the fictive voltage is used. The actual
voltage is applied again as soon as the voltage rises above 0.1 x Un for at least 100
ms. The fictive voltage is also discarded if the measured voltage stays below 0.1 x
Un for more than 300 seconds.
6.1.4.7.Setting groups
Two parameter sets can be configured for the directional overcurrent protection
function. Switchover between the parameter sets can be performed in dependency of
the network configuration. If this is not required, set 1 and set 2 can be
parameterized identically to avoid wrong setting if switchover of parameters has
happened accidentally.
REF 542plusREF 542plus
6.1.4.8.Parameters and events
Table 6.1.4.8.-1Parameters
ParameterValuesUnitDefaultExplanation
StatusOn/OffOnOperating status
ModeDefinite time/
IDMT
A (ratio multiplier) 0.005 … 200.00013.500Parameter for operation
P (ratio
exponent)
B (offset time)0.000 … 50.000s0.000Parameter for operation
Td (time dial)0.050 … 5.000s0.5000Parameter for operation
Reset typeNot used/Definite
Reset time (Tr)0.020 … 100.000 s1.000Parameter for reset
DirectionForward/
Start Value0.050 … 40.000In0.5000Current threshold for start
Def. operate time 0.015 … 300.000 s0.080Time delay for trip condition
0.005 … 3.0001.000Parameter for operation
time/Inverse time
backward
Definite time Operation characteristic
characteristic
characteristic
characteristic
characteristic
Not usedReset Characteristic
characteristic
backwardSetting for fault direction
condition
83
Page 84
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
1MRS755860
Protection Functions: Configuration and Settings
Protection manual
Table 6.1.4.8.-2Events
CodeEvent reason
E0Protection start on phase L1 (fault in set direction)
E1Start on phase L1 cancelled
E2Protection start on phase L2 (fault in set direction)
E3Start on phase L2 cancelled
E4Protection start on phase L3 (fault in set direction)
E5Start on phase L3 cancelled
E6Trip signal is active
E7Trip signal is back to inactive state
E8Protection general start (logical OR combination of starts)
E9General start is cancelled (after expiration of reset time)
E16Block signal is active
E17Block signal is back to inactive status
E18Protection block signal is active
E19Protection block signal is back to inactive status
a)
E20Protection operation
E21Operation on phase L1 cancelled
E22Protection operation on phase L2
E23Operation on phase L2 cancelled
E24Protection operation on phase L3
E25Operation on phase L3 cancelled
E26Protection general operation (logical OR combination of all faults)
E27General operation cancelled (after expiration of reset time)
E28Operation on fault direction forward
E29Operation on fault direction backward
E30Operation on fault direction unknown
a)
Protection operation is the start of protection on faults independent on direction
on phase L1
By default all events are disabled.
6.1.5.Overcurrent protection (single stage)
REF 542plus provides three overcurrent definite time protection functions, see the
following figures. Each of them can be independently activated.
Fig. 6.1.5.-1Overcurrent definite time instantaneous (I>>>)
84
A050873
Page 85
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Fig. 6.1.5.-2Overcurrent definite time high set (I>>)
Fig. 6.1.5.-3Overcurrent definite time low set (I>)
6.1.5.1.Input/output description
REF 542plusREF 542plus
A050874
A050875
Table 6.1.5.1.-1Input
NameTypeDescription
BSDigital signal (active high)Blocking signal
When the BS signal becomes active, the protection function is reset (no matter its
state). This means that all the output pins go low generating the required events (if
any) and all the internal registers and timers are cleared. The protection function will
then remain in idle state until BS signal goes low.
Table 6.1.5.1.-2Outputs
NameTypeDescription
S L1Digital signal (active high)Start signal of IL1
S L2Digital signal (active high)Start signal of IL2
S L3Digital signal (active high)Start signal of IL3
TRIPDigital signal (active high)Trip signal
S L1-3 are the start signals phase selective. The phase starting signal will be
activated when the respective phase current start conditions are true.
The TRIP signal will be activated when at least for a phase current the start
conditions are true and the operating time has elapsed.
85
Page 86
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.5.2.Configuration
1MRS755860
Fig. 6.1.5.2.-1General
Fig. 6.1.5.2.-2Fast I/O
A050876
A090010
86
Output Channel different from 0 means a direct execution of the trip or general start
command, that is, skipping the FUPLA cyclic evaluation.
Page 87
1MRS755860
Multifunction Protection and Switchgear Control
Unit
REF 542plusREF 542plus
Protection Functions: Configuration and Settings
Protection manual
Input Channel different from 0 means a direct execution of the block command, that
is, skipping FUPLA cyclic evaluation.
A050877
Fig. 6.1.5.2.-3Sensors
The protection functions operate on any combination of phase currents in a triple,
for example, it can operate as single phase, double phase or three-phase protection
on the phase currents belonging to the same system.
Fig. 6.1.5.2.-4Parameters
A050878
87
Page 88
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Start Value:Current threshold for overcurrent condition detection.
Time:Time delay for overcurrent Trip condition detection.
1MRS755860
Fig. 6.1.5.2.-5Events
Fig. 6.1.5.2.-6Pins
A050879
A050880
88
Page 89
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.5.3.Measurement mode
All overcurrent definite time functions evaluate the current RMS value at the
fundamental frequency. In case of the overcurrent definite time instantaneous, the
peak value of the measured current is also used under transient condition for a faster
response. When the instantaneous peak value is higher than three times SQRT (2)
the RMS value:
REF 542plusREF 542plus
II
xpeakxRMS__
23>⋅
6.1.5.4.Operation criteria
If the measured current exceeds the setting threshold value (Start Value), the
overcurrent protection function is started. The start signal is phase selective, that is,
when at least the value of one phase current is above the setting threshold value the
relevant start signal will be activated.
The protection function will remain in START status until there is at least one phase
started. It will come back in passive status and the start signal will be cleared, if for
all the phases the current falls below 0.95 the setting threshold value. After the
protection has entered the start status and the preset operating time (Time) has
elapsed, function goes in TRIP status and the trip signal is generated.
The protection function will exit the TRIP status and the trip signal will be cleared
when the measured current value falls below 0.4 the setting threshold value.
All overcurrent definite time functions can be used in parallel to generate a current
time-step characteristic, as shown in the following figure.
(13)
Fig. 6.1.5.4.-1Current time-step characteristic
A050882
89
Page 90
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.5.5.Setting groups
Two parameter sets can be configured for each of the overcurrent definite time
protection functions.
6.1.5.6.Parameters and events
Table 6.1.5.6.-1Setting values
ParameterValuesUnitDefaultExplanation
Start Value I>,
I>>
Time20 ... 300000ms80Time delay for overcurrent
Start Value I>>>0.1 ... 40.00In0.50Current threshold for
Time15 ... 30000ms80Time delay for overcurrent
0.05 ... 40.00In0.50Current threshold for
1MRS755860
overcurrent condition
detection.
Trip condition.
overcurrent condition
detection.
Trip condition.
Table 6.1.5.6.-2Events
CodeEvent reason
E0Protection start on phase L1
E1Start on phase L1 cancelled
E2Protection start on phase L2
E3Start on phase L2 cancelled
E4Protection start on phase L3
E5Start on phase L3 cancelled
E6Trip signal is active
E7Trip signal is back to inactive state
E18Protection block signal is active
E19Protection block signal is back to inactive state
REF 542plus has two directional definite time functions, each of which can be
independently activated:
90
A050825
Fig. 6.1.6.-1Overcurrent directional high set (I>>>)
Page 91
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Fig. 6.1.6.-2Overcurrent directional low set (I>>)
6.1.6.1.Input/output description
Table 6.1.6.1.-1Input
NameTypeDescription
BSDigital signal (active high)Blocking signal
When the BS signal becomes active, the protection function is reset (no matter its
state). This means that all the output pins go low generating the required events (if
any) and all the internal registers and timers are cleared. The protection function will
then remain in idle state until the BS signal goes low.
REF 542plusREF 542plus
A050826
Table 6.1.6.1.-2Outputs
NameTypeDescription
S L1Digital signal (active high)Start signal of IL1
S L2Digital signal (active high)Start signal of IL2
S L3Digital signal (active high)Start signal of IL3
TRIPDigital signal (active high)Trip signal
BODigital signal (active high)Block output signal
S L1-3 are the start signals phase selective. The phase starting signal will be
activated when respective phase current start conditions are true (current exceeds the
setting threshold value and the fault is in the specified direction).
The TRIP signal will be activated when at least for a phase current the start
conditions are true and the operating time has elapsed.
The Block Output (BO) signal becomes active when the protection function detects
a current exceeding the preset value and the fault direction opposite to the specified
direction.
91
Page 92
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.6.2.Configuration
1MRS755860
Fig. 6.1.6.2.-1General
Fig. 6.1.6.2.-2Fast I/O
A050827
A090012
92
Output Channel different from 0 means a direct execution of the trip, general start or
block-out command, that is, skipping the FUPLA cyclic evaluation.
Page 93
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
REF 542plusREF 542plus
A050828
Fig. 6.1.6.2.-3Sensors
The protection function operates on any combination of current phases in a triple,
for example, it can operate as single phase, double phase or three-phase protection
on the phase currents belonging to the same system.
The faulty phase current is combined with the voltage of the corresponding sound
phases. The required voltage measure is automatically selected and displayed in the
General dialog.
Fig. 6.1.6.2.-4Parameters
A050829
93
Page 94
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
1MRS755860
Protection Functions: Configuration and Settings
Protection manual
Direction:Directional criteria to be assessed together to overcurrent
condition for the START detection.
Start Value:Current threshold for overcurrent condition detection.
Time:Time delay for overcurrent trip condition detection.
Fig. 6.1.6.2.-5Events
Fig. 6.1.6.2.-6Pins
A050830
A050871
94
Page 95
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.6.3.Measurement mode
The directional overcurrent protection function evaluates the current and voltage at
the fundamental frequency.
6.1.6.4.Operation criteria
If the measured current exceeds the setting threshold value (Start Value), and
the fault is in the specified direction (backward/forward), the protection
function is started. The start signal is phase selective. It means that when at least for
one phase current the above conditions are true, the relevant start signal will be
activated.
If the preset threshold value (Start Value) is exceeded and the fault is in the
opposite direction to the specified one, the Block Output signal becomes active. The
protection function will remain in START status until there is at least one phase
started. It will come back in passive status and the start signal will be cleared if for
all the phases the current falls below 0.95 the setting threshold value (or the fault
current changes direction).
REF 542plusREF 542plus
When the protection has entered the start status and the preset operating time
(Time) has elapsed, the function goes in TRIP status and the trip signal is
generated.
The protection function will exit the TRIP status and the trip signal will be cleared
when the measured current value falls below 0.4 the setting threshold value.
To determine the fault direction REF 542plus must be connected to the three-phase
voltages. The protection function has a voltage memory, which allows a directional
decision to be produced even if a fault occurs in the close up area of the voltage
transformer/sensor (when the voltage falls below 0.1 x Un).
6.1.6.5.Current direction
Detection of the current direction is obtained by calculating the reactive power,
which is computed combining the faulty phase current with the voltage of the
corresponding sound phases. The reactive power calculation uses voltage and
current measurements at the fundamental frequency. Before the calculations, the
voltages are shifted to a lagging angle of 45°.
The reactive power is calculated like the following:
Q
=××+
(sin)
IU
L123
××+ ××
(sin)(sin)
IUIU
L231L312
ϕ
1
(14)
ϕϕ
23
95
Page 96
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
Where is:
QReactive power
I
L1,2,3
U
12,23,31
φ
1,2,3
Current of phase 1, 2 and 3
Line voltages between phases 1-2, 2-3 and 3-1 after shifting -45°
Angles between the currents and the corresponding voltages
1MRS755860
Only the phases whose current exceeds preset threshold are used in the calculation.
If the result of the calculation leads to a negative reactive power, which is greater
than 5% of the nominal apparent power, the fault is in forward direction. Otherwise,
the fault is in backward direction.
A directional signal can be sent to the opposite station using the output (trip) and/or
the Block Output (BO) signal. The content of a directional signal from the opposite
station (BO output) can be used to release tripping of its own directional protective
function. This enables a directional comparison protection to be established.
Fig. 6.1.6.5.-1 shows the forward and backward direction in the impedance plane in
case of a balanced three-phase fault.
A052091
Fig. 6.1.6.5.-1Diagram of the directional overcurrent protection in case of balanced
three-phase faults
Because the application of the fault-current is in combination with the sound
voltages, the directional decision area can change. This change depends on the
power system parameters in case of nonsymmetrical fault condition. The criteria for
forward and backward direction is derived from the calculated reactive power.
6.1.6.6.Voltage memory
The directional overcurrent protection function includes a voltage memory feature.
This allows a directional decision to be produced even if a fault occurs in the close
up area of the voltage transformer/sensor.
96
Page 97
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
At a sudden loss of voltage, a fictive voltage is used for direction detection. The
fictive voltage is the voltage measured before the fault has occurred, assuming that
the voltage is not affected by the fault. The memory function enables the function
block to operate up to 300 seconds after a total loss of voltage.
When the voltage falls below 0.1 x Un, the fictive voltage is used. The actual
voltage is applied again as soon as the voltage rises above 0.1 x Un for at least 100
ms. The fictive voltage is also discarded if the measured voltage stays below 0.1 x
Un for more than 300 seconds.
6.1.6.7.Setting groups
Two parameter sets can be configured for each of the overcurrent directional definite
time protection functions.
6.1.6.8.Parameters and events
REF 542plusREF 542plus
Table 6.1.6.8.-1Setting values
ParameterValuesUnitDefaultExplanation
Start Value0.05 ... 40In0.2Current threshold for fault
detection.
Time40 ... 30000ms80Operating Time between start
and trip.
Directionforward/
backward
-backward Direction criteria.
Table 6.1.6.8.-2Events
CodeEvent reason
E0Protection start on phase L1
E1Start on phase L1 cancelled
E2Protection start on phase L2
E3Start on phase L2 cancelled
E4Protection start on phase L3
E5Start on phase L3 cancelled
E6Trip signal is active
E7Trip signal is back to inactive state
E16Block signal is active
E17Block signal is back
E18Protection block started
E19Protection block back
By default all events are disabled.
6.1.7.Overcurrent IDMT (single stage)
REF 542plus makes available an IDMT function in which one at the time of the four
current-time characteristics can be activated:
97
Page 98
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
*
Normal inverse
*
Very inverse
*
Extremely inverse
*
Long-term inverse
Fig. 6.1.7.-1Overcurrent IDMT
6.1.7.1.Input/output description
Table 6.1.7.1.-1Input
NameTypeDescription
BSDigital signal (active high)Blocking signal
1MRS755860
A050883
When the BS signal becomes active, the protection function is reset (no matter its
state). This means that all the output pins go low generating the required events (if
any) and all the internal registers and timers are cleared. The protection function will
then remain in idle state until the BS signal goes low.
Table 6.1.7.1.-2Output
NameTypeDescription
S L1Digital signal (active high)Start signal of IL1
S L2Digital signal (active high)Start signal of IL2
S L3Digital signal (active high)Start signal of IL3
TRIPDigital signal (active high)Trip signal
S L1-3 are the start signals phase selective. The phase starting signal will be
activated when the respective phase current start conditions are true (the phase
current value is above 1.2 times the setting threshold value).
The TRIP signal will be activated when at least for a phase current the start
conditions are true and the calculated operating time has elapsed.
98
Page 99
1MRS755860
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
6.1.7.2.Configuration
REF 542plusREF 542plus
Fig. 6.1.7.2.-1General
Fig. 6.1.7.2.-2Fast I/O
A050884
A090014
Output Channel different from 0 means a direct execution of the trip or general start
command, that is, skipping the FUPLA cyclic evaluation.
Input Channel different from 0 means a direct execution of the block command, that
is, skipping the FUPLA cyclic evaluation.
99
Page 100
REF 542plusREF 542plus
Multifunction Protection and Switchgear Control
Unit
Protection Functions: Configuration and Settings
Protection manual
1MRS755860
Fig. 6.1.7.2.-3IDMT type
Fig. 6.1.7.2.-4Sensors
A050885
A050886
100
The protection functions operate on any combination of phase currents in a triple,
for example, it can operate as single phase, double phase or three-phase protection
on phase currents belonging to the same system.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.