ZPA Pecky MODACT MOKPED 100 Ex, MODACT MOKPED 600 Ex, MODACT MOKPED 250 Ex Installation And Operating Instructions

Electric single-turn rotary actuators
INSTALLATION AND OPERATING
INSTRUCTIONS
in non-explosive version, with constant
velocity of changing-over the output part
– IP 67 protection
Type numbers 52 320 - 52 322
12/18
CONTENS
1. Application ...........................................................................................................3
2. Operating conditions; Operating position ........................................................................5
3. Operation mode; Service life of actuators ........................................................................7
4. Technical data .......................................................................................................8
5. Actuator outfit .......................................................................................................8
6. Elektric parameters .................................................................................................9
7. Description ...........................................................................................................9
8. Adjustment of electric actuator .................................................................................. 10
9. Assembling and putting the electric actuator into operation ................................................ 31
10. Operation and maintenance of electric actuators ............................................................. 40
Tables ............................................................................................................. 42–44
Dimensions of the actuators MODACT MOKPED Ex ........................................................... 45–48
List of spare parts ..................................................................................................... 49
The Installation and Operating Instructions specify basic principles for mounting, connection, adjustment, operation, maintenance, and repairs of electric explosion-proof actuators. The fundamental prerequisite is that assembly, operation, maintenance, and revisions are performed by skilled technicians qualified for operation and works on explosion-proof electric devices and the works are supervised by a professionally qualified expert instructed in a demonstrable way.
1. APPLICATION
The actuators are designed for shifting valves with reversing rotary motion in circuits of remote control and automatic control. They can also be used for other devices for which they are suitable with their characteristics and parameters. Special cases are to be discussed with the manufacturer.
MODACT MOKPED Ex electric actuators in non-explosive version are intended for control and operation in an environment with danger of explosion of explosive gaseous atmosphere in zone 1 and zone 2 and for areas with flammable dust in zone 21 and zone 22 according to ČSN EN 60079-10 (332320). The actuators are designed in compliance with the standards ČSN EN 60079-0:2013 and ČSN EN 60079-1:2008 for explosive gaseous atmosphere and with the standard ČSN EN 60079-31:2014 for areas with flammable dust.
These are non-explosive electric appliances of the group II, category 2, in areas where occurrence of explosive atmosphere created by gases, vapours or mist – “G“ is probable. The actuators can also be used in areas with flammable dust according to ČSN EN 50281-1-3. The actuators are labelled with a sign of protection against explosion and symbols of the group and category of appliance II 2GD.
The entire electric actuator is designed as explosion-proof enclosure “d” with marking according to the performed certification as follows:
II 2GD Ex d IIC T6 Gb -25 ≤ Ta ≤ 55 °C
Ex d IIB T6 Gb -50 ≤ Ta ≤ 55 °C Ex tb IIIC T80°C Db -50 ≤ Ta ≤ 55 °C
The electric actuator must not be subjected to heavy charging, eg. an intense flow of a dust-air mixtures in order to prevent the occurrence of creeping electrostatic discharges.
Nomenclature
Environment with explosion danger – Environment in which an explosive atmosphere can be created. Explosive gaseous atmosphere – A mixture of flammable substances (in the form of gases, vapours or mist)
with air under atmospheric conditions in which, after initialization, burning spreads out to non-consumed mixture.
Explosive dust atmosphere – mixture of flammable substances in the form of gas, vapour, mist and dust
with air, under atmospheric conditions, in which, after ignition, combustion spreads to the entire unburned mixture.
Maximum surface temperature
Closure – All walls, doors, covers, cable bushings, shafts, rods, pull-rods, etc. which
The highest temperature created during operation under the most unfavourable conditions device, which could induce ignition of surrounding atmosphere.
contribute to the type of protection against explosion and/or to the level of protection (IP) of the electric device.
(however within approved limits) on any surface part of the electric
3
Explosion-proof closure „d“
Zone 1 – A space where probability of occurrence of an explosive atmosphere of
Zone 2 – A space where occurrence of an explosive gaseous atmosphere formed of
Zone 21 – An area in which the explosive atmosphere is created by a cloud of whirled
Zone 22
Type of protection in which the parts capable of causing ignition of an explosive atmosphere are installed inside the closure; in case of internal explosion this closure should withstand pressure of the explosion and prevent spreading of the explosion into the surrounding atmosphere.
a mixture of flammable substances in the form of gas, vapour or mist with the air is occasional under normal operation.
a mixture of flammable substances in the form of gas, vapour or mist with the air is improbable under normal operation; however, if this atmosphere is formed it will only persist for a short period of time.
flammable dust in air formed in normal operation is occasional. An area in which an explosive mixture is not likely to occur in normal operation
and if it occurs it will exist only for a short time.
Applied Standards
The following basic standards apply to explosion-proof actuators:
ČSN EN 60079-14
ČSN IEC 60721 Types of environment for electrical devices.
ČSN EN 60079-0 Electrical devices for explosive gaseous atmosphere. General requirements.
ČSN EN 60079-1 Electrical devices for explosive gaseous atmosphere. Explosion-proof closure “d“.
ČSN EN 60079-10 Electrical devices for explosive gaseous atmosphere. Specification of dangerous areas.
ČSN 33 0371 Non-explosive mixtures. Classification and testing methods.
ČSN 34 3205 Operation of electric rotating machines and work with them.
ČSN EN 1127-1 Explosive atmospheres – Explosion prevention and protection.
ČSN EN 60079-31 Explosion properties. Equipment protected against dust ignition with “t“ closure.
Regulations for electrical devices in areas with a danger of explosion of flammable gasesand vapours.
Designation of explosion-proof properties
It consists of the following symbols:
Ex Electric device complies with the standard ČSN EN 60079-0 and related standards for various types of
protection against explosion. d Designation of the type of protection against explosion, explosion-proof closure according to ČSN EN 60079-1. tb Protection by enclosure “t“ – according to ČSN EN 60079-31. IIC, IIB IIIC Designation of explosion-proof electric equipment for explosive atmospheres with combustible dust, according
T6 T80°C Designation of explosion-proof electric equipment for explosive atmospheres with combustible dust, according
Gb
Db Designation of explosion-proof equipment for explosive dust atmospheres, having a
IP 67 Identification of the degree of protection; according to ČSN EN 60079-0 and ČSN EN 60529.
Designation of the group of explosion-proof electric device according to ČSN EN 60079-0.
to standard ČSN EN 60079-0.
Designation of temperature class of explosion-proof electric device of the Group II according to ČSN EN 60079-0.
to standard ČSN EN 60079-0.
Designation of explosion-proof equipment for explosive gaseous atmospheres, having a “high“ level of protection,
and not a source of ignition in normal operation or during expected malfunctions; according to ČSN EN 60079-0.
“high“
level of protection,
and not a source of ignition in normal operation or during expected malfunctions; according to ČSN EN 60079-0.
Data on actuators
The actuators are fitted with the following plates:
1) Plate with data of non-explosive closures:
or
4
2) Rating and instrument plate contains: – manufacture's name and address
– type designation of product (type number) – serial number – year of production – rated value of tripping torgue Nm – rated speed of shifting s/90° – rated working stroke ° – designation of protective enclosure of actuator IP – weight of actuator kg – mark of conformity CE – electrical data of power circuits (voltage and frequency, current and output of electric motor) – electrical data of control circuit of micro-switches (voltage, current) – position transmitter (resistance, voltage or current)
3) Warning plate
4) Plates on covers with marking of used protection against explosion
or
or front label No. 23354393 for design with local control switches and display.
66 66
2. OPERATING CONDITIONS, OPERATING POSITION
Operating conditions
The MODACT MOKPED Ex actuators should withstand the effect of operating conditions and external influences, Classes
AC1, AD7, AE6, AF2, AG2, AH2, AK2, AL2, AM-2-2, AN2, AP3, BA4, BC3 a BE3 according to ČSN 33 2000-5-51 ed. 3.
Temperature and humidity
The operating temperature for actuators
humidity from 10% to 100% with condensation.
MODACT MOKPED Ex
is -25 °C to +55 °C or -50 °C to +55 °C, relative
5
Classes of external effects – excerpt from ČSN 33 2000-5-51 ed. 3.
Class:
1) AC1 – elevation above sea level ≤ 2000 m
2) AD7 –
3)
AE6
4) AF2 –
5) AG2 – medium mechanical stress by impacts – common industrial processes.
6) AH2 – medium mechanical stress by vibrations – common industrial processes.
7) AK2 – serious risk of growth of vegetation and moulds.
8) AL2 – serious danger of the occurrence of animals (insects, birds, small animals).
9) AM-2-2 – normal level of the signal voltage. No additional requirements.
10) AN2 – medium solar radiation with intensities > 500 W / m2 and ≤ 700 W / m2.
11) AP3 – medium seismic effects; acceleration > 300 Gal ≤ 600 Gal.
12) BA4 – personal abilities. Instructed people.
13) BC3 – frequent contact with the earth potential. Persons coming frequently into contat with “live“ parts or standing
14) BE3 – danger of explosion, production and storage of explosive substances.
water occurrence – shallow dipping strong dustiness occurrence of corrosive or polluting substances from atmosphere. Presence of corrosive substances is significant.
on a conducting base.
Corrosion protection
Actuators are standardly delivered with surface treatment corresponding to category of corrosion aggressiveness
C1, C2 and C3 according to ČSN EN ISO 12944-2.
On customer's request is possible to do surface treatment correcponding to category of corrosion aggressiveness
C4, C5-I and C5-M.
In following table is provided and overview of environment for each categories of corrosion aggressiveness accor-
ding to ČSN EN ISO 12944-2.
Corrosion
aggressiveness
level
C1 Heated buildings with clean atmosphere
(very low) e.g. offices, shops, schools, hotels.
C2 Atmosphere with low level of pollution. Unheated buildings, in which may occur (low) Mostly outdoor areas. condensation, e.g. stocks, sports halls.
(middle) Seaside areas with middle salinity. factories, breweries.
C4 Industrial areas and seaside areas Chemical plants, swimming pools, (high) with middle salinity. seaside shipyard.
C5-I (very high
– industrial)
C5-M (very high Seaside areas with high salinity. – seaside)
MOKPED Ex electric actuators designed for an ambient temperature of -50 ° C to +55 ° C must be resistant to
operating conditions characterized by an ambient temperature range from -50 ° C to +55 ° C.
The actuators are designed with three-phase motors. The aforementioned actuators will be designated with the letter F at the last place of the supplementary type num-
ber: thus 5232x.xxxxEDF.
In all denominations of explosion-proof design of electric actuators Type No. 5232x.xxxxEDF the designation of subgroup II of explosion-proof electric device according to ČSN EN 60079-0 changes from IIC to IIB, i.e. to Ex d IIB T6 Gb.
Urban industrial atmospheres, Production areas with high humidity and low air
C3
mild pollution of sulfur dioxide. pollution, e.g. food industry, processing
Industrial areas with high humidity Buildings or areas with predominantly continuous and aggressive atmosphere. condensation and high air pollution.
Outdoor Indoor
Example of typical environment
Buildings or areas with predominantly continuous condensation and high air pollution.
6
When located in open areas, we recommend you to provide a light shelter to prevent direct impact of
atmospheric conditions. The shelter should overreach the actuator’s ground plan by at least 10 cm at the level of 20 to 30 cm.
When actuators are located in a working environment with temperatures below -10°C, with relative humidity exceeding
80%, below a shelter, or in cold areas, it is always necessary to use the thermal element that is mounted to all actuators.
The heating elements used are resistors TRA 25 5K1/J with a power output of 25W and resistance of 5 kOhm (lo-
cated in the Control area of the actuator) and TRA 15 10K/J with a power of 15 W and a resistance 10 kOhm (located in the area of local control). They are switched by a switch for the heating resistor located on the source circuit board. Computer program can be used to set the switching temperature in the range of -40 to +70 °C. Permanent heating can be reliably ensured the temperature setting +70 °C. Maximum heating flow of the switch is 0.4 A / 230 V.
The present temperature range limit values for the use of the actuators (-40 ° C and +70 ° C), which can be changed
according to customer needs. Exceeding these limits close the fault contact READY and an error signal occurs.
Note: Sheltered areas are considered those where the fall of atmospheric precipitations under an angle up to 60°
is prevented.
Operating position
The actuators MODACT MOKPED Ex can operate in any operating position.
3. OPERATION MODE, SERVICE LIFE OF ACTUATORS
Operation mode
The actuators can operate at rated load torque, which is 50% of the maximum tripping torque, with S2 type load.
The operation time is in this kind of load is 10 minutes at ambient environment temperature up to +55 ° C. The actuators can operate at rated load torque and intermittent operation with start-up with the S4 type of load according to ČSN EN 60034-1 (35 0000). The load factor is 25%, and switching frequency up to 1200 times per hour. The maximum duty cycle is determined by the run time at a full stroke of the actuator. Maximum medium level of load torque equals to rated torque of actuator. The highest mean value of loading torque is equal to rated torque of the actuator.
Run time N
Mz starting torque ≥ 1,3 . M
M
Mv maximum value of tripping torque
Cycle time
mean value of loading torque
stř
Idle time R
v
Course of working cycle
Service life of actuators
The actuator intended for shut-off valves must be able to perform at least 10,000 operating cycles (C - O - C). The actuator intended for regulating purposes must be able to perform at least 1 million cycles with operation time (during
which the output shaft is moving) at least 250 hours. Service life in operating hours (h) depends on load and number of switching. Not always, high frequency of switching influences positively accuracy of regulation. For attaining the longest possible faultless period and service life, frequency of switching is recommended to be set to the lowest number of switching necessary for the given process. Orientation data of service life derived from the set regulation parameters are shown in the following table.
Service life of actuators for 1 million starts
Service life [h] 830 1000 2000 4000 Number of starts [1/h] Max. number of starts 1200 1000 500 250
7
4. TECHNICAL DATA
Basic technical parameters are given in Table 1.
Power supply
– nominal value of the AC voltage is 1 x 230 V or 3 x 400 V (according to version) – permitted power supply voltage tolerance is -10 % to +6 % of the nominal value – rated frequency of supply voltage is 50 Hz – permitted power supply voltage frequency tolerance is 2% of the nominal value
Within this supply voltage range, all parameters are kept up except the starting torque which varies with the square of the supply voltage deviation from the rated value. This dependence is directly proportional to the supply voltage variation; no larger supply voltage and frequency fluctuations are permitted.
Protective enclosure
Protective enclosure of the MODACT MOKPED Ex actuators is IP 67 according to ČSN EN 60529 (33 0330).
Noise
Level of acoustic pressure A max. 85 dB (A)
Level of acoustic output A max. 95 dB (A)
Tripping torque
At the factory, the tripping torque has been adjusted as shown in Table 1, according to the customer’s requirements. If no tripping torque adjustment has been specified by the customer the maximum tripping torque is adjusted.
Self-locking
Actuator self-locking capacity is provided by mechanical electric motor brake, at actuator type no. 52 320 by mechanic gearbox brake.
Sense of rotation
When looking at the output shaft in the direction towards the control box, the CLOSE direction of rotation is identical with the clockwise sense.
Working stroke
The working stroke of MODACT MOKPED Ex actuator is 90° (after agreement with the manufacturer actuators can be supplied with working stroke 60 °, 120 ° or 160 °).
Manual control
The actuators are controlled by a hand wheel directly (without a clutch) and control is possible even during operation of the electric motor. When rotating the hand wheel in clockwise direction, the actuator’s output shaft also rotates in clockwise direction (looking at the local position indicator). Handwheel direction of rotation is also indicated on the label of the handwheel.
Torque-limit switches in the actuator are set and work when the actuator is under voltage.
When using the manual control, ie. actuator is controlled mechanically, the torque-limit switches doesn´t work and the valve can be damaged.
5. ACTUATOR OUTFIT
Position indicator
The actuator can be fitted with a display as an option for DMS2 ED electronic system. Actuator with DMS2 electronic system is equipped with two-line display.
Heating element
Actuators are equipped with a heating element to prevent water vapour condensation. As a heating element they apply resistors TRA 25 10 K/J with an output of 25 W and resistance of 10 kΩ. They are switched by a switch for the heating resistor located on the source circuit board. It is possible to use a computer to set the switching temperature in the range of -40 to +70 °C. Permanent heating can reliably be ensured by the temperature setting +70 °C. Maximum heating current of the switch is 0.4 A/230 V.
8
The preset temperature range limit values of the actuators (-40 °C and +70 °C) can be changed according to
customer needs. Exceeding these limits close the fault contact READY and an error signal occurs.
Local control
Local control serves for controlling the actuator from the site of its installation. For DMS2 ED electronic system includes
two change-over switches: one with positions “Remote control – Off - Local control“, the other “Open – Stop – Close“.
The first change-over switch can be built-in as two-pole or four-pole. The change-over switches are installed in
a terminal-board box and the control elements on the lid of this terminal-board box.
If the actuator is equipped with DMS electronic system local control consists of 3 buttons – “Open“, “Stop“, “Close“
and rotary switch “Local, Remote, Off“.
6. ELECTRIC PARAMETERS
Terminal board of the actuator
Electrical equipment consists of electronics power supply circuit and motor control circuit. Connection of the dis-
tribution network is performed by means of the terminal board located on the control module. The terminal block is designed that the total connection does not need any other terminals.
This terminal board uses screw terminals allowing to connect conductors with a maximum cross-section of
2,5 mm2.
Actuator internal wiring
The internal wiring diagrams of the MODACT MOKPED Ex actuators with terminal designation are shown in this
Mounting and operating instructions.
Each actuator is provided with its internal wiring diagram on the inner side of the actuator. The terminals are
marked on a self-adhesive label attached to a carrying strip under the terminal block.
Isolation resistance
Isolation resistance of electric control circuits against the frame and against each other is min. 20 MΩ.
Isolation resistance of the electric motor is min. 1,9 MΩ. After a dump test, isolation resistance of control circuits is min. 2 MΩ.
Electric strength of electric circuits isolation
MOKPED Ex actuator with electronic system are tested:
circuits of anti-condensation heater 1500 V 50 Hz circuits of electric motor 1000 V +2.Ujm 50 Hz, at least 1500 V circuits of outgoing and control signal circuits 50 V DC
Deviations of basic parameters
Tripping torque ±15 % of max. value of range Adjusting time
+10 % till -15 % of rated value (idle run)
Protection
The actuators are fitted with one internal and one external protective terminals ensuring protection against electric
shock according to ČSN 33 2000-4-41. One protective terminal is also fitted to the electric motor. The protective terminals are labelled with a mark according to ČSN EN 60417-1a2 (013760).
7. DESCRIPTION
The entire actuator is designed as explosion-proof closure “d“ marked Ex d IICT6 Gb or Ex d IIB T6 Gb for
explosive gaseous atmosphere and Ex tb IIIC T80°C Db IP67 for areas with flammable dust.
If the actuator is equipped with local control unit, the local control unit makes another explosion-proof closure “d“.
Both explosion-proof closures are in such case separated by a bushing.
9
The motors consist of two parts: a) Power part – is used to draw the necessary torque to the valve and is composed of a single- or three-phase
asynchronous electric motor, countershaft gear box, planet gear box with output shaft, device for manual control
with a hand wheel and floating screw. b) Control (electronic) part onsisting of DMS2 or DMS2 ED electronic system is used to control the actuator. The individual
modules of both electronic systems and their functions are described in Chapter ELECTRONIC OUTFIT.
Operation of the position-limit is derived from rotation of the output shaft via special mechanisms. Operation of the torque-limit switches is derived from axial displacement of the “floating worm” of the manual control unit which is scanned and transferred to the control box.
The tripping torque can be adjusted within the range specified in the table 1. Torque switches may be blocked when actuator needs to produce a starting torque.
Showing position of the output shaft of the actuator can be either on site using mechanical indicators or display that can be installed in the actuator or remotely via an analog output signal and the corresponding indicator. Indicator is not included in the delivery.
8. ADJUSTMENT OF ELECTRIC ACTUATOR
Stop screws
The stop screws are used to limit the working stroke of the electric actuator to a required value in compliance with and positions “Closed“ or “Opened“ of the piping fittings which do not have their own stops. The stop screws are located on the external side of the electric motor where the external protective terminal is also fitted. When viewing the stop screws, the right stop screw is intended for the position “Closed“ and the left one for the position “Opened“. Herewith, it is assumed that, when viewed in the direction to the local position indicator, the output shaft moves in the clockwise sense if it rotates in the direction to “Closed“. Adjustment of the stop screws is carried out in such a way that the stop screws are first released, the electric actuator with the piping fitting is moved to the position “Closed“ and the particular stop screw is rotated until there is a perceptible increased resistance as the screw strikes against the contact plate of the output shaft of the electric actuator. The stop screw is secured by proper tightening of its safety nut. Then, the output shaft of the electric actuator is turned to the position “Opened“ and the stop screw is adjusted for the position “Opened“ in a similar way.
If a tight closure is required in the end position of the piping fitting and, hence, cutting-out of the electric actuator by means of the moment switches the cutting-out moment should be transferred to the piping fitting. In such case the particular stop screw is set so that the piping fitting is properly tight when the trips of the output shaft strike against the stop screw with cutting-out of the moment switch. Herein, the position and moment switches are connected in series. This can only be realized in the case when a tightly closed piping fitting is not required.
Clamp rings according to DIN 6799 are use to avoid removing of stop screws. These rings are removable only from the inside of explosion-proof closure and may in no case be removed.
ELECTRONIC OUTFIT
The actuator is controlled with the electronic system DMS2 or DMS2 ED. Both systems scan position of the output shaft and torque of the electric actuator by contact-free magnetic sensors. Long service life is guaranteed for the contact-free sensors that do not get mechanically worn.
The sensor of the output shaft position is absolute and does not require any backup power supply in case supply voltage is disconnected during operation of the electric actuator. Both systems can be set and monitored by a computer with controlling program (set parameter can be backed up on a computer) or manually without a computer (for the
electronics DMS2, parameters can be manually set and it can be checked without computer only if the system is equipped with a display and local control). They contain diagnostic functions – error messages on the display, memory
of recent failures and number of occurrences of respective failures.
The more simple system DMS2 ED substitutes the electro-mechanical board and/or provides for controlling the electric actuator by input analog signal as in the version Control.
The system DMS2 enables the electric actuator to be used for two-position and three-position regulation or to be connected to the industrial bus bar Profibus.
10
DMS2 ED SYSTEM
Basic outfit of the DMS2 ED electronics:
Position control unit – main part of the system DMS2 ED – includes microcomputer, position
sensor, 3 signal lamps LED, 4 push-buttons for simple setting and checking the actuator, connectors for connecting the torque sensor, source board, and interface RS 232 (connection of computer for setting and diagnostics).
Source unit
Torque sensor – provides contactless torque sensing
Optional outfit of the DMS2 ED electronics:
Analog module – output of feed-back signal 4 – 20 mA, in version CONTROL input of
LCD display – communication, position indicator
Local control
Reversing relays – for three-phase motors
electronic power supply, user's terminal board (connection of power supply and control signals), 2 torque relays, 2 position relays, 2 signal­ling relays, 1 relay for signalling errors (READY), switch of resistance anti- condensation heater and its thermostatic control, connectors for connecting the control unit and analog CPT module.
control signal 0/4 – 20 mA
Technical parameters of the DMS2 ED electronics:
Scanning of position contact-less, magnetic
Scanning of torque contact-less, magnetic
Working stroke see 90°
Torque blocking 0 – 20 s at reversing in limit positions
Input signal 0(4) – 20 mA, 20 – 0(4) mA with switched on regulator function
Local/Remote control, Local open/close
Output signal 7 x relay 250 V AC, 3 A (MO, MZ, PO, PZ, SO, SZ, READY)
Position signal 4 – 20 mA, max. 500 Ω, active/passive, galvanic-isolated, 2x12 character LED display
Power supply of electronic 230 V AC, 50 Hz, 4 W, over-voltage category II
Design of DMS2 ED electronics:
Replacement of electromechanical board
CONTROL the electronics covers also function of the regulator; the output shaft
– the provided relay contacts substitute position, torque and signalling micro-
switches; current feed-back signal 4 – 20 mA can also be brought out; the actuator is controlled by the superior control system with signals “open“ and
“close“.
position is controlled by analog input signal.
Function and setting of output relays
The output relays replace end-limit micro-switches; to some extent, function of the output relays differs according to
chosen mode of electronics or it can be selected, preferably by the setting program.
Setting program – allows to select multiple authorization levels (user, service, manufacturing) and thereby change
various parameters of the electronic equipment.
Setting program – is same for communication with the electronics DMS2ED and DMS2. The users' version can
be freely downloaded. The next level of approval is given by the HW key, which must be connected to the computer.
Program is modified to leading the user by excluding the impossible variants.
11
Note: In the window “Parameters” of the setting program, column “Access”, the word “NO” designates parameters that cannot be changed by the user (change of these parameters is blocked).
For actuator with DMS2 ED electronic system in “Replacement of electro-mechanical board“ design have two contacts function of torque switches, two contacts function of position switches and two contacts can be used according to the customer requirements according to the list below (typically a function of signalling
switches).
In version CONTROL have two contacts function of motor relay (they control the actuator in “open“ and “close“ position by comparison result of the output shaft of the actuator and input signal), two contacts have
function of torque switches or torque + position switches according to setting, two contacts are available to the customer.
Parametr – Parameter Změna – Change Chyba – Error Přístup – Access Setrvačnost (0,1 %) – Inertia [0.1 %] Setr. Doběh (0,1 s) – Inertial run-out [0.1 s] Necitlivost (%) – Insensitivity [%] NE – NO
Relay MO, MZ, SO, SZ
Relay DMS2 ED DMS2 ED Control
torque open
MO
(also changes-over to errors)
torque closed
MZ
(also changes-over to errors)
PO position open
PZ position closed
torque open (also changes-over to errors )
+ optional tripping in position open (parameter Tripping)
torque closed (also changes-over to errors )
+ optional tripping in position closed (parameter Tripping)
motor open
motor closed
In the version Control, the function of relay MO/MZ is same as that of motor relays.
Their operation is controlled by: regulation loop (deviation of required and actual position)
active errors
Any induced active error will change over both relays to a standstill position (coils not energized). In case of errors, the relays with a function of torque relays (in both versions DMS2 ED and DMS2 ED Control) are also controlled.
List of functions that can be selected for signalling contacts SO, SZ:
off torque and position O position torque O or Z
position O torque and position Z position negated
position Z opening control – local
torque O closing control – remote
torque Z movement control – off
Ready contact relays for errors signalling and non-standard states according to the following list:
off warnings + errors torque O or Z
warning errors + not remote
errors errors + warnings + not remote
12
Note:
COM
POWER
TORK
AIN
LED1
LED2 LED3
MENU
P
O
C
Error – a condition that affects the electronics, actuator reacts according to “Response to failure and SAFE
signal“ (SAFE – external signal, which can impose error condition to the actuator. May use, for instance, when the actuator must be set as an error because the error occurred in another device).
Warning – condition, which is only indicated, will not affect the electronics. Can be set what condition will be evaluated as a Warning and what as an Error.
Procedure of setting parameters by means of push-buttons
For simple programming of required operating parameters, the control unit is fitted with four push-buttons:
MENU, P, O, C and three signal lamps.
Colours of diodes:
LED1 – yellow (menu number) LED2 – red (parameter value) LED3 – green
Push-buttons and signal lamps LED on control unit DMS2.ED.S and DMS2.ED.S90
Yellow Red Green State
- - - System without feeding
- - lit on Everything OK – working regime (remote, local or switched off control)
- blinking lit on Error or warning – working regime (remote, local or switched off control) lit on - lit on Enter or exit of Setting of parameters by means of push-buttons or Setting of parameters by means of PC blinking - lit on blinking blinking lit on Setting of parameters by means of push-buttons blinking lit on lit on
Zápis poloha zavřeno, otevřeno a autokalibrace
– The actuator is set to position Closed and position Closed is stored by long pressing of push-button C – until the
LED1 turns on (without entering the Menu).
– The actuator is set to position Open and position Open is stored by long pressing of push-button O – until the LED1
turns on.
– The calibration routine is started by means of push-button P (in remote control) that, in the three-position regulation,
will measure actual inertial masses of the system and store them into the memory of the control unit.
This function is designed for 3P regulation only and serves to measure the inertial mass. – In case the actuator stroke is to be increased and the switching off is set to “from position“, the actuator will
switch off during shifting in position 0 or 100 %. To further change the position, press C or O, and, while keeping it depressed, the actuator can be further shifted.
Overview of MENU
BROWSING THROUGH MENU –
The setting mode is entered by pressing and keeping depressed push-button MENU for at least 2 s; LED1 is then lit on.
Shortly press MENU to select the basic MENU – menu M1 to M8 of P, O, C they are entered
Shortly press P to select required value of the parameter. In case the parameter can be set to several values, they are changed by short pressing of P
(LED2 signalizes particular parameter).
(number of blinking of LED2 indicates its value).
chosen parameter; the record is confirmed by lighting on of LED2.
– –
Shortly press MENU to gradually set the required menu and parameters. After setting all required parameters, exit the setting menu by pressing and keeping depressed push-button MENU for at
least 2 s. The setting menu will also be left in case that no push-button is pressed within 1 minute.
(LED1 signalizes the menu number);
13
by short pressing
Keep pressing of P to record the
Main window of setting program Selection of electronics
MENU 1 – Setting of tripping torques
– After entering the menu by means of push-button C or O, select required torque. – Shortly press P to select the set value of the parameter 50 – 100 % (5 – 10 blinking of LED2) and keep pressing
push-button P to store the parameter to memory.
MENU 2 – Setting function of signalling relays
– Basic setting of the signalling relays is SZ 1 % and SO 99 % of stroke. – In case different setting is required, it can be changed after shifting the actuator to required position by means of
push-button C or O. – Using push-button P, perform basic setting SZ 1 % and SO 99 % of stroke.
MENU 3 – Setting of blocking of torque in end-limit positions
– Shortly press P to select the set value of blocking time 0 – 20 s (0 – 20 blinking of LED2) and keep pressing push-
-button P to store the parameter to memory. – Keep pressing push-button C to store actual position for blocking torque on the side Closed to memory. – Keep pressing push-button O to store actual position for blocking torque on the side Open to memory.
MENU 4 – Setting transducer characteristics
– Shortly press P to select the value 4 – 20 mA – 1x blinking of LED2 or 20 – 4 mA – 2x blinking of LED2, and keep
pressing push-button P to store the parameter to memory.
Other menus only serve for board setting in version Control
MENU 5 – Setting control signal in 3P regulation
– Shortly press P to select value 4 – 20 mA - 1x blinking of LED2, or 20 – 4 mA - 2x blinking of LED2, or 0 – 20 mA - 3x blinking of LED2, or 20 – 0 mA - 4x blinking of LED2
and keep pressing push-button P to store the parameter to memory.
MENU 6 – Setting insensitivity in three-position regulation
– Shortly press P to select value 1 – 10 % (1 – 10x blinking of LED2) and keep pressing push-button P to store
the parameter to memory.
MENU 7 – Response in case of losing control signal in three-position regulation
– Shortly press P to select value OPEN - 1x blinking of LED2, or CLOSSE - 2x blinking of LED2, or STOP - 3x blinking of LED2
and keep pressing push-button P to store the parameter to memory.
14
MENU 8 – Way of switching off in end-limit positions in 3P regulation
– Shortly press P to select value TORQUE - 1x blinking of LED2, or TORQUE+PO - 2x blinking of LED2, or TORQUE+PZ - 3x blinking of LED2, or TORQUE+PO+PZ - 4x blinking of LED2
and keep pressing push-button P to store the parameter to memory.
PROCEDURE OF SETTING PARAMETERS BY PROGRAM DMS2
Before starting the actuator, it is necessary to set some parameters of the system by means of program DMS2 on PC.
For safety reasons, the system is delivered in the state of induced error of Calibration when the functions are limited in order to reduce the risk of damaging the actuator by wrong wiring. In controlling the actuator from program DMS2, its run is stopped when any torque is induced.
Working torque
– Check and, if necessary, set the value of working torque 50 – 100 % in program DMS2.
End-limit positions – working stroke
Position Z – Shift to position Closed either manually or by means of menu Motor in program DMS2. –
The actuator can only be controlled by means of the program if no torque is induced. The torque should be left manually.
– Press push-button Z to confirm consent with the record.
Position O – Shift to position Open either manually or by means of menu Motor in program DMS2. –
The actuator can only be controlled by means of the program if no torque is induced. The torque should be left manually.
– Press push-button O to confirm consent with the record.
Autocalibration (CONTROL only)
– The autocalibration can only be started by means of the program if no torque is induced. The torque should be left
manually.
– The autocalibration is started by push-button Start in program DMS2. – Wait until the autocalibration is completed; information on its course is signalized next to push-button Start.
Other parameters
Check and, if necessary, change other parameters:
Control signal 4 – 20 mA, 20 – 4 mA, 0 – 20 mA, 20 – 0 mA Insensitivity 1 – 10 % Function in case of error open, close, stop, to position Time of torque blocking in end-limit positions 0 – 20 s (default 5s from producer) Position of torque blocking in end-limit positions 1 – 10 % Output of position signal 4 – 20 mA, 20 – 4 mA Function READY combined error
Note: Signal READY is brought out as contact of the relay on the terminal board. If the state ERROR or WARNING is not detected (setting can be made of what is to be evaluated as error or warning), the contact is closed; in case of error, warning, or if feeding of electronics is interrupted, the contact is opened. The state of the relay READY is indicated by the LED diode on the source board.
AUTODIAGNOSTICS
DMS2 ED performs continuously its diagnostics and, if a problem is detected, it reports warning or error. The
warning or error is signalized by LED of the display and, possibly, by relay Ready. The warning has no effect on operation of the system, the error stops the actuator.
Assigning or switching off of warnings and errors is set in window “Warning and error” of the setting program
(it is opened by clicking one of parameters Warning 1 – 4 or Error 1 – 4 in window “Parameters”).
15
List of warnings and errors
No. Name Warning1 Error1 Description
1 SAFE * X Input SAFE activated (external error, irrelevant in DMS2 ED) 2 Control signal X 4 Torque X 6 Heat protection X Input heat protection activated 7 Sense of rotation X Reverse sense of rotation (for CONTROL only) 8 EEPROM X Wrong control sum of parameters in EEPROM 9 RAM X Wrong control sum of parameters in RAM 10 Parameters X Wrong parameters in EEPROM 11 Setting modes X Setting mode from push-buttons or PC 12 Torque sensor X Disconnected or defective torque sensor 13 Sensor 1 X Error of sensor of position 1 (lowest stage) 14 Sensor 2 X Error of sensor of position 2 15 Sensor 3 X Error of sensor of position 3 16 Sensor 4 X Error of sensor of position 4 (highest stage) 17 Calibration X Autocalibration not carried out 18 Torque setting X Wrong setting of torques (parameters Torque O/Z/50/100%) 19 Stroke X Wrong setting of stroke (parameters Position O/Z)
20 Rotation error X The actuator does not rotate
21 High temperature X 22 Low temperature X
23 LCD internal * X Display of LCD internal does not communicate or not added
24 LCD external * X Display of LCD external does not communicate or not added
25 Fieldbus * X Module of industrial bus does not communicate or not added in
26 CAN * X 27 Fieldbus activity* X Connection to industrial bus not active 28 Phase * X Inverse order of phases or some phase missing 29 Relay of service X Service life of relay MO/MZ at CONTROL exceeded
life (parameter Relay of service life) 30 Reset X Non-standard Reset of unit induced (watchdog etc.) 31 ROM X Wrong control sum of program in ROM
32 CAN version * X Sensor, LCD display or module Fieldbus have incompatible versions
33 Wrong command * X Commands Open and Close entered at the same time 34 Wrong inertia Wrong inertia measured by autocalibration 35 Wrong run-down – 41 Wrong position X Servo-drive is in position 25 % behind working stroke
Value of control signal ≤ 3 mA (it applies to ranges 4 – 20 / 20 – 4 mA) Induced torque beyond end-limit positions or disconnected torque sensor
Permitted max. temperature exceeded (parameter Temperature Permitted max. temperature exceeded (parameter Temperature min.)
in parameter CAN of configuration
in parameter CAN of configuration
parameter CAN of configuration Error of bus CAN (short circuit, interruption, only sensor communicates)
of firmware
(for autocalibration only)
Wrong run-down measured by autocalibration (for autocalibration only)
max.)
1)
Assignment can vary depending on the version of firmware of the sensor control unit.
* Applies to DMS2 only.
Memory of number of induced errors
– For all ascertained warnings and errors, DMS2 uses counters of occurrence of these warnings and errors during
operation of the system.
Values of the counters are stored to the EEPROM memory and are preserved even in case of the power supply fall-out. – Reading of the counters is possible by means of the program for PC – Clearing of the counters is possible by means of the program for PC with the level of authorization “SERVICE”.
16
– In version DMS2ED with display is shown number of the current error in the display. – Errors / warnings EEPROM, RAM, ROM, Reset are internal electronics errors
for EEPROM warning restore parameters from a backup, unless you have not saved the last state as a backup, if so check and reset of some parameters is necessary.
Restoring parameters from backup – can be done from PC or by using buttons on the sensor:
– turn off power of electronics – press and hold O + C buttons – turn the power on (all LED lit) – wait for blink of yellow and red LED, by this writing of back up parameters is signalled – RAM error is in operation corrected automatically by reloading parameters from EEPROM to RAM – ROM error signals overwrite of program memory, this sensor must be replaced
Terminal board of the actuator with DMS2 ED electronics
If the actuator is of the single-phase version the power supply is connected only to terminals PE, N, U. The
terminals V, W remain non-connected. If the actuator is of the version “Replacement of electric-mechanical board” with three-phase electric motor without power relays, the electric motor is connected to a separate terminal board
(not shown here).
17
E0010
Local control
“R” “L” “O” “C”
with single-phase electric motor
Passive output
Remote
Active output
Analog
“Open”
module
“Close”
Remote
Source board
sensor
Position
Torque
sensor
Remote allowed
Supply mains
In version without local
control, the jumper from
terminal U is connected
to terminal 2
Example of wiring diagram of electronics DMS2 ED in version Substitution of electro-mechanical board
Note: Here, contacts of relay MO, MZ, SO, SZ are shown with power supply switched off; with power supply switched off contacts PO, PZ are shifted to the position drawn in dashed line.
18
E0011
the version. “Substitution
of electro-mechanical
board without block of
power relays” is also
available; electric motor
Note: For three-phase actuator,
is connected to separate
terminal board.
Local control
“R” “ L” “O” “C”
with three-phase electric motor
Passive output
Remote
Active output
Analog
“Open”
module
“Close”
Remote
Power relays board
Source board
sensor
Position
sensor
Torque
Remote allowed
3x400 V
In version without local
control the jumper from
terminal U is connected
to terminal 2
Example of wiring diagram of electronics DMS2 ED in version Substitution of electro-mechanical board
Note: Here, contacts of relay MO, MZ, SO, SZ are shown with power supply switched off; with power supply switched off contacts PO, PZ are shifted to the position drawn in dashed line.
19
E0102
“O“ „C“ “R“ “L“
Local control
“R” “L”
„Open“
Remote
Analog
module
Snímač
polohy
sensor
Torque
„Close“
Remote
Remotely permitted
Power relay board
Source board
board
Phase
monitoring
Example of connection of DMS2ED electronics with phase tripping monitoring module dual local control switch
20
In the version without local
control the jumper from
terminal U is connected to
terminal 2
E0012
Passive output
Active
output
Analog
module
Local control
Example of wiring diagram of electronics DMS2 ED in version Control with single-phase electric motor
“R” “L” “O” “C”
Position
sensor
sensor
Torque
Source board
Supply mains
In version without local
control the jumper from
terminal U is connected
to terminal 2
21
Note: Here, contacts of relay MO, MZ, SO, SZ are shown with power supply switched off; with power supply switched off contacts PO, PZ are shifted to the position drawn in dashed line.
E0013
Passive
output
Active
output
Power relays board
Local control
Example of wiring diagram of electronics DMS2 ED in version Control with three-phase electric motor
“R” “ L” “O” “C”
sensor
Position
Analog
Torque
module
sensor
Source board
3x400 V
In version without local
control the jumper from
terminal U is connected
to terminal 2
22
Note: Here, contacts of relay MO, MZ, SO, SZ are shown with power supply switched off; with power supply switched off contacts PO, PZ are shifted to the position drawn in dashed line.
DMS2 SYSTEM
Main properties of DMS2 electronics:
Complete control of the actuator run of the two- and three-position regulation or connection to the industrial bus Profibus.
Synoptic signalization of operation and service data on the character LCD display.
Autodiagnostics of error reports on the LCD display, memory of recent failures and number of occurrences of respective failures.
Setting of parameters by the PC program and by local control provided that the actuator is fitted with local
control.
Basic outfit of DMS2:
The control unit is the main part of the system DMS2; it comprises: – Microcomputer and memory of parameters – Position sensors – 2 signalling LED – Connectors for connecting the torque sensor, relay board, and two-position inputs, source board, communication
adapter, LCD display, and local control
Torque unit provides for scanning torque by the contactless sensor.
The source unit consists of: – Power supply for electronics. – 2 relays for electric motor control, – Ready relay with change-over contact separately led on a terminal board – 1 – 4 signalling relays with one pole of contact switch led on terminal board. Second poles of relay contacts 1 – 4 are
connected to COM terminal.
– User terminal for supply voltage and output relays connection.
The unit allows connection of the heating resistor and its control with thermostat. The unit controls power switches of the electric motor (reversing relay) and can directly control a low power single
phase electric motor.
Display unit – dual line display, 2 x 12 alphanumeric characters Button unit – buttons sensor "open", "close", "stop" and rotary switches "local, remote, stop." Power relays – for three-phase electric motor (according to design).
Note:
DMS2 electronics – in 2P or 3P control design are motor relays for controlling of the actuator (associate torque and
position function) connected directly to the contactors and not to the terminal board. Four relay contacts R1 to R4, led to the terminal board, have only a secondary function and are used like a signalling switches to indicate the status of the actuator.
DMS2 electronic system as DMS2ED electronic system designed for 2P or 3P regulation has contact Ready led to
the terminal board for error and non-standard states signalling according to the following list:
OFF warnings + errors torque O or Z
warning errors + not remote error errors + warnings + not remote
Electronics DMS2 in version Profibus communicates with the master control system exclusively via industrial bus,
no other signals are brought out.
Optional DMS2 electronics outfit (in the actuator must be one of these units):
The two- and three-position control unit – allows controlling the actuator by moving to the "open" and "closed"
positions or by analog signal 0 (4) – 20 mA.
Profibus connection unit – allows you to control actuator by PROFIBUS.
23
Technical parameters of DMS2 electronics:
Scanning of position contact-less, magnetic Scanning of torque contact-less, magnetic Working stroke see 90° Torque blocking 0 – 20 s at reversing in limit positions Input signal 0(4) – 20 mA with switched on 3P regulator function Open, Close 15 – 60 V AC/DC with switched on 2P
regulator function Safe 15 – 60 V AC/DC Local/remote control, local open, stop, local close Output signals 5 x relay 250 V AC 3A (R1, R2, R3, R4, READY) Position signal 4 – 20 mA, max. 500 Ω,
active/passive, galvanic-isolated LCD display 2 x 12 alpha-numeric characters Power supply 230 V AC, 50 Hz, 4 W, over-voltage category II Monitoring the presence and sequence of a phase
PROCEDURE OF SETTING PARAMETERS BY PROGRAM DMS2
Before putting the actuator into operation, it is necessary to set some parameters of the system by means of program DMS2 on PC.
Warning:
For safety reasons (reduced risk of damage to the actuator by wrong wiring), the system is delivered in the state of the induced error of calibration when the functions are limited and, during controlling the actuator from program DMS2, its run is stopped if any torque is induced.
Note:
The setting program is the same for electronics DMS2 ED. See the figure on page 12 for the main window and the window of Selection of electronics.
Working torque
– Check and, if necessary, set the value of the working torque 50 – 100 % in DMS2 program.
Tripping in end-limit positions
– Check and, if necessary, set the way of tripping in the end-limit positions: – Torque – Torque+position O – Torque+position Z – Torque+position O+Z
End-limit positions – working stroke
– Position Z – Shift to position Closed either manually or by means of menu Motor in program DMS2. – The actuator can only be controlled by means of the program if no torque is induced. The torque should be
left manually.
– Press push-button Z to confirm consent with the record. – Position O
– Shift to position Open either manually or by means of menu Motor in program DMS2. – The actuator can only be controlled by means of the program if no torque is induced. The torque should be
left manually.
– Press push-button O to confirm consent with the record.m.
Autocalibration
– The autocalibration can only be started by means of the program if no torque is induced. The torque should be
left manually.
24
– The autocalibration is started by push-button Start in program DMS2. – Wait until the autocalibration is completed; information on its course is signalized next to push-button Start.
Other parameters
Check and, if necessary, change other parameters:
Control signal 2 position Bus
Insensitivity 1 – 1 0 % Function SAFE Open Close Stop To position Active SAFE 0 V 230 V
Time of blocking torque in end-limit positions
Position of blocking torque in end-limit positions
Output of position signal 4 – 20 mA 20 – 4 mA
READY function error
Ready – Local Switched off Switched on
Switched off Position O Position Z Torque O Torque Z
Relay 1 – 4
Opening Closing Movement Position Relay 1 – 4 0 – 100%
4 – 20 mA 20 – 4mA 0 – 20 mA 20 – 0 mA
Combined
Torque and position O Torque and position Z
0 – 20 s
1 – 10 %
Error code
Note:
SAFE – input information on the error of an external device can be set so that the actuator would respond as to its
own error.
Autodiagnostics
The table List of errors – same as for electronics DMS2 ED (page 13)
Memory of number of induced errors
– same as for the DMS2 ED electronics
Memory of recently induced errors
– DMS2 stores 3 recently induced errors to the memory EEPROM. – DMS2 provides for displaying the errors by means of the PC program or the switches of the local/ remote control. – Reading and clearing of the counters with the local / remote control switches: – Display – OFF position and the O or C position. – Reset – after switch from errors to remote control.
Terminal board of actuator with electronics DMS2
– Terminals on source board
Terminals on source board
25
Note:
If the actuator is of the single-phase version the power supply is connected to terminals PE, N, U only. Terminals V, W remain unconnected.
Terminals in local control box
26
Example of wiring diagram of system DMS2 in version for control with signals “open”
and “close” or in version for control with analog current signal
with single-phase electric motor
E0014
OPEN
STOP
CLOSE
DMS2 D - LCD display
REM
2 x 12 characters
OFF
LOC
Open
Close
(test)
Analog board
DMS2.A2
Source board
Passive output
Active output
DMS2.ZD2
Supply main 230 V
27
Example of wiring diagram of system DMS2 in version Profibus
with single-phase electric motor
E0015
OPEN
STOP
CLOSE
DMS2 D – LCD display 2 x 12 characters
REM
OFF
LOC
Board DMS2.PR2
Source board
DMS2.ZD2
Supply main 230 V
28
E0016
Power relays board
with analog current signal with three-phase electric motor
LOC
OFF
REM
OPEN
STOP
Passive output
DMS2.A2
Analog board
LCD display
2 x 12 characters
CLOSE
DMS2 D -
Active output
Open
DMS2.ZD2
Source board
Close
(test)
3x400 V
Example of wiring diagram of system DMS2 in version for control with signals “open” and “close” or in version for control
29
OPEN
STOP
CLOSE
Example of wiring diagram of system DMS2 in version Profibus
with tree-phase electric motor
OFF
REM
LOC
E0017
DMS2 D -
LCD display
2 x 12 characters
3x400 V
Board DMS2.PR2
Source board
DMS2.ZD2
30
Power relays board
Note:
The setting program enables data to be copied from the memory of parameters of the electronics DMS2 and
DMS2 ED into the computer as a file with suffix “par” (in the example in the figure the file 52 030.par is created in the directory Flash). The file can serve as a back-up for the case that it will be necessary to replace the position sensor in the given actuator and to set it in the same way as the replaced one; or it can be sent as an enclosure to e-mail to the manufacturing or service firm in solving possible problems.
9.
ASSEMBLING AND PUTTING THE ELECTRIC ACTUATOR
INTO OPERATION
Upon receipt of the actuator from the factory, it is essential to check that no damage was caused during transport
and to compare the data on the actuator rating plates with those contained in the order and accompanying documentation. Any discrepancy, defect or damage should be immediately reported to the supplier. Putting into operation is excluded in this case. When the unpacked actuator is not immediately installed it should be stored at a dust­free location with a temperature within the range of -25 °C to +50 °C and relative humidity up to 80% where there are neither aggressive gases nor vapours and which is secured against the harmful effects of climatic conditions. Any manipulation of the equipment at a temperature below -25 °C is forbidden. Storing the actuator out of doors or at a location that is not protected against the effects of rain, snow or ice accretion is inadmissible. Before putting the actuator into operation, excess grease should be removed. When unpacked actuators are to be stored longer than 3 months it is advisable to place a bag with silica gel or another suitable desiccant in the terminal box.
The user can only put into operation electric installations with compliance documented by a report of the initial
revision.
Before fitting in place, the actuator should be carefully inspected, particularly in case that it has been stored for
a prolonged period; the following should be checked: – condition of parts and connections forming explosion-proof closure; – insulation resistance of the motor winding; – possible damage during storage.
It should also be checked that location corresponds to provisions of the par. “Working conditions”. If different way
of assembly is required by local conditions the manufacturer should be contacted.
The protective conductor must be connected to a protective terminal marked according to ČSN IEC 417. On the actuator,
the protective terminals are located on the body and inside the actuator, on the control board at the terminal board.
Connection
The actuator should be connected according to the wiring diagram placed inside the cover in such a way that
power supply wires have permanent good contact with the connecting terminals. The supply voltage must correspond to the voltage stated on the rating plate of the actuator. Internal space of the cover should be clean and dry. No free wires may stick out of the connected conductors.
Protection
Electric motors of the actuators are fitted with a built-in automatically restoring thermal protection according to
ČSN EN 600034-11. For the actuators type no. 52320 with single-phase electric motors ES 7150-2AL, ES 7130-4AL and FCJ2B52D, it is connected in series with the electric motor winding; hence, it controls the motor directly and is not
31
connected to the terminal board of the actuator. For other electric motors, the thermal cut-out is connected by two separate outlet wires to the terminal board of the electric motor and the motor is controlled by means of another device
(contactor, relay, etc.).
Insulation resistance
Before putting the actuator into operation or restarting it after a longer idle time, it is necessary to check that insulation conditions have not been worsened and that there is no danger of the winding damage or electric shock. Insulation conditions should also be checked during inspections in compliance with provisions of ČSN 34 3205 and standards valid for non-explosive electric installations. Insulation resistance of electric control circuits against the frame and against each other should be min. 20 Mohm. Insulation resistance of the electric motor should be min 1.9 Mohm. Insulation resistance of the current transducer is 20 Mohm at 50 V DC.
The actuators with a lower insulation resistance must not be put into operation. The cause can lie in a damaged winding or excess humidity. Damp motors with insulation resistance lower than the stated value must be carefully dried before being put into operation. By drying the winding, moisture is removed from the insulation and insulation resistance is thus increased to the prescribed value. Drying can be carried out in different ways. Drying directives are given by the standard ČSN 35 0010 or local recommended methods can be applied.
Supply line and wiring
Cable entries into actuators flameproof enclosure are equipped with the followings threaded holes: a) Actuator – has 2 or 3 threaded entries M20x1,5 nebo M25x1,5 (see dimensional drawing of actuators) b) Local control – has 2 threaded entries M20x1,5.
Threaded holes for cable entries are marked M20x1,5 or M25x1,5 in accordance with article 13 of ČSN EN 60079-1.
These entries are sealed by appropriate plugs.
The customer is obliged to establish electrical connection for direct entry to the flameproof enclosure, that corresponds to the requirements of ČSN EN 60079-14 and the protective enclosure is at least IP67.
At the customer's request, the manufacturer can supply motors with cable bushing system that meets the requirements of ČSN EN 60079-14 Article 10.4.2.d for direct entry into flameproof enclosure of group IIC. For entry into actuators flameproof enclosure are used Peppers glands (type CR-U) or HAWKE glands (type ICG 623) according to following table.
Cable diameter Gland Threaded entry
CR-U/25 M25x1,5 11,7 – 20,0 mm ICG 623/B M25x1,5 13,0 – 20,2 mm CR-U/20 M20x1,5 9,5 – 14,0 mm ICG 623/A M20x1,5 11,0 – 14,3 mm
32
CR-U* Compound-Filled Cable Gland
CR-U* Compound-Filled Cable Gland
- ASSEMBLY INSTRUCTIONS FOR SAFE USE
Where cable gland CR-U* is used customer is obliged to follow the following instructions
with sealing individual cable cores when connecting the actuator.
Brief Description
The Peppers CR-U* type Compound-filled cable gland is for outdoor use in the appropriate Hazardous Areas with unar- moured cable of any construction, with or without braids or screens, where the braids or screens pass trough the compound. A variant giving electrical continuity to a lead sheath is available. It gives environmental protection to IP 66, IP 68 and Deluge.
Warning:
PLEASE STUDY CAREFULLY THESE INSTRUCTIONS BEFORE INSTALLATION. These glands should not be used in any application other than those mentioned here or in Peppers Data Sheets, unless Peppers states in writing that the product is suitable for such application. Peppers can take no responsibility for any damage, injury or other consequential loss caused where the glands are not installed or used according to these instructions. This leaflet is not intended to advise on the selection of cable glands. Further guidance can be found in the standards listed below.
ZADNÍ SESTAVA
MONTÁŽNÍ NÁVOD PO JEDNOTLIVÝCH KROCÍCH
Protimatice
ROZDĚLENÍ
VÝVODKY
PŘÍPRAVA KABELU
STLAČENÍ TĚSNICÍ
HMOTY
VYTLAČENÍ TĚSNICÍ
HMOTY
DOKONČENÁ
MONTÁŽ
Středový
uzávěr
Převlečná matice
Vstupní díl
U A
Velikost vývodky
élka těsnicí hmoty
Olověný plášť
Kontinuální t ěsnění
(typ CR-U2* )
Continuity washer
(CR-U2* types)
Back nut Union nut
SPLIT GLAND
REAR ASSEMBLY
STEP-BY-STEP FITTING INSTRUCTIONS
COMPLETED INSTALLATION
CABLE PREPARATION
COMPOUND EXTRUSION
COMPOUND PACKING
Entry body
Gland size
TABLE 1
Compound lenght
Mid cap
Lead sheath
– ASSEMBLY INSTRUCTIONS FOR SAFE USE
Where cable gland CR-U* is used customer is obliged to follow the following instructions
with sealing individual cable cores when connecting the actuator.
Brief Description
The Peppers CR-U* type Compound-filled cable gland is for outdoor use in the appropriate Hazardous Areas with unarmoured cable of any construction, with or without braids or screens, where the braids or screens pass trough the compound. A variant giving electrical continuity to a lead sheath is available. It gives environmental protection to IP 68 and Deluge.
Warning:
PLEASE STUDY CAREFULLY THESE INSTRUCTIONS BEFORE INSTALLATION. These glands should not be used in any application other than those mentioned here or in Peppers Data Sheets, unless Peppers states in writing that the product is suitable for such application. Peppers can take no responsibility for any damage, injury or other consequential loss caused where the glands are not installed or used according to these instructions. This leaflet is not intended to advise on the selection of cable glands. Further guidance can be found in the standards listed below.
STEP-BY-STEP FITTING INSTRUCTIONS
1. Split gland as shown in the figure.
2. Fit Entry Body. Hand-tighten, then using wrench tighten a further 1/2 turn. DO NOT EXCEED MAX TORQUE FOR
ENCLOSURE.
3. Slide Rear Assembly (locking nut, central enclosure and cap nut) onto cable as shown in the figure.
4. CABLE PREPARATION Strip jacket so that cores are fully exposed in the compound chamber, length to suit installation. Lead sheath must
be cut to push through the continuity washer. Remove protective foils, and any cords/fillers from around and between
the cores. Take care not to cut the insulating sleeves of the cores. Pigtail and sleeve any screens to be passed
through compound.
33
HEALTH AND SAFETY WARNING The resin used in the compound can cause eye and skin irritation. For
your personal protection, wear the gloves supplied while mixing and applying. The uncured compound should not be allowed to come into contact with foodstuff.
A COMPREHENSIVE SAFETY DATA SHEET PROVIDED BY THE COMPOUND MANUFACTURER IS AVAILABLE
ON REQUEST.
5.
Check compound has not passed its “Use By” date. Installation at temperatures below 10 °C should be avoided if possible.
6.
Trim any hardened pieces from ends of stick. Mix the compound by rolling, folding and breaking. Ease mixing by cutting large sticks in half. Fully mixed compound has a uniform yellow colour with no streaks.
7.
Support the cable and Rear Assembly, holding them roughly concentric. Any lead sheath should be pushed through the continuity washer – ensure that contact has been made. Splay out the cores. Starting at the middle, pack small amounts of rolled-out compound between the cores. Restraighten each core and work outwards until all gaps are filled. Bundle the cores with cord or tape so they are not disturbed. Pack around the outside of the outer cores to completely fill the Rear Assembly cup. Build up compound around the outside of the cores, with a slight taper & to approximate compound length shown in diagram & Table 1 column 7.
8.
Pass cores through & push compound into Entry Body until Rear Assembly engages. Remove squeezed out compound at arrow A. Screw Union Nut 7 full turns onto Entry Body (arrow B). Ensure that compound emerges at entry thread (arrow C).
9.
Clean off excess compound from Entry Body to allow withdrawal when cured (arrow C). Cores may be disturbed after 1 hour. Leave to cure for 4 hours when working at 21 °C.
10.
To release and pull back joint for inspection, unscrew Union Nut. Ensure that the compound is uniform and full form to fit into the entry body.
11.
Hand-tighten Union Nut to remake joint. Then refer to table below table and tighten Union Nut using wrench to the given amount.
12.
Hold Mid Cap with wrench and tighten Back Nut onto cable. Ensure seal makes full contact with cable sheath, then tighten 1 extra turn.
13.
The equipment should not be energised until the compound has been left to cure for at least 4 hours when working at 21 °C. See chart ´Energising Time vs. Temperature´ for further guidance.
Wrench tightening information (Instruction 11),
cable sizes (mm) & permitted cores
size
Tighten Union
Nut using
wrench up to
Gland
16 ½ -turn 8,4 7 3,4 8,4
20S ½ -turn 10,4 8 4,8 11,7
20 ½ -turn 12,5 14 9,5 14,0
25 ½ -turn 17,8 25 11,7 20,0
32 ¼ -turn 23,5 50 18,1 26,3
40 ¼ -turn 28,8 80 22,6 32,2
50S ½ -turn 34,2 100 28,2 38,2
50 ½ -turn 39,4 100 33,1 44,1
63S ½ -turn 44,8 120 39,3 50,1
63 ½ -turn 50,0 120 46,7 56,0
75S ½ -turn 55,4 140 52,3 62,0
75 ½ -turn 60,8 140 58,0 68,0
80 ½ -turn 64,4 160 61,9 72,0
85 ¾ -turn 69,8 180 69,1 78,0
90 ¾ -turn 75,1 200 74,1 84,0
100 ¾ -turn 80,5 220 81,8 90,0
Max
Diameter
over Cores
Max No
of Cores
Outher sheath
Min. Max.
Doba zapnutí
Energising Time
proudu v závislosti
vs. Temperature
na teplotě
hodin
hrs
Installation Guidance
Point Advice
1. BS EN 60079-10:2003 Classification of Hazardous areas
BS EN 60079-14:1997 Electrical Installations in hazardous areas (other than mines)
BS 6121, Part 5 Selection, Installation and Maintenance of Cable Glands
2. Installation should only be carried out by a competent electrician, skilled in cable gland installation.
3. NO INSTALLATION SHOULD BE CARRIED OUT UNDER LIVE CONDITIONS.
4. To maintain Ingress Protection ratings above IP54, use IP washers or O-rings for parallel threads. For taper threads use thread sealant.
34
5. To ensure the stated IP rating is maintained, at the point of interface the surface of the enclosure should be flat, free from debris and rigid with the hole drilled straight as a maximum of 1.5 mm above the thread diameter.
6. Once installed do not dismantle except for routine inspection. The gland is not serviceable and spare parts are not supplied.
7.
Parts are not interchangeable with any other design. If manufacturers parts are mixed, certification will be invalidated.
Limitations on Usage. Be sure your installation complies with the following:
Feature Comment
Enclosure entry thread The female thread in the entry enclosure must comply with clause 5.3 of EN 50018:2000
or with a paragraph 5.3 of the IEC 79-1 standard.
Do not damage threads on assembly. Check that the number of fully engaged threads is at
least 5.
Interpretation of Markings. Markings on the outside of this gland carry the following meanings:
Cable Gland Type and Size CR Product range U Gland over the counter for unarmoured cable
Seal type: epoxy resin-based sealant (temperature -60 °C to +85 °C)
2 Continuity washer option for lead sheathed cable B Main component material, B=brass, S=stainless
steel SIRA Certification Body
20S Gland size IP68 Protection Code PG16 Entry thread type and size Year code: XX
ATEX marking (directive 94/9/ES) Ex European explosive atmosphere symbol acc. to EU I M2 Mining equipment, category M2
Non-mining equipment,
II 2
suitable for use in category 2, zone 1, 2, 21, 22
G For use with potential explosive gas mixtures D For use with flammable types of dust
CENELEC certification marks E Conformity with European standard Ex Symbol of protection against explosion d Type of protection: d=flameproof
Code for group of gases suitable for group I
(for example Methane) and group IIC (for example
I & IIC
hydrogen) flammable gases/ air mixtures and also
groups IIA and IIB
03 Year of certification ATEX Certified conformity with standard ATEX 94/9/ES 1479 Serial number of certification
Special conditions for safe use. These glands must
not be used with enclosures where the temperature
X
at the point of mounting exceedss -60 °C to +85 °C
35
3
4
5
2
1
1.1
1.2
In the case of using ICG outlet glands the customer is obliged to connect the electric actuator in accordance with
the following instructions, sealing the individual cable cores.
Instruction for Use no. N740052 – issue no.1 Non-explosive cable bushings, type lCG 623
Assembly Instructions for cable gland: ICG 623 EExd IIC/EExe II
Certificate BASEEFA No. BAS 01 ATEX 2079X (Ex) II 2 GD IP66 CE 623 EExd I/EExe I Certificate BASEEFxA No. BAS 02 ATEX 0177X (Ex) IM 2 IP66 CE
Operating temperature range -60 °C +80 °C
1. Backnut
1.1 Rear Compression Spigot
1.2 Rear Seal
2. Middle Nut
3. Pot Cap
1
2
4. Rubber Pot
5. Entry
3
1.1
1.2
4
5
Assembly Instructions
AI 305 / Issue L - 08/06
HAWKE International
Detail for specification. The parts 1 and 2 should not be dismounted.
Cable Preparation Gland Preparation
I
3
2
1
Shroud Option
Shroud Option
A
Strip Cable to suit equipment as shown above, removing all cable fillers. Length I to suit equipment. If required, fit shroud. See Notes re. Drain Wires.
3
B
Position rear of pot cap (3) level with prepared face of cable insulation, ensuring that the cap remains concentric to cable at all times.
Compound
Compound
3
C
Spread the cable cores out for the compound packing. Pack the compound between the cores as shown. See notes overleaf and Fig. 7 for compound preparation.
36
4
3
5
4
5
2
1
Tape
5
4
Remove surplus compound
4
5
Compound
3
D
With all gaps and voids filled, bring the conductors back together and pack more compound around the outside of the conductors. Tape the conductors together to prevent disturbance of the compound seal. Pass the rubber pot (4) over pot cap (3) and remove any surplus com­pound from the top of rubber pot (4) and joint faces as indicated.
Remove
surplus
compound
Remove surplus compound
E
Replace the entry (5) over the rubber pot (4) ensuring that compound does not cover end of rubber pot (4).
5
2
1
F
Locate and hand tighten the sub-as­sembly (1) and (2) to the entry (5).
2
1
G
To further locate and support the compound and rubber pot assem­bly, while holding the middle nut (2) with a spanner/wrench, tighten the backnut (1) until the seal grips the cable to prevent movement of the cable gland.
Important note:
The conductors must not be moved for a minimum of four hours.
4
3
2
1
H
Allow the compound to cure. (See Fig. 7 for Curing Times). Untighten firstly the backnut (1) from (2) and secondly the middle nut (2)
from the entry (5). The rubber pot (4) may be removed for inspection to en­sure that the packing is satisfactory. Add further compound if necessary.
5
2
1
I
Re-assemble rubber pot (4) and the entry (5). Hand tighten the sub-assem­bly (1) and (2) to the entry (5) and add half a turn to (2) with a spanner/wrench. Tighten the backnut (1) to form a seal around the cable, then tighten a further half to full turn using a spanner/wrench. Ensure that the middle nut (2) does not rotate when tightening the backnut (1). Locate the shroud over the cable gland if
applicable.
37
EPOXY COMPOUND PREPARATION
When handling this material, the gloves supplied must be worn. The epoxy compound is supplied in the form of a two part package. These should be mixed into the ratio of I: I until both colours have blended into one, without any streaks. Rolling and folding is the most satisfactory method of obtaining an even blend. Once mixed, the compound must be used within 30 minutes. After this time it will begin to stiffen. The compound should be kept at an ambient temperature of no less than 20 °C prior to using. At lower temperatures it becomes difficult to mix. Should any compound come into contact with the skin it should be cleaned off with skin cleaner and not allowed to dry on the skin. Only compound for immediate terminations should be mixed.
The mixing and installation of the compound at an ambient temperature below 4 °C is not recommended due to extended curing period.
The following instructions are the various BASEEFA approved methods of passing drain wires etc. through the com­pound barrier and should be followed if permitted by cable installation specifications.
Drain wire preparation
1.0. Insulating drain wires with heat shrink or cold shrink tubing
1.1. Fold back the armour I braid and bend it to right angles from the inner sheath.
1.2. Remove foils and tape level with the outer sheath. exposing the drain wires and insulated conductors. Cut
back a further 10 mm of inner sheath.
1.3. Pass 100 mm length of heat shrink or cold shrink tubing over the drain wire until it comes into contact with the
foils, then shrink the tubing evenly down onto the drain wire so that no air pockets occur.
1.4. To insulate the joint between the foils and the tubing a suitable piece of 10 mm long shrink tubing or neoprene
stretch tubing or a 10 mm wide lap of PVC tape may be used.
1.5. After completing 1.1 to 1.4 on each drain wire, lay the armour I braid parallel to the cable, if applicable, then
carry out instruction B.
2.0. Insulating drain wires i screens with separate insulated crimped conductors or soldered connection
2.1. Fold back the armour I braid and bend to right angles from the inner sheath.
2.2. Remove a further I 5mm of inner sheath (See Fig. I).
2.3. Unravel one or two groups of wires from the screen wires, then remove the remainder of the screen wires
(See Fig. 2).
2.4. Twist the group of screen wires into a pigtail and cut to 15 mm long.
2.5. Crimp an insulated conductor to the pigtail with a suitable insulated butt ferrule (or soldered connection),
leaving enough length of the insulated conductor to enable the remote end to be connected to the earth terminal in the equipment. (See Fig. 3).
Note: There shall be a minimum of 10 mm of compound on both ends of the crimped I soldered joint.
2.6. To insulate the joint between the screen wires and the insulated conductor, place one lap of PVC insulating
tape over the exposed metallic joint.
2.7. After completing 2.1 to 2.6 on each drain wire. lay the armour I braid parallel to the cable. Then carry out
instruction B.
Armour / braid
Inner Sheath
Screan Wires
One or two groups of screen wires
Crimp or Solder
Fig. 1 Fig. 2 Fig. 3
38
Insulated Conductor
3.0. Insulating drainwires with insulating varnish or paint
3.1. Fold back the armour I braid and bend it at right angles from the inner sheath.
3.2. Remove the foil and tape level with the inner sheath exposing the drain wires and conductor pairs.
3.3. Cut back a further 10 mm of inner sheath (See Fig. 4).
3.4. Spray or paint the drain wires with insulating varnish or paint, then leave to dry (See Fig. 5)
3.5. To insulate the foil ends a suitable piece of 10 mm long shrink tubing or neoprene stretch tubing or a 10 mm wide lap of PVC tape may be used (See Fig. 6).
3.6. After completing the steps as per point 3.1 to 3.5 on each drain wire, lay the armour I braid parallel to the cable. Then carry out instruction B.
Armour / braid
Inner Sheath
Foils
Outer Sheath
Fig. 4
Drain Wire
Insulated Drain Wire
Fig. 5 Fig. 6
Epoxy Compound Cure Time Vs. Temperature
- The compound may be adversely affected by some sol­vent vapours. lf such vapours are likely to be present in the vicinity of the cable gland in service, suitable precautions may be necessary. (Contact Hawke's Technical Dept).
- The compound cures at a Shore D hardness of 85, when
it can be handled. The compound when fully cured is sui­table for use at a temperature range of -60 °C to +80 °C.
Fig. 7
Sleeving
CABLE GLAND SELECTION TABLE
Cable Acceptance Details
Size
Entry Thread Size
Ref.
Metric NPT
Os M20 ½" 8.0 8.0 6 3.0 8.0 - - 66 24.0 27.7 O M20 ½" 8.9 10.0 6 7.5 11.9 - - 66 24.0 27.7 A M20 ½" – ¾" 11.0 12.5 10 11.0 14.3 8.5 13.4 63 30.0 34.6 B M25 ¾" – 1" 16.2 18.4 21 13.0 20.2 9.5 15.4 68 36.0 41.6 C M32 1" – 1¼" 21.9 24.7 42 19.0 26.5 15.5 21.2 70 46.0 53.1 C2 M40 1¼" – 1½" 26.3 29.7 60 25.0 32.5 22.0 28.0 72 55.0 63.5 D M50 1½" – 2" 37.1 41.7 80 31.5 44.4 27.5 34.8 87 65.0 75.1 E M63 2" – 2½" 48.8 53.5 100 42.5 56.3 39.0 46.5 90 80.0 92.4 F M75 2½" – 3" 59.0 65,3/66,2 120 54.5 68.2 48.5 58.3 92 95.0 109.6
Inner Sheath/Cores
Max. Over
Cores
Max. Inner
Sheath
Max. No.
of
Cores
Standard Seal
Min. Max. Min. Max.
Outer Sheath
Alternative
Seal (5)
Max.
Length
Hexagon
Dimensions
Across
Flats
Across
Corners
39
Limiting conditions:
1. Cable bushings OS and O can only be used for braided cables and firm instruments; the cable should be properly fixed to prevent its possible pulling out or twisting.
2. Operating temperature of the cable bushing is -60 °C to +80 °C.
3. The space between the equipment and the cable bushing should be sealed in order to preserve particular degree of protection against penetration of dust, solid particles, and water.
Accessories:
Before assembling or dismounting the cable bushing, become familiar with accessories of the cable bushing which include, for instance: – coat providing additional protection against corrosion; – safety nut securing position of the cable bushing; – sealing washer under the additional protection of the cover of the cable bushing front part against penetration; – knurled washer damping vibrations that could loosen the safety nut or the cable bushing assembly
The inlet to the actuator and connection to its switching, protection and securing instruments can only be installed by
technicians with particular qualification who must follow pertaining standards and wiring diagrams as provided in these Instructions for Use. After connecting the inlet cables, all screws of the connecting terminals should be checked for tightness so that they do not get warm during operation due to increased transition resistance. The connecting terminals must not be under tension or bending stress from the connected conductors. In case of connection with aluminium conductors the following measures are recommended. One-step before connecting the conductor, the oxidized layer should be removed from the conductor and new oxidation should be prevented by smearing the connection with a neutral vaseline.
After the connection, make sure, by short starting of the actuator in the intermediate position of the working stroke,
that the output shaft of the actuator rotates in a proper direction. If this is not the case, reconnect any two conductors on the terminals U, V, W of the motor (actuator) terminal board. Then, repeat the functional check. After verifying correct electric connection, the actuator is fitted to the valve and adjusted according to the paragraph Actuator Setting. The adjustment is best carried out using the manual control mode.
Important warning!
1) During adjusting, repair, and maintenance, secure the actuator in the prescribed way in order to rule out its connection
to the power supply and thus to prevent possibility of an injury due to electric shock or the actuator rotation.
2) When the thermal protection is disconnected, is necessary to realize that – if the power supply is on the terminals
– after cooling of the thermal protection the actuator will start automatically.
After adjusting the actuator check its function by means of the control circuit. Especially check whether the servo
actuator correctly starts up and whether the electric motor after turning off the respective relay is not energized. If not, switch off the actuator power supply off immediately to prevent damage to the electric motor, and find the case of the fault.
10.
OPERATION AND MAINTENANCE OF ELECTRIC ACTUATORS
Operation of the electric actuators results from the operating conditions and, as a rule, it is limited to giving
impulses to respective functional tasks. The electric actuator can be controlled electronically in remote way as well as manually on site of the installation. Manual control is possible by means of a hand wheel of the electric actuator, it does not require any change-over switch and can be used without any danger to the staff even in case that the electric motor is running.
The operator should take care that a prescribed maintenance is carried out, the electric actuator is protected
against dangerous effects of the environment and weather conditions which are not listed in the chapter “Working Conditions”. Moreover, care should be taken to prevent abnormal heating-up of the surface of the solid closure of the electric actuator. Make sure to avoid exceeding the nameplate values and abnormal vibrations of the actuator, maintain quiet operation of the actuator, ensure proper tightening of bolted joints of the parts of the flameproof enclosure, check insulating state after a longer break Sometimes it is necessary to make sure that all connecting and earthing terminals are tight and that they do not heat up during operation.
Maintenance
The maintenance of electric actuators lies in possible replacement of defective parts. Grease filling is stable for
the electric actuator service life, i.e. 6 years. If the electric actuator is capable of operating even after 6 years the old grease should be taken out from the power part and new grease filled in.
After 6 months at most from putting the electric actuator into operation and then at least once a year, the connecting screws
between the piping fitting and the electric actuator should be retightened. The screws are tightened in a crosswise manner.
40
Cleaning – general inspection
The electric actuators should be kept clean and care should be taken to prevent their clogging by impurities and dust. Cleaning should be carried out regularly and as often as required by operating conditions. Surface temperature of the actuator 80 °C (T6) should be determined without a dust layer. General inspection of the electric actuator is recommended to be carried out once a year unless otherwise stated in revision regulations of electric devices.
Checking the parts of non-explosive closure
The parts of the electric actuator forming the solid closure are inspected for possible ruptures or other damages (attacked by corrosion, abrades etc.). With the electric actuator disconnected, sealing rings of cable outlets should be inspected. Material of the sealing rings undergoes ageing and its hardness increases. Therefore, after 3 years they should be replaced during the reassembly. Defective parts of the closure must not be used again during assembly of the electric actuator.
In all relevant repairs of the non-explosive closure which effect its safety it is recommended to have the electric actuator ex repaired at the manufacturer who can, on the basis of approved documentation and prescribed tests, put the closure into a state corresponding to ČSN EN 60079-0 and ČSN EN 60079-1.
41
Table 1 – Electric actuators MODACT MOKPED Ex
– basic technical parameters
Type number
Type
52320.x=1+ED
52320.x=2+ ED
52320.x=3+ ED
52320.x=4+ ED
52320.x=5+ ED
MOKPED 100 Ex
52320.x=6+ ED
52320.x=7+ ED
52321.x=1+ ED
52321.x=2+ ED
52321.x=3+ ED
52321.x=4+ ED
52321.x=5+ ED
MOKPED 250 Ex
52321.x=6+ ED
52321.x=7+ ED
52321.x=8+ ED
52322.x=1+ ED
52322.x=2+ ED
52322.x=3+ ED
52322.x=4+ ED
52322.x=5+ ED
52322.x=6+ ED
MOKPED 600 Ex
52322.x=7+ ED
52322.x=8+ ED
52322.x=9+ ED
Shifting
time
[s/90°]
10 20 40 80 10 20 40 10 20 40 80 10 20 40 80 10 20 40 80
160
20 40 80
160
Tripping
torque
[Nm]
25 – 100
25 – 85
25 – 100
16 – 32
25 – 90 25 – 100 63 – 125
100 – 250
63 – 200
100 – 250
250 – 510
250 – 600
250 – 450 250 – 550
250 – 600
Power
[W]
74 74 15 17 15 15 15 90 90 40
EAMRB56N04A
40
EAMRB56N04A 90 90 60 20
180 120
60 20 20
180
90 40 40
Type
ES 7150-2AL ES 7150-2AL
FCJ2B52D
ES 7130-4AY
FT2B52C FT2B52C
FT2B52C EAMRB56N02 EAMRB56N02
EAMR56N02L EAMR56N02L EAMR56N02A EAMR56N04A
EAMR63N04 EAMR63N04L EAMR63L02A EAMR63L04A EAMR63L04A EAMRB63N04 EAMRB63L02
EAMRB63L04A EAMRB63L04A
Electric motor
RPM
[1/min]
2750 2750 2780 1300 2680 2680 2680 2780 2780 1380 1380 2790 2790 2790 1440 1370 1390 2790 1440 1440 1320 2780 1380 1380
Voltage
[V]
1 x 230 1 x 230 1 x 230 1 x 230 3 x 400 3 x 400 3 x 400 1 x 230 1 x 230 1 x 230 1 x 230 3 x 400 3 x 400 3 x 400 3 x 400 3 x 400 3 x 400 3 x 400 3 x 400 3 x 400 1 x 230 1 x 230 1 x 230 1 x 230
Current
[A]
0,67 0,67 0,37 0,27 0,10 0,10 0,10
0,9
0,9 0,55 0,55 0,25 0,25 0,20 0,20
0,6 0,45 0,20 0,20 0,20 1,35 0,90 0,55 0,55
Capacity
µF
7
7 3,5 3,5
-
-
­8 8 5 5
-
-
-
-
-
-
-
-
-
10
8 5 5
Weight
[kg]
9,7
18,5
31
42
The type number shall include:
Place in type number 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Type number 5 2 3 2 x . x = x + ED x
6th place: the letter “U”, if there is letter C, P, R or S on the 7th place (electric actuator is fitted with electronics DMS2), the letter “T” if there is letter C or R 7th place – the actuator is not equiped with display and block of local
control
character from Table 2, if there is letter E on the 7th place (electronics DMS2 ED)
Table 2 – actuator with electronics DMS2 ED
Character 0 1 2 3 4 5 6 7 8 9 A B C D E F H J K L M N P R
Local control x x x x x x x x x x x x Display x x x x x x x x x x x x Power relays x x x x x x x x x x x x Analogo
Analog
module
modul regulator x x x x x x x x
7th place: E – electric actuator is fitted with electronics DMS2 ED P – electric actuator is fitted with electronics DMS2 for connection to Profibus, power relays S – electric actuator is fitted with electronics DMS2 for connection to Profibus R – electric actuator is fitted with electronics DMS2 for two- or three-position control **), power relays C – electric actuator is fitted with electronics DMS2 for two- or three-position control **) **) Two- or three-position regulation of the actuator is set at the manufacturer. Unless otherwise specified in the order, the actuator will be set for three-position regulation (control by signal 4 – 20 mA).
transmitter
x x x x x x x x x x x x x x x x
th
8
place – adjusting time, tripping torque - according to Table 1
9th place – mechanical connection – the numeber or letter according to Table 3
10th place ED – actuators with DMS2 or DMS2 ED electronic system
11th place – surrounding temperature
For surrounding temperature from -25 °C till +55 °C no designation For surrounding temperature from -50 °C till +55 °C F
In all markings of explosion-proofness of actuators type no. 52 32x.xxxxF, the marking of sub-groups of group II of
an explosion-proof electric device according to standard ČSN EN 60079-0 will be changed from IIC to IIB, namely Ex d IIB T6.
The version 52 32x.xxxxF is only available with three-phase electric motors.
43
Table 3 – Way of connecting MODACT MOKPED Ex electric actuators – specifying of the 9th place in type number
Flange size Connection
Type number 52 320
F05 F05 F04
keyway
square
keyway F04 F05 F04 F04
square F04 F05 F05
Type number 52 321
F10 F07
square
keyway F07 F10 F07 F07 F07
square F10 F10 F10 F10
Type number 52 322
F12 F12 F10
keyway
square
keyway F10 F12 F10 F10 F10
square F10 F10 F12 F12
Square size
s [mm]
Ø
22
14
Ø
18
11 14 11 12 12 16 16
22
Ø
28
17 22 17 19 19 24 24 27 27
Ø
50
27
Ø
42
22 27 22 24 24 27 27 32 32
Square position
basic
basic positioned at a 45° positioned at a 45°
basic positioned at a 45°
basic positioned at a 45°
basic
basic positioned at a 45° positioned at a 45°
basic positioned at a 45°
basic positioned at a 45°
basic positioned at a 45°
basic
basic positioned at a 45° positioned at a 45°
basic positioned at a 45°
basic positioned at a 45°
basic positioned at a 45°
Marking of the
9th position
in the type number
0 1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 A B
0 1 2 3 4 5 6 7 8 9 A B
Structural design
of output
collar
exchangeable
inserts
exchangeable
inserts
collar
exchangeable
inserts
Actuator output shaft position
(when viewing towards the local position indicator).
The handwheel tallies with the CLOSED position
Another connection of electric actuators on demand.
Keyway connection Square
open
close
basic position positioned at a 45°
(to DIN 3337) (to ISO 5211)
duct axis
44
Connecting dimensions of MODACT MOKPED Ex electric actuators
for valves and control devices - connecting with square
I3
h2
h1
The position of the square hole in end position of electric actuator. The position “Opened” is to the left of the position “Closed” when viewing in the direction to the local indicator of position. The square hole is according to DIN 79:2013-02. Connecting dimensions are according to DIN 3337 or ISO 5211. The position “Z” (“C”) of the square hole for spindle is identical with the position “Z” (“C”) on the local indicator of position.
„O“
ø d1
A
ø d5
ø d2
“Z” (“C”)
ø d3
d4
h4
s
“Z” (“C”)
s
e
„O“
e
B
Flange
F04
F05
F07
F10
F12
ø d1
65
65
90
125
150
ø d2
f8
30
35
55
70
85
ø d3
42
50
70
102
125
d4
M6
M6
M8
M10
M12
min.
1,5
3
3
3
3
h4
max.
0,5
0,5
0,5
1
1
45
h2 min.
12
12
13
16
20
A – connection by square in basic position B – connection by square turned by 45 °
h1 max.
3
3
3
3
3
I 3 min.
15,1 16,1 19,1 22,1 23,1 26,1 30,1 33,1 37,1 37,1 44,1
s
H 11
11 12 14 16 17 19 22 24 27 27 32
e min.
14,1 16,1 18,1 21,2 22,2 25,2 28,2 32,2 36,2 36,2 42,2
ø d5
25
28
40
50
70
Connecting dimensions of MODACT MOKPED Ex electric actuators
for valves and control devices – connecting with keyway
I1
The position of groove for keyway according to ISO 5211 and DIN 3337 is in the position “Closed”. The position “Opened” is to the left of the position “Closed” when viewing in the direction to the local indicator of position. The position “Z” (“C”) of the groove for keyway is identical with the position “Z” (“C”) on the local indicator of position.
h2
h1
“O”
ø
d1
ø
d7
ø
d5
ø
d2
“Z” (“C”)
b4
ø
d3
h3
t3
Flange
F04
F05
F07
F10
F12
ø d1
65
65
90
125
150
ø d2
f8
30
35
55
70
85
ø d3
42
50
70
102
125
d4
M6
M6
M8
M10
M12
d7 H9
18
22
28
42
50
h3 max.
3
3
3
3
3
46
h2 min.
12
12
13
16
20
d4
h1 max.
3
3
3
3
3
I1 min.
26
30
35
45
55
b4
Js 9
6
6
8
12
14
+0,4
t3
+0,2
20,5
24,5
30,9
45,1
53,5
ø d5
25
28
40
50
70
Rozměronáčrtek elektrických servomotorů MODACT MOKPED 100 Ex a 250 Ex
Dimensional sketch of MODACT MOKPED 100 Ex and 250 Ex electric actuators
F
E
98
A
B
H
D
K
G
Block of local control (BMO)
Místní ovládání (MO)
Odpadá u provedení s MO
Not applied for version with BMO
C
2x cable bushing
2x kabelovstup
MOKPED 100 Ex - M20x1,5 MOKPED 250 Ex - M25x1,5
1x cable bushing M20x1,5
1x kabelovstup M20x1,5
pro MOKPED 100 Ex i MOKPED 250 Ex
MOKPED 100 Ex and MOKPED 250 Ex
2x kabelovstup M20x1,5
2x Cable bushing M20 x 1,5
pro místní ovládání
for local control
Type
MOKPED 100 Ex
MOKPED 250 Ex
A
253
306
B
276
312
C
297
368
47
D
308
385
E
311
376
F
316
363
G
160
200
H
170
183
K
72
72
Návod k montáži a obsluze servomotorů MOKPED Ex t.č. 52320 52322
Strana 44
Dimensional sketch of MODACT MOKPED 600 Ex electric actuators
463
362
80
78
400
ø 250
Cable bushing M20x1,5
2x cable bushing M20x1,5 for version with BMO
346
264
403
Block of local control (BMO)
125
Not applied for version with BMO
2x cable bushing M25x1,5
48
Spare parts
Name Order number Type Using, note
Sealing ring 180x3 52 320 Sealing between cover and gear box Sealing ring 210x3 52 321 Sealing between cover and gear box Sealing ring 250x3 52 322 Sealing between cover and gear box Source board DMS2.ED.ZT 2339620300 DMS2.ED Position sensor DMS2.ED.ST90 2339620302 DMS2.ED Torque sensor DMS2.TORK 2339620003 For DMS2.ED and DMS2 Analogue module DMS.ED.CPTT 2339620304 DMS2.ED Power relays board DMS2.FIN 2339620031 For 3-phase only Relay Finder 62.33.8.230.0040 2334513109 For 3-phase only Sensor-torque cable K.TORK 2339620007 For DMS2.ED and DMS2 Sensor-source board cable K.ZED2 2339620009 DMS2.ED Sensor-analogue module cable K.AED2 2339620011 DMS2.ED Sensor-COM cable K.COM 2339620040 For DMS2.ED and DMS2 Display DMS2.ED.DT 2339620305 DMS2.ED Display cable DMS2.ED Source board DMS2.ZD2 2339620024 DMS2 For analogue and profibus Analogue board DMS2.A22 2339620042 DMS2 Profibus board DMS2PR2 2339620026 DMS2 Position sensor DMS2.S90 2339620039 DMS2 Display DMS2.DP 2339620018 DMS2 Local control board DMS2.H3 2339620041 DMS2 Source-sensor cable K.ZDR2 DMS2 Display-control cable K.H2 DMS2 Source-analogue/profibus cable K.ZA DMS2 Source-display cable K.D2 DMS2 Sensor-analogue K.SA2 cable DMS2 Analogue
49
NOTES
50
Development, production and service of electric actuators and switchboards.
Top-quality sheet-metal processing (TRUMPF equipment), power paint shop.
SURVEY OF PRODUCED ACTUATORS
KP MINI, KP MIDI
Electric rotary (90°) actuators (up to 30 Nm)
MODACT MOK, MOKED, MOKP Ex, MOKPED Ex
Electric rotary (90°) actuators for ball valves and flaps
MODACT MOKA
Electric rotary (90°) actuators for nuclear power stations
application outside containment
MODACT MON, MOP, MONJ, MONED, MOPED, MONEDJ
Electric rotary multi-turn actuators
MODACT MO EEx, MOED EEx
Explosion proof electric multi-turn actuators
MODACT MOA
Electric multi-turn actuators for nuclear power stations
application outside containment
MODACT MOA OC
Electric multi-turn actuators for nuclear power stations
application inside containment
MODACT MPR Variant
Electric rotary single turn lever actuators with a variable output speed
MODACT MPS Konstant, MPSED
Electric rotary single turn lever actuators with a constant output speed
MODACT MTN, MTP, MTNED, MTPED
Electric linear thrust actuators with a constant output speed
Deliveries of assembled actuator + valve (or MASTERGEAR gearbox) combinations
TRADITION
QUALITY
RELIABILITY