Motor Lead Pigtail Splice

for 5/8 kV Non-Shielded Cables

for 1000 Volts or less cables (heavy-duty and two-hole lug applications)

Instructions

CSA Certified for 600V or Less

Kit Contents (kit contains 3 splices):

3—Lug Covers 3—Locking Pins 3—Tubes Silicone Grease

3—Bag Solvent Cleaning Cloths

3—Mastic Sealing Strip(s)*

3—Strips Scotch® Linerless Rubber Splicing Tape 130C

3—Instruction Sheet

*Quantity varies with kit number.

Table 1

Kit

Cable Size Range

Cable

 

Max.

Number

(AWG/kcmil)

Insulation

Bolt

 

Feeder

Motor Lead

O.D.Range

Length

5316

8–4

10–4

0.30–0.51 in.

12 in.

5317

2–1/0

4–1/0

0.43–0.65 in.

34 in.

5318

1/0–250

2–250

0.53–0.88

in.

114 in.

5319

250–500

4/0–500

0.75–1.12

in.

112 in.

Technical Information:

•  For non-shielded cables •  Rated 5/8 kV

•  For cables rated 1000 Volts or less (heavy-duty and two hole lug applications)

•  Cable Size Range:  Feeder:  #8 AWG—500 kcmil Motor Lead:  #10 AWG—500 kcmil

•  Copper Conductors

Caution

Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product.

3MMotor Lead

Pigtail Splice Kits

for 5/8 kV or less Non-Shielded Cables

5316, 5317, 5318, 5319

78-8096-4634-8-F

3M 5317, 5319, 5316, 5318 User Manual

1.0  Prepare Cable According to Standard Procedures

1.1  Check to be sure cables fit within cable kit range as shown in Table 1 on cover.

1.2  Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available, remove fordepth of lug barrel.

2.0  Install Lugs

2.1  Install and crimp lugs per manufacturer’s direction. See back page if 3MScotchlokCopper Lugs are used. 2.2  Clean insulation for approximately 6 using solvent saturated cloths provided in kit.

2.3  FOR 8kV ONLY. Fill lug/insulation gaps with Scotch® Linerless Rubber Splicing Tape130C (Figure 1).

Figure 1

Scotch® Linerless Rubber Splicing Tape 130C

2.4  Bolt lugs together.  See Table 1 on cover for maximum bolt length.  See Figure 2 for proper bolt/lug arrangement.

Figure 2

3.0  Install Lug Cover

3.1  Separate cables and apply mastic strip between and around them, 12" from ends of cable insulations (Figure 3).  Build mastic to an overall diameter that is greater than the inside diameter of the Lug Cover.  Press cables together and make certain that no void exists between them (Figure 3).

3.2  Overwrap the mastic with 1 or 2 wraps of vinyl tape (Figure 3).