Signal converters
PT1000
PT100
PT10
Resistance [q]
Temperature [°C]
J
H
G
Burden
R M 4.7 kq
Burden
R m 600 q
supply
24 V DC or 110-240 V AC
1 2 43 5 6 1 2 43 5 6
PT10
PT100
PT1000
0...500 °C
0...550 °C
0...600 °C
0...650 °C
0...700 °C
0...750 °C
0...800 °C
0...850 °C
0...50 °C
0...60 °C
0...70 °C
0...80 °C
0...90 °C
0...100 °C
0...200 °C
0...400 °C
0...300 °C
0...500 °C
0...10 °C
0...20 °C
0...30 °C
0...40 °C
0...50 °C
0...60 °C
F
E
D
C
B
A
9
8
F
E
B
A
9
8
3
1
2
0
8
3
2
1
0
0
-
-
Type Range
Switch 1 Switch 2Input
Low fail safe *)
High fail safe *)
Gain
Coarse
1 2 43 5 6
-10...-2 V
-5...-1 V
0...5 V
0...10 V
1...5 V
2...10 V
-10...+10 V
-5...+5 V
-10...0 V
-5...0 V
0...8 V
0...4 V
-8...0 V
-4...0 V
0...1 mA
0...20 mA
4...20 mA
0...10 mA
0...800 µA
0...8 mA
0...400 µA
125...625 µA
166...833 µA
2...10 mA
100...500 µA
0...666 µA
0...16 mA
0...0.5 mA
0...13.33 mA
2.5...12.5 mA
3.33...16.66 mA
0.2...1 mA
1.66...8.33 V
-6.66...+6.66 V
-3.33...+3.33 V
Switch 3
Output
1.25...6.25 V
0...6.66 V
-10...+3.33 V
-5...+1.66 V
-7.5...+2.5 V
-3.75...+1.25 V
1 2 43 5
6
Switch 3
Output
OFF
Legend
no inuence
ON
& Isolators
Temperature signal converter for RTD sensors
CC-U/RTD
CC-U/RTD universal signal converter for PT10, PT100, PT1000 temperature sensors
(acc. to IEC 751 and JIS C 16041, linearized with 3-way electrical isolation
• Congurable output signal response on
input signal interruption (low fail safe /
high fail safe)
• Adjustment and operating elements on
the front-side
• Short-circuit proof signal outputs
• Plug-in connecting terminals for inputs, outputs and supply
Wiring instruction
CC-U/RTD
1 Plug-in connecting
terminals
2 Gain: Coarse adjustment
3 Gain: Fine adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
12
Type Rated supply voltage Order code
CC-U/RTD 24-48 V DC
110-240 V AC
1SVR 040 002 R0500
1SVR 040 003 R0600
Characteristic curves
Resistance of PT10, PT100 and PT1000 sensors depending on the temperature
DIP switch settings
Pack. unit
pieces
1
1
12.8 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
*) Detection of input signal interruptions:
If the input signal circuit is interrupted, the output signal changes
to the adjusted minimum value (low fail safe) or maximum value
(high fail safe).
1 Japanese standard