supply family. In terms of design and functionality,
the new range perfectly supplements the existing
products and extends the range appropriately.
The devices can be supplied with a three-phase
voltage as well as with two-phase mains. Here,
ABB offers a power supply unit with 48 V DC
output with 20 A and efficiency of up to 93 %. As
in the case of all products, they are designed for
an ambient temperature of up to 70 °C.
2CDC 271 049 S0009
Characteristics
– Rated output voltage 48 V DC
– Output voltage adjustable via front-face rotary
potentiometer “OUTPUT Adjust“
– Active current balancing for parallel mode
– Rated output current 20 A
– Rated output power 960 W
– Wide supply voltage range 3 x 400-500 V AC
(340-575 V AC, 480-820 V DC)
– Two-phase supply with a derating of the output to 75 %
possible / permitted
– High efficiency of up to 93 %
– Low power dissipation and low heating
– Free convection cooling (no forced cooling with
ventilators)
– Ambient temperature range during operation -40...+70 °C
– Open-circuit, overload and short-circuit stable
– Integrated input fuse
ANSI/ISA-12.12 (Class I, Div. 2, Hazardous Locations),
H
CAN/CSA C22.2 No. 213
UL 60950, CAN/CSA C22.2 No. 60950
H
GB4943, GB9254, GB17625.1
R
GOST
D
1)
Approvals refer to rated input voltage U
Marks
CE
a
C-Tick pending
b
1)
in
1)
1)
Page 2
1 Wide input range
INPUT L1, L2, L3, PE: terminals - input
Optimised for worldwide applications: The CP-T
power supply units can be supplied for a wide range
of AC and DC voltages. Both kinds of power supply
(three-phase and two-phase) are possible.
2 Circuit diagram
2CDC 271 049 S0009
3 Adjustable output voltage
OUTPUT Adjust: potentiometer
The CP-T range types feature a continuously
adjustable output voltage. Thus, they can be optimally
adapted to the application, e.g. compensating the
1
23 456
voltage drop caused by a long cable length.
4 Indication of operational states
OUTPUT LOW: red LED - output voltage too low
OUTPUT OK: green LED - output voltage OK
5 Current balancing
Current balance CB+, CB-
For active current balancing in parallel operation
6 Output
OUTPUT L+, L+, L-, L-: terminals - output
Application
The primary switch mode power supply offers a three-phase supply voltage range of 3 x 400-500 V AC. A two-phase power
supply is also possible and it can also be supplied by 480-820 V DC. Furthermore, this power supply unit is equipped with
two generous capacitors, which ensure mains buffering of at least 15 ms. That is why the devices can be used worldwide
also in high fluctuating networks and battery-powered plants.
Operating mode
By means of the potentiometer “OUTPUT Adjust“ the output voltage can be adjusted within a range of 47-56 V DC. Thus,
the power supply can be optimally adapted to the application, e.g. compensating the voltage drop caused by a long line
length.
The green LED “OUTPUT OK“ is lightening during proper operation, i. e. when the output voltage exceeds 75 %.
The red LED “OUTPUT LOW“ is lightening when the output voltage is less than 70 % of the rated output voltage.
Two-phase supply is permissible with a derating of the output to 75 %.
2 - Power supply CP-T 48/20.0 | Data sheet
Page 3
Installation
The device must be installed by qualified persons only and in accordance with the specific national regulations (e.g. VDE, etc.).
The devices are maintenance-free chassis-mounted units.
Before installation
DANGER!
Components with high stored energy and circuits with high voltage
Danger to be electrocuted!
►Disconnect the system from the supply network and protect against switching on before any installation,
maintenance or modification work.
►Do not introduce any objects into the unit and do not open the unit.
►Ensure that the service personnel is protected against inadvertent contact with parts carrying energy.
Mounting
The switch mode power supply can be snapped on a DIN rail (TH 35-15 or TH 35-7.5 according to IEC/EN 60715) as
shown in the accompanying picture. For that the device is set with its mounting rail slide on the upper edge of the mounting
rail and locked by lifting it downwards.
2CDC 272 016 F0010
Demounting
Remove the switch mode power supply as shown in the accompanying picture. For that the latching lever is pulled
downwards by means of the screwdriver. Alternatively you can press the unlock button to release the device. Then in both
cases the device can be unhinged from the mounting rail edge and removed.
2CDC 272 017 F0010
Mounting position
The devices have to be mounted horizontally with the input terminals on the bottom. In order to ensure a sufficient
convection, the minimum distance to other modules should not be less than 25 mm (0.98 in) in vertical and horizontal
direction.
[B]
[A]
L1 L2 L3
L2
L3
L+L1
PWM
L+
LL-
[B]
CP-T 48/20.0
13 14
L+ L+ L- L-
[A]
2CDC 272 014 F0010
Data sheet| Power supply CP-T 48/20.0 - 3
Page 4
Electrical connection
o
L+L-L+L-
L2
L3
PWM
o
L1 L2 L3
L+L1
L+
LL-
CB+ CB-
L+, L- Output voltage
L1, L2, L3 Input voltage
o Protective earth
CB+, CB- Current balance
2CDC 272 008 F0010
Connection diagram
Preparations:
–Connect to main according to the specific national regulations.
–Power supply cables and unit must be sufficiently fused. A disconnecting device has to be provided for the power
supply to disengage unit and supply cables from supply mains if required.
–We recommend to choose the cable section as large as possible in order to minimize voltage drops.
–In order to ensure sufficient air-cooling the distance to other devices has to be considered.
Instructions:
1. Connect the input terminals L1, L2 and L3.
2. Connect the protective earth conductor to the terminal o (protection class I).
3. Provide a suitable disconnecting device (e.g. line protection switch) in the supply line acc. to IEC/EN 60950.
4. Rate the lines for the maximum output current (considering the short-circuit current) or provide a separate fuse
protection. The input side is protected by an internal input fuse.
5. Observe the polarity.
The device is overload, short-circuit and open-circuit proof. The secondary side of the power supply unit is electrically
isolated from the input and internally not earthed (SELV) and can therefore be earthed by the user according to the needs
with L+ or L- (PELV).
Operation
DANGER!
High current
Risk of electric arcs and electric shocks!
►Do not modify the installation (primary and secondary side).
►Intended use.
CAUTION!
Depending on the operation conditions the enclosure can become very hot
Risk of burns!
►In order to ensure sufficient air-cooling the distance to other devices has to be considered.
The device is intended for use as a primary switch mode power supply. Any other usage is not supported by the
manufacturer. Other usage may impair safety and cause operational difficulties or destruction of the unit.
Service
The internal fuse is not user-replaceable. If the internal fuse blows, most probably the device is defective. In this case, an
examination of the switch mode power supply by the manufacturer is necessary.
4 - Power supply CP-T 48/20.0 | Data sheet
Page 5
Technical data
Data at Ta = 25 °C, Uin = 3 x 400 V AC and rated values, unless otherwise indicated
Input circuit - supply circuitL1, L2, L3
Rated input voltage U
Input voltage range340-575 V AC
Frequency range AC47-63 Hz
Typical current consumption1,72 A
Typical power consumption1050 W
Inrush current limiting30 A
Power failure buffering timemin. 15 ms
Internal input fuseper phase T5 A / 500 V AC
Recommended backup fuse3 pole miniature circuit breaker ABB type S 203
Power factor correction (PFC)yes, passive, 0.8
Discharge / leakage currenttowards PE < 3.5 mA
Indication of operational states
Output voltageOUTPUT OK: green LED output voltage OK
in
characteristic B or C
max. rating 20 A
input / output < 0.25 mA
OUTPUT LOW: red LED output voltage too low
3 x 400-500 V AC
480-820 V DC
Output circuitL+, L+, L-, L-
Rated output power960 W
Rated output voltage48 V DC
Tolerance of the output voltage0...+1 %
Adjustment range of the output voltage47-56 V DC
Rated output current I
Derating of the output current60 °C < Ta ≤ 70 °C 3.5 %/°C
Maximum deviation withload change statical ±1 % (single mode)
Control timeat rated load < 2 ms
Starting time after applying the supply voltageat Irmax. 1 s
Rise timeat rated load max. 150 ms
Fall timemax. 150 ms
Residual ripple and switching peaksBW = 20 MHz 80 mV
Parallel connectionto increase power, up to 2 devices,
Series connectionyes, to increase voltage, max. 2 devices
r
change of output voltage within the
input voltage range
Ta ≤ 60 °C 20 A
±5 % (parallel mode)
±0.5 %
with 7000 µF max. 1.5 s
with 7000 µF max. 500 ms
min. 0.1 Ir - max. 0.9 Ir
use active current balancing
Data sheet | Power supply CP-T 48/20.0 - 5
Page 6
Output circuit - no-load, overload and short-circuit behaviour
Characterstic curve of outputhiccup mode / fold back behaviour