Zooper Premier Elite User Manual

Page 1
Instruction Manual: 4-8 zone F.A.C.P.
Page 2
INSTRUCTION MANUAL – 4 to 8 ZONE FIRE ALARM PANEL
INDEX
INDEX......................................................................................................................................2
Introduction...............................................................................................................................3
Mains & Battery........................................................................................................................4
Connecting the mains.. ........................ ....................... ......................... ........................ ..........4
Connecting the batteries...................... ....................... ......................... ........................ ..........4
Charger Short Circuit Protection...........................................................................................4
Detectors & sounders................................................................................................................5
Wiring the detectors..............................................................................................................5
Diode Bases...........................................................................................................................5
Zone Short Circuit Protection...............................................................................................5
Wiring the sounders..............................................................................................................5
Setting a Sounder Activation Delay......................................................................................6
Other Connections.....................................................................................................................7
Fire Relay..............................................................................................................................7
Fault Relay............................................................................................................................7
Class Change Input ...............................................................................................................7
Display & Controls ...................................................................................................................8
Display..................................................................................................................................9
Controls...............................................................................................................................10
Alarm Condition & Resetting an alarm ..................................................................................11
What to do in the event of a fire..........................................................................................11
Resetting from an alarm condition......................................................................................11
Fault display & fault-finding ..................................................................................................12
Fault Finding.......................................................................................................................12
Supply fault.....................................................................................................................12
Zone Fault.......................................................................................................................13
Sounder Circuit Fault......................................................................................................13
Earth Fault.......................................................................................................................14
System Fault....................................................................................................................14
Disablement ............................................................................................................................15
TO PROGRAMME ZONE (OR SOUNDERS) AS DISABLED.......................................15
Test Mode ...............................................................................................................................16
TO PROGRAMME ZONE IN TEST.................................................................................16
Optional Repeater Driver........................................................................................................17
Battery Calculation .................................................................................................................18
Sample Calculation.............................................................................................................18
Specifications..........................................................................................................................19
Electrical Specifications......................................................................................................19
Enclosure Specifications.....................................................................................................19
Fuse Ratings........................................................................................................................19
Log Book ................................................................................................................................20
MAINTENANCE WORK..................................................................................................20
FALSE ALARMS...............................................................................................................21
ALL OTHER EVENTS......................................................................................................22
Approved Document No: GLT.MAN-119 PAGE 2 Issue : 1 Author: NRPJ Date: 22/11/2006
Page 3
INSTRUCTION MANUAL – 4 to 8 ZONE FIRE ALARM PANEL
Introduction
The Premier Elite 4 to 8 zone panels have been designed to meet the requirement of an easy to use fully functional fire alarm control panel.
It is available as either a 4 zone panel, 6 zone panel or an 8 zone panel. Each version has 2 sounder circuits, an alarm relay , and a fault relay. The sounder circuits can have a programmable delay set. There is an option to add a zonal output board, which can be used to drive zonal
relays, or a hard wired repeater panel. There is no configuration, simply connect the detectors & sounder s and apply
power. The Premier Elite range also includes a low cost 1 & 2 zone version These panels
are NOT covered in this manual. They have a separate manual.
Approved Document No: GLT.MAN-119 PAGE 3 Issue : 1 Author: NRPJ Date: 22/11/2006
Page 4
INSTRUCTION MANUAL – 4 to 8 ZONE FIRE ALARM PANEL
Mains & Battery
Connecting the mains.
The Mains supply to the FACP is fixed wiring, using
Fire resisting
(Between 1 mm² and 2.5mm²) or a suitable 3-conductor system, fed from an isolating double pole switch fused spur, fused at 3A.
IT SHOULD NOT BE
CONNECTED THROUGH AN RCD. This should be secure from unauthorised
operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’. The supp ly must be exclusive to the Fire Panel.
COVERED WITH THE GROMMETS PROVIDED
MAKE SURE ANY SPARE E NTRY HOLES ARE
Connecting the batteries
The Premie r Elite requires 2 x 12 V sealed lead acid (SLA) batteries The two batteries are wired in series. The +ve of one battery is connected to the red battery lead. The The –ve of the first battery is connected to the +ve of the second battery using the
link wire supplied. Although there are many sizes of suitable battery, the sizes we usually recommend
are 12V 2Ah for standard backup, or 12V 7Ah for extended backup (72 hour or more) , and the enclosure has been designed to hold these two battery sizes.
of the other battery is connected to the
–ve
battery lead.
black
3-core cable
TO PCB
BATTERY INTERCONNECTING CABLE
2 x 2Ah Batteries
SEALED LEAD ACID BATTERY
12V / 2 Ah
Charger Short Circuit Protection
The Premier Elite has an intelligent charger, that senses if too much current is being drawn (for instance in the case of totally discharged batteries, or the charger leads being shorted together). In such an event, the Premier Elite 4-8 zone panel will turn off the power to its charger circuit.
The panel also turns off the charger when the batteries are disconnected.
Approved Document No: GLT.MAN-119 PAGE 4 Issue : 1 Author: NRPJ Date: 22/11/2006
SEALED LEAD ACID BATTERY
12V / 7 Ah
BATTERY INTERCONNECTING CABLE
TO PCB
CLAMP
SEALED LEAD ACID BATTERY
12V / 7Ah
Page 5
INSTRUCTION MANUAL – 4 to 8 ZONE FIRE ALARM PANEL
Detectors & sounders
Wiring the detectors
The Premier Elite has been designed to use a 1N4002 diode end of line on the detector zones.
Zone -
R
-
N
I
1
L
L
2
E A R T H
L
1
O
U
T
R
-
N
I
1
L
L
2
E A R T H
L
1
O
U
T
R
-
N
I
1
L
L
2
E A R T H
L
1
O
U
T
Zone +
When common bases are used, call points should be connected to the start of the zone, so that removing a detector head will not remove power from the call points.
Diode Bases
The Premier Elite 4-8 zone can also be used with diode bases. Diode bases allow call points & detectors to be mixed on the same zone without any restrictions. The diode (also known as a continuity diode) passes power to the downline detectors and call points, if a detector head is removed for any reason.
Zone Short Circuit Protection
The Premier Elite 4-8 zone panel has a higher zone output current than the 1-2 zone panels. This is to allow them to drive larger zones, and zone powered beam detectors etc.
In order to protect the panel in the event of an overload, the panel will turn off the zone voltage if the current in that zone exceeds 70mA. The panel will then try to restart the zone during the next “Open circuit monitoring cycle”. These occur once every 60 seconds.
1N4002 End of line diode.
Stripe to +ve
Wiring the sounders
The Premier Elite has 2 so under circui ts, each rated at 400mA. Each sounder circuit must be fitted with a 10k end of line resistor
SND+
SND-
SOUNDER SOUNDER
+--+
Approved Document No: GLT.MAN-119 PAGE 5 Issue : 1 Author: NRPJ Date: 22/11/2006
+--+
SOUNDER
SOUNDER
10K
+--+
+--+
End of Line Resistor
Page 6
INSTRUCTION MANUAL – 4 to 8 ZONE FIRE ALARM PANEL
Setting a Sounder Activation Delay
On the Premier Elite there is the option to delay the sounder activation in the event of a fire. This might be useful in schools or clubs where the responsible person might want to verify the alarm, before having a “mass evacuation” of the building. A false alarm can be reset before the sounders operate. If it is a true alarm, the sounders can be started before the timer finishes by pressing the DELAY OVERRIDE BUTTON.
To set a delay open the panel door using Alan Key provided and set switch 7 ( using a terminal screw driver to the delay required
SW7 Setting External
sounder delay in minutes
0 No delay 1 1 minute 2 2 minutes 3 3 minutes 4 4 minutes 5 5 minutes 6 6 minutes 7 7 minutes 8 8 minutes 9 9 minutes
SW7
)
When a delay is set, the panel will show GENERAL DISABLEMENT and DEL (sounder DELay)
Approved Document No: GLT.MAN-119 PAGE 6 Issue : 1 Author: NRPJ Date: 22/11/2006
Page 7
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Other Connections
The Premier Elite also has the following connections:-
Fire Relay
The Premier Elite has one volt free change over relay that operates on an alarm. It is rated at 1Amp, SELV. The relay remains operated until the panel has been reset.
Fault Relay
The Premier Elite has one volt free change over relay that operates on any fault condition. The Relay is Normally energised, so that it gives a signal in the event of total power failure (Mains & Battery back-up). It is rated at 1Amp, SELV. The relay remains operated until the fault has been cleared.
Class Change Input
The class change input on a Premier Elite 4-8 zone F.A.C.P. will remotely operate the sounder circuits.
The Class change terminals should be connected to a normally open contact, that closes when the sounders are required to sound.
Historically it was used to ring bells in school momentarily to signal end of lessons, and lunch break.
It can also be used as a simple way of linking 2 control panels. You would link from the fire relay versa.
on one panel to the class change on the other, and vice
Approved Document No: GLT.MAN-118 PAGE 7 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 8
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Display & Controls
Here is the fascia for the Premier Elite.
Operating Instructions
Normal Operat ion:
Under normal conditions, the system will be silent and the green "POWER" LED will be on.
Fire Condition:
In a fire condition, the "GEN FIRE" LED and the specific zones(s) "FIRE" LED will be on and the internal panel buzzer will sound.
Fault Condition:
In any fault condition, the "GEN FAULT" LED and the specific zone fault(s) LED will be on and the internal fault buzzer will sound.
Disabled C ondition:
In the disabled condition, the "GEN DISABLEMENT" LED and the specific zone(s) LED will be on.
Start/Stop Fire Sounders:
To start or stop the fire sounders, turn the key switch to the "CONTROLS ENABLED" position and press button 1 . Pressing this button again will toggle between stop/start so unders.
FAULT TONE
Elite
FIRE ALARM CONTROL PANEL
DESIGNED TO EN54 PARTS 2 & 4
To Re set From Fire Condition:
After all detecto r s and manual call points have been returned to normal, turn the key switch to the "CONTROLS ENABLED" position and press button 1 to stop the fire sounders. Press button 2 to silence the internal fault buzzer and then press but to n 3 t o R ESET the system.
Silence Fault Tone
If the panel is showing a fault conditi on, t ur n the key switch to the "CON TROLS ENABLED" position and pr ess button 2 (SILENCE FAULT CONDITION). If new faults are subsequently detected, the specific fault(s) LED will be on and the internal f ault buzzer will sound. CALL ENGINEER.
External Sounder Delay Override:
When the panel is i n a Fire Condition and the system has bee n configured with delayed alarm function, the "DEL" LED will be on. At the end of the delay period the "DEL " LED will go off and the fire sounders w il l th en operate. This delay may be ove rri dden by pressing the “DELAY OVERRIDE" button.
It should be noted that the Yellow zonal indication LEDs are used to in dic ate several conditions. They are used for:-
Zone fault (GEN FLT will also be lit)
Zone Disablement (GEN DISABLEMENT will also be lit)
Approved Document No: GLT.MAN-118 PAGE 8 Issue : 1 Author: NRPJ Date: 15/11/2006
Zone Test (GEN TEST will also be lit)
Page 9
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Display
The Premie r Elite has the following LED indicators:-
LEDs LIT LED CONDITION PANEL STATUS
POWER CONSTANT G REEN The panel is supplied with power, and has no fault s / fires (Sy st em No rmal) GEN FLT
ONLY GEN FLT &
SUPPLY FLT GEN FLT &
EARTH FLT GEN FLT &
ZONAL FLT GEN FLT &
ZONAL FLT GEN S/C
GEN FLT & SND FLT
GEN FLT & SND FLT GEN S/C
GEN FLT & SYSTEM FLT
GEN FIRE ONLY
GEN FIRE & ZONE FIRE
GEN FIRE & ZONE FIRE & GEN DISABLE & DEL
GEN DISABLE
GEN DISABLE
GEN DISABLE ZONE DISABLE
GEN DISABLE ZONE DISABLE
GEN DISABLE DEL
GEN TEST ZONE DISABLE
CONSTANT YE LLOW Problem with keyswitch connections
CONSTANT YELLOW FLASHING YELLOW
CONSTANT YELLOW FLASHING YELLOW
CONSTANT YELLOW FLASHING YELLOW
CONSTANT YELLOW FLASHING YELLOW FLASHING YELLOW
CONSTANT YELLOW FLASHING YELLOW
CONSTANT YELLOW FLASHING YELLOW FLASHING YELLOW
CONSTANT YELLOW CONSTANT YELLOW
CONST ANT RED A manual evacuation has occurred.
CONSTANT RED CONSTANT RED
CONSTANT RED CONSTANT RED CONSTANT YELLOW CONSTANT YELLOW
FLASHING YELLOW (FAST – 4 HZ)
FLASHING YELLOW (SLOW – 0.5 HZ)
FLASHING YELLOW (SLOW – 0.5 HZ)
CONSTANT YELLOW CONSTANT YELLOW
CONSTANT YELLOW CONSTANT YELLOW
FLASHING YELLOW FLASHING YELLOW (VERY SLOW – 0.25 HZ)
There is a problem with either the mains supply or the battery backup
There is a wiring problem. One of the cables is touching the earth screen.
There is an open circuit fault in the wiring of the zo ne indi cat ed.
There is a short circuit fault in the wiring of the zone indicated.
There is an open circuit fault in the wiring of one or both of the soun de r circuits
There is a short circuit fault in the wiring of one or both of th e soun de r circuits
A processor fault has occurred. To reset, turn keyswitch on then back off. If problem persists, consult your dealer.
The sounders will be active. A fire has occurred in the zone indicat ed.
The sounders will be active. A fire has occurred in the zone indicat ed.
The sounders have a delay set, and will become active af ter the programmed delay. To override the display, press delay override.
The panel is ready for selecting disable or test mode
The panel is in SELECT DISABLEMENT MODE
The user is scrolling through zones to select which one to disable/or user has just enabled the zone.
The indicated zone is disabled.
The Sounders are delayed by the amount set on the rotary switch.
The indicated zone is in Test Mode.
Approved Document No: GLT.MAN-118 PAGE 9 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 10
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Controls
The Premier Elite has the following controls:-
BUTTON LABEL USE 1 START/STOP Used to silence the sounders in an alarm, or to
manually start the sounders to evacuate building
2 SILENCE FAULT TONE Used to silence the panel`s internal buzzer in a fault
or alarm condition.
3 RESET Used to return the panel to its normal condition after
an ALARM condition. (Reset will not clear faults)
4 LED TEST To check that all indicator LEDs are working. Use as
part of the daily / weekly fire alarm inspection. Engineer ENGINEER Used to access Disablement mode or Test Mode. Delay Override
Note that the controls can only be used after the keyswitch has been turned to the ON position.
DELAY OVERRIDE Used to start sounders immediately in the event of
the panel having a delay to the sounders
Approved Document No: GLT.MAN-118 PAGE 10 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 11
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Alarm Condition & Resetting an alarm
The Premier Elite signals an alarm by the following:­Turn on the General Fire LED
Turn on the Zonal Fire Indicator Turn on internal buzzer Start any sounders connected to the panel`s sounder circuits Activate the fire relay
What to do in the event of a fire.
1. Follow the building evacuation procedure, and check that everyone has left the building safely.
2. The building fire officer or responsible pers on should CAREFULLY enter the building, and locate the area of the alarm from the fire alar m panel.
3. Investigate to determine the cause of the alarm. Look for the detector in the zone in alarm that signalled the fire. The detector that signalled an alarm will have its RED ALARM LED on.
4. If a small fire is found, a suitably trained person could tackle this with a suitable fire extinguisher.
5. If a larger fire is found, leave the building immediately, and contact the fire brigade.
6. If no fire is found, make a note of the detector that signalled fire, and look for anything nearby that could be the cause of the activation, eg cooking, or use of a hot air gun etc.
7. Record findings in the fire alarm log book.
Resetting from an alarm condition
After the relevant action has been taken, the Premier Elite fire alarm panel can be reset by the following:-
1 Press Stop/Start sounder button (BUTTON 1). This will silence the external
sounders.
2 Press Silence Fault Tone button (BUTTON 2). This will silence the panel`s
internal buzzer.
3 Press the Reset button (BUTTON 3). This will return the panel to it`s norm al
condition.
If the panel goes straight back into alarm, then the cause of the alarm has not been cleared. This could be a detector still exposed to smoke, or a call point still in the active position. Press Buttons 1 & 2 on the panel, then investigate for a call point, or detector that still has it`s RED ALARM LED on. Reset the call point, or clear the smoke. If the problem persists, contact an engineer.
Approved Document No: GLT.MAN-118 PAGE 11 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 12
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Fault display & fault-finding
The Premier Elite 4 to 8 zone panels monitor for the following fault s :­Low or failed mains (Including fuses)
Low or failed battery (Including fuse) Detection Zone open circuit wiring fault Detection Zone short circuit wiring fault Detection Zone detector removed. Sounder circuit open circuit wiring fault Sounder circuit short circuit wiring fault Earth Fault System fault
Most of these faults will need to be checked by an engineer, but the system can be checked for a removed detector by the responsible person.
All faults in the Premier Elite are NON-LATCHING. IE they can not be reset with the reset button. They will clear automatically when the fault has been fixed. The exception is a SYSTEM FAULT, which means that the processor may have crashed, and may or may not have restarted correctly.
Fault Finding
Supply fault
A power supply fault is indicative of one or more of the following faults: ­Loss of Mains power
Check mains fuse
Check that there is 30-34V coming from the transformer secondary
Check that 230V AC is present at the mains terminal block
Check charger fuse FS1.
Loss of Battery power
Check that 2 X 12V batteries are fitted in series to give 24V backup
Check battery fuse FS2.
Check that battery connections are secure.
Check that the batteries are not over 5 years old
Check that the 2 batteries have a combined voltage of over 21V DC
Approved Document No: GLT.MAN-118 PAGE 12 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 13
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Zone Fault
A Zone Fault is indicative of one or more of the following faults:­Open Circuit fault.
Check that the correct end of line DIODE (1N4002) has been fitted
Check that there are no breaks in the cable, and that all screw connections are
secure.
Check that no detectors have been removed from the circuit.
Check that all detectors are correctly fitted to their bases.
As a cable check, remove zone wire from panel. Temporarily join the + & - cables
at the end of line & Check for continuity. (If a break is found, splitting the line in half & fitting EOL will help determine which section of cable has the fault)
As a panel check, remove cable & fit EOL at the panel. If the fault clears, the
panel is working correctly.
If a panel does not report a fault when an detector is removed, check with your
Short Circuit Fault (Gen S/C LED will be lit)
Check that the correct end of line has been fitted (1N4002 DIODE), and check
Check that no equipment, other than detectors or call points has been fitted to the
Check for shorts to the cable screen.
Check that none of the heads have become damaged (remove one at a time).
As a panel check, remove cable & fit EOL at the panel. If the fault clears, the
supplier if the detector is compatible with the Premier Elite.
that it has not been fitted backwards. It should be fitted stripe to +ve. zone.
panel is working correctly.
Sounder Circuit Fault
A Sounder Fault is indicative of one or more of the following faults:­Sounder Open Circuit fault.
Check that the correct end of line resistor (10K) has been fitted to both circuits
Check that sounder fuses FS4 & 5 are intact.
Check that there are no breaks in the cable, and that all screw connections are
secure.
As a panel check, remove both circuits cable & fit both EOLs at the panel. If the
fault clears, the panel is working correctly
.
Short Circuit Fault (Gen S/C LED will be lit)
Check that the correct end of line has been fitted to both circuits (10k resistor)
Check that ALL sounders, Bells etc are POLARISED, and are fitted the correct
way round. (see diagram after list)
Check for shorts to the cable screen.
As a panel check, remove cable & fit EOL at the panel. If the fault clears, the
panel is working correctly.
SND+
CONNECTOR BLOCK
SND-
POLARISING DIODE
+--+
BELL
BACK EMF DIODE
BELL BELL
+--+ +--+
RELAY
NC
CM
NO
10K End of Line Resistor
back EMF protection diode. (symptoms: Chattering sounder relays that don’t turn off).
Note: If non-polarised alarm devices (eg some types of old mechanical bell, or a relay) are used, then a diode will have to be placed in line with the device to enable fault monitoring. They may also need a
Approved Document No: GLT.MAN-118 PAGE 13 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 14
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Earth Fault
An EARTH fault indicates that something is shorting to earth (usually through the cable screen). Disconnect the earth screens one at a time to determine the problem line.
(Note: connecting other equipment , eg an oscilloscope or PC, to the panel can give an earth fault)
The voltage between battery –Ve and earth should be 14-16 volts. If it is not, the voltage should indicate what is shorting to earth.
System Fault
A system fault is an abnormal microprocessor running condition due to various unexpected phenomena.
This will result in the panel attempting to correct itself. Should this fault occur, the System Fault LED, General Fault LED, General Fault relay and fault internal buzzer will be constantly active until the control keyswitch is turned from off position to control enable position. This should cause this fault condition to reset. If not, consult your supplier.
Approved Document No: GLT.MAN-118 PAGE 14 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 15
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Disablement
The Premier Elite 4-8 zone allows any zone, or the sounder circuit to be disabled to aid commissioning and assist routine maintenance work.
When a zone (or sounder cct) is disabled, the panel will not respond to any fault or fire signals it receives from that zone. This might be used if the system requires routine maintenance, and the customer needs the system to continue running, but doesn’t want spurious false alarms.
The panel will respond in the usual manner to any events in any non-disabled zones.
To Programme Zone (Or Sounders) As Disabled
Any number of zones (or the sounders) can be disabled, but it is good practice to only disable one zone at a time.
Insert and turn control key to enabled position; Press Engineer switch and the GENERAL DISABLEMENT LED will come on (flashing fast); Press Scroll switch and the GENERAL DISABLEMENT LED will flash slowly. The panel is
now in SELECT DISABLEMENT MODE. Press scroll button again. Zone 1 DISABLEMENT LED will be lit. Continue to press scroll until
the desired Zone or sounder is lit. Press the Engineer button. The GENERAL DISABLEMENT LED will be lit constantly indicating that this zone (or sounder) is now disabled.
If more than one zone needs to be disabled, then press scroll again until the required zone is selected.
If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on another part of the system), turn the keyswitch off, then back on again.
Once all the work has been done the zones need to be enabled again. If the panel is still in SELECT DISABLEMENT MODE, jump to paragraph 8, otherwise, turn the keyswitch to controls enabled, press engineer button (GENERAL DISABLEMENT LED will flash fast). Press scroll and it will return to being on steady. The panel is now in SELECT DISABLEMENT MODE
Press the scroll button until the disabled zone has been selected. Press engineer but ton. Scroll to any other disabled zone and enable in the same way. When all zones are enabled again, the GENERAL DISABLEMENT LED will flash slowly. Turn the keyswitch to off to return the system to normal.
Approved Document No: GLT.MAN-118 PAGE 15 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 16
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Test Mode
To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is available.
When a detector or manual call point is triggered on any zone in Test, the Alarm sounders operate for approximately seven seconds on and seven seconds off. This cycle continues until the cause of the Alarm is removed (either by the test smoke clearing from the detector or the manual call point being reset), at which point, the detector circuit also automatically resets.
Should an Alarm occur on a zone that is not programmed to test, the Alarm will be processed in the normal way. The testing of the zone in test will temporarily be suspended until the Alarm(s) from the other zones are reset. At this point, zone retesting may resume.
To Programme Zone In Test
NOTE: Only one zone can be programmed in test at any one time.
1. Insert and turn control key to enabled position;
2. Press engineer switch until the General Zone test LED is on (flashing fast);
3. Enter Engineer Code 4114 and then the General Zone Test LED is on (flashing slow);
4. Press scroll switch and Zone one fault LED will flash in synchronisation with the General Zone test;
5. Press scroll button to the desired Zone for test. Once the desired Zone LED is flashing, this Zone is now in test mode.
6. Once testing of that zone is completed, press scroll button to move to another Zone or turn the control key switch to off position to exit test mode.
Approved Document No: GLT.MAN-118 PAGE 16 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 17
Zonal Output Card
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Optional Repeater Driver
The Premier Elite has a connection to fit an optional Zonal Output Card. The card fits next to the display PCB on the fire alarm panel door.
This can either be used in two ways:-
1 As a stand alone board that has zonal 29 Volt outputs, suitable for
connecting relays etc.
2 It can be used to drive a hard wired repeater panel. The panel
would need the following connections to the repeater:-
+V – Supply Voltage 0V – Supply ground GA – General Alarm signal CF – Common Fault Signal TN – Buzzer Active Signal (tone)
It will also need 1 connection per zone.
Zonal Card Connection
Approved Document No: GLT.MAN-118 PAGE 17 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 18
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Battery Calculation
Here are the current consumption of the Premier Elite panels in various conditions:­Control Panel Model Mains Fail,
buzzer sounding
Premier Elite 4-8 Zone 50mA 31mA 163mA
Sample Calculation
A Premier Elite 4 zone panel has the following items connected:­Zone 1: 2 x MCP, 8 x Optical, 2 x heat detector
Zone 2: 1 x MCP, 7 x Optical, 1 x heat detector Zone 3: 3 x MCP, 9 x Optical, 1 x heat detector Zone 4: 1 x MCP, 10 x Optical, 0 x heat detector Sounder CCT 1: 10 x Maxitone sounder Sounder CCT 2: 12 x Maxitone sounder
ITEM QUIESCENT ALARM PREMIER ELITE 2 66mA 99mA MCP 0mA 40mA OPTICAL 100uA 40mA HEAT 50uA 40mA MAXITONE SOUNDER 0mA 25mA
To calculate the required battery backup required, we use the equation:­Battery Size (Standby time in Amp Hours) = 1.25 x [(T
Where: T
I T I
I
ALM
=0.163 + 22x 0.025 + 1x 0.040 + 7x0 + 33x0.0001 + 4x0.00005 =0.163 + 0.55 + 0.04 + 0 + 0.0033 + 0.0002 =0.757 Amps
I
SBY
=0.050 + 22x0 + 7x0 + 34x0.0001 + 4x0.00005
=0.050 + 0 + 0 + 0.0034 + 0.0002 =0.0536
Therefore:­Battery size
= 1.25 X (0.3785 + 1.2864) = 1.25 x 1.6649 = 2.08 Ah
So 2.2 Ah batteries will be suitable for this installation.
= Maximum time in hours required for the alarm [½ hour is most common time]
ALM
= Total Alarm Current in amps for all alarm devices connected to the alarm circuits
ALM
= Standby time in hours for the system after mains failure [normally 24, 48 or 72 hr]
SBY
= Quiescent current in amps of control panel in fault condition [because of mains failure]
SBY
all detection zones.
PLUS
= PREMIER ELITE ALM + 22 X MAXITONE ALARM + 1 X DETECTOR A LM + 7 X MCP QU + 33
X OPT QU + 4 x HT QU
= PREMIER ELITE QU + 22 X MAXITONE QU + 7 X MCP QU + 34 X OPT QU + 4 x HT QU
= 1.25 X ((0.5 x 0.757) + (24 x 0. 0536))
Mains Fail, buzzer silenced
x I
ALM
ALM
) + (T
SBY
x I
It is always best to calculate battery requirements, but our general guideline would be:-
1,2 or 4 zone – use 2 x 12V 2.2Ah 6 or 8 zone - use 2 x 12V 7.0Ah
Mains fail, panel in alarm
)]
SBY
Approved Document No: GLT.MAN-118 PAGE 18 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 19
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Specifications
Electrical Specifications
ELECTRICAL DESCRIPTION VALUE MAINS VOLTAGE 230V AC +/- 10% @ 50/60 Hz
BATTERY VOLTAGE 24V DC (2 X 12V SLA BATTERY) SYSTEM VOLTAGE 24V DC NOMINAL (18 – 32 V) SYSTEM VOLTAGE RIPPLE 2V PK-PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL (20 - 22.5V) SOUNDER ALARM OUTPUTS 2 x 400mA @ 24V DC (Nominal) AUXILIARY FAULT OUTPUT 1 x RELAY SELV (1A MAX) AUXILIARY FIRE OUTPUT 1 x RELAY SELV (1A MAX) NUMBER OF ZONES 1/2/4/6/8 MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE MAXIMUM ZONE RESISTANCE 70 ohms REMOTE SOUNDER ACTIVATION VIA N/O CONTACTS SOUNDER ACTIVATION DELAY 0-9 MINUTES -IN 1 MIN INCREMENTS ZONE END OF LINE DEVICE 1N4002 DIODE (CATHODE STRIPE TO +) SOUNDER END OF LINE DEVICE 10 K RESISTOR CHARGER VOLTAGE 28.4V @ 25oC (NO BATTERY CONNECTED) ZONE SHORT CIRCUIT PROTECTION 100mA CHARGER SHORT CIRCUIT PROTECTION Batteries less than 21V TOTAL CHARGER OUTPUT 1.1 Amp
Enclosure Specifications
DESCRIPTION VALUE ENCLOSURE SIZE 355 x 275 x 100 mm
TOP CABLE ENTRIES 12 x 19mm DIA GROMMETED ENTRIES BOTTOM CABLE ENTRIES 2 x 19mm KNOCKOUT ENTRIES REAR CABLE ENTRIES 2 SNAP OUTS, 60 x 20mm
Fuse Ratings
FUSE NO DESCRIPTION RATING FS1 Charger Fuse 1.6A time delay 5 x 20mm glass FS2 Battery Fuse 1.6A time delay 5 x 20mm glass FS3 EN54 SUPPLY (NOT USED) 1.6A time delay 5 x 20mm glass FS4 Sounder circuit 1 400mA time delay 5 x 20mm glass FS5 Sounder circuit 2 400mA time delay 5 x 20mm glass INLET FUSE Mains Protection Fuse 2A Quick Blow HBC 5 x 20mm ceramic
Approved Document No: GLT.MAN-118 PAGE 19 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 20
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
Log Book
MAINTENANCE WORK
DATE TIME ZONE / LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED
Approved Document No: GLT.MAN-118 PAGE 20 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 21
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
FALSE ALARMS
DATE TIME ZONE /
LOCATION
CAUSE (IF KNOWN) OR ACTIVITIES IN ALARM AREA
MAINTENANCE
VISIT NEEDED
(YES/NO)
MAINTENANCE
FINDINGS
CATEGORY OF FALSE ALARM
FURTHER ACTION REQUIRED
SIGNED
Approved Document No: GLT.MAN-118 PAGE 21 Issue : 1 Author: NRPJ Date: 15/11/2006
Page 22
INSTRUCTION MANUAL– 4 to 8 ZONE FIRE ALARM PANEL
ALL OTHER EVENTS
DATE TIME ZONE / LOCATION DETAILS OF EVENT
(INCLUDING CAUSE IF KNOWN)
ACTION
REQUIRED
DATE
COMPLETED
INITIALS
Approved Document No: GLT.MAN-118 PAGE 22 Issue : 1 Author: NRPJ Date: 15/11/2006
Loading...