ABB C575 Application Information

Application examples
C575
Electronic
Safety relays
7
Application
C 575 is suitable for installation in controls for presses.
• Hydraulic presses DIN EN 693,
• Eccentric and related presses EN 692,
• Screw presses EN 692.
Functions and connections
The two-hand control unit C 575 possesses two release circuits (safety outputs) confi gure as NO contacts and two signal outputs confi gured as NC contacts. Five LEDs indicate the operating status and the functions.
The safety outputs are closed by simultaneous operation (< 0.5s) of the push-buttons S1, S2. If one pushbutton is no longer pressed, the outputs open. They do not close again until both pushbuttons are no longer pressed and then simultaneously pressed again.
1. Operating voltage to be applied to the terminals A1 and A2. The operating voltage must be de-energized with the operating energy of the press.
2. Feedback loop to be closed: Y11, Y12 to be jumperd or connected to the NC contacts of external contactors.
3. Input circuits to be connected: Pushbutton S1 to terminals Y21, Y22, Y23 and pushbutton S2 to terminals Y31, Y32, Y33.
Terminal marking
Supply voltage A1 L/+ A2 N/-
Outputs 13, 14 Safety output 1 (n/o contact) 23, 24 Safety output 2 (n/o contact) 31, 32 n/c signal output 41, 42 n/c signal output Inputs Y11,12 Feedback loop Y21, 22, 23 Pushbutton S1 Y31, 32, 33 Pushbutton S2
Operation
LEDs Operation
POWER S1 ON S2 ON Channel 1 Channel 2 Pushbutton
non activated
only S1 activated
only S2 activated
S1 and S2 activated
The unit cannot be started with the following faults:
• Short circuit, e.g. between the pushbuttons
• Defective relay coils
• Conductor failure
• Welded contacts
The output relays does not enegize if:
• The pushbuttons are not pressed simultaneously (< 0.5s)
• Only one pushbutton is pressed
• The feedback loop Y11, Y12 is open.
Cable length
max. 1000m for 2 x 1.5mm and power supply lines)
External circuit S1, S2 pushbuttons on two-hand control console, H1 indicator light, K1and K2 must be positively guided contactors,
Safety category 4 acc.to EN 954-1
L/+
2
(Total cable length for sensors
L/+
7
Internal circuit
K1K2S1
A1
A2
Y11 Y12 13 23 4131
Y21 Y22 Y23
2
1
3
J
Y31 Y32 Y33
4
5
6
C575
A2
N/-
13 23A1 31 41Y22Y23Y12 Y21Y11
K1
K2
M
Y32Y31
14 24
32 42
Y33
S2
N/-
K2K1 H1