AF16(Z) contactors are used for controlling power circuits
up to 690 V AC and 220 V DC.
They are mainly used for controlling 3-phase motors,
non-inductive or slightly inductive loads.
AF..(Z) contactors include an electronic coil interface providing reduced –
pull-in and holding consumption, particularly for AC control circuits
Only four coils are needed to cover control voltages between 24...500 V –
50/60 Hz or 20...500 V DC.
AF..(Z) offer extended operating limits and are suitable worldwide for
different control voltages.
e.g.: the coil 100...250 V 50/60 Hz - DC is suitable for Europe (230 V
50 Hz) and for North America (120 V 60 Hz and 208 V 60 Hz). AF..(Z)
contactors can manage large control voltage variations
AF..Z contactors equipped with a 24...60 V 50/60 Hz - 20...60 V DC coil –
allow direct control by 24 V DC 500 mA PLC-output
AF..Z contactors withstand short voltage dips and voltage sags (SEMI –
F47-0706 compliance)
AF..(Z) contactors have built-in surge protection and do not require –
additional surge suppressors
2-stack contactors are mounted with a non-removable auxiliary contact –
block. They have mechanically-linked auxiliary contacts compliant with
Annex L of IEC 60947-5-1, including the "Mechanically Linked" symbol
on their side
N.C. auxiliary contacts are mirror contacts in compliance with Annex F of –
IEC 60947-4-1.
3D CAD outline drawings available on «Control Product 3D» portal
7.5 kW
10 hp
Ordering Details
IECUL/CSA Control voltageMain
Rated
power
400 V
AC-3480 V1 piece
kWhpV 50/60 Hz V DC
3-phase
motor
rating
Uc min. ... Uc max.
contacts
Auxiliary
contacts
fitted
TypeOrder codeEANWeight
(ing)
Pack
kg
2-stack 3-pole Contactors
7.51024...6020...603022
48...13048...1303022
100...250100...2503022
250...500250...5003022
Note: AF16-30-22-11 not suitable for a direct control by PLC-output. AF16-30-22-11 available in some countries: please consult your ABB representative.
Note: Only AF..Z contactors with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and A2- for the negative pole
Main Pole - Utilization Characteristics according to IEC
M
3
M
3
StandardsIEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.690 V
Rated frequency limits25 ... 400 Hz
Conventional free-air thermal current Ith
without thermal O/L relay - Motor protection excluded
Ue ≤ 500 V AC - gG type fuse
Rated short-time withstand current Icw
at 40 °C ambient temperature, in free air from a cold state
Maximum breaking capacity
cos φ = 0.45
Heat dissipation per pole
at 440 V
at 690 V
Ie / AC-1
Ie / AC-3
Max. electrical switching frequency
AC-2, AC-4
415 V
440 V
500 V
690 V
415 V
440 V
500 V
690 V
1 s
10 s
30 s
1 min
15 min
AC-1
AC-3
35 A
30 A
30 A
26 A
18 A
18 A
18 A
18 A
15 A
10.5 A
4 kW
7.5 kW
9 kW
9 kW
9 kW
9 kW
32 A
300 A
150 A
80 A
60 A
35 A
250 A
106 A
1.2 W
0.35 W
600 cycles/h
1200 cycles/h
300 cycles/h
ABB | Technical Datasheet 1SBC101409D0201 3
Built-in Auxiliary Contacts according to IEC
Rated operational voltage Ue max.690 V
Conventional free air thermal current Ith - θ ≤ 40 °C16 A
Rated frequency limits25 ... 400 Hz
Rated operational current Ie / AC-15
acc. to IEC 60947-5-1
Making capacity AC-1510 x Ie AC-15 acc. to IEC 60947-5-1
Breaking capacity AC-1510 x Ie AC-15 acc. to IEC 60947-5-1
Rated operational current Ie / DC-13
acc. to IEC 60947-5-1
Short-circuit protection gG type fuse10 A
Rated short-time withstand current Icw
Minimum switching capacity12 V / 3 mA
with failure rate acc. to IEC 60947-5-4
Non-overlapping time between N.O. and N.C. contacts≥ 2 ms
Heat dissipation per pole at 6 A0.1 W
Max. electrical switching frequency
24-127 V 50/60 Hz
220-240 V 50/60 Hz
400-440 V 50/60 Hz
500 V 50/60 Hz
690 V 50/60 Hz
24 V DC
48 V DC
72 V DC
110 V DC
125 V DC
220 V DC
250 V DC
400 V DC
500 V DC
600 V DC
for 1.0 s
for 0.1 s
AC-15
DC-13
6 A
4 A
3 A
2 A
2 A
6 A / 144 W
2.8 A / 134 W
1 A / 72 W
0.55 A / 60 W
0.55 A / 69 W
0.27 A / 60 W
0.27 A / 68 W
0.15 A / 60 W
0.13 A / 65 W
0.1 A / 60 W
100 A
140 A
-7
10
1200 cycles/h
900 cycles/h
Main Pole - Utilization Characteristics according to UL / NEMA / CSA
StandardsUL 508, CSA C22.2 N°14
Rated operational voltage Ue max.600 V
NEMA sizeNEMA continuous amp rating
NEMA maximum H.P. ratings 1-phase, 60 Hz
NEMA maximum H.P. ratings 3-phase, 60 Hz
UL General use rating
600 V AC30 A
With conductor cross-sectional areaAWG 10
80 V DC - 1-pole30 A
With conductor cross-sectional areaAWG 10
for contactors without thermal O/L relay - Motor protection excluded
Fuse rating60 A
Fuse type, 600 VNTD
Max. electrical switching frequency
for general use600 cycles/h
for motor use1200 cycles/h
thermal current
115 V AC
230 V AC
200 V AC
230 V AC
460 V AC
575 V AC
120 V AC
240 V AC
120 V AC
240 V AC
200-208 V AC
220-240 V AC
440-480 V AC
550-600 V AC
200-208 V AC
220-240 V AC
440-480 V AC
550-600 V AC
20 A
17 A
1-1/2 hp
3 hp
17.5 A
15.2 A
14 A
17 A
5 hp
5 hp
10 hp
15 hp
4Technical Datasheet 1SBC101409D0201 | ABB
Built-in Auxiliary Contacts according to UL / CSA
B2
A
A
B1
C2
C1
Max. rated operational voltage Ue max.600 V AC, 600 V DC
Pilot dutyA600, Q600
AC thermal rated current10 A
AC maximum volt-ampere making7200 VA
AC maximum volt-ampere breaking720 VA
DC thermal rated current2.5 A
DC maximum volt-ampere making-breaking69 VA
General Technical Data
Rated insulation voltage Ui
acc. to IEC 60947-4-1
acc. to UL /CSA
Rated impulse withstand voltage Uimp.6 kV
Electromagnetic compatibilityDevices complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature
close to contactor
Operationfitted with thermal overload relay-25 ... +60 °C
without thermal overload relay-40 ... +70 °C
Storage-60 ... +80 °C
Climatic withstandCategory B according to IEC 60947-1 Annex Q
Operating altitude≤ 3000 m
Mechanical durability
Number of operating cycles10 millions operating cycles
Max. switching frequency3600 cycles/h
Shock withstand
acc. IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
Closed or open
Shock direction
position
Vibration withstand5 ... 300 Hz
acc. to IEC 60068-2-6
690 V
600 V
1/2 sinusoidal shock for 11 ms: no change in contact position
A
30 g
B1
25 g Closed position / 5 g Open position
B2
15 g
C1
25 g
C2
25 g
4 g Closed position / 2 g Open position
Magnet System Characteristics
Coil operating limits
acc. to IEC 60947-4-1
AC control voltage Rated control circuit voltage Uc24 ... 500 V AC
50/60 HzCoil consumption
Average pull-in value
Average holding value
DC control voltage Rated control circuit voltage Uc12 ... 500 V DC
Coil consumption
Average pull-in value
Average holding value
PLC-Output control(AF..Z) ≥ 500 mA 24 V DC
Drop-out voltage in % of Uc min.≤ 60 % Uc min
Voltage sag immunity
Dips withstand
according to SEMI F47-0706(AF..Z) conditions of use on request
(level 0% according to IEC 61000-4-11)(AF..Z) 22 ms average for Uc = 24 ... 250 V 50/60Hz