Zooper MX-32 User Manual

Written by: JBJ Checked by: RP Approved by JBJ
GLT Exports Limited
Premier MX
Fire Detection/Alarm Panel and
Premier MX
Repeater
1. List Of Contents
1. List Of Contents ........................................................................................................1
2. Premier MX
2.1. If a fire is detected:............................................................................................. 3
2.2. To Silence the fire alarm sounders:.................................................................... 3
2.3. To Resound the fire alarm sounders after they have been silenced: .................. 3
2.4. To Reset the panel from a Fire Alarm:............................................................... 3
2.5. To operate the fire alarm sounders in Evacuate Mode:...................................... 4
2.6. If a fault is detected:........................................................................................... 4
2.7. To Silence the Buzzer: ....................................................................................... 4
3. Premier MX User Indications.................................................................................... 5
3.1. User Indications [showing optional Clock Module] .......................................... 5
3.2. User Controls - [showing optional Clock Module]............................................ 6
4. Premier MX User Controls – Disablement and Test Conditions. ............................. 7
4.1. To Disable/Enable any Zone or Zones............................................................... 7
4.2. To Disable/Enable all Sounders......................................................................... 7
4.3. To Disable/Enable the Fire Routing Output....................................................... 8
4.4. To Disable/Enable the Fault Routing Output..................................................... 8
4.5. To Disable/Enable Fire Protection Output[s]..................................................... 9
4.6. To Select/Clear One Man Zone Test................................................................ 10
4.7. To Select/Clear One Man Sounder Test........................................................... 10
4.8. To Enable/Disable Delay Mode....................................................................... 11
4.9. To Override the Delay Mode ...........................................................................12
4.10. To Extend the Delay [from 1
4.11. Silencing the Alarms During the Delay: .......................................................... 12
4.12. Resounding the Alarms after the Delay: [Alarms previously silenced]........... 12
User Operation - Fire and Fault Conditions .........................................3
st
stage to 2nd Stage] ...........................................12
5. User Operating Instructions for Optional Clock Module........................................ 12
5.1. To Display Alarm Event Count: ......................................................................12
5.2. To access the User Clock Module Edit Functions ........................................... 13
6. Premier MX
6.1. If a fire is detected:........................................................................................... 15
6.2. To Silence the fire alarm sounders:.................................................................. 15
6.3. To Resound the fire alarm sounders after they have been silenced: ................ 15
6.4. To Reset the panel & repeater(s) from a Fire Alarm: ......................................15
6.5. To operate the fire alarm sounders in Evacuate Mode:.................................... 16
6.6. If a fault is detected:......................................................................................... 16
6.7. To Silence the Buzzer: ..................................................................................... 16
Premier MX Repeater Panel Operation [16 zone version shown] ............................... 17
Document Number: Premier MX User 1.doc Page 1 of 19 14/12/06
Repeater Panel User Operation - Fire and Fault Conditions.............. 15
1
Written by:.JBJ Checked by: RP
7. Premier MX Repeater Panel User Controls [16 zone panel shown] ....................... 18
8. Routine Testing and maintenance ........................................................................... 18
9. User responsibilities ................................................................................................ 18
10. Premier MX Isolate/De-isolate/Test Mode Select Flowchart............................ 19
Danger
This equipment contains hazardous voltages that can cause death, serious personal injury, or equipment damage. This equipment contains no user serviceable parts. Refer all maintenance to suitably qualified personnel.
Document Number: Premier MX User 1.doc Page 2 of 19 14/12/06
Written by:.JBJ Checked by: RP
2. Premier MX User Operation - Fire and Fault Conditions
2.1. If a fire is detected:
On the Premier MX
Fire Alarm Panel:
o The general Fire LED will flash and the buzzer will sound o The relevant zone Fire LED will flash, indicating the location of the
fire.
o If the Delay is OFF [Delay LED off]:
The Fire Routing output and LED will operate immediately The Fire Alarm sounders will operate immediately The Fire Protection output will operate immediately
o If the Delay is ON [Delay LED flashing]:
The Fire Routing output and LED will operate after a delay [if
the Fire Routing fault/disabled LED is illuminated].
The Fire Alarm sounders will operate after a delay [if Sounder
fault/disabled LED is illuminated].
The Fire Protection output will operate after a delay [if Fire
Protection fault/disabled LED is illuminated].
Locate the source of the fire alarm (an LED will be visible on the detector
which has been activated).
2.2. To Silence the fire alarm sounders:
Turn the Access Controls Keyswitch on the panel door to position “1”.
Press the Silence Alarms/Resound button once only.
The fire alarm sounders will become silent.
The General Fire LED and the Zone Fire LED will become steady.
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
2.3. To Resound the fire alarm sounders after they have been silenced:
Turn the Access Controls Keyswitch on the panel door to position “1”.
Press the Silence Alarms/Resound button once only.
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
2.4. To Reset the panel from a Fire Alarm:
After the fire has been extinguished, turn the Access Controls Keyswitch
on the panel door to position “1”.
Press the Reset button.
The General Fire LED and the Zone Fire LED will clear.
Document Number: Premier MX User 1.doc Page 3 of 19 14/12/06
Written by:.JBJ Checked by: RP
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
2.5. To operate the fire alarm sounders in Evacuate Mode:
Turn the Access Controls Keyswitch on the panel door to position “1”.
Press the Evacuate button.
The Evacuate LED will light and the panel buzzer will operate.
All fire alarm sounders will operate.
Press the Silence/Resound Alarm button to silence the fire alarm sounders
and clear the Evacuate LED.
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
2.6. If a fault is detected:
The panel buzzer will sound.
The General Fault LED will flash.
One or more fault LEDs will flash; identifying which element of the
system is faulty.
When the fault is corrected the fault indication will clear automatically
unless the panel is configured to latched fault mode – in which case, operating the Reset button will clear the fault indication.
2.7. To Silence the Buzzer:
Press the Silence Buzzer button.
The Silence Buzzer button LED will light.
The buzzer will silence.
Document Number: Premier MX User 1.doc Page 4 of 19 14/12/06
Written by:.JBJ Checked by: RP
3. Premier MX User Indications
This section gives an overview of the functions available to the end user.
3.1. User Indications [showing optional Clock Module]
General Indicator Section
Indicator Description
Power Supply On Green Illuminates Steady for Mains or Standby power On.
Fire Red Flashes on any new fire alarm condition, changing to a steady indication on
Fire Routing Active Red Illuminates Steady when the Fire Routing Output is active.
General Fault Yellow Flashes for any fault condition.
Power Supply Fault Yellow Flashes for mains or standby power supply/charge fault
System Fault Yellow Illuminates Steady to indicate Microcontroller or Memory Failure.
Earth Fault Yellow Flashes for any positive or negative power supply earth fault.
Fuse Fault Yellow Flashes for any auxiliary supply fuse failure
Repeater Fault Yellow Flashes for any Repeater fault or repeater communication fault,
Sounder Fault/Disabled Yellow Flashes for any sounder fault. Steady for sounders disabled.
Sounder Test Yellow Illuminates Steady while sounder walk test is active.
Fire Protection Fault/Disabled Yellow Flashes for a fault on the Fire Protection Output. Steady when Fire
Fire Routing Fault/Disabled Yellow Flashes for a fault on the Fire Routing Output. Steady when Fire Routing
Fault Routing Fault/Disabled Yellow Flashes for a fault on the Fault Routing Output. Steady when Fault Routing
Indication
Colour
Operating Condition
operation of Silence Alarms.
Flashes to indicate Engineer’s Configuration Mode active.
Protection Output is disabled.
Output is disabled.
Output is disabled.
Access Controls Keyswitch:
0 – Controls Locked 1 – Controls Unlocked
Indicator Description
User Generated Zone Location Text Red Flashes when zone is in a fire condition, turning to steady on
User Generated Zone Location Text Yellow Flashes when zone is in a fault condition. Illuminates steady when
POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SUPPLY FAULT SYSTEM FAULT EARTH FAULT FUSE FAILED REPEATER FAULT SOUNDER FAULT/DISABLED SOUNDER TEST FIRE PROTECTION FAULT/DISABLED FIRE ROUTING FAULT/DISABLED FAULT ROUTING FAULT/DISABLED
01
EVACUATE
TEST DISPLAY
SILENCE/ RESOUND ALARMS
RESET
SILENCE BUZZER
DELAY ON/OFF/ OVERRIDE
SELECT ON/OFF
ENABLE
DISABLE
SELECT
21: 18: 05 D/N OFF
Clock Module [Optional]:
Showing time and Day/Night off Back light flashes for Clock Module fault.
Zone Location Indications
Indication
Colour
TEST
FIRE
1. THE RED ZONE INDI CATOR WILL PULSE SHOWING THE LOCATION OF THE FIRE.
2. CARRY OUT THE REQUIRED FIRE DRILL.
3. TO SILENCE ALARMS PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE CONDITION PRESS RESET.
ZONE LOCATION ZONE LOCATION
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
FAULT
1. DETERMINE THE CAUSE OF THE FAULT.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE ENGINEER. SYSTEM FAULT THE PANEL IS INOPERATIVE. ARRANGE FOR ALTERNATIVE FIRE DETECTION MEASURES.
DISABLEMENT AND TEST
1. PRESS SELECT ON/OFF. THE LED WILL ILLUMINATE.
2. SELECT THE ZONE OR
AND . THE
OUTPUT USING FAULT LED WILL PULSE.
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT THE ZONE OR OUTPUT AND PRESS ENABLE.
User Instructions
Operating Condition
operation of Silence Alarms.
zone is disabled or in test.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
MODEL: PRECEPT EN 32 EN54-2: 1997, EN54-4: 1997 C.I.E. PRODUCTION PERIOD: 1
Certificate Number 018c/06
C.E.L. No 1800456 - 32 ZONE
Document Number: Premier MX User 1.doc Page 5 of 19 14/12/06
Written by:.JBJ Checked by: RP
3.2. User Controls - [showing optional Clock Module]
POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SUPPLY FAULT SYSTEM FAULT EARTH FAULT FUSE FAILED REPEATER FAULT SOUNDER FAULT/DISABLED SOUNDER TEST FIRE PROTECTION FAULT/DISABLED FIRE ROUTING FAULT/DISABLED FAULT ROUTING FAULT/DISABLED
01
21: 18: 05 D/N OFF
EVACUATE
SILENCE/ RESOUND ALARMS
RESET
SILENCE BUZZER
DELAY ON/OFF/ OVERRIDE
SELECT ON/OFF
TEST DISPLAY
ENABLE
DISABLE
TEST
SELECT
FIRE
1. THE RED ZONE INDI CATOR WILL PULSE SHOWING THE LOCATION OF THE FIRE.
2. CARRY OUT THE REQUIRED FIRE DRILL.
3. TO SILENCE ALARMS PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE CONDITION PRESS RESET.
ZONE LOCATION ZONE LOCATION
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
FAULT
1. DETERMINE THE CAUSE OF THE FAULT.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE ENGINEER. SYSTEM FAULT THE PANEL IS INOPERATIVE. ARRANGE FOR ALTERNATIVE FIRE DETECTION MEASURES.
DISABLEMENT AND TEST
1. PRESS SELECT ON/OFF. THE LED WILL ILLUMINATE.
2. SELECT THE ZONE OR OUTPUT USING FAULT LED WILL PULSE.
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT THE ZONE OR OUTPUT AND PRESS ENABLE.
AND . THE
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
C.E.L. No 1800456 - 32 ZONE
MODEL: PRECEPT EN 32 EN54-2: 1997, EN54-4: 1997 C.I.E. PRODUCTION PERIOD: 1
Certificate Number 018c/06
Access Controls Keyswitch:
0 – Controls Locked 1 – Controls Unlocked
Switch Description
Evacuate Operates all sounders continuously and lights the Evacuated LED adjacent the
button until the silence button is operated
Silence/Resound Alarms
Following a fire alarm condition, 1st operation stops sounders. The General Fire LED and the Zonal fire LED will change from flashing to steady. 2nd operation restarts the previously silenced sounders
Reset Clears the panel display, resets the zones, outputs and operates the reset relay. When controls are unlocked
1] Press to stop the buzzer sounding in fire or fault conditions. When controls are locked or unlocked Silence Buzzer
2] In 2 Stage Delay Mode, with stage 1 delay running, press to start stage 2 delay otherwise all delayed outputs operate when Stage 1 timer times out.
Delay On/Off/Override
1] Press once to Enable the delay mode, lighting the adjacent delay on LED. Press again to disable the delay mode and turn off the LED
2] Overrides the delay when delay is running, turning the delay mode and the LED off. All delayed outputs will operate immediately.
Select On/Off Enables the User select feature [ Select Select ] for selection of zones or
outputs for disablement/re-enablement also Day/Night On/Off selection and setting current time on Clock Module when fitted.
Test Display Press to illuminate all LEDs on the display and operate the buzzer. All
indications remain active for approx 5 seconds after button release. Also displays alarm count on Clock Module [when fitted]
Enable Press to clear the disablement or test condition on a zone or output selected via
the User Select feature.
Disable Press to disable a zone or output selected via the User Select feature. As above. Test Press to initiate the One Man Test on sounders or zones as selected via the User
Select feature.
Select Select Used to scroll the cursor indication through the zone and output fault LEDs on
the display to select a zone or output for disablement, or test. [LED illuminated when Select Mode is active]. Also scrolls through Clock Module menu [when fitted].
Functionality Button Availability
When controls are unlocked
When controls are unlocked
and [if silence before reset is configured] alarms silence switch has been operated.
When the panel is in the fire condition and the delay is running. Controls are locked or unlocked 1] When controls are unlocked and delay period is set to a value > 0.
2] When the panel is in the fire condition and the delay is running.
When controls are unlocked
When controls are locked or unlocked
When controls are unlocked, the Select switch has been operated and a zone or output has been selected.
As above.
When controls are unlocked and the Select switch has been operated.
Document Number: Premier MX User 1.doc Page 6 of 19 14/12/06