ABB hd4 Installation And Service Instructions Manual

Medium voltage products
HD4
Installation and service instructions
Index
1. Packing and transport 5
2. Checking on receipt 6
3. Storage 7
4. Handling 8
6. Instructions for circuit-breaker operation 12
7. Installation 13
8. Putting into service 32
9. Periodical checking 34
10. Maintenance operations 34
11. Indications for handling apparatus with SF6 35
12. Spare parts and accessories 36
12-40.5 kV – 630-3600 A – 16-50 kA
3
Make sure that the installation room (spaces, divisions
and ambient) are suitable for the electrical apparatus.
Check that all the installation, putting into service and
maintenance operations are carried out by qualified personnel with in-depth knowledge of the apparatus.
Make sure that the standard and legal prescriptions
are complied with during installation, putting into service and maintenance, so that installations according to the rules of good working practice and safety in the work place are constructed.
Strictly follow the information given in this instruction
manual.
Check that the rated performance of the apparatus is
not exceeded during service.
Pay special attention to the danger notes indicated in
the manual by the following symbol:
Check that the personnel operating the apparatus
have this instruction manual to hand as well as the necessary information for correct intervention.
Responsible behaviour safeguards your own and others’ safety!
For any requests, place contact the ABB Assistance Service.
For your safety!
4
I. Introduction
This publication contains the information necessary for installation and putting into service of HD4 medium voltage circuit-breakers. For correct usage of the product, please read this manual carefully. For correct mounting of accessories and/or spare parts please refer to the relevant instructions. Like all the apparatus manufactured by us, the HD4 circuit­breakers are designed for different installation configurations. They do, however, allow further technical-constructional variations (at the customer’s request) to suit special installation requirements. For this reason, the information given below does not always cover special configurations.
Apart from this booklet, it is therefore always necessary to refer to the latest technical documentation available (circuit diagram, wiring diagrams, assembly and installation drawings, any studies of protection co-ordination, etc.), especially with regard to any variations from standardized configurations requested.
All the operations regarding installation, putting
into service, operation and maintenance must be carried out by suitably qualified personnel with in­depth knowledge of the apparatus.
Only use original spare parts for maintenance operations. For further information, also see the technical catalogue of the circuit-breaker and the spare parts catalogue.
II. Programme for the environmental
protection
The HD4 circuit-breakers comply with ISO 14000 Standards (Guidelines for the Environmental Management). The production system of the Medium Voltage factories complies for the environmental protection in terms of energy consumption, raw materials and waste. The environmental impact of the product life cycle is assessed by the LCA - Life Cycle Assessment procedure, which is also the result of a well-focused project phase in the selection of materials, processes and packaging. The Product environmental declaration is available for the HD4 circuit-breakers Production techniques are carried out in order to achieve an easy dismantling and separation of the components at the end of the circuit-breaker life cycle, while optimizing the recycling process.
5
1. Packing and transport
The circuit-breaker is shipped in special packing in the open position with the springs discharged and with absolute pole pressure corresponding with the service value. Each piece of apparatus is protected by a plastic film to prevent any infiltration of water during the loading and unloading stages and to keep the dust off during storage.
Handling and transport must only be carried out by expert and properly trained personnel. Do not remove or alter the switch identification contents and labels. Switches subject to UN3164 standards for transportation by air and / or sea. Safety data sheet: 1VCD850182
6
Caption
A Circuit-breaker nameplate
B Operating mechanism nameplate
1 Type of apparatus
2 Symbols and compliance with Standards
3 Serial number
4 Circuit-breaker characteristics
5 Characteristics of the operating auxiliaries
Nameplate
Fig. 1
A
B
3
4
2
CIRCUIT-BREAKER IEC 62271-100
HD4 ... ... ... CEI 17-1
CLASSIFICATION ... ... ...
SN ... ... ... PR. YEAR ......
M MASS ... Kg Ur
m SF6 mass for circuit-breaker .... Kg
ELECTRIC DIAGRAM ... ... ... ...
FIG. ... ...
.. ... ... ... OPERATING MECHANISM
-MO1 ... ... ... V
Made by ABB
1
5
Before carrying out any operation, always make
sure that the operating mechanism dprings are discharged and that the apparatus is in the open position.
On receipt, check the state of the apparatus, that the packing is undamaged and that the nameplate data corresponds (see fig. 1) with that specified in the order acknowledgement and in the delivery note. Also make sure that all the materials described in the shipping note are included in the supply. If any damage or irregularity is discovered on unpacking, notify ABB (directly or through the agent or supplier) as soon as possible and in any case within five days of receipt. The apparatus is only supplied with the accessories specified at the time of order and confirmed in the order acknowledgement sent by ABB. The following accompanying documents are inserted in the shipping packing: – Instruction manual (this document) – Test certificate – Identification tag – Fiscal copy of shipping note – Electrical diagram These other documents are sent prior to shipment: – Order acknowledgement – Original copy of shipping note – Any drawings or documents regarding special
configurations/conditions.
2. Checking on receipt
7
3. Storage
In case a storage period is foreseen, on request our workshops will provide a suitable packing to the specified storage conditions. On receipt, the apparatus must be carefully unpacked and checked as described in chapter 2: Checkink on receipt. If immediate installation is not possible and the circuit breaker has to be re-stored again, it is necessary to restore the packaging at least suitable for protection against dust.
Insert hygroscopic substances in the packaging in the quantity of at least one standard pack per apparatus. Therefore, store in a sheltered, well-ventilated area with a dry, non-dusty, non-corrosive atmosphere away from highly flammable materials, with a temperature between -5 °C and +45 °C. In any case, avoid accidental shocks or accommodations that stress the structure of the circuit breaker.
8
1
2
2
2
1
3
4. Handling
Before carrying out any operation, always check that the operating mechanism springs are discharged and that the apparatus is in the open position.
Circuit-breakers up to 24 kV
– To lift and handle the circuit-breaker, use the tool (1) (fig. 2a:
shortest hooks for circuit-breakers up to 17.5 kV; all hooks for 24 kV circuit-breakers).
– Put the hooks (2) in the holes prepared in the circuit-breaker
frame and lift.
– On completion of the operation (and in any case before
putting into service) unhook the lifting tool (1) (fig. 2b) and dismantle the crosspiece (2) by unscrewing the screws (3).
Fig. 2a
36 kV circuit-breakers
– Attach the tools (1) to lift and handle the circuit-breaker
(fig. 2c); – Attach the hooks (2) as illustrated in fig. 2d and lift; – On completion of the operation, remove the tools (1).
Always take great care during handling not to stress the insulating parts and the circuit-breaker terminals.
The apparatus must not be handled by inserting
lifting devices directly under the apparatus itself. Should it be necessary to use this method, place the circuit-breaker on a sturdy supporting surface (see fig. 3).
Fig. 2b
9
1
2
Fig. 2c
Fig. 3 Fig. 2d
10
Fig. 4
Caption
1 Signalling device for state of SF6 pressure (on request)
2 Opening push button
3 Closing push button
4 Operator counter
5 Signalling device for circuit-breaker open/closed
6 Shaft for manual closing spring charging
5. Description
5.1. General features
The HD4 series are sulphur hexafluoride circuit-breakers for indoor installation. For the electrical performance, please refer to the corresponding technical catalogue code 1VCP000004. For special installation conditions please ask ABB. The following versions are available: – fixed – withdrawable for CBE, PowerCube enclosures and CBF
fixed parts
– withdrawable for switchgear: UniGear type ZS1, UniGear
type ZS2, UniGear type ZS3.2
– withdrawable for switchgear: UniSwitch, UniMix and
UniSec.
5.2. Reference Standards
The HD4 series circuit-breakers comply with the following Standards: – IEC 62271-100.
5.3. Fixed circuit-breaker
The fixed circuit-breaker (see fig. 4) corresponds to the basic version complete with a front protection shield and frame. The anchoring holes are drilled in the lower part of the frame. The terminal box, fixed on the upper protection, is available for connection of the circuit-breaker auxiliary circuits. The earthing screw is located on the circuit-breaker side. For further details, refer to the caption of fig. 4.
5.4. Withdrawable circuit-breaker
The withdrawable circuit-breakers (see fig. 5) are consist of a truck on which the supporting structure of the circuit­breaker itself is fixed. The cord with the connector (plug) for connection of the operating mechanism electrical accessories comes out of the front protection of the circuit-breaker.
Fixed circuit-breaker
7 Signalling device for closing springs charged/discharged
8 Characteristics nameplate
9 Terminals (only available for certain versions)
10 Pressure switch (on request)
11 Valve for checking the SF6 gas pressure
12 Resetting button for protection circuit-breaker of geared motor (on request)
10 - 11 (36 kV)
11
Withdrawable circuit-breaker
Caption
1 Signalling device for state of SF6 pressure (on request)
2 Opening push button
3 Closing push button
4 Operator counter
5 Signalling device for circuit-breaker open/closed
6 Shaft for manual closing spring charging
7 Signalling device for closing springs charged/discharged
8 Characteristics nameplate
9 Isolating contacts
Fig. 5
5.5. Enclosures and fixed parts
For information about the enclosures and fixed parts, please consult the relative documentation.
The strikers for activating the contacts (connected/isolated), located in the enclosure or in the switchgear, are fixed in the top part of the circuit-breaker. The slides for activating the segregation shutters of the medium voltage contacts of the enclosure or switchgear are fixed on the sides of the circuit­breaker. The crosspiece for hooking the circuit-breaker for the connection/isolation operation by means of the special operating lever is mounted on the front part of the circuit­breaker truck. The circuit-breaker is completed with the tulip isolating contacts. The withdrawable circuit-breaker is fitted with special locks, on the front crosspiece, which allow hooking into the corresponding joints in the enclosure or fixed part. The locks can only be activated by the handles with the truck resting completely on the crosspiece.
The activating lever (connection/isolation) must be fully inserted. A lock prevents the truck from advancing into the enclosure or fixed part (for example when the earthing switch is closed). With the truck in the middle position between isolated and connected, the lock prevents closure of the circuit-breaker (both mechanical and electrical). On request, a locking magnet can be mounted on the truck which, when de-energised, prevents truck operation.
10 Pressure switch (on request)
11 Valve for checking the SF6 gas pressure
12 Slide for activating the enclosure shutters
13 Truck
14 Locks for hooking into the fixed part
15 Lock activating handles (17)
16 Strikers for activating the contacts located in the enclosure
17 Connector (plug)
18 Resetting button for protection circuit-breaker of geared motor (on request)
10 - 11 (36 kV)
12
7
6
8
3
5
4
1
2
6.1. Safety indications
HD4 circuit-breakers ensure a minimum degree
of protection IP2X if installed under the following
conditions: – fixed version, with protection netting – withdrawable version, installed in a switchgear. Under these conditions, the operator is guaranteed
against accidental contact with moving parts. Should any mechanical operations be carried out
on the circuit-breaker outside the switchgear or
with the protection netting removed, be very careful
of any moving parts. If the operations are prevented, do not force the
mechanical interlocks and check that the operation
sequence is correct. The racking-in and racking-out operations of
the circuit-breaker must be carried out gradually
to prevent any impacts which might deform the
mechanical interlocks.
6.2. Operating and signalling parts
Fig. 6
6.3. Circuit-breaker closing and opening operations (fig. 6)
Circuit-breaker operation can be manual or electrical.
a) Manual operation for spring charging
To manually charge the closing springs, it is necessary fully insert the charging lever into the seat (6) and turn it clockwise until the yellow indicator (7) appears. The force which can normally be applied to the charging lever fitted is 130 N. In any case, the maximum force which can be applied must not exceed 170 N.
b) Electrical operation for spring charging
On request the circuit-breaker can be fitted with the following accessories for electrical operation: – geared motor for automatic charging of the closing springs – shunt closing release – shunt opening release. The geared motor automatically recharges the springs after each closing operation until the yellow indicator (7) appears. Should there be no voltage during charging, the geared motor stops and then starts recharging the springs automatically when the voltage is on again. It is, however, always possible to complete the charging operation manually.
c) Circuit-breaker closing
This operation can only be carried out with the closing springs completely charged. For manual closing, push the push button (3). When there is a shunt closing release, the operation can also be carried out with remote control by means of a control circuit. The indicator (4) shows that closing has been accomplished. In case of earthing truck with making capacity, activate the key lock (in the closed position) and remove the key. This is to prevent accidental opening operations during any maintenance work on the installation.
d) Circuit-breaker opening
For manual opening, push the push button (2). When there is a shunt opening release, the operation can also be carried out with remote control by means of a control circuit. The indicator (4) shows that opening has been accomplished.
Caption
1 Signalling device for state of SF6 pressure (on request)
2 Opening push button
3 Closing push button
4 Operator counter
5 Signalling device for circuit-breaker open/closed
6 Shaft for manual closing spring charging
7 Signalling device for closing springs charged/discharged
8 Resetting button for protection circuit-breaker of geared motor (on request)
6. Instructions for circuit-breaker operation
Loading...
+ 26 hidden pages