6
6
Designed for motor currents from 3 to 45 A, PSR Softstarters complement the existing advanced PST Softstarters for 30 - 1050 A and the fl exible PSS Softstarters for 30
- 1050 A. The PSR Sofstarter is compact and easily accessible for installation in places where space is limited.
The PSR range comprises three physical sizes with widths from 45 to 54mm, covers rated currents from 3 to 45 A and is available for supply voltages of 24 VDC or 100-240 VAC. All sizes include a Run signal relay while sizes from 25 A also have an output signal for TOR (Top of Ramp, i.e., full voltage).
Cooling function
With standard performance, the PSR Softstarters handle ten starts per hour. When an auxiliary cooling fan is added, the starting capacity is increased to 20 starts per hour.
Installation
The PSR Softstarter is easy to set and operate thanks to the clearly marked settings. All terminals are distinctly marked and easily accessible for cable connecction. Both screw and DIN rail mounting are possible.
Flexible communication
PSR can also be remote controlled by bus communication using ABB's FieldBusPlug. The FieldBusPlug accessories are available for several protocols such as Profi bus DP and Device Net.
The PSR Softstarter is ideal for the replacement of DOL starters and for installation in places with limited space.
Low Voltage Products & Systems 6.1
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 000 023 C0201
Softstarters
Type PSR
6
6
Type PSR16-600-70
Open
PSR Open type
Connected In-Line Catalog number
PSR3-600-70 PSR3-600-81 PSR6-600-70
PSR6-600-81 PSR9-600-70
PSR9-600-81 PSR12-600-70
PSR12-600-81 PSR16-600-70
PSR16-600-81 PSR25-600-70
PSR25-600-81 PSR30-600-70
PSR30-600-81 PSR37-600-70
PSR37-600-81 PSR45-600-70
PSR45-600-81
Maximum motor current
UL IEC 208V 240V 480V 600V
3.4 3.9 0.5 0.75 2 2
6.1 6.8 1 1.5 3 5
9.0 9.0 2 2 5 7.5
11.0 12.0 3 3 7.5 10
15.2 16.0 3 5 10 10
24.2 25.0 7.5 7.5 15 20
28.0 30.0 7.5 10 20 25
34.0 37.0 10 10 25 30
46.2 45.0 15 15 30 40
Maximum horsepower
Type PSR30-600-70
Type PSR45-600-70
PSR Open type
PSR3 - 600 - 70
Control voltage
70 = 100 - 240 VAC 81 = 24 VDC
Maximum motor current
when connected in-line
Line voltage
208V - 600 VAC
6.2 Low Voltage Products & Systems
1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Loading...
+ 3 hidden pages