Zuden ZDAS-16CA-16, ZDAS-16CA-8, ZDAS-16CA, ZDAS-16CA-16G User Manual

-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 0 OF 19
SYSTEM ZDAS-16CA SERIES PROGRAMMING GUIDE
USER MANUAL
ZDAS-16CA SERIES
Ver 1210 2010-12-27
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 1 OF 19
Thanks for choosing ZUDEN
ZDAS-16CA Series
Multi-Function Alarm Control Panel. We
suggest you reading carefully this guide, operating this system strictly on the standard procedure.
System ZDAS-16CA Series
is suitable for most circumstances and convenient for using, no matter its appearance, function, or operation. We hope this Guide could answer most of your questions when using the system.
Chapter 1 Summarize
1.1 Summarize
ZDAS-16CA Series
takes advanced microprocessor as its core technology. So it has the
advantages of high integration, very good stability, flexible function and convenient use.
1.2 Attentions before usage
σ Get approval from local police office before presetting the police phone number as the
alarm phone number
σ Ensure the system is in the correct installation, then connect AC power supply with
the panel
σ Only suitable for DC 12V 7AH sealed lead rechargeable storage battery, be cautious
to connect red positive line with positive terminal +,and black negative line with negative terminal(-). The incorrect connection will cause damage of main panel.
σ Rechargeable current 1.5A σ Avoid metal parts or hand contact to the electronic parts on the circuit when install the
lines.
σ Must use 2.7K resistor short unused wired zone σ Mark wires to avoid miss-connection when using too many wired zones σ Cut off all AC power supply, battery and telephone line before maintenance σ Short JP1 when reset main panel σ The 1.00MM copper-core wire from the keypad to alarm panel is up to 150 meters, 4
keypads can be connected in series
Note: After the host programming, please pull out the jumper from JP1 on main board,
which can prevent other person operate the main panel and enhance the security of the host
1.3 Features
σ High speed digital communication, compatible ADEMCO 4+2, CID digital
communication protocolSend alarm signal to alarm center.
σ Can add a eight-way output module(optional), the output mode can be customized:
Linkage output; remote control output (mainly used for monitoring, control home appliances, Lamp. See 4.35
σ Different programmable settings, such as alarm sounds, zone types, recording,
monitoring, remote controlling, telephone number, phone line Check, and etc.
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 2 OF 19
σ Compatible with wired and wireless function(only for ZDAS-16CA-8/16/16G) σ 1 group 6 bit primary passwords, 15 groups subsidiary setting passwords are
available to improve security;
σ 6 groups of phone number and 3 group alarm center phone number could be set.
When the alarm activated, it could repeat dialing the preset numbers.
σ 7 ARM modes: Away ARM, Boundary(Home) ARM, Single zone ARM, Delay ARM,
Remote ARM, Compelled ARM and Time Auto-ARM.
σ 6 DISARM modes: Single zone DISARM, DISARM by keypad, DISARM by remote
controller, Remote DISARM, Timed Auto-DISARM, DISARM when connecting alarm.
σ 9 Zone Types: Instant zone, Emergency Zone, Delay zone, 24 Hours zone,
Anti-Tamper Zone, Fire Zone, Gas Zone, BY-PASS zone, Access Zone
σ Remote control function, external monitor, monitoring from long-distance. σ Built-in voice module, 10~20seconds record, voice alarm function σ Set the alarm delay time and siren yelp time σ Search record of emergency σ Remote controller can be used to set alarm, DIS-Arm, emergency alarm and other
operation(only for ZDAS-16CA-8/16/16G).
σ Operate from keypad, easily and convenient. σ Phone line malfunction indication function: system will alarm when phone line is cut
off or short.
σ The alarm dialling is in priority σ Backup DC 12V 7AH sealed lead rechargeable battery support work when AC power
cut off
σ “Watch dog” function, to avoid system down.
1.4 Configuration
Main configuration Metal box 1pc (transformer and main board inside) Keypad 1pc User Manual 1pc Accessories bag 1pc phone line, 1 bag terminal resistance, 1 pc antenna
1.5 Main specification
Power supply AC220V/110V+10% Stand by consume current: 100mA Power: <1.5W Alarm output current: <650mA, 12V Output voltage: DC12V15V Wireless receiver frequency: 315MHZ /433MHZ Working temperature: -10 55°C Working Humidity: 40 70% Weight: 2.5 kgs Metal box size 255mm×235mm×70mm Keypad size: 159mm×138mm×33mm
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 3 OF 19
Chapter 2 Installation and Connection
2.1 Wiring Diagram
2.1.1 Wiring diagram on main board
indicator LED will light on when working normally, Z1-Z8 means 18 zone
2.1.2 Wiring diagram of expand board(only for ZDAS-16CA/16CA-16)
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 4 OF 19
Z9Z16 means 916 zone
2.1.3 8 zones Expand module(only for ZDAS-16CA/16CA-16) Z9Z16 means 916 zone
It must connect 2.7K resistors, connecting is the same with Z1-Z8. Set expanded 9-16 wired zones ON/OFF.
1. Insert the expand module (Factory setting: inserted)
2. Start setting mode (see 4.3)
3. Format: 79 + status + (Confirm key)
Status: 0 9-16 zones OFF
1 9-16 zones ON (Factory setting: 0)
4. Exit (see 4.4)
Note: The RESET can not return to factory default setting, it must be manual setting.
2.1.4 8-way output module(Optional)
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 5 OF 19
* How to Connect with mainboard: Both 8-way output module and keypad connect to the keypad port of mainboard.
2.2 Connection of Power supply
2.2.1 Connection of transformer: 2 red wires of transformer connect with AC220V/110V Input directly, 2 black wires(output AC16.5V) of transformer connect to AC terminal of AC1 and AC2 on mainboard.
2.2.2 DC12V storage battery connection: The red wire of mainboard connect to the positive of battery, the black wire of mainboard connect to negative of battery.
2.3 Connection of Wired Detector
2.3.1 Connection of signal wires of wired detector:
There are two connection way to avoid destroy,
cutoff or short connection, see picture: 1, NORMALLY CLOSED: Connecting a 2.7K EOL resistor in series to the terminal detector of the
loop of each zone; connecting the other end of the resistor to the signal terminal of wired detector. One of the signal connector should be soldered to the resistor. The other end of resistor should be connected to the other signal
terminal of detector by corresponding signal wire,
and then connected to GND port of main board.
2, NORMALLY OPENED: Connecting a 2.7K resistor in parallel connection to the terminal
detector of the loop of each zone.
2.3.2 Connection of power of Wired Detector: connecting the POSITIVE of wired detector to the AUX port; connecting the negative to the ground wire GND port.
2.3.3 Connecting the unused zones with 2.7K EOL resistor connection, otherwise the
corresponding indicator light will keep lighting, so that the ARM cannot be set.
Note: Mark wires to avoid miss-connection when using too many wired zones!
2.4 Connection of Siren
Siren Port: The POSITIVE of siren should be connected to BELL end of alarm panel; the
negative should be connected to the ground wire GND.
2.5 Connection of Telephone Line
Phone Communication Port: The exterior line should be connected to LIN1, LIN2. TEL1 and
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 6 OF 19
TEL2 should be connected to the telephone.
2.6 Connection of Sound Monitor
Sound Monitor Port: The signal line should be connected to MIK, the POSITIVE should be connected to MIK+, and the negative should be connected to ground wire GND.
2.7 Installation of Keypad
2.7.1 Opening of the keypad: use a screwdriver to open the plastic hole of the back cover upside of the keypad.
2.7.2 Connection of the keypad: SEE PICTURE, use a copper core wire to connect the keypad with connector of alarm panel. The wire from the keypad to alarm panel is up to 150 meters, 4 keypads can be connected in series; to avoid destroy of keypad, the anti temper port could be connected to the terminal of alarm panel.
2.7.3 Keypad address: no address jumper means NO. 1 keypad; insert address jumper “1” means NO. 2 keypad; insert address jumper “2” means NO. 3 keypad; insert address jumper “1” “2” means NO. 4 keypad.
2.7.4 Close the cover when the connection is finished.
2.8 Installation when wireless zones only
(only for ZDAS-16CA-8/16/16G)
If you want to use the wireless zones only, connect the wired zones with GND by 2.7K resistors in short connection, keep close of the wired zones.
Note: Make sure all the connections are correct before power up the alarm panel. Avoiding any opposite connection, short connection of power line, siren line and detector power line; avoiding short connection of detector power line and signal line!
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 7 OF 19
Chapter 3 System Operation
3.1 System Operation
The main usage of the alarm system is to prevent illegal intruder from your home or office, or to get help in emergency. When you are leaving your office or home, make sure all the windows and doors are locked. Set ARM by remote controller or keypad of alarm panel, the system will be in guard status. If any alarm zone is activated, the following circs will happen:
3.1.1 If panel connect with siren, and zone is under “sound alarm” status, the siren will be yelp loudly and there will also be “di” from keypad on spot.
3.1.2 Alarm panel will send the alarm message to control center by telephone network if set to send the alarm to control center.
3.1.3 If telephone number is set, it will dial the preset numbers in turn, After connecting telephone, it can remote control (see 3.7) by telephone.
3.1.4 Zone LED will keep light on in alarm status untill
alarm memory is erased.
3.2 Operation of Remote Controller
(only for ZDAS-16CA-8/16/16G)
Remote Controller
ARM::: Set Away ARM status
DIS-ARM::: Set DIS-ARM status
BOUNDARY (Home) ARM Set BOUNDARY ARM
Emergency: Emergency in robbing status or emergency call
Erasing Alarm message::: Fast press twice “ ” Key of the Remote Controller Note: BOUNDARY ARM will be in effect only when BOUNDARY Zone was set.
3.3 Keypad Panel and Indicator LED Light
Parts Name:
---Function Indicator Light --Zone Indicator Light ---Emergency Key ---Number Key ---Shortcut Key (
-ARM; -Home ARM; - Pause; -Confirm Key)
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 8 OF 19
Specification:
. Function Indicator Light (Power, ARM, Signal, Status, Communication, Setting): Indicate
the working status of the System
Function
Indicator Light
Display
Explanation
ON AC Power Supply Normal
Power Supply
OFF AC Power Failure ON Dialing and Sending message Status, the line is busy
Communication
OFF The line is not in use ON Signal from Wireless Detector Received
Signal
OFF Normal Status ON Keypad Work Normal Flashing Keypad Anti-Tamper Triggered
Status
OFF Keypad ERR ON EXIT/BOUNDARY/Single Zone ARM
ARM
OFF DIS-ARM Status ON Programming Status
Setting
OFF Normal Status
②②
Zone Indicator Light(1, 2, 3……14, 15, 16): Display the Zone Status
Display Explanation
Lighting
Zone triggered; under learning status, ready to learn wireless detector
Fast Flashing
Indicate the Zone disarm after Alarm, but the alarm status hasn’t been erased
Slow Flashing Wired Zone bad connection, the Circuit is Open or Short Lighting in 1
Second
Zones in Effect on ARM Status
Emergency Key (③③③ , , ) 24 hours Alarm Status, can be defined as Fire Alarm, Robbery
Alarm, Emergency Call; No indicator, no sound while alarm; If telephone preset, it will dial the number while alarm, the communication light will on
Number Key (1, 2, 3, 4, 5, 6, 7, 8, 9, *, 0,
④④
##
): For password and program set use.
Shortcut Key (⑤⑤⑤ , , , ) Easy to operation with One Key. --ARM; --Boundary
ARM (Only when boundary Zones Preset); --Pause; --Confirm Key).
Buzzer Sound⑥⑥⑥ ; In this operation, different buzzer sound indicates different meaning
Sound reminde
r
Explanation
A long “di” Remote Controller or Keypad command received Long “di” in 1
minute
“Sound Zone” Alarm
A short “di” A short sound “di” per press the Keypad Short “di” 3
times
Invalid Input or Remote Control Operation
A short “di” per second
“Delay ARM” Started, or “Delay Zone” Activated, the sound will end till the delay time is over
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 9 OF 19
3.4 ARM
ARM means the system is in arm status and ready to response the alarm signal by detectors.
If arm successful, the buzzer give a long sound “di”, the light in corresponding zone is on for 1 second, and the “ARM” indicator light is on; If arm failed, the buzzer will give short sound “di” 3 times and “ARM” indicator light is off, and user should check if any zone is triggered or in open-circuit condition, or the system is already in “ARM” status; If there is “ARM Delay”, the system will exit the delay time after “ARM”, and it will give a short sound “di” per second till delay time is over. The system will not alarm if any zone is triggered before the delay time is over.
3.4.1 Set Away ARM: All zones (except BY-PASS or Screened Zones) start “ARM” Status, if any zone activated, the system will take relevant reaction, dial the alarm center, preset telephone number or local police.
Operation: Press shortcut key on keypad or press “ ” on remote controller to set ARM.
3.4.2 Set BOUNDARY ARM, also named Home ARM, when start “BOUNDARY ARM” status, non-BOUNDARY ARM will not activate alarm.
1, Operation: Press Shortcut Key on keypad or press on Remote Controller to set “Boundary ARM”.Boundary Arm see 4.9
3.4.3 Set Single Zone ARM/ DIS-ARM: the specified zone start “ARM“status, the other zones will not activated alarm.
Operation: Set single zone ARM: Zone Number(0116) Shortcut Key, Set single zone DIS-ARM: Password(6 bit)+Zone Number(01~16)+ Shortcut Key,
3.4.4 Set Fast ARM: system will ignore the “Delay Arm” status to “ARM” the system directly. Operating: press *+
3.4.5
Set Compelled ARM:
1, Start Set Mode (see 4.4) 2, Operation: 76+0/1+ (Confirm Key) (1 means Open, 0 means close, Factory setting is 0) Note: Boundary ARM and Single Zone ARM can be set at the same time, or switch to “ARM” directly during Alarming status.
3.5 Set Disarm
1, Operation: User Password (6 bit) (Confirm Key) (Factory User Password: 123456), or press “ ” key on Remote Controller
2, Disarm Succeed, the buzzer will give a long sound “di”, and ARM Indicator Light off; if system refuse the command, the Buzzer will give a short sound “di” 3 times, or system already in disarm status.
3.6 Remote Control
When System is set as Remote Controllable (See 4.18), (Factory Setting: non-remote control), use telephone or mobile phone to remote control the alarm system to ARM, Disarm, Siren sound, Record or Monitor etc.
Ringing times when dial the preset phone: (Set in Step 4.19, Factory Setting is 8 times); after connected, Input user password: after a long sound “Di”, Access Remote Control Status;
3.6.1 Remote ARM, Disarm
ZDAS-16CA SERIES PROGRAMMING GUIDE
--------------------------------------------------------------------------------------------------------------------------------------------------------
PAGE 10 OF 19
In remote control status: input “1” to start ARM status, if succeed, you will hear a long sound ”Di”, if not succeed, you will hear 3 short sound “di”; input “2” to disarm, if succeed, you will hear a long sound ”Di”, if not succeed, you will hear 3 short sound “di”.
3.6.2 Remote Monitor
In remote control status: press “3” can hear the local sound; press “8” to return.
3.6.3 Remote control to drive the siren
In remote control status, press “4” start siren, press “5” close siren.
3.7 Set Receiving Alarm by Telephone:
when user’s phone received alarm telephone from alarm panel, user can remote control the system by phone or mobile phone. There are 2 methods as following:
3.7.1 It can be programmed as: (See 4.21) automatically play the recorded voice message after picking up phone, press “3” to stop playing the recorded voice during playing, input user password to access Remote Control Status or press “3” to stop playing the recorded voice during playing, access Remote Control Status directly without user password(see4.20),.
3.7.2 Pick-up the alarm telephone after alarm, press “2” hang up (Panel stop dial-up) Remote Control Status: Start remote control status by using telephone or mobile phone, press “1” to start ARM; press “2” to Disarm(stop dial the next phone number after ARM started): press “3” to start Remote Monitor; press “8” to Return, end monitor; press “7” change recorded voice message, press “6” play the recorded voice and confirm, press “8” Exit recording voice; press “4” Start siren, press “5” Close siren and return to remote control status.
Note: the meaning of "1 ", “2”, “3” in Remote control status and Pick up phone operation is not the same.
3.8 Record:
Recording voice message for alarm reminder thru another phone or mobile phone,
There are 2 recording methods: recording from receiving alarm, recording from Dial-up.
3.8.1
Recording from receiving alarm: Access remote control status after picking up the alarm telephone(see3.7.2), press “7” to speak what you want to telephone or mobile phone for recording(10~20 seconds), press “8” exit recording, press “6” play the finished recorded voice message, then hand-up. If need record new voice, press “7” for recording again till it’s satisfied.
3.8.2 Recording from Dial-up 1, Keypad Input Installer password (Factory Setting: 666666) (Confirm Key) Start Set
Status; 71 +1+ Start Remote Control Status; 72 +2+ Set Ring time as 2 times; * # Exit Set Status
2, Record: Use another phone or mobile phone dial phone number of alarm system, after connected, input user password (Factory Setting: 123456), there is a long sound “di”, then press “7” to speak what you want for recording to telephone or mobile phone, press “8” exit recording,
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 11 OF 19
press “6” paly the finished recorded voice message, then hang -up. If need record new voice, press “7” for recording again till it’s satisfied.
3.9 Erasing Alarm message:
Stop the flashing status of alarm indicator light, stop sending
messages to alarm center. 1, Operation: User password (6bit) (Confirm Key) (User Password Factory Setting: 123456)
Or press “ ” key on the remote controller to erasing alarm message 2, If succeed, the buzzer will give a long sound “Di”, the zone indicator LED light off.
3.10 BY-PASS Zone Checking:
Press , the zone LED will light on no more than 1 second.
Chapter 4 System Settings
4.1 Basic Settings from Factory
Name Factory Settings
1. Installer Password 666666
2. User Password 123456
3. Zone Type 0---Instant alarm zone
4. Play recorded voice automatically 0---Inefficacy
5. AC Power Failure check 0---no checking
6. Keypad line cut –off check 0---no checking
7. Keypad anti-disassembly check 0---no checking
8. Telephone Remote Control 0---Inefficacy
9. Ring Times 8 times
10. Delay ARM 0---no delay time
11. Telephone Line Check No Checking
12. Central Communication Protocol 0---CID
13. Telephone alarm control Input ”1” ARM, input ”2” Disarm, input “3” Monitoring
14. Recording No recording
15. Wireless Detector No wireless detector
16. User Number FFFF
17. Alarm Telephone Number No number
Note::: Items from 1 to 12 will return to factory default setting after “RESET”.
4.2 Reset
1. Operation; 951753082 (Confirm Key);
2. Status: Reset successfully, the buzzer will sound a long” Di”, all the indicator LED will light on
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 12 OF 19
for 1 second.
Note: JP1 jumper on the main board must be short connected before this operation.
4.3 Change user Password
1.Change Primary password: Primary password (6 bit) + 08 + (Confirm Key), the setting indicator LED on, input new primary password (6 bit) + (Confirm Key), after the buzzer sound a long “Di”, the indicator LED light off, new primary password is in effect. (Factory default Primary password: 123456)
2. Add Subsidiary Password: Primary password (6 bit) + 08 + (Confirm Key), the setting indicator LED on, input subsidiary password number (2 bit) + (Confirm Key),(01-15 means the serial number of 15 groups subsidiary password) the corresponding LED light on. Input subsidiary password (4 bit) + (Confirm Key), after the buzzer sounds a long “Di”, new subsidiary password is in effect.
3. Delete subsidiary password: Primary password (6 bit) + 08 + + subsidiary password serial number + + , the buzzer will give a long “di” if deleting succeed
4*# Exit setting status,or exit automatically after 30 seconds Note:::Subsidiary password can be used disarm for Away ARM, Fast Arm, Boundary ARM and Compelled ARM.
4.4 Start & Exit Set Mode
1. Start Set Mode:
Operation: Installer password (6 bit) + (Confirm Key) (Factory Installer Password: 666666) Status: If set successfully, the buzzer will sound a long ”Di”; the Indicator LED will light on; If failed,
the buzzer will sound 3 shot “Di”.
2...Exit Set Mode:
Operation: * # Or exit automatically after 30 seconds Status: If Exit set status successfully; the buzzer will sound a long “Di”, the indicator LED will light off;
Or exit automatically after 30 seconds, the buzzer will not sound, indicator LED off. Note: All operations for the following step(4.5-4.39) must be carried out under Set Mode
status(please exit set mode if need normal operation).
4.5 Change Installer Password
Format: 30New Installer Password (6 bit) (Confirm Key);
4.6 Learn Wireless Detectors
(only for ZDAS-16CA-8/16/16G)
1.Format: 20 zone number (2 bit) (Confirm Key), Zone number is from 01~16. Corresponding zone LED will light on.
2. Learning Code: Press any button of remote controller or trigger the detector to send wireless signal to alarm panel. The signal LED will light up when the alarm panel received the signal, Press
(Confirm Key), the corresponding zone LED light off, means the panel’s memory already saved the wireless address code to specified zone, then the panel will receive, and identify the corresponding wireless signal address, and give alarm once detector is triggered.
4.7 Delete Wireless Detectors
(only for ZDAS-16CA-8/16/16G)
Format: 21zone number (2 bit) (Confirm Key); Zone number is from 01~16.
Note: If the deleted detectors activated, the LED indicator on keypad will not light on.
4.8 Set Zone Type and Siren Output
1. Operation: Zone number (2 bit) Zone type (1 bit) Siren status (1 bit) (Confirm Key);
Zone number: 0116, indicates 1~~~~16 zone. Zone Type: 0 Instant zone; 1 Fire Zone; 2 Emergency Zone; 3 Delay zone; 4 24 Hours zone; 5
Anti-Tamper Zone (alarm while the zone is triggered at least 2 times in 30 seconds); 6 Gas Zone; 7 BY-PASS zone, 8 Access Zone (System will under
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 13 OF 19
“Dis-Arm” status once the Access Zone is triggered; system will restore “ARM “ status if it’s no trigger of this special zone); Factory setting is “0”
(Note: “1”, “2”, “4” , “6” zone type is 24-hour ARM status, not effected by ARM or DIS-ARM operation.
Siren status: 0 alarm without sound; 1 sound alarm, factory setting is “1”
4.9 Set Boundary(Home) ArmOnly for ZDAS-16CA-8/16CA-16/16CA/8CA
Format: 19 + Zone number (2 bit) + 0/1(0 close, 1 open)+ (Zone number: 01~16)
4.10 Doorbell function setting(Only for ZDAS-16CA-8/16CA-16/16CA/8CA
Format: 60 + Zone Number (1 bit) + 0/1 + (confirm key) zone number:1~8 “1” open, “0” close Factory setting is “0”), when zone set as Door-Bell zone, it will be Doorbell function in DIS-ARM status, zone will restore normal in ARM status.
Note: The 8th Zone is defined as fixed doorbell zone. The 8th zone will not be affected by set Arm or Dis-Arm if it’s set as doorbell zone.
4.11 Set User Code (Alarm Center Code)
Format: 314 bit User code (Confirm Key);
Delete User Code: 32 (Confirm Key)
4 bit user code is allocated the entering code for alarm center.
Note: Don’t use this operation if not connect with alarm center.
4.12 Set ARM Delay(Exit Delay) Time
Format: 40Time(3 bit) (Confirm Key) Time: 000255 seconds
4.13 Set Alarm Delay(Entry Delay) Time
Format: 43Time(3 bit) (Confirm Key) Time: 000255 seconds
4.14 Set Telephone Number
1. Set Central alarm telephone number Format: 50Telephone Number (Confirm Key) (Don’t use this operation if not connect
with alarm center.) Delete center telephone number: 50 (Confirm Key) 2Set User alarm telephone number Format: 5+ group of phone number (1bit)+phone number+ (Confirm Key) Group of phone number: 1-6 means: 1st to 6th group telephone number.
3. Delete User alarm telephone number Format: 5+ group of phone number (1bit) + (Confirm Key) 4 Set telephone number for connecting internal line to external line
Format: 5+ group of telephone number (1bit) + Preset number in Program control exchange machine (the preset number is the additional dialing number such as 0 or 9 etc before you dial external line from internal line) + + phone number + (Confirm Key)
Group of telephone number: 1~6 means: 1st to 6th group telephone number Note: The system will auto-dial preset telephone number cycled for 10 times until confirmed when
accident happen. Alarm center phone number will not be stopped dialing after Dis-Arm, but user alarm number will stop dialing immediately after Dis-Arm.
4.15 Set 7 Groups Telephone Format
Format: 77 + group of telephone number (0-6) + Format (1 bit) (group 0~6 correspond 50-56) Format: “0” “1” is center communication protocol (“0” CID, “1” program 4+2), “5” user’s telephone, ”6”
ARM
telephone,”7”
Dis-Arm
telephone, “8” Regular checking
Format after reset: “0” is 0, “1--6” group is 5
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 14 OF 19
4.16 Set Report Output
Format: 330/1 (ARM or DIS-ARM)+ 0/1 (program) + 0/1 (low battery) + 0/1 (panel start)
340/1 (AC power Failure)+ 0/1 (AC power recovery) + 00
0 means No Output, 1 means Output (Factory Setting: “1” Output)
4.17 Set
, ,
Key
Format: 670/1 (Confirm Key) ( 0 means close , , key, 1 means open , , key. Factory setting is 1)
4.18 Open/Close Remote Control
Format: 71status(1 bit) (Confirm Key) Status; 0 Close Remote Control, 1 Open Remote Control (Factory Setting: 0 Close)
4.19 Telephone Ringing Times Setting
Format; 72Time(1 bit) (Confirm Key) Time; 19 times (Factory Setting: 8 times)
4.20 Set Accessing Remote Control Status without password
Format: 74status(1 bit) (Confirm Key) Status: 0 need user password, 1 no need user password (Factory setting is “0”)
4.21 Option for Alarm Receiving Control
Format; 75status(1 bit) (Confirm Key) status; 0 Press “1” to play voice message after picking up phone.
1 Automatically play voice message within 5 seconds after picking up phone, or press
“1” to play voice message
4.22 Open/Close Telephone Line Checking
Format: 78Status(1 bit) (Confirm Key)
Status: 0 No Checking, 1 Checking, Alarm while line is cut (Factory Setting: “0” No Checking)
4.23 Set Programmable 4+2 Code for different Alarm Center
Format: 8+ zone number(01~16)+ set alarm code (2 bit) + Set alarm code for zone: 1~8
8+17+set alarm code (2 bit) + Set Arm Code
8+18+set alarm code (2 bit) + Set Dis-Arm Code 8+19+set alarm code (2 bit) + Set key Code 8+20+set alarm code (2 bit) + Set key Code 8+21+set alarm code (2 bit) + Set key Code 8+22+set alarm code (2 bit) + Set Self-Inspection Code 8+23+set alarm code (2 bit) + Programming Changes Code 8+24+set alarm code (2 bit) + Set System Startup Code 8+25+set alarm code (2 bit) + Set AC Power Recovery Code 8+26+set alarm code (2 bit) + Set AC Power Failure Code 8+27+set alarm code (2 bit) + Set Low Battery Code
4.24 Set interval time of Self-inspection Report
Format: 41+ time (2 bit)+ (confirm key)
Time: 00~99 (hours) 00 means cancel report of Self-inspection
Conversion Table
16 Bit Number Related Key
A *0 B *1 C *2 D *3 E *4 F *5
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 15 OF 19
4.25 Set Siren Sound Time
Format: 42+ time (2 bit)+ (confirm key) Time: 00~40 Siren time=(00~40) x 30 seconds Factory setting: 02 means 02 x 30=60seconds
4.26 Set Arm/Disarm with Siren Sound
Format: 61+0/1+ (0, no sound; 1, ARM with 1 sound, Dis-Arm with 2 sounds; Reset won’t change the setting)
4.27 Timed Auto-Arm/ Auto-Disarm Time Setting
1. Time setting format: 45+ hour (2bit) + minute (2 bit) + .
2. Auto-ARM Format: 46+ hour (2bit) +minute (2 bit) + .
3. Auto-Disarm Format: 47+hour (2bit) +minute (2 bit) + .
4.28 Time Adjusting Coefficient Setting
Format: 48 + Coefficient (00--99) + Status: coefficient is 50 after reset make coefficient up if time is too quick (more than 50)
make coefficient down if time is too slow (less than 50)
Note: Time adjusting coefficient is for adjusting the difference per second between system time and the current time. (Each interval coefficient is 1/150S)
4.29 Set Alarm if AC power Failure
Format: Press 62+0/1+ (1. sound; 0. no sound; Factory setting: 0)
4.30 Checking Time Setting
Format: 25+ AC power checking time(1 bit)+ Battery voltage checking time(1 bit)+ Telephone
line checking time(1 bit) +
Time: 0=1S, 1=2S, 2=5S, 3=10S, 4=30S, 5=180 Seconds
(Factory setting: AC power checking time: 3; Battery voltage checking time: 3; Telephone line checking time: 0)
4.31 Zone Sensitivity Setting
Format: 26+ Zone Number(2 bit) + Sensitivity(1 bit) + (Zone number: 01~16) Sensitivity: 0=40 Milli-Seconds, 1=80MS, 2=200MS, 3=500MS, 4=1S, 5=2S, 6=5S (Factory setting: 2)
4.32 Delay Power Off of Low Battery
Format: 28+ Power off delay time (3 bit) +
Power off delay time: 000~255 minutes (Factory setting: 30 minutes)
4.33 Zone Anti-false Report Setting
Format: 29+ Zone triggered times (1bit) + Stop Alarm time (2 bit) +
Zone triggered times: 0~9(Means the maximum continuous triggering times per hour) (Factory
setting: 5) Stop Alarm time: 00~16 hours (Factory setting: 06)
Note: Stop alarm time means how long the system will be activated again after the zones reached the maximum triggering times.
4.34 Open/Close Keypad Anti-Tamper Function
Format: 63+0/1+ (1. open, 0. close. Factory Setting: 0)
4.35 Keypad Line Cutting Inspection
Format: 64+0/1+ (1. open, 0. close. Factory Setting: 0)
4.36 Set Center Precision
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 16 OF 19
Format: 65+ precision value (1 bit)+ (Value: 0~9. Factory Setting: 6)
4.37 Set Center Signal Time
Format: 66+ Signal time (1 bit) + (Time: 0~9. Factory Setting: 6)
4.38 Set Dial-up Rounds
Format: 69+ dial rounds (1-9) + (Factory Setting: 9)
4.39 Set Output Module
* 8 way output time: Format: 35 + Way Number (1~8) + Second (4 bit) + Seconds: 0000—9999 seconds (Factory setting: 60 seconds) * 8 way output conditions: Format: 36 + Way Number (1~8) + Condition 1(2 bit) + Condition 2(2 bit) + (Factory
setting: 0) 8 way output corresponding conditions: 00 means siren following, 01~16 is corresponding
Zone alarm output 17 means Zone alarm output 18 means press emergency key 19 means ARM 20 means DIS-ARM 21 means ARM with output, and DIS-ARM without
output
Remote control of module output:
Format: * + way number(1bit) + status(1bit) + # (Way number: 1~8, means 1st to 8th way, status: 1 open output, 2 close output) For example: under remote control status, * +1 +1 + # (means open output of the 1st way)
* +1 + 0 + # (means close output of the 1st line)
4.40 View The Recording Event Log
Operating: 99 + 2 + (Enter viewing events status)
Record method + ※ ※ + + + + + + + +※ ※ ※ ※ ※ ※ ※ ※
number)days)things)(hour)(minute
Events: 01-16 is zone alarm,30 is Arming, 40 is Disarming, press to view the next event under viewing events status.
4.41 PROG GSM function
(only for ZDAS-16CA-16G) Insert a valid GSM SIM card into the SIM socket, then plug the GSM antenna into the terminator. If the system works well, GSM working indicator & Mainboard working indicator on PCB will be regular flash, and the Status indicator on keypad will light on.
Programming
Note: The following 0 ~ 5 operating is under setting status: (666666+F4)
0. Open Remote Control:
71 + status (1bit) + F4 (Confirm key) Status: 0 Remote Control Off, 1 Remote Control On (Factory Setting: 0 Off)
1. Set phone format for SMS alarm or Call alarm:
77 + group of telephone number (1 bit) + status (1 bit) + F4 (confirm key).
Status: 4 SMS alarm; 5 Call alarm; (Factory default setting: 2nd to 7th group is 5)
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 17 OF 19
(Group of telephone number: 0 ~ 6 correspond 50~56, means: 1st to 7th group telephone number) For example: 1.1 Set Mobile phone numbers with SMS alarm:
77 + group of telephone number (1 bit) + 4 + F4 (confirm key).
1.2 Set phone numbers with call alarm(See: 4.15 in page 18): 77 + group of telephone number (1 bit) + 5 + F4 (confirm key).
2、、Set GSM & PSTN dial-up method:
79 + dial-up method (1 bit) + F4
Dial-up method: “0” for only GSM dialing; “1” for using PSTN first, PSTN cut, it will use GSM;
2” for only PSTN dialing. (Factory default setting: 0)
3、、Select report output format for sending SMS:
32 + Arming (0/1) + Disarming (0/1) + AC power failed (0/1) + Low battery (0/1) + F4. (Factory default setting: 0)
4、、Select report output format for sending message to alarm center:
33 + Arming (0/1) + Disarming (0/1) + Programming (0/1) + Start (0/1) + F4 34+AC power failed (0/1)+AC power ok (0/1)+Low battery (0/1 +Bus short circuit (0/1) F4. (Factory default setting: 0)
5、、Set zone responding time:
26 + Zone number (2 bit) + time (2 bit) + F4 (Zone number: 01 ~ 16) Time parameter: 00~99(00=1/500second, 01=1/50second, (Factory default: 02),
6、、Program the SMS for Remote Arming and Disarming:
Sending the SMS to panel by mobile phone, to realize the remote operation of arming and disarming
SMS Format: User password (6 bit) + “+1” for arming
User password (6 bit) + “+2” for disarming. Note: Above operation must be under remote control statis: 711+F4 (See: 4.18 in page 18 of manual ZDAS-16CA-8)
7、、How to Program the SMS for every zone, every event by users
: Program and send following SMS to the SIM card of GSM panel, if the SMS setting is successfully, the panel will give a short sound “di” and store these messages automatically, then when alarm is triggered or any event is happened, the panel will send the corresponding SMS to the users mobile phone. (User Password: 123456)
User password (6 bit) + Zone number (2 bit) + SMS content for Zone Alarm; Zone number: 01 ~ 16
User password (6 bit) + 17+ SMS content for Arming
User password (6 bit) + 18+ SMS content for Disarming User password (6 bit) + 19+ SMS content for Fire alarm by keypad User password (6 bit) + 20+ SMS content for Emergency alarm by keypad User password (6 bit) + 21+ SMS content for Theft alarm by keypad User password (6 bit) + 22+ SMS content for AC power failed User password (6 bit) + 23+ SMS content for Low battery User password (6 bit) + 24 + SMS content for Bus short circuit User password (6 bit) + 25 + SMS content for Telephone line cut off
For example: if set SMS content of Zone 2 as “Zone 2, Door Sensor Alarm”, program the SMS: 12345602Zone 2, Door Sensor Alarm, then send the SMS.
8. Set
Boundary Arm, Doorbell functionOnly for ZDAS-16CA-16G
Format: 19 + Zone number (2 bit) + Boundary Arm (0/1) + Doorbell (0/1) + Zone number: 01~16; “1” open, “0” close, Factory setting is “0”,
ZDAS-16CA SERIES PROGRAMMING GUIDE
-------------------------------------------------------------------------------------------------------------------------------------------------------­PAGE 18 OF 19
Note: when zone set as Door-Bell zone, it will be Doorbell function in DIS-ARM status, zone will restore normal in ARM status.
Loading...