Electronic
7
Safety relays
Application examples
C576, C577
Application
The safety relay C 576 can be used in safety circuits as per
VDE 0113 Part 1 (11.98) or EN 60 204-1 (11.98), e.g. with movable covers and
safety gates; the safety relay C 577 in EMERGENCY STOP circuits as per EN
418. Depending on external connections, category 4 as per DIN EN 954-1 is
achievable.
Functions and connections
The safety relays C 576/C 577 have two release circuits (safety outputs) confi gured
as NO contacts. The number of release circuits can be increased by adding one or
more C 579 extension units.
Three LEDs indicate operating state and function.
When the EMERGENCY STOP button or the limit switch is unlocked
and when the ON button is pressed, the internal circuit of the safety relay and the
external contactors are checked for proper functioning.
On the C 577, the ON circuit Y33, 34 is checked for short circuit.
7
This means that a fault is detected when Y33, 34 is closed before
the EMERGENCY STOP button is closed.
The EMERGENCY STOP button or the limit switch are connected to terminals Y11,
12, 21, 22. The ON button is connected in series to the NC contacts of the external
contactors (feedback loop) to terminals Y33, 34.
Terminal marking
Supply voltage A1 L/+
A2 N/-
Sensors Y11, 12 Channel 1 EMERGENCY
STOP
or limit switch
Y21, 22 Channel 2 EMERGENCY
STOP
or limit switch
Y33, 34 ON button, feedback loop
Outputs 13, 14 Safety output 1 (n/o contact)
23, 24 Safety output 2 (n/o contact)
Fault clearance
1. Switch supply voltage off.
2. Clear fault or replace device.
3. Switch supply voltage back on.
Cable length
for 2 x 1.5mm
150nF/km sensors and power supply lines)
Internal circuit
2
max. 1000m total cable length for
Y21 Y33
Y11
A1
ϑ
1
2
13 23
4
3
5
Operation
LEDs Operation
POWER Channel 1 Channel 2 PS E-Stop ON Safety outputs
ON non activated closed
activated
activated non open
activated
non non open
activated activated
Faults
Relay fusion-welded open
Motor cont. fusion-welded
Defect in electronic
Short circuit in ON circuit
Cross or ground faults in
EMERGENCY STOP circuit
(min. fault current
I
C 577 with monitored start for EMERGENCY STOP
Category 4 acc. to EN 954-1
24 V AC/DC
open closed
N/ñ
C 577 with monitored start for EMERGENCY STOP
Category 4 acc. to EN 954-1
24 V AC/DC
EMERGENCY-STOP
N/ñ
= 0.5A; PTC fuse trips)
Kmin
Y12Y11
Y33 Y34
C576
A2
Y22Y21
K1
K2
A1 Y12Y11
C577
Y21Y22 A2
L/+
13 23A1
K1
K2
M
14 24
N/ñ
L/+
ON
Y34Y33
13 23
K1
K2
14 24
M
K2
K1
N/ñ
Y22 Y34
Y12
A2
14 24
7.46 Low Voltage Products & Systems
AC 1000 - 11/03