Signal converters
without cold-junction compensation:
switch SW2.2 = OFF
Burden
R M 4.7 kq
Burden
R m 600 q
supply
1 2 43 5 6
-10...-2 V
-5...-1 V
-8...0 V
-4...0 V
0...1 mA
0...20 mA
4...20 mA
0...10 mA
0...800 µA
0...8 mA
0...400 µA
125...625 µA
166...833 µA
2...10 mA
100...500 µA
0...666 µA
0...16 mA
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
-5...+5 V
-10...0 V
-5...0 V
0...8 V
0...4 V
Switch 2
Output
1.25...6.25 V
0...6.66 V
-10...+3.33 V
-5...+1.66 V
-7.5...+2.5 V
-3.75...+1.25 V
1.66...8.33 V
-6.66...+6.66 V
-3.33...+3.33 V
0...0.5 mA
0...13.33 mA
2.5...12.5 mA
3.33...16.66 mA
0.2...1 mA
OFF
Legend
no inuence
ON
1 2 43 5 6 1 2 43 5 6
R
B
mV
N
K
J
T
S
E
0-100...900 °C
0-250...1350 °C
0-100...750 °C
0-100...400 °C
-150-0...400 °C
0-250...1550 °C
0-100...700 °C
0-200...1000 °C
0-100...650 °C
0-200...1300 °C
0-250...1350 °C
0-450...1700 °C
0-700...1750 °C
0-2...10 mV
0-10...50 mV
Type Range
Switch 1 Switch 2Input
Low fail safe *)
High fail safe *)
Typ T
Typ N
Typ K
Typ J
Typ E
Typ R
Typ S
Typ B
-250
-200
-150
-100
-50
0
50
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
80000
75000
70000
65000
60000
55000
50000
45000
40000
35000
30000
25000
20000
15000
10000
5000
0
-5000
-10000
-15000
Temperature [°C]
Thermoelement-Spannung [µV]
Temperature signal converter for thermocouples
& Isolators
CC-U/TC
CC-U/TC universal signal converter for thermocouples with 3-way electrical isolation
CC-U/TC
1 Plug-in connecting
terminals
2 Gain: Coarse adjustment
3 Gain: Fine adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
• Temperature signal converter for thermo-
Wiring instruction
couples of the types K, J, T, S, E, N, R, B
• Continuously adjustable voltage signal input
0-10 mV and 0-50 mV
• Differential temperature measurement possible
1)
• Congurable output signal response on input
signal interruption (low fail safe / high fail safe)
• Adjustment and operating elements on the
front-side
• Short-circuit proof signal outputs
• Plug-in connecting terminals for inputs,
outputs and supply
Type Rated supply voltage Order code
CC-U/TC 24-48 V DC
110-240 V AC
1SVR 040 004 R0700
1SVR 040 005 R0000
DIP switch settings
Pack. unit
pieces
1
1
12
Low Voltage Products & Systems 12.11
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
*) Detection of input signal
interruptions:
If the input signal circuit is inter-
rupted, the output signal changes
to the adjusted minimum value
(low fail safe) or maximum value
(high fail safe).
Characteristic curves
Thermocouple voltages depending on the temperature