Please read this instruction carefully before use and follow this instruction to operate the de vice in order to
prevent damages on the device or injuries to staff.
Switch off the power before wiring.
DVPDNET-SL is an OPEN TYPE device. Therefore it should be installed in an enclosure free of airborne
dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from
operating the device (e.g. key or specific tools are required for operating the enclosure) in case danger
and damage on the device may occur.
DVPDNET-SL is to be used for controlling the operating machine and equipment. In order not to damage
it, only qualified professional staff familiar with the structure and operation of DVPDNET-SL can install,
operate, wire and maintain it.
DO NOT connect AC power supply to any of the I/O terminals; otherwise serious damage may occur.
Check all the wirings again before switching on the power and DO NOT touch any terminal when the
power is switched on. Make sure the ground terminal
electromagnetic interference.
1.1 Features .............................................................................................................................................1
1.2 Basic Functions of DVPDNET-SL ......................................................................................................1
2.5 Function Switch ..................................................................................................................................4
2.6 Digital Indicator...................................................................................................................................5
2.7 Extension Port ....................................................................................................................................5
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with
DVPDNET-SL.
PIN Signal Color Content
1 V- Black 0V DC
2 CAN_L Blue Signal-
3 SHIELD - Shielded
4 CAN_H White Signal+
5
4
3
2
1
5 V+ Red 24V DC
Note: Either end of the communication cable should be connected with the terminal resistor of
121Ω and the resistors should be connected between “Signal+” and “Signal-”.
DVP-PLC Operation Manual
3
Page 7
DeviceNet Network Scanner DVPDNET-SL
2.4 Address Switch
The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99
are forbidden).
Switch setting Content
0 … 63 Valid DeviceNet node address
64…99 Invalid DeviceNet node address
Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding
switch of x10
1
to 2 and the corresponding switch of x100 to 6.
Note:
z Please set up the node address when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
z When DVPDNET-SL is operating, changing the setting of node address will be invalid.
z Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.5 Function Switch
The function switches are for:
Setting up the work mode (IN0)
Setting up the baud rate of DeviceNet (DR0 ~ DR1)
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
DR1 DR0 Baud rate
OFF OFF 125kbps
OFF ON 250kbps
ON OFF 500kbps
ON ON
ON
IN0
OFF
Entering the mode of extended baud rate
( see Chapter 9)
When the slave is off-line, the I/O data in
the buffer area will be held.
When the slave is off-line, the I/O data in
the buffer area will be cleared.
IN1 Reserved
Note:
z Please set up the function switch when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
z When DVPDNET-SL is operating, changing the setting of the function switch will be invalid.
z Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.
4
DVP-PLC Operation Manual
Page 8
DeviceNet Network Scanner DVPDNET-SL
2.6 Digital Indicator
The digital indicator provides the following two functions:
DVPDNET
POWER
MS
NS
1) Displaying the node address and error messages of DVPDNET-SL .
2) Displaying the error message of slave.
Note:
z When the module works normally, the digital displayer will show its own node ID.
z When "E1" and "03" are on display continuously, it indicates that the error that "E1" refers to
occurs in the slave of node 03.
z When the error codes such as "E7" and "E1" are on display, please refer to section 11.2 for the
correction.
2.7 Extension Port
The extension port is mainly used on connecting DVPDNET-SL to the left-side extension port on DVP-SV PLC
MPU.
DVP-PLC Operation Manual
5
Page 9
DeviceNet Network Scanner DVPDNET-SL
3 Installation
3.1 Connecting DVPDNET-SL to DVP-SV MPU
Adjust the extension clip on the left side of DVP-SV.
Meet the extension port of the MPU with DVPDNET-SL as shown in the figure below.
Fasten the extension clip.
DVPDNETDVP28SV
RUN
STOP
3.2 Installing DVPDNET-SL and DVP-SV MPU on DIN Rail
Use 35mm DIN rail.
Open the DIN rail clip on DVP-SV and DVPDNET-SL. Insert DVP-SV and DVPDNET-SL onto the DIN
rail.
Clip up the DIN rail clips on DVP-SV and DVPDNET-SL to fix DVP-SV and DVPDNET-SL on the DIN rail,
as shown below.
DVPDNET
DVP28SV
35mm DIN rail
RUN
STOP
6
DVP-PLC Operation Manual
Page 10
DeviceNet Network Scanner DVPDNET-SL
3.3 Connecting to DeviceNet Connection Port
The colors on the PINs on the DeviceNet connection port match the colors of the connection cables.
Make sure you connect the cable to the right PIN.
We recommend you also apply Delta’s power module in the connection.
DVP-PLC Operation Manual
7
Page 11
DeviceNet Network Scanner DVPDNET-SL
4 Configuration of DVPDNET-SL
4.1 Configuration through DeviceNet Builder Software
Before DVPDNET-SL starts to work normally, it must be configured through DeviceNet Builder
software.
4.1.1 Selection of Communication Channel
Max 8 DVPDNET-SL modules can be connected to the left side of PLC and every DVPDNET-SL is a
communication channel. When there are three DVPDNET-SL modules connected to PLC’s left side and
DeviceNet Builder software is on line, the following dialog box will pop up for selecting the current channel.
Parameter Explanation
The unit No. of the first DVPDNET-SL(DNET Scanner)on the left side of PLC is 1.
Unit No.
Name
Code
Input
mapping
Output
mapping
PLC’s left side can be connected with max 8 DVPDNET_SL. The further
DVPDNET-S is from PLC MPU, the larger its unit No is.
DVPDNET-SL’s name in DeviceNet Builder software.
For displaying the current mode of DVPDNET-SL: master mode or slave mode.
The register areas which PLC MPU distributes to DVPDNET-SL.The areas are
mainly used to receive the message from DeviceNet Slave and the data from
slave in the bus will be automatically updated to these registers.
The register areas which PLC MPU distributes to DVPDNET-SL. The areas are
mainly used to control DeviceNet slave and the control data in these registers will
be automatically sent to DeviceNet slave in the bus. Slave will take some action
accordingly after receiving the data.
8
DVP-PLC Operation Manual
Page 12
DeviceNet Network Scanner DVPDNET-SL
4.1.2 Setup of Scan Module
The following dialog is for setting DVPDNET-SL’s current mode: master mode or slave mode.
Parameter Explanation
Master
mode
Scan
interval
time
Timeouts
(EPR)
Extended
baud rate
Slave mode
Bit-strobe
Polled
For setting DVPDNET-SL as master mode.
The cycle time for master to send and receive the real time data after real-time
data connection is successful.
The result value of the parameter multiplied by 4. (Unit:ms)
Master assumes that the slave is offline if it receives no response from slave after
timeout.
The parameter gets effective only in master mode.
Selecting “Startup” activates the function of extended baud rate.
Select the appropriate baud rate according to actual demand then.
For setting DVPDNET-SL as slave mode
Reserved; no actual purpose now.
The parameters get effective only in slave mode.
The filled byte number corresponds to the data length for output and input as
DVPDNET-S is taken as slave. “Sending data length” corresponds to “Output
length” and “Receiving data length” corresponds to “Input length”.
COS/CC
Device
mapping
address
Note: These parameters and the configuration information are downloaded to DVPDNET-SL together.
DVP-PLC Operation Manual
Reserved; no actual purpose now.
For AH modes specially; no actual purpose now.
9
Page 13
DeviceNet Network Scanner DVPDNET-SL
4.1.3 Setup of Scan List
Double click the existing icon of DVPDNET-SL in the DeviceNet Builder interface and then the following
dialog box appears for configuring the scan module.
Parameter Explanation
Available
node
Scan list
Node
address
Node name
All already scanned slaves appear in “Available list”.
After the configuration information is downloaded to DVPDNET-SL, the slave in
“Available node” will not conduct the real-time data exchange with DVPDNET-SL.
After the configuration information is downloaded to DVPDNET-SL, the slave in
“Scan list” will conduct the real-time data exchange with DVPDNET-SL.
The station No. for the slave in DeviceNet bus.
The name that “Node address” corresponds to.
10
DVP-PLC Operation Manual
Page 14
DeviceNet Network Scanner DVPDNET-SL
4.1.4 Input Table and Output Table
Select the device in “Scan list” and then the data length of input and output of the device will be displayed
respectively in the lower part of the following dialog box.
Parameter Explanation
Output
Table
Input Table
Register
Device
mapping
PLC MPU’s registers and the corresponding output data are shown in “Output list”.
The values in PLC’s registers will be sent to slave in real time as the control data
of slave.
PLC MPU’s registers and the corresponding input data are shown in “input list”.
The data that slave sends to master will be updated in PLC’s registers in real time.
The number of the register of PLC MPU; “D6289_H” indicates the high byte of
register D6289; “D6289_L” indicates the low byte of register D6289.
For displaying the data type and the name of current slave; “Poll” means the polled
data.
DVP-PLC Operation Manual
11
Page 15
DeviceNet Network Scanner DVPDNET-SL
4.2 Data Mapping Areas
The data mapping introduced in this chapter is the data mapping between PLC MPU and DVPDNET-SL. The
mapping relation is unchanged and user has no right to revise this area.
Max 8 PLC DVPDNET-SL modules can be connected to PLC’s left side. After all DVPDNET-SL are connected
to DVP-SV, DVP-SV will distribute data mapping areas to every DVPDNET-SL.
DVPDNETDVPDNETDVPDNETDVPDNETDVPDNETDVPDNETDVPDNET
DVPDNETDVP28SV
RUN
STOP
The index of DVPDNET-SL is its unit number. The first DVPDNET-SL on the left hand side of DVP-SV is No. 1,
the following DVPDNET-SL modules are No. 2, No. 3, No. 4 and so on.
DVPDNET-SL
index
Output mapping Input mapping
1 D6250 ~ D6497 D6000 ~ D6247
2 D6750 ~ D6997 D6500 ~ D6747
3 D7250 ~ D7497 D7000 ~ D7247
4 D7750 ~ D7997 D7500 ~ D7747
5 D8250 ~ D8497 D8000 ~ D8247
6 D8750 ~ D8997 D8500 ~ D8747
7 D9250 ~ D9497 D9000 ~ D9247
8 D9750 ~ D9997 D9500 ~ D9747
Mapped D registers
4.3 I/O Mapping Table (as master mode)
As DVPDNET-SL of unit No. 1 serves as master mode, the data mapping areas are distributed as below table.
Output mapping area Input mapping area
D register Mapping area Data lengthD register Mapping area Data length
D6250 ~ D6281
D6282 ~ D6285
Explicit message
program request
Bit-strobe
command
D6286 Reserved
D6287 ~ D6476
DeviceNet output
data
D6477 ~ D6497 Reserved
12
32 words D6000 ~ D6031
4 words
1word
D6032 ~ D6035
D6036
190 wordsD6037 ~ D6226
21 words
D6227 ~ D6247 Reserved 21 words
Explicit message
program response
Status of nodes in
the scan list
DVPDNET-SL
status
DeviceNet input
data
DVP-PLC Operation Manual
32 words
4 words
1 word
190 words
Page 16
DeviceNet Network Scanner DVPDNET-SL
Note: If the unit No. is 2, the number of the registers above will all be added by 500 respectively; if the unit No.
is 3, the number of the registers above will all be added by 1000 respectively; if the unit No. is 4, the number of
the registers above will all be added by 1500 respectively and so on.
4.4 I/O Mapping Table (as slave mode)
As DVPDNET-SL serves as slave mode, the data mapping areas are distributed as below table and these
registers are applied for real-time data exchange.
Unit No.
1 D6000 255Bytes D6250 255Bytes
2 D6500 255Bytes D6750 255Bytes
3 D7000 255Bytes D7250 255Bytes
4 D7500 255Bytes D7750 255Bytes
5 D8000 255Bytes D8250 255Bytes
6 D8500 255Bytes D8750 255Bytes
7 D9000 255Bytes D9250 255Bytes
8 D9500 255Bytes D9750 255Bytes
When the unit No. of DVPDNET_SL is 1, the control data which DeviceNet sends out will be updated in real
Initial register Max data length Initial register Max data length
Input mapping area Output mapping area
time in the registers of PLC MPU with D6000 as the initial register. In the meanwhile, the value in the registers
of PLC MPU with D6250 as the initial register will be automatically sent back to DeviceNet master so as to
realize the real-time data exchange.
DVP-PLC Operation Manual
13
Page 17
DeviceNet Network Scanner DVPDNET-SL
3
5 Sending Explicit Message from Ladder Diagram
DVPDNET-SL supports the sending of explicit messages through WPL programs.
5.1 The Principle of Explicit Message Sending
1
Explicit request message
(PLC DVPDNET-SL)
4
Explicit response message
DVPDNETDVP28SV
RUN
STOP
(DVPDNET-SL PLC)
Explicit request message
from master
2
DeviceNet
DNA02
RJ12
VFD-B
Explicit response message
from slave
①: DVP-SV MPU sends out explicit request message to DVPDNET-SL according to WPL program.
②: DVPDNET-SL sends out request message to the target equipment.
③: The target equipment processes the request message and responds DVPDNET-SL.
④: DVP-SV MPU stores the response message from DVPDNET-SL to D register. One explicit message
transmission is therefore completed.
14
DVP-PLC Operation Manual
Page 18
DeviceNet Network Scanner DVPDNET-SL
5.2 Structure of Explicit Message
You can edit explicit messages in “explicit request message editing area” and “explicit response message
editing area”. See the table below for the corresponding relation between the two areas and PLC devices. If
you transmit the request message to be sent out to D6250 ~ D6281, DVPDNET-SL will fill the response
message to D6000 ~ D6031.
PLC device Mapping area Mapping length
D6000 ~ D6031 Explicit response message editing area 64 bytes
D6250 ~ D6281 Explicit request message editing area 64 bytes
1) Structure of request message
See the table below:
PLC device
D6250 ReqID Command
D6251 Port Size
D6252
D6253 High byte of Class ID Low byte of Class ID
D6254 High byte of Instance ID Low byte of Instance ID
D6255
D6256 ~ D6281 Service Data
Command: Fixed to “01Hex”.
ReqID: The request ID. Whenever an explicit message is sent out, the message will be given a ReqID
for DVPDNET-SL to identify. For the next explicit message to be sent out, you have to change the ID
number. ReqID = 0 indicates that DVPDNET-SL will not send out explicit message. Range of ReqID:
00Hex ~ FFHex.
Size: The length of the message, starting from D6253. The high bytes of D6255 are reserved. When
the data length is being calculated, D6255 is counted as 1 byte. The maximum data length is 58 bytes.
Errors will occur when the length is longer than 58 bytes. Unit: byte.
Message Header
Message Data
15 14 13 12 11 10 9876 5 4 3 210
Service Code MAC ID
Reserved Attribute ID (optional)
Request Message
Port: The communication port. Fixed to “00Hex".
MAC ID: The node address of the target equipment on DeviceNet.
Service Code: The service code of the explicit message. See the meanings of the codes in the table
below:
Service Code Explanation
01Hex Read all attributes (Get_Attribute_All)
02Hex Set up all attributes (Set_Attribute_All)
0EHex Read a single attribute (Get_Attribute_Single)
10Hex Set up a single attribute (Set_Attribute_Single)
DVP-PLC Operation Manual
15
Page 19
DeviceNet Network Scanner DVPDNET-SL
2) Structure of response message
See the table below:
PLC device
D6000 ReqID Status
D6001 Port Size
D6002
D6003 ~ 6031 Message Data Service Response Data
The definitions of ReqID, Port, Service Code and MAC ID are the same as their definitions in request
message.
Size: The length of the message, starting from D6003. Max. 58 bytes. Errors will occur when the
length is longer than 58 bytes. Unit: byte.
See the table below for the meanings of Status (status codes):
Status Explanation
0 No explicit message is sent out.
1 The communication of explicit message is successful.
2 The explicit message is being sent out.
3 Error: No response from the target equipment.
4 Error: Command is invalid.
5 Error: Size of request message is invalid.
6 Error: Size of response message is invalid.
7 Error: Failing to establish a connection to the target equipment.
8 ~ 255 Reserved
Message Header
15 14 13 12 11 10 9876 5 4 3 210
Service Code MAC ID
Response Message
3) Notes:
DVPDNET-SL can only send out 1 explicit message at a time.
Before sending explicit message by using WPL program, we suggest you clear the request message
editing area and response message editing area to 0.
If the slave responds with standard error code, and DVPDNET-SL also consider the communication
being successful, “The communication of explicit message is successful.” will indicate that the
communication has been completed successfully.
16
DVP-PLC Operation Manual
Page 20
4) Application example (I)
Target When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502
1> The connection
DeviceNet Network Scanner DVPDNET-SL
DVPDNETDVP28SV
RUN
STOP
Node Address:00
DeviceNet
Node Address:02
RJ12
Note: IFD9502, a Delta DeviceNet slave module can connect VFD AC motor drive to DeviceNet network.
2> Compulsory settings and explanations on devices
Compulsory settings in DVPDNET-SL
Parameter Set value Explanation
Node address 00 Set the node address of DVPDNET-SL to “00”.
Baud rate 500kbps
Set the communication speed of DVPDNET-SL and bus to
“500kbps”.
Compulsory settings in DNA02
Parameter Set value Explanation
Node address 02 Set the node address of DNA02 to “02".
Baud rate 500kbps
Set the communication speed of DNA02 and bus to
“500kbps”.
Compulsory settings in VFD-B
Parameter Set value Explanation
02-00 04 The main frequency is operated on RS-485 interface.
02-01 03
09-00 01 Communication address of VFD-B: 01
09-01 03 Baud rate: 38,400
09-04 03 Modbus RTU mode. Data format <8, N, 2>
DVP-PLC Operation Manual
The operation commands are operated on the
communication interface. Operation by keys is valid.
17
Page 21
DeviceNet Network Scanner DVPDNET-SL
Explanations on devices
PLC device Content
Request
message
editing area
Response
message
editing area
3> PLC program
M1002
Explanation
15 14 13 12 11 10 98765 4 3 2 10
D6250 0101Hex ReqID = 01Hex Command = 01Hex
D6251 0005Hex Port = 00Hex Size = 05Hex
D6252 0E02Hex Service Code = 0EHex MAC ID = 02Hex
D6253
D6254
D6255
0001Hex
0001Hex
0001Hex
High bye of Class ID =00Hex Low byte of Class ID = 01Hex
High byte of Instance ID =
00Hex
Low byte of Instance ID =
01Hex
N/A Attribute ID = 01Hex
D6000 0101Hex ReqID = 01Hex Status = 01Hex
D6001 0002Hex Port = 00Hex Size = 02Hex
D6002 8E02Hex Service Code = 8EHex MAC ID = 02Hex
D6003 031FHex
ZRSTD6000D6031
ZRSTD6250D6281
High byte of Service Data =
03Hex
Reset response message editing area
& request message editing area
Low byte of Service Data =
1FHex
M0
MOVH0101D6250
MOVH0005D6251
MOVH0E02 D6252
MOVH0100D6253
MOVH0100D6254
MOV
H0100D6255
ReqID = 01, Command = 01
Port = 00, Size = 05
Service Code = 0E, MAC ID = 02
Class ID to be read = 01
Instance ID to be read = 01
Attribute ID to be read = 01
4> Program explanations:
In the beginning of the program, clear the response message editing area and request message
editing area to 0.
When M0 = On, DVPDNET-SL will send out request message, reading Class 1>>Instance 1>>
Attribute 1 of the target equipment (node address: 02). If the communication of explicit message is
successful, the slave will return with a response message.
18
When M0 = On, DVPDNET-SL will only send out request message once. If you would like it to send out
request message again, you will have to change ReqID.
When the reading is successful, the message responded from the target equipment will be stored in
D6000 ~ D6003.
DVP-PLC Operation Manual
Page 22
5) Application example (II)
Target M1 = On, set 0x99>>Instance 1>>Attribute 2 of IFD9502 to “0004Hex”.
1> The connection
DeviceNet Network Scanner DVPDNET-SL
Note: IFD9502, a Delta DeviceNet slave module can connect the temperature controller to DeviceNet
network.
2> Compulsory settings and explanations on devices
Compulsory settings in DVPDNET-SL
Parameter Set value Explanation
Node address 00 Set the node address of DVPDNET-SL to “00”.
Baud rate 500kbps
Compulsory settings in DNA02
Parameter Set value Explanation
Node address 02 Set the node address of DNA02 to “02”.
Baud rate 500kbps
Compulsory settings in VFD-B
Parameter Set value Explanation
02-00 04 The main frequency is operated on RS-485 interface.
02-01 03
09-00 01 Communication address of VFD-B: 01
09-01 03 Baud rate: 38,400
09-04 03 Modbus RTU mode. Data format <8, N, 2>
Set the communication speed of DVPDNET-SL and bus to
“500kbps”.
Set the communication speed of DNA02 and bus to
“500kbps”.
The operation commands are operated on the
communication interface. Operation by keys is valid.
DVP-PLC Operation Manual
19
Page 23
DeviceNet Network Scanner DVPDNET-SL
Explanations on devices
PLC device Content
Request
message
editing area
Response
message
editing area
3> PLC program
M1002
Explanation
15 14 13 12 11 10 98765 4 3 2 10
D6250 0101Hex ReqID = 01Hex Command = 01Hex
D6251 0005Hex Port = 00Hex Size = 07Hex
D6252 0E02Hex Service Code = 10Hex MAC ID = 02Hex
D6253
D6254
D6255
0099Hex
0001Hex
0002Hex
High byte of Class ID = 00Hex Low byte of Class ID = 99Hex
High byte of Instance ID =
00Hex
Low byte of Instance ID =
01Hex
N/A Attribute ID = 02Hex
D6256 0004Hex High byte of data = 00Hex Low byte of data = 04Hex
D6000 0101Hex ReqID = 01Hex Status = 01Hex
D6001 0002Hex Port = 00Hex Size = 02Hex
D6002
D6003
9002Hex
0004Hex
Service Code = 90EHex MAC ID = 02Hex
High byte of Service Data =
00Hex
ZRSTD6000D6031
ZRSTD6250D6281
Low byte of Service Data =
04Hex
Reset response message editing area
& request message editing area
M1
MOVH0101D6250
MOVH0008D6251
MOVH0E02D6252
MOVH0099D6253
MOVH0001D6254
MOV
MOV
H0002
H0004
D6255
D6256
ReqID = 01, Command = 01
Po rt = 00, Si ze = 08
Servi ce Code = 0E, MAC ID = 02
Class ID to be write= 99
Instance ID to be = 01written
Attribute ID to be = 02written
Data to be written = 0004
4> Program explanations
In the beginning of the program, clear the response message editing area and request message
editing area to 0.
20
When M1 = On, DVPDNET-SL will send out request message. Write 0004Hex into Class 99 >>
Instance 1 >> Attribute 2 of the target equipment (node address: 02). If the communication of
explicit message is successful, the slave will return with a response message.
DVP-PLC Operation Manual
Page 24
DeviceNet Network Scanner DVPDNET-SL
When M1 = On, DVPDNET-SL will only send out request message once. If you would like it to
send out request message again, you will have to change ReqID.
When the writing is successfully done, the message responded from the target equipment will be
stored in D6000 ~ D6003.
DVP-PLC Operation Manual
21
Page 25
DeviceNet Network Scanner DVPDNET-SL
6 Bit-Strobe Command
6.1 Principle of Bit-Strobe
Bit-strobe is one of the standard I/O transmission methods for DeviceNet. The length of command is fixed to 8
bytes (i.e. 64 bits), and every bit corresponds to a slave.
PLC
device
D6282 Node 15 Node 14 Node 13 … Node 1 Node 0
D6283 Node 31 Node 30 Node 29 … Node 17 Node 16
D6284 Node 47 Node 46 Node 45 … Node 33 Node 32
D6285 Node 63 Node 62 Node 61 … Node 49 Node 48
When b0 of D6282 = 0, the node 0 equipment will be selected, and it will need to respond with a message to
the master. When b0 and b1 of D6282 = 0, the node 0 and node 1 equipment will be selected, and they will be
to respond with a message to the master.
In the bit-strobe mode, the master will not send control data to the slave node. However, when its
b15 b14 b13 … b1 b0
D8283
Corresponding nodes on the network
D6282
b0b1b17b15 b14b30b2b18b16b31
Node 0
Node 1
Node 2
Node 14
corresponding bit is set to 0, the slave node will have to respond with I/O data to the master. When its
corresponding bit is set to 1, the slave node will not have to respond with I/O data to the master.
22
DVP-PLC Operation Manual
Page 26
DeviceNet Network Scanner DVPDNET-SL
7 Display of Node Status on Network
7.1 Display of Node Status in Scan List
This function is to monitor if DeviceNet slave is offline or not. DVPDNET-SL does read-time monitoring to the
nodes in the scan list and maps the status of every node to a bit. You can acquire the node status by
monitoring D6032 ~ D6035. See the table below for the corresponding relation between PLC devices and the
nodes on the network:
PLC
device
D6032 Node 15 Node 14 Node 13 … Node 1 Node 0
D6033 Node 31 Node 30 Node 29 … Node 17 Node 16
D6034 Node 47 Node 46 Node 45 … Node 33 Node 32
D6035 Node 63 Node 62 Node 61 … Node 49 Node 48
When the node in the scan list is normal, the corresponding bit will be off. If the node occurs with abnormality,
its corresponding bit will be On.
b15 b14 b13 … b1 b0
7.2 Status of DVPDNET-SL
You can acquire the real-time status of DVPDNET-SL by monitoring D6036. When DVPDNET-SL runs
normally, D6036 = 0. When DVPDNET-SL is being initialized, the high byte of D6036 = 1 and the low byte = 0.
When error occurs in DVPDNET-SL, the high byte of D6036 = 2. For detailed error information, please refer
to the error codes, i.e. the low byte of D6036.
PLC
device
D6036
b15 b14 b13 b12 b11 b10 b9b8b7b6b5b4b3 b2 b1 b0
Status of DVPDNET-SL
(0: normal, 1: initializing, 2: error)
Corresponding nodes on the network
Explanation
Error codes of DVPDNET-SL
DVP-PLC Operation Manual
23
Page 27
DeviceNet Network Scanner DVPDNET-SL
8 Setup of Slave Mode
DVPDNET-SL can serve as slave through modifying of the mode by software. As DVPDNET-SL serves as slave,
the default input / output data length is 8 bytes and max input / output data length is 255 bytes.
DVPDNET-SL can be set as slave mode in the following method.
1) Connect the devices according to below figure. PC accesses PLC MPU via RS232 or RS485.
DVPDNET-SL
DVP28SV
DeviceNet Builder
2) Open DeviceNet Builder software, and select “Setup” => “Communication Setting” => “System Channel”,
and the “Serial Port Setting” dialog box will appear as below.
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud
rate and communication format. Click on “OK” after configuration is finished.
24
Item Function Default
COM Port
Address
Baud rate
Data Bits 7
Parity Even Parity
Stop Bit
Mode
COM port on the PC to be used to communicate
with DVP-SV
Communication address of DVP-SV
Communication speed between the PC and
DVP-SV
Communication protocol between the PC and
DVP-SV
Communication mode between the PC and
DVP-SV
COM1
01
9,600 (bps)
1
ASCII
DVP-PLC Operation Manual
Page 28
DeviceNet Network Scanner DVPDNET-SL
4) Select “Network” => "Online” and the “Select Communication Channel” dialog box will appear. Click on “OK”
to start scanning the DeviceNet network after selecting “analog online” in the following window.
5) Select “Network” >> “Scan module” and then “Scan module setting” dialog box appears. After “Slave mode”
is selected there, fill the appropriate slave data length. Finally click on “OK” to finish the setting.
6) Select “Network” >> “Download” and then below dialog box appears. Click on “Y” to download the
configuration data to DVPDNET-SL.
7) After download is finished, power PLC off and then repower it. At this time, DVPDNET-SL has been set as
slave mode.
DVP-PLC Operation Manual
25
Page 29
DeviceNet Network Scanner DVPDNET-SL
9 Setup of Extended Baud Rate
9.1 Setup of Extended Baud Rate (as master mode)
1) Connect the device to the Devicenet network according to the following figure. PC accesses PLC MPU via
RS232 or RS485.
DVPDNET-SL
DVP28SV
DeviceNet Builder
2) Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System Channel”. And
then the following dialog box appears.
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud
rate and communication format. Click on “OK” after configuration is finished.
Item Function Default
COM Port
Address
Baud rate
Data Bits 7
Parity Even Parity
Stop Bit
Mode
COM port on the PC to be used to communicate
with DVP-SV
Communication address of DVP-SV
Communication speed between the PC and
DVP-SV
Communication protocol between the PC and
DVP-SV
Communication mode between the PC and
DVP-SV
COM1
01
9,600 (bps)
1
ASCII
4) Select “Network” => "Online” and the following “Select Communication Channel” dialog box will appear. Click
on “OK”.
26
DVP-PLC Operation Manual
Page 30
DeviceNet Network Scanner DVPDNET-SL
5)
Select “Network” => "Setup of scan module” and the following "Setup of scan module” dialog box appears.
Select “Master mode” and “Startup” to activate the function of extended baud rate. In the meanwhile, select
the appropriate baud rate according to the actual demand. Click “OK” to finish setting.
6) Select “Network” => “Download” and the following dialog box appears. Click “OK” to download the
configuration information to DVPDNET-SL.
7) After download is completed, set DVPDNET-SL’s function switch DR0 and DR1 as ON and then repower
PLC to finish the setting of the extended baud rate.
DVP-PLC Operation Manual
27
Page 31
DeviceNet Network Scanner DVPDNET-SL
)
9.2 Setup of Extended Baud Rate (as slave mode)
1) Connect the relevant devices to the DeviceNet network according to the following figure.
DVPDNET-SL(Master
DVP28SV
DeviceNet Builder
DeviceNet
DVP28SV
DVPDNET-SL(Slave)
Note:
a. DVPDNET-SL at the bottom of the above figure has been set as slave mode.
b. The node addresses of two DVPDNET-SLs must not be repeated. (See section 2.4).
c. The baud rates of two DVPDNET-SLs are both 500K bps (See section 2.5).
2) Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System Channel”,
In result, you can see the following dialog box.
28
DVP-PLC Operation Manual
Page 32
DeviceNet Network Scanner DVPDNET-SL
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud
rate and communication format. Click on “OK” after configuration is finished.
Item Function Default
COM Port
Address
Baud rate
Data Bits 7
Parity Even Parity
Stop Bit
Mode
4) Select “Network” => "Online” and the “Select Communication Channel” dialog box will appear. Click on “OK”
to start scanning the entire DeviceNet network.
COM port on the PC to be used to communicate
with DVP-SV
Communication address of DVP-SV
Communication speed between the PC and
DVP-SV
Communication protocol between the PC and
DVP-SV
Communication mode between the PC and
DVP-SV
COM1
01
9,600 (bps)
1
ASCII
5) After scanning is successful, right click DNET (Slave) to select “Parameter editing”.
DVP-PLC Operation Manual
29
Page 33
DeviceNet Network Scanner DVPDNET-SL
6)
Set parameter 5 as “Enable” and select the baud rate in parameter 6 in the following page. Click on
“Download” to download the newly set parameter value to
DVPDNET-SL(Slave).
7) After download is completed, set DVPDNET-SL(Slave)’s function switch: DR0 and DR1 as ON. And then
30
repower PLC to finish the setting of the extended baud rate.
DVP-PLC Operation Manual
Page 34
DeviceNet Network Scanner DVPDNET-SL
10 Application Example on Constructing DeviceNet Network
In this section, we will present an application example, illustrating how to construct a DeviceNet network and the
configuration of the network.
Target Using an X point of DVP28SV to control RUN/STOP of the remote VFD-L AC motor drive.
10.1 How to Construct a DeviceNet Network
1) The connection
DVPDNET-SL
DVP28SV
DeviceNet
VFD-L
VFD-L
START
STOP
RS232
X0
X1
DeviceNet Builder
RTU-DNET
T
E
N
D
U
T
R
Note:
RTU-DNET, a Delta DeviceNet remote IO communication module supports the MODBUS communication
function.
2) Set up DVPDNET-SL, RTU-DNET and
Module Node address Baud rate
DVPDNET-SL 01 500kbps
RTU-DNET 02 500kbps
DVP-PLC Operation Manual
RS485
VFD-L according to the table below.
31
Page 35
DeviceNet Network Scanner DVPDNET-SL
VFD-L
parameter
02-00 4 Transmit the frequency of VFD-L via RS485
02-01 3 Control operation of VFD-L via RS485
09-00 1 Set the node address of VFD-L in Modbus to 1.
09-01 1 Set the communication rate of VFD-L in Modbus 9600
09-04 1 Set the communication format of VFD-L in Modbus to
10.2 How to Configure Network by DeviceNet Network Configuration Tool
1) Configuration of DeviceNet slave
1> Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System
Channel”, and the “Serial Port Setting” dialog box will appear as below.
Set value Explanation
communication.
communication.
7, E, 1, ASCII.
2> Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address,
baud rate and communication format. Click on “OK” after configuration is finished.
Item Function Default
COM Port
Address
Baud rate
Data Bits 7
Parity Even Parity
Stop Bit
Mode
COM port on the PC to be used to
communicate with DVP-SV
Communication address of DVP-SV
Communication speed between the PC and
DVP-SV
Communication protocol between the PC
and DVP-SV
Communication mode between the PC and
DVP-SV
COM1
01
9,600 (bps)
1
ASCII
32
DVP-PLC Operation Manual
Page 36
DeviceNet Network Scanner DVPDNET-SL
3> Select “Network” => "Online”, and the “Select Communication Channel” dialog box will appear.
Clicking on “OK” starts scanning the DeviceNet network.
4> If the bar on the dialog box does not progress, it means the connection between the PC and DVP-SV
is abnormal, or there are other programs also using the COM port on the PC. After the scan is
completed, the dialog box will tell you that the scan is completed, and the icons and device names of
all the nodes scanned on the network will be shown on the screen. See the figure below, in which the
node address of DVPDNET-SL and
RTU-DNET are 01 and 02 respectively.
DVP-PLC Operation Manual
33
Page 37
DeviceNet Network Scanner DVPDNET-SL
5> Double click on RTU-DNET (node 02), and the "Node Configuration…” dialog box will appear.
6> Click on “IO Configure…” button in “Node Configuration” dialog box, and you will then see “RTU
Configuration” page where you click on “Scan IO” button and “Warning” dialog box will appear. Click
“OK” then DeviceNet Builder will detect the devices connected to RTU-DNET as below.
7> Because no special module is connected to the right side of RTU-DNET, “None” will show in the
location of the special module in the following window. The point number for X and Y are both 0.Then
34
click on “Gateway setting”.
DVP-PLC Operation Manual
Page 38
DeviceNet Network Scanner DVPDNET-SL
8> In the interface of “Modbus gateway setting”, use the parameters of one slave and fill the relevant
values there. You can refer to the user manual of RTU-DNET.
Note: The slave here is the slave in Modbus network without direct relation with DeviceNet network.
9> Click on “OK” in the above window and then click on “Download” in the following window to
download the configuration data to RTU-DNET. After download is finished, the configuration
of RTU-DNET is completed.
DVP-PLC Operation Manual
35
Page 39
DeviceNet Network Scanner DVPDNET-SL
>
2) Configuration of DeviceNet Master
1> Double click on DNET Scanner (node 01), and the “Scan Module Configuration..." dialog box will
appear. You can find the currently available nodes, RTU-DNET and VFD-B Drives 230V 3HP, in
the list on the left side. On the right side, there is an empty “Scan List”.
2> (2) Move the slave devices on DeviceNet in the "Available Nodes” list on the left side to the "Scan
List” on the right side. Select a node and click on
scan list.
36
. Follow the steps to move all the nodes to the
DVP-PLC Operation Manual
Page 40
DeviceNet Network Scanner DVPDNET-SL
3> Confirm all the settings and click on “OK”. Next, download the configuration to DVPDNET-SL. If
DVP-SV is in RUN mode while you are downloading the configuration, a “Warning” dialog box will
appear.
4> Click on “OK” to continue the download. Make sure DVP-SV is in RUN mode.
The mapping relation between DVPDNET-SL and slave device is shown as below after
configuration of the DeviceNet network following the above steps is completed.
DVP28SV → DVPDNET-SL → slave device
DVP28SV DVPDNET-SL RTU-DNET & VFD-L
D6287
D6288
Control word of VFD-L
(2000H)
Control frequency of VFD-L
(2001H)
DVP28SV ← DVPDNET-SL ←slave device
DVP28SV DVPDNET-SL RTU-DNET & VFD-L
D6037
DVP-PLC Operation Manual
Output frequency of VFD-L
(2103H)
37
Page 41
DeviceNet Network Scanner DVPDNET-SL
d
s
10.3 Ladder Diagram Program
This section introduces how to edit the ladder diagram program to meet the control request of DeviceNet network.
When X0=ON, VFD-L AC motor drive runs;
Control
request
Explanation of PLC Program
X0
X1
When X1=ON, VFD-L AC motor drive stops;
After VFD-L has run for 6 seconds and at this time the running frequency still has not
reached the designated frequency, Y0 of DVP28SV=ON.
MOVH12D6287
When X0=ON, VFD-L starts up and
its target frequency is 20Hz.
MOVK2000D6288
MOVH1D6287
When X1=ON, VFD-L stops running.
X0
T0
TMRT0K60
LD<>K2000D6037
Y0
( )
Y0 will be ON in DVP28SV if the
frequency of VFD-L has not reache
20Hz after starting up for 6 second
38
DVP-PLC Operation Manual
Page 42
DeviceNet Network Scanner DVPDNET-SL
11 LED Indicator & Trouble-shooting
DVPDNET-SL supports two diagnostic methods: indicator diagnosis and digital displayer diagnosis.
DVPDNET
POWER
MS
NS
11.1 LED Indicator Diagnosis
POWER LED
LED status Indication How to correct
Off Power is abnormal. Make sure DVPDNET-SL is powered.
Green light on Power is normal. --
NS LED
Green light on Normal operation --
MS LED
Green light on Normal operation --
LED status Indication How to correct
Off
Green light
blinking
Red light
blinking
Red light on
LED status Indication How to correct
Off No power Make sure DVPDNET-SL is powered.
Green light
blinking
Red light
blinking
Red light on Internal error
No power or duplicate ID
check has not completed
No communication
Error in communication Check the digital indicator and eliminate the error.
Network error; cannot check
duplicate ID; bus-off (check
the digital indicator)
The master is not
configured.
Some slaves encounter
communication error.
1. Make sure DVPDNET-SL is powered.
2. Make sure at least 1 node or more are
communicating on the network.
No correction is needed; check the digital indicator for
the error.
1. Make sure all the devices have their unique node
address.
2. Check the network for correcting media installation
and baud rate.
3. Check if the node address of DVPDNET-SL is valid.
4. Check if the network power is normal.
Configure the scan list and re-download it to
DVPDNET-SL.
Check the digital indicator and make sure the salve
information in the scan list is consistent with the salve
actually connected.
1. Check if the configuration is valid.
2. Re-power it. If the error still exists, send it back to
the factory for repair.
DVP-PLC Operation Manual
39
Page 43
DeviceNet Network Scanner DVPDNET-SL
MS & NS LED
LED status
NS LED MS LED
Off Off No power Make sure DVPDNET-SL is powered.
Off
Red light on
Red light on
Red light on Red light onHardware error
Green light
on
Green light
on
Red light
blinking
Duplicate ID check has not
completed.
MAC ID detection failure
or bus-off
No 24V DC power from
DeviceNet network
Indication How to correct
11.2 Digital displayer diagnosis
Code Indication How to correct
Node address of
0 ~ 63
80
F0
F1
F2 Low voltage is detected.
F3 Entering test mode
F4 Bus-off
F5 No network power
F6
F7
F8
F9
FA Invalid configuration data
E0
E1
DVPDNET-SL (in normal
operation)
DVPDNET-SL is in STOP
status.
Duplicate MAC ID check
failure
No slave device in the scan
list.
Internal error; Flash or RAM
check error
Internal error; GPIO check
error
Error produced in factory
manufacturing
Internal error; EEPROM
access failure
Device key parameter does
not match the scan list
table.
Data size returned does not
match the scan list.
Make sure at least 1 node or more are
communicating in the network, and the baud
rate is the same as the setting in
DVPDNET-SL.
Change the MAC ID setting and re-power
DVPDNET-SL.
1. Check if the network cable is correctly
connected to DVPDNET-SL.
2. Check the 24V DC network power.
Go to your manufacturer or distributor for
problem-solving.
--
Turn the PLC MPU to RUN and start I/O data
exchange.
Check the node address and re-power DVPDNET-SL.
Configure the scan list and download it to
DVPDNET-SL.
Check if the power of DVPDNET-SL and PLC MPU is
normal.
Switch IN1 from On to Off and re-power
DVPDNET-SL.
1. Check if the network cable is normal.
2. Check if the baud rate is correct.
3. Re-power DVPDNET-SL.
Make sure the cable is correctly connected and check
if the network power is normal.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
1. Configure the network correctly and re-download it
to DVPDNET-SL.
2. Check if the node address of the slave in the scan
list is the same as the node address of
DVPDNET-SL.
Make sure that the device parameter in the scan list
matches the desired key parameter, including vendor
ID, product code, device type and version.
Re-configure the scan list using correct data size.
40
DVP-PLC Operation Manual
Page 44
DeviceNet Network Scanner DVPDNET-SL
Code Indication How to correct
1. Check if there is any change for the node address of
E2
E3
E4
E5
E6
E7
Slave device in the scan list
does not exist or is offline.
DVPDNET-SL fails to
transmit a message.
Error detected in sequence
of fragmented I/O
messages from device
Slave device returns error
when DVPDNET-SL
attempts to communicate
with it.
Data size returned is bigger
than expected.
DVPDNET-SL is checking
MAC ID.
the slave.
2. Check if the communication cable is disconnected
or connected loosely.
Make sure that the connection is valid and check if the
baud rate is correct.
Check if the slave is operating normally.
Check if the slave is operating normally.
Check the configuration of slave device and scan list.
If the code is displayed long, do the troubleshooting
according to the following steps.
1. Make sure that at least two nodes work normally in
the network.
2. Check if either end of the network is connected with
the terminal resistor of 121Ω.
3. Check if the baud rates of the node devices in the
network are consistent with each other.
4. Check if the communication cable is normal so as to
avoid that the cable is disconnected or connected
loosely.
5. Re-power 10DNET scanner module.
DVP-PLC Operation Manual
41
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.