Z-Wave T100R Installation Manual

DCN: 140-01773-01 Page 1
Installation Guide
Model T100R
Z-Wave Thermostat
This thermostat is compatible with most HVAC systems, including the following:
24VAC systems Note: requires both the 24R and 24C (common) wires Standard gas/oil/electric heating systems
o 1 stage heating and cooling o 2 stage heating and cooling
Heat Pump systems:
o 1 stage heating and cooling o 2 stage heating and cooling o 2ndor 3rdstage Auxiliary heating (heat strips)
Do NOT use for line voltage controls (120/240VAC)
Stop! Before removing your existing thermostat, be sure to label the
wires with the terminal markings on the old thermostat and record them below
. Standard HVAC System Wiring Terminal
Marking
Meaning Typical Wire Color Record the old thermostat wire
connections and terminal marking here
C
24VAC Common Blue
R
24VAC Return Red
G
Fan Green
W or W1
Heat stage 1 White
Y or Y1
Cool stage 1 Yellow
W2
Heat stage 2 Orange
Y2
Cool stage 2 Black Heat Pump HVAC System Wiring Terminal
Marking
Meaning Typical Wire Color Record the old thermostat wire
connections and terminal marking here
C
24VAC Common Blue
R
24VAC Return Red
G
Fan Green
W or W1
Aux Heat White
Y or Y1
Compressor stage 1 Yellow O (or B*)
Change Over Valve Orange (brown*) Y2
Compressor stage 2 Black * if you have a terminal marked “B” with a brown wire attached to it, that means you have a changeover (C/O) with heating type heat pump system. Be sure to set the change over type in the
Installer Settings menu to C/O Type: w/Heat. Otherwise leave it set to
w/Cool.
DCN: 140-01773-01 Page 2
INSTALLATION
HVAC System Setup
The thermostat requires that you setup the type and configuration of your HVAC system for proper operation. This is done in the
Thermostat Info screen Setup button or the Installer
Settings
screen on the thermostat. The Installer Settings is a hidden screen. To access it, press the main menu button and when the main menu screen appears, press and hold the middle two buttons for 5 seconds.
Thermostat Main Menu
Installer Settings screen
Installer Settings
Before operating the system, you must configure the thermostat for the correct HVAC system type. You will need to know the following information to correctly configure the thermostat. The HVAC setup is in the
Mechanical Settings menu screen.
HVAC system type: What type HVAC system do you have? Standard or Heat pump For Standard systems: Fan Type: Do you have Gas heat or Electric heat? For Heat Pump systems: Change over valve (or reversing valve) type: Does your system
change over with cooling operation or with heating operation? Check your existing
Press and hold two middle buttons to enter the Installer Settings screen
75
Done Select
Display Lock N Service Mode System Settings Max Heat SP 90
Installer Settings
+
_
75
Done Select
User Settings Away Setpoints ZWave Install Thermostat Info
Menu Selection
DCN: 140-01773-01 Page 3
thermostat connects to help determine this. If the original system had an orange wire connected to an “O” terminal, then you have a “changeover with cool” system. If you have a brown wire connected to the “B” terminal, then you have a “change over with heat” system.
Installer Settings Menu items
Display Lock Range: Y or N Default: N
Y = Display LOCKED N = Display unlocked Allows you to lock or unlock the thermostat buttons. When the buttons are locked, you can still access the main menu, but you will not be allowed to select any menu options. The Installer Settings hidden button operation is always operational, allowing you to return to this screen and turn Display Lock off.
Service Mode Test Mode Range: Y or N Default: N
Y= Test mode on. Reduces all delays to 10 sec for quicker system testing N= Test mode off. Normal system delays
CAUTION: in test mode all system safety delays are shorten. Do not operate the system compressor in test mode. Disconnect Y1 or Y2 outputs if using test mode on a live system.
System Settings
Submenu: Sets the HVAC operational settings below Mechanical Settings Submenu: Sets HVAC system type and configuration Type Range: Gas/Elec or Heat pump Default: Gas/Elec
Selects HVAC type, Gas/Electric or Heat pump Fan Type Range: Gas or Elec Default: Gas
Selects the Fan type if system is Gas or Electric C/O Type Range: w/Cool or w/Heat Default: w/Cool
Selects the Heat Pump Changeover Valve type
2ndStage Heat Range: Y or N Default: N Enables the 2
nd
Stage Heat operation
Aux Heat (HP) Range: Y or N Default: Y Enables the Auxiliary Heat operation. Typically the Aux Heat will be heat-strips in a Heat Pump system
2ndStage Cool Range: Y or N Default: N Enables the 2
nd
Stage Cool operation
Schedule Enable Range: Y or N Default: N When enabled, the local thermostats scheduler function is enabled.
Recovery enable Range: Y or N Default: N For Heat Pump Systems. Intelligent setback recovery is an automatic advance start of heating to allow the system to be at setpoint by the schedule time, without the use of Aux heating.