Zyliss CS9BE-THO, CS9B-THO User Manual

CompleteStat-Series Environmental Controllers
THO Models (Temperature, Humidity and Occupancy) THOC Models (Temperature, Humidity, Occupancy and CO2)
Model CS9B-THO and CS9BE-THO Shown
4 Models: CS9B-THO Temperature, Humidity, Occupancy
CS9B-THOC Temperature, Humidity, Occupancy, and CO2 CS9BE-THO Temperature, Humidity, Occupancy w/Ethernet Connection
CS9BE-THOC Temperature, Humidity, Occupancy, and CO2 w/Ethernet Connection
Features---All Models except as Noted:
All-in-One Multi-Function Controllers: THO models: Temperature, Humidity (dehumidification only), Occupancy
THOC models: Temperature, Humidity (dehumidification only), Occupancy and CO2 (On/Off control)
Adaptive Occupancy Scheduling:
1. Automatically learns the start of the 1st persistent occupancy for each day of the week using on­ board motion sensor to create a 7-day start of occupancy schedule
2. Continuously adapts the schedule with any changes to the usage pattern
3. Provides adaptive optimized space warm-up or cool-down with respect to the learned start of occupancy for each day
User-friendly, high contrast, backlit LCD display with Continuous “On” option Simple 5-Button user interface for menu-driven configuration and operation No need for connected PC or programming All models are BACnet capable for MS/TP, EIA-485 using shielded twisted pair for networking BACnet is an ANSI and ISO global standard open communications protocol developed by ASHRAE The “E” Ethernet versions offer alternate method of networking using CAT 5 port on the sub-base 9-relay output for complete and reliable HVAC system control F or C temperature option Conventional modes: 1H/1C, 2H/2C, 1H/2C, 2H/1C, 2H/3C if configured for economizer Heat Pump modes: 1-Stage (2H/1C), 2-Stage (3H/2C, 3H/3C if configured for economizer) Wide Range Occupancy Sensor: senses up to 33 feet distance, 120-degree horizontal and 100-degree vertical
sensing from controller location. Remote occupancy sensor(s) can be added for extreme applications
Built-in alarms and trend logs Configurable password protection with 3 levels of password-protected access Programmable (7-day, 5+2, individual days, up to 12 holidays) or non-programmable No batteries, retains date/time settings for 72-hours during power loss All settings except time maintained permanently in non-volatile memory until changed by user Auto or manual changeover option Fan Operation: Auto/On/Programmed (Programmed is On during Occupied, Auto during Un-Occupied)
Form No F1943-512 Supersedes F1943-212
Page 1 of 2
Temperature Range: Cool 66-90F (19-32C), Heat 60-80F (16-27C)
D
Dehumidification
Output
24VAC SPST RELAY
SC
24VAC to Relay Outputs D, A, W2
Power
A
Ventilation Call
Output
24VAC SPST RELAY
W2
2nd Stage Heating
Output
24VAC SPST RELAY
W1/E
1st Stage Heating/Emer. Heat
Output
24VAC SPST RELAY
SC
24VAC to Relay Outputs W1/E, Y2, Y1
Power
Y2
2nd Stage Compressor
Output
24VAC SPST RELAY
Y1
1st Stage Compressor
Output
24VAC SPST RELAY
Y0
Economizer
Output
24VAC SPST RELAY
SC
24VAC to Relay Outputs YO, O/B, G
Power
O/B
Reversing Valve
Output
24VAC SPST RELAY
G
Indoor Blower
Output
24VAC SPST RELAY
IN9
Not Used
ROS
Remote Occupancy Sensor
Input
Dry Contact (Input to GND)
GND
REM
Remote Temperature Sensor
Input
10K Type II Thermistor
+B
Communications
-A
Communications
OAT
Outdoor Air Temperature Sensor
Input
10K Type II Thermistor
LAS
Leaving Air Temperature Sensor
Input
10K Type II Thermistor
GND
Control Ground
L
Lockout Alarm
Input
Dry Contact (Input to GND)
Com
24VAC Common
Power
24V
24VAC Hot
Power
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com
Form No.
F1943
May, 2012
Supersedes: F1943-212
Due to our continuous product improvement policy, all specifications subject to change without notice.
Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
Page 2 of 2
Temporary Temperature Override feature: 45-minute default setting, adjustable in 5-minute increments Humidity control: Dehumidification only, Range 50-75%, Span is 5-10%. Requires special HVAC system with
dehumidification circuit
Pre-purge capability: Span 0-7200 seconds, default is 0 CO2 control: Range 500-2000 ppm, Span 50-500 ppm Can optionally display space humidity, CO2, and outdoor temperature Dedicated ventilation output Outdoor sensor option, Bard PN 8403-061, can be used to:
o Limit minimum outdoor temperature for cooling operation o Limit minimum outdoor temperature for heat pump operation (compressor lockout) o Inhibit electric heat operation for heat pumps above selected outdoor temperature
Remote indoor sensor option, Bard PN 8403-062, can be used to with following options:
o Use remote indoor sensor only o Average remote indoor sensor and on-board sensor o Highest of connected sensors o Lowest of connected sensors
Vertical mount, mounts to standard 2x4 handy-box installed vertically or horizontally Off-white
Controller Connections: Terminal legend Terminal Function Type Form