ABB AF26, AF210, AFN00, AF30, AF260 General information

...
Page 1
General information
Product overview
Description
AF09 – AF750 and AFN00 - AFN4
• Maximum UL/CSA horsepower ratings
• Available with non-reversing, reversing, two speed one winding and two
speed two winding
• Available in non-combination and combination
• Available in UL type 1,3R,12, 4, and 4X stainless steel enclosures
magnetic circuit breaker
• Compact space saving design
• Standard auxiliary contact configurations: AF09 – AF750 (AFN00-AFN4)
1 N.O. & 1 N.C.
• Double break contact design
• Lowest possible contact bounce
• Operates over an extended voltage range of 85% to 110% of rated control
voltage
Overload relay protection
Starters, sizes AF09 – AF300 (AFN00-AFN4), have Class 10 adjustable ther­mal bimetallic overload relay protection as standard.
Sizes AF400 – AF750, have selectable Class 10, 20, 30 adjustable electronic
overload relay protection as standard.
Optional electronic overload relay protection is available for all starter sizes.
Field modification kits
Offers a wide variety of pilot device kits for non-reversing, reversing, two speed one winding and two speed two winding starters.
Control circuit transformer kits are also available with the following voltages:
Control Voltage 200-208 230-240 460-480 575-600
120V AC @ 50/60 Hz A B C D
24V AC @ 50/60 Hz E F G H
The field kits are pre-wired, ready to operate, making installation easy and reliable
2 | IEC & NEMA Enclosed starters
Page 2
General information
Features and benefits
7
56
1
8 3
Features and benefits
1. Durable protective finish (carbon steel enclosures)
- Industry exclusive electrophoretic dip coat prime
- Power coated surface for added protection
2. Flange trough collar opening
- Channels liquids and dust away from enclosure gasket and enclosure interior
3. Seamless foamed-in-place gasket
- Provide secure seal against contaminates
- Ensures a dust tight and water tight seal
4. Pre-drilled mounting plate
- Easy mounting for control circuit transformer kit
2
4
5. Rugged and compact 22 mm pilot devices
- Meets UL/NEMA Type 1, 3R. 4, 4X. 12, 13
6. Convenient hole plugs for pilot device control
- Allows for quick installation of pilot device kit
7. Disconnect handle accepts 3 -3/8” padlocks in off position for safe
maintenance
8. Quarter turn enclosure latches
- Allows for quick entry and proper sealing of enclosure
IEC & NEMA Enclosed starters | 3
Page 3
Catalog number explanation
Non-combination starter
AF26 1 S N 1 - 2 H A
Contactor size
AF26 AF210 AFN00 AF30 AF260 AFN0 AF50 AF300 AFN1 AF63 AF400 AFN2 AF75 AF460 AFN3 AF110 AF580 AFN4 AF145 AF750 AF185
Starter type
1 - Non reversing 2 - Reversing 3 - 2 Speed, 1 winding 4 - 2 Speed, 2 winding
Single phase
S - Single phase (insert only for single phase)
Disconnect type
Blank - Non-combination (starter only)
N - Non-fusible disconnect
Enclosure type
2 - NEMA/UL Type 1, 3R, 4, 12 X - NEMA/UL Type 4X (Stainless steel)
Coil voltage CCT
Option 1
See factory installed modifications on pages 29 & 30
Overload selection
See overload relay selection on pages 34 - 37
Coil voltage selection
24 AC 100 - 250 AC 250 - 500 AC
1 2 3
Control Voltage 200-208 230-240 460-480 575-600
120V AC @ 50/60 Hz A B C D
24V AC @ 50/60 Hz E F G H
AC Volts, 40-60 Hz
CCT Selection
IEC & NEMA Enclosed starters | 5
Page 4
IEC & NEMA Non-combination
AF26 - AF750; AFN00 - AFN4
Non-reversing, three phase
IEC Non-combination
Maximum ratings - UL Listed UL Type 1, 3R, 4, 12 UL Type 4X
UL motor
switching
current
28 AF26 7.5 7.5 15 20 AF2612-2∆ AF261X-2∆ 34 AF30 10 10 20 25 AF3012-2∆ AF301X-2∆ 54 AF50 15 20 40 50 AF5012-2∆ AF501X-2∆ 68 AF63 20 25 50 60 AF6312-2∆ AF631X-2∆
80 AF75 25 30 60 75 AF7512-2∆ AF751X-2∆ 110 AF110 30 40 75 100 AF11012-2∆ AF1101X-2∆ 130 AF145 40 50 100 125 AF14512-2∆ AF1451X-2∆ 156 AF185 50 60 125 150 AF18512-2∆ AF1851X-2∆ 192 AF210 60 75 150 200 AF21012-2∆ AF2101X-2∆ 248 AF260 75 100 200 250 AF26012-2∆ AF2601X-2∆ 302 AF300 100 - 250 300 AF30012-2∆ AF3001X-2∆ 414 AF400 125 150 350 400 AF40012-2∆ AF4001X-2∆ 480 AF460 150 200 400 500 AF46012-2∆ AF4601X-2∆ 590 AF580 200 250 500 600 AF58012-2∆ AF5801X-2∆ 722 AF750 250 300 600 700 AF75012-2∆ AF7501X-2∆
∆ Overload relay suffix code. Select from the overload relay selection chart on pages 34 & 35.
Contactor Size
200/208V 230/240V 460V/480V 575/600V
Maximum motor horsepower ratings
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog number
NEMA Non-combination
Maximum ratings - UL Listed UL Type 1, 3R, 4, 12 UL Type 4X
NEMA
size
00 AFN00 9 1.5 1.5 2 AFN0012-2∆ AFN001X-2∆
0 AFN0 18 3 3 5 AFN012-2∆ AFN01X-2∆ 1 AN1 27 7.5 7.5 10 AFN112-2∆ AFN11X-2∆ 2 AFN2 45 10 15 25 AFN212-2∆ AFN21X-2∆ 3 AFN3 90 25 30 50 AFN312-2∆ AFN31X-2∆ 4 AFN4 135 40 50 100 AFN412-2∆ AFN41X-2∆
∆ Overload relay suffix code. Select from the overload relay selection chart on pages 36 & 37.
Contactor Continuous
Maximum motor horsepower ratings
200V 230V 460/575V
General Purpose,
Rainproof,
Waterproof, Dusttight
Catalog number
Watertight Corrosion
Resistant
Stainless steel
Catalog number
Watertight Corrosion
Resistant
Stainless steel
Catalog
number
Coil voltage selection 1)
All AC operated catalog numbers include a 100-250V AC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart
for the suffix code after the dash in the catalog number. Ex.: A 24V AC coil is required for an AF26 starter: AF2612-1K
Coil voltage selection chart
Coil voltage
AC Volts, 40-60 Hz
24 AC 100 - 250 AC 250 - 500 AC
1 2 3
1) 24 AC coil voltage is available only with AF26 & AF30, AFN00 - AFN1, For factory modifications, see pages 29 & 30.
Control transformer voltage selection
To select starter with control transformer, substitute the code from the con­trol transformer voltage selector chart after the dash in the catalog number.
Ex.: A 480V primary voltage with a 120V secondary voltage is required for an AF26 starter: AF2612-CK
Control transformer voltage selection chart
Control Voltage 200-208 230-240 460-480 575-600
120V AC @ 50/60 Hz A B C D
24V AC @ 50/60 Hz E F G H
IEC & NEMA Enclosed starters | 7
Page 5
General information
Factory installed options
Control cover factory modifications - NEMA/UL Type 1, 3R, 4, 4X & 12
Pilot device kits
One
operator
Two
operators
Three
operators
Starter type Description Nameplate Suffix code
DOL 2-Position Switch OFF-ON C DOL 3-Position Switch HAND-OFF-AUTO D DOL Pilot Light "ON" Red pilot light E
REV 3-Position Switch FOR-OFF-REV L
2 Speed 3-Position Switch SLOW-OFF-FAST M
DOL Push Buttons START/STOP A DOL Push Buttons START/ EMERGENCY STOP N
DOL 2 Position Switch & Pilot Light OFF-ON/"ON" H DOL 3 Position Switch & Pilot Light HAND-OFF-AUTO/"ON" J
DOL Push Buttons & Pilot Light START/STOP/"ON" F DOL 2 Position Switch & Pilot Lights OFF-ON/"ON"/"FAULT" P DOL 3 Position Switch & Pilot Lights HAND-OFF-AUTO/"ON"/"FAULT" Q
REV Push Buttons FORWARD- REVERSE-STOP B
REV 3 Position Switch & Pilot Lights FOR-OFF-REV/"FORWARD"/"REVERSE" G 2 Speed Push Buttons FAST-SLOW-STOP K 2 Speed 3 Position Switch & Pilot Lights SLOW-OFF-FAST/"SLOW"/"FAST" R
IEC & NEMA Enclosed starters | 29
Page 6
General information
Factory installed options
Control circuit transformers
Contactor size Description Option
50VA, 200-208/120 VAC A 50VA, 230-240/120 VAC B
AF09 -AF30
AFN00 & AFN1
AF50 -AF75
AFN2 & AFN3
AF110
AF145 - AF185
AF400-AF460
AFN4
AF210 - AF300
AF580-AF750
50VA, 460-480/120 VAC C
50VA, 575-600/120 VAC D
50VA, 200-208/24 VAC E
50VA, 230-240/24 VAC F 50VA, 460-480/24 VAC G
50VA, 575-600/24 VAC H
75VA, 200-208/120 VAC A 75VA, 230-240/120 VAC B 75VA, 460-480/120 VAC C
75VA, 575-600/120 VAC D
100VA, 200-208/120 VAC A 100VA, 230-240/120 VAC B 100VA, 460-480/120 VAC C
100VA, 575-600/120 VAC D 150VA, 200-208/120 VAC A 150VA, 230-240/120 VAC B 150VA, 460-480/120 VAC C
150VA, 575-600/120 VAC D 250VA, 200-208/120 VAC A 250VA, 230-240/120 VAC B 250VA, 460-480/120 VAC C
250VA, 575-600/120 VAC D
30 | IEC & NEMA Enclosed starters
Page 7
General information - NEMA Starter
Standard thermal overload relays
Standard - Thermal, Type TF and TA, Class 10
Correct sizing of overload relay per motor HP
1-phase 3-phase
120V 240V 208V 240V 480V 600V
- - - - - - TF42-0.13 A 0.10-0.13
- - - - - - TF42-0.17 B 0.13-0.17
- - - - - - TF42-0.23 C 0.17-0.23
- - - - - - TF42-0.41 D 0.31– 0.41
- - - - - - TF42-0.55 E 0.41-0.55
- - - - - - TF42-0.74 F 0.55-0.74
- - - - - 1/2 TF42-1.0 G 0.74-1.0
- - - - 1/2 3/4 TF42-1.3 H 1.0-1.3
- 1/10 - - 3/4 1 TF42-1.7 J 1.3-1.7
- 1/8 - 1/2 1 - TF42-2.3 K 1.7-2.3
1/10 1/6, 1/4 1/2 - 1 1/2 1 1/2, 2 TF42-3.1 L 2.3-3.1
1/8 1/3 3/4 3/4 2 - TF42-4.2 M 3.1-4.2
1/6 1/2 1 1 - - TF42-5.7 N 4.2-5.7
1/4 3/4 1 1/2 1 1/2 - - TF42-7.6 P 5.7-7.6 1/3 1 - - - - TF42-10 Q 7.6-10
- - - - - 3 TF42-4.2 M 3.1-4.2
- - - - 3 TF42-5.7 N 4.2-5.7
- - 2 2 5 5 TF42-7.6 P 5.7-7.6
1/2 1 1/2 - 3 - - TF42-10 Q 7.6-10
- 2 3 - - - TF42-13 R 10-13
3/4, 1 - - - - - TF42-16 S 13-16
- - - - - 7.5 TF42-10 Q 7.6-10
- - - - 7.5 10 TF42-13 R 10-13
- - - 5 10 - TF42-16 S 13-16
- 3 5 - - - TF42-20 T 16-20
2 - - 7.5 - - TF42-24 U 20-24
- - 7.5 - - - TF42-29 V 24-29
- - - - 15 20 TA75DU25 A 18-25
3 7 1/2 - 15 25 - TA75DU42 C 29-42
- - - - - 30 TA75DU42 C 29-42
- - 15 30 40 TA75DU52 D 36-52
- - 20 20 40 50 TA75DU63 E 45-63
- - 25 25, 30 50 - TA75DU80 F 60-80
- - 30 - 60 75 TA200DU90 A 65-90
- - 40 50 100 - TA200DU135 C 100-135
Catalog Number Code
Setting
Range (A)
Contactor
Size
AFN00
AFN0
AFN1 1)
AFN2- - 10 10 20 25 TA75DU32 B 22-32
AFN3
AFN4- - - 40 75 100 TA200DU110 B 80-110
1) AFN1 contactor can use AFN00 and AFN0 overloads.
36 | IEC & NEMA Enclosed starters
Loading...