AAF International Type LVN RotoClone User Manual

Type N RotoClone
®
Hydrostatic Precipitator - Model LV
Installation, Operation and Maintenance Instructions
Better Air is Our Business
®
Figure 1 Cross section of Type N RotoClone Impeller.
500 1,000 1,500 2,000
Maximum Operating
Wt. Lbs. (Note 1)
1,670 1,700 2,360 2,400
Normal
Operating
Wt. Lbs. (Note 2)
1,570 1,600 2,160 2,200
Water
Capacity
Gallons
61
61 102 102
Erecting
Weight
(Lbs.)
1,045 1,075 1,320 1,360
Note 1: Weight based on maximum sludge capacity with a sludge
weight of 80 pounds per cubic foot.
Note 2: Weight based on weight of water 62.4 pounds per cubic foot.
1.0 Description
1.1 General Information
The Type N RotoClone is a complete dust control unit. Designed to perform its various functions automatically, the RotoClone requires very little maintenance. Like any other mechanical equipment, however, it should have regular attention and be operated according to instructions to insure long life and trouble-free service.
1.2 Operating Principle
The Model LV RotoClone collector cleans the air by the combined action of centrifugal force and a violent inter-mixing of water and dust­laden air. The dust is separated from the gas stream by means of a water curtain created by the high velocity flow of air through a stationary impeller (see Figure 1). This high velocity flow carries water with it in a heavy turbulent sheet. The centrifugal force exerted by the rapid changes in direction of air flow causes the dust particles to penetrate the water droplets and become permanently trapped within them (Figure 1).
The dust-laden water droplets are then removed from the air stream by the water eliminator. The dust settles in the bottom of the collector and the water is reused. Since the water curtain is produced by the airflow, no pumps or nozzles are required.
2.0 Installation Instructions
Read the following instructions completely and carefully.
2.1 Foundations
Foundations must be true, level and rigid enough to prevent vibration and to support the weight of the RotoClone with its maximum dust and water load given below.
Mist Eliminator Baffles
Dirty Air Side
Clean Air Side
Entering Edge
Table of Contents
1.0 Description
1.1 General Information
1.2 Operating Principle
2.0 Installation Instructions
2.1 Foundations
2.2 Lubrication
2.3 Duct Connection
2.4 Water Supply Connection
2.5 Drain Connection
2.6 Electrical Connections
2.7 Water Level Control
3.0 Operating Instructions
3.1 To Fill RotoClone
3.2 To Start RotoClone
3.3 To Stop RotoClone
4.0 Maintenance Instructions
4.1 Removal of Collected Material
4.2 Routine Maintenance
5.0 Troubleshooting
5.1 Correction of Poor
RotoClone Operation
6.0 LVN Bench Attachment
6.1 Description
6.2 Installation Instructions
6.3 Operating Instructions
6.4 Maintenance
Instructions
6.5 Troubleshooting
Figure 2 Typical Type N RotoClone Model LV.
2
control. The regulator should be set at 5 psi. A solenoid valve is also provided. It is to be interlocked with the fan motor starter. The solenoid valve prevents overfilling during shut down. Controls also include a low water level switch and timer.
C.Level probe control (Model A) – Includes an electronic level
controller, level probe, solenoid valve and timer/relay to shut the unit down when water level in the RotoClone is too low. The water level controller and timer/relay are housed in a NEMA 4 control box, shipped separately. The water level controller actuates the solenoid valve when water level does not touch the electronic probe for more than 2 minutes (the time delay minimizes solenoid “chatter”), and allows the solenoid to close when water level again touches the probe. If water does not reach its proper level in the preset time (usually 3 minutes), the timer/relay shuts down the system.
3.0 Operating Instructions
3.1. To Fill RotoClone
A. Close drain valve or insert drain plug (on older units without drain
valve), and open any manual valves in the supply piping.
B. Fill the RotoClone with water to approximately 1
1
2" to 2 " below the operating level on the level indicating tube. The unit will be marked with a horizontal line indicating “Air (Fan) On” water level. For units with the electronic probe, water level should be 1
1
2" to 2 " below the probe tip.
3.2 To Start RotoClone
A. Check that the water level is approximately 2" below the
operating level on the level indicating tube.
B. Make sure sludge removal door is in place.
C. Press “start” button for exhauster motor.
D. Adjust water level to the correct operating level as shown on the
level indicating tube, or until it just touches the electronic probe.
Clean Air Discharge
Sludge Removal Door
Water Inlet
Water Level Control Box
Piping
Fill Valve
Overflow
Drain
Set RotoClone on foundation and adjust base until unit is level. Use care in leveling in both directions as functioning of RotoClone depends on accuracy of this operation.
Note: This level can be checked by filling the unit with water until the level reaches the entering edge (Figure 1) of the impeller. This entering edge should be level with the water along its entire length with maximum variation of1 16" plus or minus. (See Item
1.2, Operating Principles)
2.2 Lubrication
All motor bearings are packed with grease before leaving the factory. Do not add more grease during installation. Some motors have lubrication plugs. They should be removed and replaced with grease fittings. Lubricate every six months under dusty operating conditions, and every 12 months under reasonably clean conditions.
2.3 Duct Connections
The inlet duct must be supported from the floor, wall or ceiling, not from the RotoClone. Four (4) to five (5) inlet diameters of straight duct, prior to the RotoClone, should be allowed to “balance out” uneven air/dust flow from elbows branch entries or other disturbances in front of the RotoClone.
2.4 Water Supply Connection
Units are supplied with a 1" (FPT) quick fill valve and
1
4" (FPT) solenoid valve for automatic water makeup. Connect supply piping to both.
2.5 Drain Connection
A 2" (FPT) drain valve is supplied at the bottom of the hopper. Drain piping, should be attached here and to the 1" (FPT) overflow coupling on the side of the sludge chute.
2.6 Electrical Connections
The normal electrical connections for the RotoClone are to the exhauster motor, water level control - solenoid valve, electronic probe (Model A control), the electrical control box (shipped loose), and the owner’s motor starter (the motor starter, S/S push buttons, control transformer and disconnect are not normally supplied by AAF International). Each connection is to be made in accordance with the appropriate wiring schematic in the RotoClone instruction packet and prevailing electrical codes.
CAUTION:
1. Insure that motor voltage matches line voltage, and wiring is per
diagram on motor.
2. After connecting the motor leads, insure that the motor rotates in
a clockwise direction as viewed from the top of the unit.
2.7 Water Level Control
Supply water makeup for the RotoClone is required because of water losses due to evaporation and sludge removal. There are three types of water level control available on the Type N RotoClone Model LV.
A. Manual control—Water is added through the sludge removal
chute. Water level is controlled to the mark found on the level indicating tube.
B. Float valve control—A float valve is mounted within a control box
located on the side of the RotoClone. The float valve must be adjusted to control the water level to the mark on the level indicating tube. A pressure regulator is provided to improve level
Installation Instructions continued
Loading...
+ 2 hidden pages