Output currents 0.42 A / 0.83 A / 1.3 A / 2.1 A / 2.5 A / 4.2 A
쐍
Power range 10 W, 30 W, 60 W, 100 W
쐍
Wide range input 100-240 V AC (90-264 V AC, 120-370 V DC)
쐍
High effi ciency of up to 89 %
쐍
Low power dissipation and low heating
쐍
Free convection cooling (no forced cooling with ventilators)
쐍
Ambient temperature range during operation -10...+70 °C
쐍
Open-circuit, overload and short-circuit stable
쐍
Integrated input fuse
쐍
U/I characteristic (fold-forward behaviour at overload –
쐍
no switch-off)
LEDs for status indication
쐍
Light-grey enclosure in RAL 7035
쐍
Approvals / Marks
쐍
(depending on device, partly pending):
CP-D range
Benefi ts and advantages
Primary switch mode power supplies
Width and structural form
With their width between 18 to
90 mm only
switch mode power supplies ar
ideally suited for installation in
distribution panels.
Wide range input
Optimised for world-wide
applications: The CP-D power
supplies can be supplied with
90-264 V AC or 120-370 V DC.
2CDC 275 031 F0b07
Adjustable output voltage
The CP-D range types > 10 W
featur
output voltage. Thus, they can
be optimally adapted to the
application, e.g. compensating
the voltage dr
long line length.
, the CP-D range
e a continuously adjustable
e
2CDC 271 027 F00072CDC 276 032 F0007-a
2CDC 276 033 F0007
op caused by a
A, H, D, E / a, b
170 Low Voltage Products & Systems
1SXU 110 079 C0201 ABB Inc. • 888-385-1221 U.S. • 866-222-8368 Mid-West & Pacific Region • 866-460-3300 Ontario • 800-567-0283 Atlantic & Quebec Region • www.abb-control.com/epr8.pdf
NEW
available in
March 2008
Primary switch mode power supplies
CP-D range
Ordering details
2CDC 271 024 F0b07
CP-D 12/0.83,
CP-D 24/0.42
2CDC 271 025 F0b07
CP-D 12/2.1
CP-D 24/1.3
Type
CP-D
12/0.83
CP-D
12/2.1
CP-D
24/0.42
CP-D
24/1.3
CP-D
24/2.5
CP-D
24/4.2
Rated input
voltage
100-240 V AC
100-240 V AC
100-240 V AC
100-240 V AC
100-240 V AC
100-240 V AC
Rated output
voltage /
current
12 V DC /
0.83 A
12 V DC /
2.1 A
24 V DC /
0.42 A
24 V DC /
1.3 A
24 V DC /
2.5 A
24 V DC /
4.2 A
Order code
1SVR 427 041 R1000
1SVR 427 043 R1200
1SVR 427 041 R0000
1SVR 427 043 R0100
1SVR 427 044 R0200
1SVR 427 045 R0400
Pack.
pieces
Price
unit
1 piece
10.06 / 0.13
10.19 / 0.41
10.06 / 0.13
10.19 / 0.41
10.25 / 0.55
10.32 / 0.71
Weight
1 piece
kg / lb
4
2CDC 271 028 F0b07
CP-D 24/2.5
2CDC 271 029 F0b07
CP-D 24/4.2
Low Voltage Products & Systems 171
ABB Inc. • 888-385-1221 U.S. • 866-222-8368 Mid-West & Pacific Region • 866-460-3300 Ontario • 800-567-0283 Atlantic & Quebec Region • www.abb-control.com/epr8.pdf 1SXU 110 079 C0201
Data at Ta = 25 °C, UIN = 230 V AC and rated values, if nothing else indicated
Typ eCP-D 12/0.83CP-D 12/2.1
Input circuit - supply circuitL, N
Rated input voltage U
Input voltage range90-264 V AC /
Frequency range AC47-63 Hz
Typical input current /
typical power consumption
Inrush currentat 230 V AC30 A (max. 3 ms)50 A (max. 3 ms)
Power failure buffering> 30 ms
Internal input fuse1 A slow-acting /
Indication of operational states
Output voltageDC ON: green LED
Output circuit+, -++, --
Rated output voltage12 V DC
Tolerance of the output voltage±1 %
Adjustment range of the output voltage-12-14 V DC
Rated output power10 W30 W
Rated output current I
Derating of the output current60 °C < T
Deviation with load changestaticalmax. 1 %
Control time< 1 ms
Starting time after applying the supply voltageat I
Response timeat rated loadtyp. 1 ms
Residual ripple and switching peaksBW = 20 MHz50 mV
Parallel connectionno
Series connectionyes, to increase voltage
Resistance to reverse feed18 V / 1 s
Power factor correction (PFC)no
Output circuit - No-load, overload and short-circuit behaviour
Output curveU/I curve
Short-circuit protectioncontinuous short-circuit statility
Short-circuit behaviourcontinuation with current limitation
Current limitation at short circuittyp. 1.4 Atyp. 5.9 A
Overload protectioncurrent limitation
No-load protectioncontinuous no-load stability
Starting of capacitive loadsunlimited
Gerneral data
Effi ciencytyp. 78 %typ. 82 %
Duty time100 %
Dimensions (WxHxD)18 x 91 x 57.5 mm
Weight0.06 kg (0.13 lb)0.19 kg (0.41 lb)
Material of enclosureplastic
MountingDIN rail (EN 60715), snap-on mounting without any tool
Mounting positionhorizontal
Minimum distance to other unitshorizontal / vertical25 mm / 25 mm (0.98 in / 0.98 in)
Degree of protectionenclosure / terminalsIP20 / IP20
Protection classII
IN
r
change of input voltage within the input voltage rangemax. 1 %
CP-D range
Technical data
DC LOW: red LED
dynamical 10-90%
100-240 V AC
120-370 V DC
at 110 V AC200 mA / 12.68 W502 mA / 31.14 W
at 230 V AC128.3 mA / 13.01 W277 mA / 31.2 W
250 V AC
2 A slow-acting /
250 V AC
V: output voltage applied
V: output voltage too low
Ta 울 60 °C0.83 A2.1 A
울 70 °C2.5 %/K
a
r
[0.71 x 3.58 x 2.26 in]
1000 ms
53 x 91 x 57.5 mm
[2.09 x 3.58 x 2.26 in]
Primary switch mode power supplies
172 Low Voltage Products & Systems
1SXU 110 079 C0201 ABB Inc. • 888-385-1221 U.S. • 866-222-8368 Mid-West & Pacific Region • 866-460-3300 Ontario • 800-567-0283 Atlantic & Quebec Region • www.abb-control.com/epr8.pdf
NEW
available in
March 2008
Data at Ta = 25 °C, UIN = 230 V AC and rated values, if nothing else indicated
Stripping length6 mm (0.24 in)
Tightening torque0.36-0.56 Nm
Environmental data
Ambient temperature rangeoperation-25…+70 °C
Damp heat (cyclic) (IEC/EN 60068-2-30)4 x 24 cycles, 40 °C, 95 % RH
Vibration (sinusoidal) (IEC/EN 60068-2-6)50 m/s
Shock (half-sine) (IEC/EN 60068-2-27)40 m/s
Isolation data
Rated insulation voltage U
Pollution category2
Standards
Product standardEN 61204
Low Voltage Directive2006/95/EC
EMC Direcitve2004/108/EC
Electrical safetyUL 508, UL 60950-1, EN 60950-1
Protective low voltageSELV (EN 60950-1)
ABB Inc. • 888-385-1221 U.S. • 866-222-8368 Mid-West & Pacific Region • 866-460-3300 Ontario • 800-567-0283 Atlantic & Quebec Region • www.abb-control.com/epr8.pdf 1SXU 110 079 C0201
4
NEW
available in
March 2008
Data at Ta = 25 °C, UIN = 230 V AC and rated values, if nothing else indicated
Typ eCP-D 24/0.42CP-D 24/1.3CP-D 24/2.5CP-D 24/4.2
Input circuit - supply circuitL, N
Rated input voltage U
Input voltage range90-265 V AC /
Frequency range AC47-63 Hz
Typical input current /
typical power consumption
Inrush currentat 230 V AC 30 A (max. 3 ms) 50 A (max. 3 ms)60 A (max. 3 ms)
Power failure buffering> 30 ms> 60 ms
Internal input fuse
Indication of operational states
Output voltageDC ON: green LED
Output circuit+, -++, --
Rated output voltage24 V DC
Tolerance of the output voltage±1 %
Adjustment range of the output voltage-24-28 V DC
Rated output power10 W30 W60 W100 W
Rated output current I
Derating of the output current60 °C < T
Deviation with load changestaticalmax. 1 %
Control time< 1 ms
Starting time after applying the supply voltageat I
Response timeat rated loadtyp. 1 ms
Residual ripple and switching peaksBW = 20 MHz50 mV
Parallel connectionno
Series connectionyes, to increase voltage
Resistance to reverse feed35 V / 1 s
Power factor correction (PFC)no
Output circuit - No-load, overload and short-circuit behaviour
Output curveU/I curve
Short-circuit protectioncontinuous short circuit statility
Short-circuit behaviourcontinuation with current limitation
Current limitation at short circuittyp. 0.78 Atyp. 4.2 Atyp. 6.05 Atyp. 11.5 A
Overload protectioncurrent limitation
No-load protectioncontinuous no-load stability
Starting of capacitive loadsunlimited
Weight0.06 kg (0.13 lb)0.19 kg (0.41 lb)0.25 kg (0.55 lb) 0.32 kg / (0.72 lb)
Material of enclosureplastic
MountingDIN rail (EN 60715), snap-on mounting without any tool
Mounting positionhorizontal
Minimum distance to other unitshorizontal / vertical25 mm / 25 mm (0.98 in / 0.98 in)
Degree of protectionenclosure / terminalsIP20 / IP20
Protection classII
IN
r
change of input voltage within the input voltage rangemax. 1 %
CP-D range
Technical data
DC LOW: red LED
dynamical 10-90%
100-240 V AC
120-370 V DC
at 110 V AC
at 230 V AC 120.6 mA / 12 W 344 mA / 38.16 W 660 mA / 70.1 W 900 mA / 114.4 W
184 mA / 11.62 W 600 mA / 37.92 W 1120 mA / 69.3 W
1 A slow-acting /
250 V AC
2 A slow-acting /
250 V AC
1800 mA / 117.3 W
3.15 A slow-acting /
250 V AC
V: output voltage applied
V: output voltage too low
Ta 울 60 °C0.42 A1.3 A2.5 A4.2 A
울 70 °C2.5 %/K
a
2.26 in]
1000 ms
71 x 91 x 57.5 mm
[2.80 x 3.58 x
2.26 in]
89.9 x 91 x 57,5 mm
[3.54 x 3.58 x
2.26 in]
r
18 x 91 x 57.5 mm
[0.71 x 3.58 x
2.26 in]
53 x 91 x 57.5 mm
[2.09 x 3.58 x
Primary switch mode power supplies
174 Low Voltage Products & Systems
1SXU 110 079 C0201 ABB Inc. • 888-385-1221 U.S. • 866-222-8368 Mid-West & Pacific Region • 866-460-3300 Ontario • 800-567-0283 Atlantic & Quebec Region • www.abb-control.com/epr8.pdf
NEW
available in
March 2008
Data at Ta = 25 °C, UIN = 230 V AC and rated values, if nothing else indicated
Typ eCP-D 24/0.42CP-D 24/1.3CP-D 24/2.5CP-D 24/4.2
Stripping length6 mm (0.24 in)
Tightening torque0.36-0.56 Nm
Environmental data
Ambient temperature rangeoperation-25…+70 °C
Damp heat (cyclic) (IEC/EN 60068-2-30)4 x 24 cycles, 40 °C, 95 % RH
Vibration (sinusoidal) (IEC/EN 60068-2-6)50 m/s
Shock (half-sine) (IEC/EN 60068-2-27)40 m/s
Isolation data
Rated insulation voltage U
Pollution category2
Standards
Product standardEN 61204
Low Voltage Directive2006/95/EC
EMC Direcitve2004/108/EC
Electrical safetyUL 508, UL 60950-1, EN 60950-1
Protective low voltageSELV (EN 60950-1)