ABB IEC 60947-3 Technical Data

0 (0)
ABB IEC 60947-3 Technical Data

SwitchLine

OT change-over switches 160 - 800

Technical data

Technical data according to IEC 60947-3

Switch size

 

 

 

 

 

OT160_

OT200_

OT250_

OT315_

OT400_

OT630_

OT800_

Rated insulation voltage and rated

Pollution

 

 

 

 

 

 

 

 

 

 

 

operational voltage AC-20, DC-20

degree 3

 

 

 

V

1 000

1 000

1 000

1 000

1 000

1 000

1 000

Dielectric strength

 

 

50 Hz 1min.

kV

10

10

10

10

10

10

10

Rated impulse withstand voltage

 

 

 

 

kV

12

12

12

12

12

12

12

Rated thermal current and rated

 

 

 

 

 

 

 

 

 

 

 

 

operational current AC-20, DC-20

 

 

 

 

 

 

 

 

 

 

 

 

in ambient 40 °C

In open air

 

 

 

A

160

200

250

315

400

630

800

 

In enclosure

 

 

 

A

160

200

250

315

400

630

800

...with minimum cable cross section

 

 

 

Cu

mm2

70

95

120

185

240

2x185

2x240

Rated operational current, AC-21A

 

 

≤ 500 V

A

160

200

250

315

400

630

800

 

 

 

 

690 V

A

160

200

250

315

400

630

800

Rated operational current, AC-22A

 

 

≤ 500 V

A

160

200

250

315

400

630

800

 

 

 

 

690 V

A

160

200

250

315

400

630

800

Rated operational current, AC-23A

 

 

≤ 500 V

A

160

200

250

315

400

630

800

 

 

 

 

690 V

A

160

200

250

315

400

630

800

Rated operational power, AC-23 1)

 

 

 

230 V

kW

45

55

75

90

132

200

250

 

 

 

 

400 V

kW

90

110

132

160

200

355

400

 

 

 

 

415 V

kW

90

110

132

160

200

355

400

 

 

 

 

500 V

kW

110

132

160

200

250

400

560

 

 

 

 

690 V

kW

132

160

250

315

400

630

800

Rated breaking capacity in

 

 

≤ 500 V

A

1280

1600

2000

2520

3200

5040

6400

category AC-23

 

 

 

690 V

A

1280

1600

2000

2520

3200

5040

6400

Rated conditional short-circuit

Ip (R.M.S.)

100 kA, 500 V

kA

40.5

40.5

40.5

61.5

61.5

75

75

current Ip (R.M.S.) and

Max. OFA_

 

 

 

 

 

 

 

 

 

 

 

corresponding max. allowed

fuse size

 

 

 

A

315/315

315/315

315/315

500/450

500/450

800/800

800/800

cut-off current îc peak value

gG/aM

 

 

 

 

 

 

 

 

 

 

 

The cut-off current îc refers to

Ip (R.M.S.)

 

80 kA, 690 V

kA

40.5

40.5

40.5

59

59

70

70

values listed by fuse

Max. OFA_

 

 

 

 

 

 

 

 

 

 

 

manufacturers (single phase

fuse size

 

 

 

A

355/315

355/315

355/315

500/500

500/500

800/1000

800/1000

test acc. to IEC60269).

gG/aM

 

 

 

 

 

 

 

 

 

 

 

Rated short-time withstand current

R.M.S. value Icw

 

690 V 0,15s

kA

15

15

15

31

31

38

38

 

 

 

690 V 0,25s

kA

15

15

15

24

24

36

36

 

 

 

690 V

1s

kA

8

8

8

15

15

20

20

Rated short-time making capacity

Peak value Icm

 

 

690 V

kA

30

30

30

65

65

80

80

Mechanical endurance

Divide by four for

 

 

 

 

 

 

 

 

 

 

 

 

oper. cycles 2)

 

 

 

Oper.

16 000

16 000

16 000

16 000

16 000

10 000

10 000

Weight without accessories

3-pole switch

 

 

 

kg

2.5

2.5

2.5

4.7

4.7

12.8

12.8

 

4-pole switch

 

 

 

kg

3.2

3.2

3.2

5.8

5.8

15.6

15.6

Terminal bolt size

Metric thread

 

 

 

 

 

 

 

 

 

 

 

 

diameter x length

 

 

 

mm

M8x25

M8x25

M8x25

M10x30

M10x30

M12x40

M12x40

Terminal tightening torque

Counter torque

 

 

 

 

 

 

 

 

 

 

 

 

required

 

 

 

Nm

15-22

15-22

15-22

30-44

30-44

50-75

50-75

Operating torque

Typical for 3-pole

 

 

 

 

 

 

 

 

 

 

 

 

switch fuses

 

 

 

Nm

7

7

7

16

16

27

27

1)These values are given for guidance and may vary acc. to the motor manufacturer.

2)Operating cycle: 0 - I - 0 - II - 0.

6