WARRANTY STATEMENT
During the applicable warranty period, any Joslyn™surge protector device which fails due to defect in materials, workmanship, or any electrical anomaly, including lightning, shall be repaired or replaced at Joslyn’s discretion.
Prior to shipment of any suspect or known defective product to Joslyn a Return Material Authorization
mber a
(RMA) number must be obtained. An official Joslyn RMA nu obtained from the distributor where the product was originally purchased. Distributors can obtain the official Joslyn RMA number by contacting the Joslyn Customer Service Department at 800-647-1911. Products arriving at Joslyn without an official RMA number will not be accepted and will be returned freight collect to the original point of shipment.
eturn
Products being r nominated point of return as shown on the RMA documentation.
The Company shall have no liability under this warranty for problems or defects directly or indirectly caused by misuse of the Product, alteration of the Product (including removal of any warning labels), accidents, improper installation, application, oper
THIS WARRANTY REPRESENTS THE ENTIRE WARRANTY OF THE COMPANY. ALL OTHER WARRANTIES EXPRESS OR IMPLIED, ORAL OR WRITTEN, INCLUDING, BUT NOT LIMITED TO, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
THE LIABILITY OF THE COMPANY, AT ITS SOLE OPTION, UNDER THIS WARRANTY IS EXPRESSLY LIMITED TO THE REPLACEMENT OR REPAIR THEREOF. IN NO EVENT SHALL THE COMPANY BE LIABLE OR RESPONSIBLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY KIND OR CHARAC­TER, NOR SHALL ITS LIABILITY EVER EXCEED THE PURCHASE PRICE PAID TO JOSLYN FOR SUCH DEFECTIVE PRODUCT.
This warranty is not transferable and may only be enforced by the original purchaser. Claims under this warranty must be submitted to Joslyn w suspected product defect.
ed with an official Joslyn RMA number should be shipped by prepaid freight to the
at
ion or improper repair of the Product.
ithin t
hirty (30) days of discovery of any
nd shipping instructions can be
OF T
HE DEFECTIVE PART
SURGITRON III Series:
1261-21
208/277V, Single-Phase, 2 Wire + Ground
1263-21
480V, Single-Phase, 2 Wire + Ground
1452-21
120/240V, 3-Phase, 4 Wire + Ground (High-Leg Delta)
1456-21
277/480V, 3-Phase, 4 Wire + Ground
1456-21-D
480V, 3-Phase, 3 Wire + Ground, Delta
1457-21
230/400V, 3-Phase, 4 Wire + Ground
Type 2 SPD
AC Surge Protective Device
Installation Operation and Maintenance Manual
Warranty Period SURGITRON
SURGITRON®III TYPE 2 INSTallaTION, OPERaTION aNd MaINTENaNcE MaNUPN: MNldaSH-SURGIII TYPE 2_cOMbO 1.11.10
®
III 3 Years from original date of purchase
5900 Eastport Boulevard Richmond, VA 23231-4453 USA TEL: 800.647.1911 FAX: 804.236.4047 www.joslynsurge.com
SURGITRON®III TYPE 2 INSTallaTION, OPERaTION aNd MaINTENaNcE MaNUal
Page 2
INTRODUCTION
The XXXX-21 Type 2 Surge Protection Device(SPD) is designed for protection of downstream distribution equipment and wiring as well as most sensitive electrical and electronic loads from the effects of overvoltage transients that might be produced from lightning, induction, load or power factor capacitor switching. Multiple LEDs indicate the functional status of the protection elements with
Impor
All work must be performed by qualified electrical personnel. The electrical system must be properly grounded in accordance with applicable codes for this suppressor to work correctly. The XXXX-21 Type 2 SPD must be connected behind a 30A maximum breaker on a system that has a short circuit current rating of 100kAIC maximum.
Installation
The unit must be i the
main service disconnect behind a 30A maximum breaker. Careful consideration should be made in selecting the knockout location because excess lead length and sharp bends in the wire drastically decrease the effectiveness of the SPD. For this reason choose a knockout location that minimizes lead length and sharp bends. metal
1. Disconnect all power supplying the electrical panel
2. Remove the panel screws and cover. Retain these parts for re-installation.
3. Either remove a knockout 0.5 inches (13mm) or install provided metal bracket
4. Remove lock washer from the SPDs threaded nipple. Carefully feed the wires through to
avoid cutting nipple Tighten the lock washer to secure the SPD.
5. Locate the neutral bar inside the electrical panel (except for 1456-21-D) and connect the
white or blue wire to the neutral bar and tighten to torque specified on inside of panel. Keep conduc
6.
Locate the ground bar inside the electrical panel. Connect the green/yellow wire to the
ground bar and tighten the terminal to the torque specified on the panel. Keep conductor length as short as possible and avoid sharp bends. If neutral is bonded to ground, green wire may be terminated to neutral.
7. Black or brown wires can
mined specified on inside of panel. Keep lead lengths as short as possible and avoid sharp bends.
8. Re-install panel cover.
in the suppressor.
tant Safety Instructions
nstalled in parallel to the electrical distribution system on the load side of
The SPD may also be mounted by it's
bracket within the equipment enclosure.
wire insulation. Slide lock washer over the wires to anchor the threaded
. Rotate the SPD so that the function status LED indicators can be easily viewed.
tor length as short as possible and avoid sharp bends in the wire.
be connected to a 30A maximum breaker (# of positions deter-
by the # of black or brown wires provided with the unit). Tighten terminals to torque
Electrical Service Entry
White
White
Green/Ye llow
Black (2 pls.)
Ground
Ground
N
Mounting Surface
Service
Service Panel Side
Panel Side
Black (1, 2, or 3 pls.)
Protector
Protector
Green/Yellow
CAUTION: Do not assume the circuit is de-energized!
!
Remove power before performing any maintenance to the device.
1261-21, 1263-21
Electrical Service Entry
G
1452-21
Operation
1. Apply power to the panel. If the electrical and grounding wirings are done correctly, the
green function status LED will illuminate. If the LED is not on, remove the power and r
eview all of the previous installation procedures.
2. If after a known heavy lightning strike has occurred and the LED is off, reset the breaker.
If the function LED lights come back on then the protector is fine. If the light is still out, or you can not reset the breaker, the protector must be replaced. This unit contains no user servicea
ble parts.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance. Should further information be desired or should particular
1456-21, 1457-21
problems arise which are not covered sufficiently for the purchaser’s purposes the matter should be referred to Joslyn.
SURGITRON®III TYPE 2 INSTallaTION, OPERaTION aNd MaINTENaNcE MaNUal SURGITRON®III TYPE 2 INSTallaTION, OPERaTION aNd MaINTENaNcE MaNUal