Engineering Specification Guide
1.0 GENERAL
Manufacturers: Capacities shall be as indicated on drawings and units shall be manufactured by Bard Manufacturing Company, Inc. or prior approved equal.
2.0 CONSTRUCTION FEATURES
2.1 CABINET
Constructed of 20 gauge pre-painted or vinyl laminated galvanized steel. Choices available are either two-tone (vinyl) finish with “slate ” front panels and “platinum” cabinet for des igner appearance, (gray) or (beige) painted steel (select one). Vinyl finish is very resistant to scratching and marring and is easy to clean. Tamper resistant fasteners are provided for access panels. Unit includes built-in rollers for each installation into wall sleeve and removal for service, if necessary. Front panel is hinged and lockable for filter service and access to primary functional electrical controls.
2.2 INSULATION
Cabinet is fully insulated with foil covered, high-density fiberglass insulation with sealed edge treatment and special sound deadening insulation material in the compressor section. All insulation is designed to resist mold and mildew growth and facilitate ease of cleaning.
QW2S-QW5S Water-to-Air H/P
F1915 (2012 04) Page 1 of 6
2.3 COMPRESSOR
All models shall use a high efficiency scroll compressor with step capacity providing 2 stages of control. The compressor shall be covered by a 5-year parts warranty. The refrigeration circuit shall be equipped with factory installed high and low-pressure controls. The refrigeration control shall be a factory installed TXV. Compressor shall be mounted on isolation rails wi th double grommets. Unit shall be provided with R-410A (HFC) non-ozone depleting r efrigerant. Unit shall be provided with liquid line filter/drier.
Current sensing relay shall be used to detect high amps caused by high ambient and/or low voltage and to s hift compressor to 1st-stage operation until conditions corrected
2.4 COAXIAL WATER COIL
All models shall have either cupronickel or copper (SELECT ONE); water coil, fully insulated, with double o-ring connections. Copper coils should not be used on open wells.
2.6 INDOOR BLOWER MOTOR
The indoor blower motor shall be a variable speed (ECM) type to produce the same rated airflow from 0 to .8 inch WC of external static pressure (.5 on Q24W model) at low sound levels. The motor is to be self-adjusting to provide proper rated airflow at high s tatic pressures without user adjustment or wiring c hanges by the user. The motor shall be programmed for 20-second ramp up and 60-second down rate for quiet, smooth starting and stopping. ECM motor shall include preprogrammed speeds for ventilation mode, first stage operation, second stage operation, ducted operation, and non­ducted operation.
2.7 ELECTRICAL COMPONENTS
Electrical components are easily accessible for routine inspection and maintenance through front service panels. Circuit breaker is standard on all 208/230-volt models and rotary disconnect standard on all 460-volt models. Circuit breaker/rotary disconnect access is through lockable access panel. Lock and key are provided as standard equipment. Unit shall have single point entry for line voltage.
2.8 CONTRO L CIRCUIT
The internal control circuit shall consist of a cur rent limiting 24VAC type 65VA transformer with circuit breaker. To prevent rapid compressor short cycling, a five-minute time delay circuit shall be factory installed. Two low-pressure controls shall be included as
F1915 (2012 04) Page 2 of 6