We ensure safety and comfort for
everyday life by bringing electric power to
domestic appliances, lighting and heating.
Through our comprehensive range of
enclosures, line protection equipment,
wiring accessories and various other
components to complete any electrical
installation we cover the full spectrum of
equipment required for control and protection
of all domestic and residential instalations.
With this EIB system all electrical functions in
a home can now be programmed and remotely
controlled.
Commercial and
industrial buildings
All over the world office buildings,
hospitals, hotels, public buildings,
shopping centers, sport complexes and
city lighting projects are equipped with
ABB Low Voltage Products and Systems.
From switchboard to light switch we cover
the complete range of equipment required
for control and protection of electrical
installations.
Architects, consultants, builders and contractors
appreciate the performance/cost ratio provided
by our products.
They have made ABB a well known reference
for high quality and extremely reliable electrical
equipment.
Automation processes in building wiring and installation can be implemented with installation
contactors. They are used chiefly for switching and controlling lighting systems, heating
systems, ventilation systems, pumps, heating pumps and other building automation actuators.
Geräte für Schalttafeleinbau auf Tragschienen (35 mm) nach DIN EN 50 022
Installation depth:System 68 mm
Installation width:1, 2 and 3 modules (1 module = 17.5 ... 18 mm)
Colour:grey, RAL 7035
suitable for the STOTZ system proM
Advantages
• hum-free solenoid drive
• low-noise switching
• switching position indicator
• integrated coil protective circuit
• attachable auxiliary switch
• overvoltage protection for the solenoid coil up to 5 kV
• high making/breaking capacity and long service life
• quick fastening with latching slide
• large connections with open box terminals
• shock-hazard protection to VDE 0106, Part 100
ABB STOTZ-KONTAKT GmbH
Construction
Type ESB 20 operates with an AC solenoid system. Types ESB 24, 40 and 63 feature a DC
solenoid actuator and are thus hum-free. The noise during switching on is hardly audible
compared with an AC solenoid. An integrated diode jumper allows connection to AC voltage.
The incorporated varistor protects the coil against remote lightening strikes and overvoltages
of up to 5 kV. In addition, it limits the interference voltage peaks of the solenoid system. The
contactors can therefore be combined with programmable logic controllers. There is no need
for a coil protective circuit. The solenoid system is provided with radio interference suppression.
Overvoltage peaks may cause a current of max. 200 A resp. an energy of max. 4 J or 106 x a
current of 5 A resp. an energy of max. 0.05 J with normal wave
(8/20 µs).
All switching elements of the contactors can be used as main contact elements or as auxiliary
contact elements (see also technical data). The contacts are not positively driven, and NO and
NC contacts can therefore overlap.
On Types ESB 24, 40 and 63, a two-pole auxiliary switch, Type EH 04 (1/2 module width) can
be attached. This auxiliary switch must be used for switching control signals.
Contactors ESB 20, 24 and 40 are also available as "EN" devices with integrated manual
switch, e.g. for "day/night" application. Data sheet on request.
5
1SAC 1011 01 D0201
Page 5
Installation contactors ESB..
Ordering details
Accessories
IEC 947-4-1
EN 60 947-4-1
IEC 1095
EN 61 095
Anschlußbezeichnungen
ESB 20
2 NO
ESB 20
2 NC
ESB 20
1 NO
1 NC
ESB 24
ESB 40
ESB 63
4 NO
ESB 24
3 NO
1 NC
ESB 24
2 NC
2 NO
ESB 24
4 NC
EH 04- 20
2 NO
EH 04- 11
1 NO
1 NC
SST 015 91 S/1
SST 015 91 S/2
SST 015 91 S/3
SST 091 92 S
SST 092 92 S
SST 015 91 S/4
SST 015 91 S/5
SST 015 91 S/6
SST 015 91 S/7
Contactor type
Contact b40 13614 1 St.
complement 50 Hz60 HzProduct No.EANDMkgpiece
ESB 20-20 12 V 14 VGH E321 1102 R 100408427 00.210
2 NO 24 V 27 ... 28 VGH E321 1102 R 000108420 1
ESB 20-02 12 V 14 VGH E321 1202 R 100408517 80.210
2 NC 24 V 27 ... 28 VGH E321 1202 R 000108430 0
ESB 20-11 12 V 14 VGH E321 1302 R 100408515 40.210
1 NO 24 V 27 ... 28 VGH E321 1302 R 000108435 5
1 NC 42 V 48 VGH E321 1202 R 000208436 2
ESB 24-40 12 VGH E329 1102 R 100408447 80.28 5
4 NO24 VACGH E329 1102 R 000108441 6
ESB 24-04 12 VGH E329 1202 R 100408456 00.28 5
4 NC24 VACGH E329 1202 R 000108451 5
ESB 24-22 12 VGH E329 1302 R 100408463 80.28 5
2 NO24 VACGH E329 1302 R 000108458 4
2 NC42 V40 ... 450 HzGH E329 1302 R 000208459 1
ESB 24-31 12 VGH E329 1602 R 100408472 00.28 5
3 NO24 VACGH E329 1602 R 000108467 6
1 NC42 V40 ... 450 HzGH E329 1602 R 000208468 3
ESB 24-13 12 VGH E329 1702 R 100421825 50.28 5
1 NO24 VACGH E329 1702 R 000121478 3
3 NC42 V40 ... 450 HzGH E329 1702 R 000221820 0
ESB 40-40 24 VGH E349 1102 R 000108482 90.45 3
4 NO 42 VGH E349 1102 R 000208483 0
c 48 VACGH E349 1102 R 000308559 8
ESB 63-40 24 VGH E369 1102 R 000108493 50.45 34 NO 42 VGH E369 1102 R 000208494 2
c 48 VACGH E369 1102 R 000312725 0
Rated operating voltage aOrder codebbnPrice
42 V 48 VGH E321 1102 R 000208421 8
48 V 55 VGH E321 1102 R 000308422 5
110 V125 ... 127 VGH E321 1102 R 000408423 2
230 V255 VGH E321 1102 R 000608425 6
231... 244 V268 ... 283 VGH E321 1102 R 000508424 9
400 V–GH E321 1102 R 000708426 3
42 V 48 VGH E321 1202 R 000208431 7
48 V 55 VGH E321 1202 R 000308518 5
110 V125 ... 127 VGH E321 1202 R 000408432 4
48 V 55 VGH E321 1302 R 000308514 7
110 V125 ... 127 VGH E321 1302 R 000408437 9
230 V255 VGH E321 1302 R 000608439 3
231... 244 V268 ... 283 VGH E321 1302 R 000508438 6
400 V–GH E321 1302 R 000708516 1
42 V40 ... 450 HzGH E329 1102 R 000208442 3
48 VorGH E329 1102 R 000308546 8
110 ... 120 VDCGH E329 1102 R 000408443 0
230 ... 240 VGH E329 1102 R 000608445 4
400 ... 415 VGH E329 1102 R 000708446 1
42 V40 ... 450 HzGH E329 1202 R 000208452 2
48 VorGH E329 1202 R 000308548 2
110 ... 120 VDCGH E329 1202 R 000408453 9
230 ... 240VGH E329 1202 R 000608454 6
400 ... 415 VGH E329 1202 R000708455 3
48 VorGH E329 1302 R 000308552 9
110 ... 120 VDCGH E329 1302 R 000408460 7
230 ... 240 VGH E329 1302 R 000608461 4
400 ... 415 VGH E329 1302 R000708525 3
48 VorGH E329 1602 R 000308555 0
110 ... 120 VDCGH E329 1602 R 000408469 0
230 ... 240 VGH E329 1602 R 000608470 6
400 ... 415 VGH E329 1602 R 000708471 3
48 VorGH E329 1702 R 000321821 7
110 ... 120 VDCGH E329 1702 R 000421822 4
230 ... 240 VGH E329 1702 R 000621823 1
400 ... 415 VGH E329 1702 R000721824 8
110 V40 ... 450 Hz. GH E349 1102 R 000408484 3230 VorGH E349 1102 R 000608486 7
240 VDCGH E349 1102 R 000508529 1
400 VGH E349 1102 R 000708530 7
415 VGH E349 1102 R 000808560 4
110 V40 ... 450 HzGH E369 1102 R 000408495 9230 VorGH E369 1102 R 000608497 3
240 VDCGH E369 1102 R 000508535 2
400 VGH E369 1102 R 000708498 0
415 VGH E369 1102 R 000812726 7
Weight
1 piece
Pack.
unit
a Other voltages on request.
b "Day/night" installation contactors, Type EN 20, EN24, EN 40 on request.
c Only delivery from ABB-Control France.1 or 2 NC up to max. 30 A (AC-1) possible.
6
1SAC 1011 01 D0201
ABB STOTZ-KONTAKT GmbH
Page 6
ESB 20
ESB 24
ESB 40/ESB 63
Installation contactors ESB..
Technical data
Rated operating currents and power ratings
AC-1 / AC-7aESB 20ESB 24ESB 40ESB 63
SST 040 94 R
SST 041 94 R
SST 039 94 R
Rated operating current I
Rated operating current I
Rated operating power (NO)
230 V single-phase 4.0 kW 5.3 kW 8.8 kW13.8 kW
230 V 3-phase– 9.0 kW15.2 kW24.0 kW
400 V 3-phase–16.0 kW26.0 kW41.0 kW
AC-3/AC-7b Switching motors
Rated operating current I
Rated operating current I
Rated operating power (NO)
230 V single-phase 1.3 kW 1.3 kW 3.7 kW 5.0 kW
230 V 3-phase– 2.2 kW 5.5 kW 8.0 kW
400 V 3-phase– 4.0 kW11.0 kW15.0 kW
DC-1/DC-3 Switching DC with NO contacts (NO)
Rated DC-1 (L/R ≤1 ms) DC-3 (L/R ≤ 2 ms)
operating1 current 2 current paths 3 current paths 1 current 2 current paths 3 current paths
Typevoltage U
ESB 24 24 V DC24.0 A24.0 A24.0 A16.0 A24.0 A24.0 A
48 V DC21.0 A24.0 A24.0 A8.0 A18.0 A24.0 A
60 V DC 17.0 A24.0 A24.0 A4.0 A 14.0 A 24.0 A
110 V DC 7.0 A16.0 A24.0 A1.6 A 6.5 A 16.0 A
220 V DC 0.9 A 4.5 A 13.0 A0.2 A 1.0 A 4.0 A
ESB 40 24 V DC40.0 A40.0 A40.0 A19.0 A40.0 A40.0 A
48 V DC23.0 A40.0 A40.0 A10.0 A20.0 A40.0 A
60 V DC18.0 A32.0 A40.0 A5.0 A 16.0 A 34.0 A
110 V DC 8.0 A17.0 A30.0 A1.8 A 7.0 A 18.0 A
220 V DC 1.0 A 5.0 A 15.0 A0.3 A 1.1 A 4.5 A
ESB 63 24 V DC50.0 A63.0 A63.0 A21.0 A44.0 A63.0 A
48 V DC25.0 A43.0 A63.0 A11.0 A22.0 A47.0 A
60 V DC20.0 A35.0 A60.0 A5.5 A 18.0 A 38.0 A
110 V DC 9.0 A19.0 A33.0 A2.0 A 8.0 A 21.0 A
220 V DC 1.1 A 5.5 A 17.0 A0.3 A 1.2 A 5.0 A
(NO)20 A24 A40 A63 A
e
(NC)20 A24 A30 A30 A
e
(NO)9 A9 A22 A30 A
e
(NC)9 A6 A
e
path in series in seriespath in series in series
e
IEC 947-4-1
EN 60 947-4-1
IEC 1095
EN 61 095
2 current paths connected in parallel permit a 1.6-fold
increase in rated operating current I
.
e
ESB 24 + EH 04
EN 24
ABB STOTZ-KONTAKT GmbH
SST 038 94 R
SST 036 95
DC-1/DC-3 Switching DC with NC contacts (NC)
Rated DC-1 (L/R ≤1 ms) DC-3 (L/R ≤ 2 ms)
Typevoltage U
operating1 current 2 current paths 3 current paths 1 current 2 current paths 3 current paths
path in series in seriespath in series in series
e
ESB 24 24 V DC14.5 A24.0 A24.0 A6.3 A11.0 A19.0 A
48 V DC7.5 A12.5 A22.0 A3.1 A5.4 A9.4 A
60 V DC 4.5 A10.0 A17.5 A2.0 A 4.3 A 7.5 A
110 V DC 1.6 A4.4 A9.5 A0.7 A 1.9 A 4.1 A
220 V DC 0.2 A 1.4 A 3.8 A0.1 A 0.6 A 1.6 A
EN 24-40 24 VGHE 3261 101 R000124 A24 V
EN 24-40 230-240 VGHE 3261 101 R000624 A230-240 V
EN 24-30 230-240 VGHE 3261 501 R000624 A230-240 V
EN 24-31 24 VGHE 3261 601 R000124 A24 V
EN 24-31 230-240 VGHE 3261 601 R000624 A230-240 V
EN 40-40 230 VGHE 3421 101 R000624 A230 V
Switching lamp loads, see Page 7.
1SAC 1011 01 D0201
7
Page 7
Installation contactors ESB..
Technical data
of ESB.. and auxiliary switches
Contact member service life
AC-1/400 V/3-phase for ESB 24, 40, 63
AC-1/230 V/single-phase for ESB 20
ESB 24
ESB 40
ESB 20
2
1
0.8
0.6
0.5
0.4
0.3
0.2
0.1
0.08
0.06
0.05
0.04
Millions of operating cycles
0.03
0.02
0.01
AC-3/400 V/3-phase for ESB 24, 40, 63
2
1
0,8
0,6
0,5
0,4
0,3
0,2
0,1
0,08
0,06
0,05
Millions of operating cycles
0,04
0,03
0,02
0,01
ESB 63
20
ESB 24
ESB 40
ESB 63
1,1 2,2 3 4 7,5 11 15
SST 006 91 K
801016350403024161,5 2 3 4 5 6 8
Breaking current [A]
SST 007 91 K
801016350403024161,5 2 3 4 5 6 8
Breaking current [A]
Switching capacity [kW]
IEC 947-4-1
EN 60 947-4-1
IEC 1095
EN 61 095
ESB 20ESB 24ESB 40ESB 63
Rated insulation400 V500 V500 V500 V
voltage U
i
Rated operation250 V440 V440 V440 V
voltage U
e
Short-circuit protection
Back-up fuse, Type "gL/gG"20 A35 A 63 A 80 A
Limiting short-time current 10 s at ambient temperature < 40 °C, in free air, from cold state
72 A72 A176 A240 A
Ohmic loss1.0 W1.5W3.0 W6.0 W
per current path at I
(AC-1, AC-7a)
e
Contact member service life and max. switching frequency
Service lifemechanical1 million1 million1 million1 million
electrical at AC-1 / AC-7a150 000150 000150 000150 000
pick-up- 8.0VA, 5.0W 4.0VA, 4.0W 5.0VA, 5.0W 65 VA, 65 W
holding- 3.2VA, 1.2W 4.0VA, 4.0W 5.0VA, 5.0W 4.2 VA, 4.2 W
On delay
- 12 ms< 40 ms
Off delay- 12 ms< 40 ms
Permissible– 25 -C to + 55 -C
Ambient temperature
If several contactors are mounted adjacently and the On time is
longer than one hour, every second contactor needs a distance
piece, Type ESB-DIS (1/2 module). This is not necessary at an
ambient temperature ≤ 40°C or on Type ESB 20.
Connection cross-sections
Main conductormax. mm
min. mm
2
Coil mm
2
2
1 x 10 or 2 x 41 x 25 or 2 x 10
1 x 0.51 x 1.5
1 x 4 or 2 x 2.5
Auxiliary switch EH 04
Thermal continuous current I
Rated operating current I
Minimum making/breaking capacity
= 6 A
th
at AC-15 for Ue< 240 V AC 4 A
e
< 415 V AC 3 A
< 500 V AC 2 A
> 17 V / > 5 mA
8
1SAC 1011 01 D0201
ABB STOTZ-KONTAKT GmbH
Page 8
Installation contactors ESB..
IEC 947-4-1
EN 60 947-4-1
Technical data
IEC 1095
EN 61 095
Switching lamp loads
Switching lamp loadsThe following table shows the number of lamps which can be connected per circuit at 230 V/50 Hz.
Please note the following:
If the specified capacitor load is exceeded, this may result in admissibly high peak inrush currents.
Other factors which influence the magnitude of peak inrush currents are as follows:
– Length and cross-section of installed supply cables
– Type of electronic ballast units
– Lamp make
The following lamp load table thus contains non-binding guideline values.
Fluorescent 150.332530100155
lamps, 200.372226 85135
p.f. uncorrected 400.431720 65105
and series 580.671012 40 65
p.f. correction 650.671012 40 65
1151.5 4 5 18 28
1401.5 4 5 18 28
Lead-lag circuit 2 x 20 2 x 0.13 2 x 22 2 x 26 2 x 85 2 x 140
2 x 40 2 x 0.22 2 x 17 2 x 20 2 x 652 x 105
2 x 58 2 x 0.32 2 x 10 2 x 12 2 x 402 x 65
2 x 65 2 x 0.34 2 x 10 2 x 12 2 x 402 x 65
2 x 115 2 x 0.65 2 x 42 x 52 x 18 2 x 28
2 x 140 2 x 0.75 2 x 42 x 52 x 18 2 x 28
Parallel 150.11681667 4.5
p.f. correction 200.13681667 4.5