Motor Lead Pigtail Splice
for 5/8 kV Non-Shielded Cables
for 1000 Volts or less cables (heavy-duty and two-hole lug applications)
Instructions
Kit Contents (kit contains 3 splices):
3—Lug Covers
3—Locking Pins
3—Tubes Silicone Grease
3—Bag Solvent Cleaning Cloths
3—Mastic Sealing Strip(s)*
3— Strips Scotch
3—Instruction Sheet
*Quantity varies with kit number.
®
Linerless Rubber Splicing Tape 130C
Table 1
Kit Cable
Number
Feeder Motor
5316 8–4 10–4 0.30–0.51
5317 2–1/0 4–1/0 0.43–0.65
5318 1/0–250 2–250 0.53–0.88
5319 250–500 4/0–500 0.75–1.12
Size
(AWG/kcmil)
Range
Insulation
Lead O.D.
Cable
Range Length
CSA Certified for
600V or Less
Max.
in.
in.
in. 1
in. 1
Bolt
1
3
⁄
in.
⁄
2
in.
4
1
in.
⁄
4
1
⁄
in.
2
Technical Information:
• For non-shielded cables
• Rated 5/8 kV
• For cables rated 1000 Volts or less (heavy-duty and two
hole lug applications)
• Cable Size Range: Feeder: #8 AWG—500 kcmil
Motor Lead: #10 AWG—500 kcmil
• Copper Conductors
Caution
Working around energized systems may cause serious
injury or death. Installation should be performed by
personnel familiar with good safety practice in handling
electrical equipment. De-energize and ground all
electrical systems before installing product.
3M
™
Motor Lead
Pigtail Splice Kits
for 5/8 kV or less Non-Shielded Cables
5316, 5317, 5318, 5319
78-8096-4634-8-F
1.0 Prepare Cable According to Standard Procedures
1.1 Check to be sure cables fit within cable kit range as shown in Table 1 on cover.
1.2 Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available, remove
fordepth of lug barrel.
2.0 Install Lugs
2.1 Install and crimp lugs per manufacturer’s direction. See back page if 3M™ Scotchlok™ Copper Lugs are used.
2.2 Clean insulation for approximately 6 using solvent saturated cloths provided in kit.
2.3 FOR 8kV ONLY. Fill lug/insulation gaps with Scotch
Figure 1
®
Scotch
Linerless Rubber Splicing Tape 130C
®
Linerless Rubber Splicing Tape130C (Figure 1).
2.4
Bolt lugs together. See Table 1 on cover for maximum bolt length. See Figure 2 for proper bolt/lug arrangement.
Figure 2
3.0 Install Lug Cover
3.1 Separate cables and apply mastic strip between and around them, 1⁄2" from ends of cable insulations (Figure 3). Build
mastic to an overall diameter that is greater than the inside diameter of the Lug Cover. Press cables together and make
certain that no void exists between them (Figure 3).
3.2 Overwrap the mastic with 1 or 2 wraps of vinyl tape (Figure 3).
Figure 3
2
78-8096-4634-8-F