ABB IEC 60947-3 Technical Data

SwitchLine OT change-over switches 160 - 800 Technical data
Technical data according to IEC 60947-3
Switch size OT160_ OT200_ OT250_ OT315_ OT400_ OT630_ OT800_
Rated insulation voltage and rated Pollution operational voltage AC-20, DC-20 degree 3 V 1 000 1 000 1 000 1 000 1 000 1 000 1 000 Dielectric strength 50 Hz 1min. kV 10 10 10 10 10 10 10 Rated impulse withstand voltage kV 12 12 12 12 12 12 12 Rated thermal current and rated operational current AC-20, DC-20 in ambient 40 °C In open air A 160 200 250 315 400 630 800 In enclosure A 160 200 250 315 400 630 800 ...with minimum cable cross section Cu mm
Rated operational current, AC-21A ≤ 500 V A 160 200 250 315 400 630 800 690 V A 160 200 250 315 400 630 800
Rated operational current, AC-22A ≤ 500 V A 160 200 250 315 400 630 800 690 V A 160 200 250 315 400 630 800
Rated operational current, AC-23A ≤ 500 V A 160 200 250 315 400 630 800 690 V A 160 200 250 315 400 630 800
Rated operational power, AC-23 400 V kW 90 110 132 160 200 355 400 415 V kW 90 110 132 160 200 355 400 500 V kW 110 132 160 200 250 400 560 690 V kW 132 160 250 315 400 630 800
Rated breaking capacity in ≤ 500 V A 1280 1600 2000 2520 3200 5040 6400 category AC-23 690 V A 1280 1600 2000 2520 3200 5040 6400
Rated conditional short-circuit I current I corresponding max. allowed fuse size A 315/315 315/315 315/315 500/450 500/450 800/800 800/800 cut-off current î
The cut-off current î values listed by fuse Max. OFA_ manufacturers (single phase fuse size A 355/315 355/315 355/315 500/500 500/500 800/1000 800/1000 test acc. to IEC60269). gG/aM
Rated short-time withstand current R.M.S. value Icw 690 V 0,15s kA 15 15 15 31 31 38 38 690 V 0,25s kA 15 15 15 24 24 36 36 690 V 1s kA 8 8 8 15 15 20 20 Rated short-time making capacity Peak value
Mechanical endurance Divide by four for oper. cycles
Weight without accessories 3-pole switch kg 2.5 2.5 2.5 4.7 4.7 12.8 12.8 4-pole switch kg 3.2 3.2 3.2 5.8 5.8 15.6 15.6
Terminal bolt size Metric thread diameter x length mm M8x25 M8x25 M8x25 M10x30 M10x30 M12x40 M12x40 Terminal tightening torque Counter torque required Nm 15-22 15-22 15-22 30-44 30-44 50-75 50-75 Operating torque Typical for 3-pole switch fuses Nm 7 7 7 16 16 27 27
(R.M.S.) and Max. OFA_
p
peak value gG/aM
c
refers to Ip (R.M.S.) 80 kA, 690 V kA 40.5 40.5 40.5 59 59 70 70
c
1)
230 V kW 45 55 75 90 132 200 250
(R.M.S.) 100 kA, 500 V kA 40.5 40.5 40.5 61.5 61.5 75 75
p
I
690 V kA 30 30 30 65 65 80 80
cm
2)
Oper. 16 000 16 000 16 000 16 000 16 000 10 000 10 000
2
70 95 120 185 240 2x185 2x240
1)
These values are given for guidance and may vary acc. to the motor manufacturer.
2)
Operating cycle: 0 - I - 0 - II - 0.
6
1SCC301011C0201