Zonex Systems DigiTract 4-2 User Manual

Installation Guide
DigiTract 4-2
Two Stage Heat/Cool
Comfort Control System
Part #DT4MAN
Rev. April 2003
Zoning Systems
That’s all we do.
INTRODUCTION.......................................................................................................................................................................................................1
SYSTEM DESCRIPTION...........................................................................................................................................................................................1
COMPONENT SELECTION GUIDE..........................................................................................................................................................................2
WIRING
Gas/Electric DTGE4-2.........................................................................................................................................................................................3
Heat Pump DTHP4-2..........................................................................................................................................................................................4
Zone Dampers....................................................................................................................................................................................................5
SYSTEM CONTROLLERS
Gas/Electric DTGE4-2
Operation...........................................................................................................................................................................................6
Status Lights .......................................................................................................................................................................................6
Components.......................................................................................................................................................................................7
Heat Pump DTHP4-2
Operation...........................................................................................................................................................................................8
Status Lights .......................................................................................................................................................................................9
Components.....................................................................................................................................................................................10
CAPACITY CONTROLLERS.....................................................................................................................................................................................11
Gas/Electric DTGE4-2.......................................................................................................................................................................11
Heat Pump DTHP4-2........................................................................................................................................................................11
Calibration .......................................................................................................................................................................................11
LAS Installation ................................................................................................................................................................................11
ZONE THERMOSTATS
Types ........................................................................................................................................................................................................12
Zonex Systems Gas/Electric Models..................................................................................................................................................................12
Digital (SADIGI)...............................................................................................................................................................................12
Digital (SADIGI) Operation..............................................................................................................................................................13
Programmable (101PROG)..............................................................................................................................................................12
Communicating (DIGICOM/DIGIHP)................................................................................................................................................12
Compatibility ....................................................................................................................................................................................................12
ZONE DAMPERS
Round ...................................................................................................................................................................................................14-15
Rectangular.................................................................................................................................................................................................16-17
Installation Notes..............................................................................................................................................................................................18
BYPASS DAMPERS
Barometric..................................................................................................................................................................................................18-19
Electronic ...................................................................................................................................................................................................20-21
Static Pressure Controller.................................................................................................................................................................22
DAMPER TRANSFORMER .....................................................................................................................................................................................23
SYSTEM STARTUP
Gas/Electric DTGE4-2.......................................................................................................................................................................................23
Heat Pump DTHP4-2........................................................................................................................................................................................24
Troubleshooting / Service Checks.....................................................................................................................................................................25
LAS Voltage – Temperature Conversion Chart..................................................................................................................................................25
Fused 24V Transformer
DIGITRACT 4-2
System Controller
73
73
73
73
5
2
3
1
4
6
ZONE 4
ZONE 3
ZONE 2
ZONE 1
LAS
INTRODUCTION
System Controller
Leaving Air Sensor
Zone Damper
Zone Thermostat
Bypass Damper Damper
Transformer
1
2
3
4
5
6
The Zonex Systems Digitract 4-2 zoning system enables up to four room thermostats to control a single HVAC system. This permits superior building temperature control over a standard single thermostat. To provide economical, effective and simplified remote control and monitoring capability of one or more Digitract 4-2 zone control systems, the ZonexCommander may be used to manage up to 80 thermostat schedules. The ZonexCommander is a Windows®based thermal management system, which can integrate gas/electric and heat pump zone systems to include stand alone HVAC systems.
SYSTEM DESCRIPTION
The DigiTract 4-2 zoning system consists of a 2-stage System Controller with built-in Capacity Control (leaving air sensor), Zone Dampers, Zone Thermostats, Bypass Damper and Damper Transformer.
The System Controller is the heart of the Digitract 4-2 zoning system. It monitors the leaving air temperature, zone thermostats and controls the HVAC System and zone dampers. See pages 6 to 10 for further information.
The Leaving Air Sensor (LAS) is part of the staging and capacity control feature of the System Controller. It is a sensor placed in the leaving air of the HVAC system. The LAS monitors the leaving air temperature of the HVAC system and sends this information to the System Controller. The System Controller uses this information to stage and temporarily cycle the HVAC system off if the leaving air gets too hot in heat mode or too cold in cool mode. For heat pumps, this information is also used to control the auxiliary heat to maintain a minimum supply air temperature of 88 degrees. See Capacity Controller section, page 11, for further information.
The Zone Dampers are air valves placed in the forced air duct work for each zone. They are controlled by the System Controller. While the HVAC system is running, the zone dampers for any zone thermostats not calling will close and zone dampers for the zones calling will remain open. Conditioned air is only directed to the zones needing it. See pages 14 to 18 for further information.
The Zone Thermostats monitor the room temperature of each zone and compare it to the heat and cool setpoints stored in them. If the room temperature drops below the heat setpoint, the zone thermostat makes a heat call telling the System Controller that zone needs heating. If the room temperature rises above the cool setpoint, that thermostat makes a cool call telling the System Controller that zone needs cooling. Two-stage thermostats are not required with the DigiTract 4-2 System. The System Controller will cycle staging and auxiliary strip heat based on leaving air temperature. See pages12 to 13 for further information.
The Bypass Damper is a pressure relief valve placed between the supply and return ducts of the forced air duct work. As zone dampers start closing, the bypass damper will open and divert some of the supply air to the return. This prevents a pressure buildup in the supply duct which can cause fan cavitation, excessive air velocities, and excessive zone damper blow-by. See pages 18 to 22 for further information.
Damper Transformer. Wired to TR1 and TR2 on the System Controller. Powers the zone dampers only. Requires an in-line fuse. See Damper Transformer section, page 23.
1
Digitract 4-2 COMPONENT SELECTION GUIDE
START
SYSTEM CONTROLLER
(DTGE4-2)
2-Stage Heat/Cool
CAPACITY CONTROLLER
System Controller includes Capacity Control
and Leaving Air Sensor
GAS/ELECTRIC THERMOSTATS
DIGITAL
(SADIGI)
5 TONS AND UNDER
(Up to 0.5 S.P.)
Round (TR diam)
Rectangular (TREC W x H)
GAS/ELECTRIC
PROGRAMMABLE
(101PROG)
COMMUNICATING
(DIGICOM)
ZONE DAMPERS
(Up to 1 S.P.)
Rectangular
(101MRTD W x H)
HEAT PUMP
SYSTEM CONTROLLER
(DTHP4-2)
3-Stage Heat/2-Stage Cool
CAPACITY CONTROLLER
System Controller includes Capacity Control
and Leaving Air Sensor
HEAT PUMP THERMOSTATS
(One per zone. Field Supplied.
See Thermostat Compatibility section, pg. 12)
COMMUNICATING
(DIGIHP)
COMMAND CENTER
(101CEC Communication Package,
one per 20 thermostats)
OVER 5 TONS
(Up to 1.75 S.P.)
Round (101AMPD diam)
Rectangular (101CD W x H)
5 TONS AND UNDER
BAROMETRIC BYPASS
Round (101ABBD diam)
Rectangular (RBB W x H)
BYPASS DAMPERS
OVER 5 TONS
ELECTRONIC BYPASS
Round (STMPD diam)
Rectangular (STCD W x H)
STATIC PRESSURE CONTROLLER
(101ASPC)
BYPASS TRANSFORMER
(FIELD SUPPLIED. 24VAC, 40VA)
DAMPER TRANSFORMER
(Field supplied. Requires in line fuse.
See Transformer/Fuse Sizing Table, pg. 23)
COMPLETE SYSTEM
2
Y1 G W1
PWR
DPR1 DPR2 DPR3 DPR4
ON
-
R C
Y1
+
1
2 3 3 4
4 TR1 TR2
2
1
DIGITRACT 4-2 GE TWO STAGE 220108
AB
JPR1
Vx.x
R72
Y2
R8 R10 R9 R5
W
2
G
W1
Y2
Y2 W1
G W2 Y1
R
C
ZONE 1 THERMOSTAT
ZONE 3 THERMOSTAT
-
+
STAT 1
W R Y G C
STAT 2
W R Y G C
STAT 3
W R Y G C
W R Y G C
STAT 4
W R Y G C
W R Y G C
W2
AIR FLOW
BYPASS
TAP
BYPASS RETURN
WIRING – GAS/ELECTRIC DTGE4-2
DigiTract 4-2 Gas/Electric 2-Stage Heat/Cool
HVAC unit and LAS terminals. Do not connect Y2 or W2 for single stage heat/cool systems.
Use minimum 18 gauge for all wiring. All wiring must meet state and local codes.
Zone damper terminals. Refer to Wiring – Zone Dampers section, pg. 5.
1
2
6
4
1
2
3
4
3
1. LAS. Locate the leaving air sensor in the supply air stream, as far from the coil/heat exchanger as possible before the bypass takeoff. Do not locate the LAS downstream of the bypass takeoff. Ensure wire polarity is correct. Refer to "CAPACITY CONTROLLER- LAS INSTALLATION" on P. 11 for further information. NOTE: Shielded conductor provided for installations with spark ignition or distances from controller to LAS beyond 10. 18/2 thermostat wire may be used in most applications.
2. Connect W2 and Y2 of the DTGE4-2 only if there are two heat and/or two cool stages.
3. Connect C from the controller to the thermostat 24V AC common terminal if hard wired. Not required with use of battery operated thermostats. Refer to "THERMOSTATS- COMPATIBILITY" on P. 12 for further information.
4. Zone damper terminals. Refer to "WIRING- ZONE DAMPERS" on P. 5.
5
5. Install one 24V AC transformer, sized and fused for the total number of zone dampers. See "DAMPER
5
TRANSFORMER" on P. 23.
6. Fan cycling jumper: A – FAU fan control; B – electric heat, fan on with heat call
6
3
Y1 G W2
PWR
DPR1 DPR2 DPR3 DPR4
ON
-
R E L C
O/B
+
1
2 3 3 4
4 TR1 TR2
2
1
DIGITRACT 4-2 HP TWO STAGE 210806
BO
JPR1
Vx.x
R72
O/B
R
Y
G
C
STAT 4
O/B
R
YG
C
STAT 3
O/B
R
Y
G
C
STAT 2
STAT 1
O/B
RYGC
E
L
Y2
O/B
R8
R10
R9 R5
Y2
Y1
G
W2
W
G
Y1
Y2
O/B
R E
C
+
-
AIR FLOW
O/B
RYG CW L
ZONE 1
THERMOSTAT
O/B R Y G C
ZONE 3
THERMOSTAT
1
2
3
4
7
5
6
BYPASS
TAP
BYPASS RETURN
WIRING – HEAT PUMP DTHP4-2
DigiTract 4-2 HP 3-Stage Heat/2-Stage Cool
LAS. Locate the leaving air sensor between the refrigerant coil and the electric heat coil(s) or other auxiliary
1
heat source. Verify that the polarity is correct. Refer to CAPACITY CONTROLLER – LAS INSTALLATION page 11, for further information.
Connect W2 from the controller to the units electric heat stage terminal designation. It is recommended to
2
install an outdoor thermostat in series with any electric heat stages.
Connect C from the controller to the thermostat 24V AC common terminal if hardwired. Refer to ZONE
3
THERMOSTATS – COMPATIBILITY page 12, for further information.
Zone damper terminals. Refer to WIRING – ZONE DAMPERS on page 5.
4
Install one 24V AC transformer, sized and fused for the total number of zone dampers. See DAMPER
5
TRANSFORMER on page 23.
Emergency heat terminal, E. Use only if emergency heat source is different from auxiliary heat W2. If used,
6
do not jumper to W2.
Reversing valve jumper: B – energize for heat; O – energize for cool
7
NOTE: Some combination thermostats do not have an E terminal. Connect W2 of the thermostat to the E ter­minal of STAT 1 terminal block.
4
WIRING – ZONE DAMPERS
FUSED 24VAC XFMR. Transformer and fuse must be sized for
total
number of zone dampers. See Transformer/Fuse Sizing Table on page 23.
TR
SERIES
DAMPER
M M
1
2 3 3 4
4 TR1 TR2
2
1
DIGITRACT 4-2 SYSTEM CONTROLLER
TO TWO MORE TR SERIES DAMPERS IF APPLICABLE
DMPR1DMPR
2
M M M M
DMPR
3
M M
DMPR
4
M M
1
2 3 3 4
4 TR1 TR2
2
1
TO ADDITIONAL TR SERIES DAMPERS IF APPLICABLE
FUSED 24VAC XFMR. Transformer and fuse must be sized for
total number of zone dampers. See Transformer/Fuse Sizing Table on page 23.
DIGITRACT 4-2 SYSTEM CONTROLLER
24VAC
relay
1
2 3 3 4
4 TR1 TR2
2
1
DIGITRACT 4-2 SYSTEM CONTROLLER
N/C - No connection
*
- Factory wired motor 101 series dampers include:
101AMPD, 101MRTD & 101CD
DAMPER RELAY BOARD
RC MCRCWWY RO
TB2
TB1
N/C N/CN/C
N/C N/C N/CN/CN/C
***
101 SERIES DAMPER
TO ADDITIONAL 101 SERIES DAMPERS IF APPLICABLE
FUSED 24VAC XFMR. Transformer and fuse must be sized for
total number of zone dampers. See Transformer/Fuse Sizing Table on page 23.
GRdBWWY
B must wire to bottom terminal and Rd must wire to top terminal. Do not reverse.
{
{
G must wire to TR2. Do not wire to TR1.
There are three methods of wiring the zone dampers. If necessary, you can mix wiring methods on different zones to suit your application.
Method 1: If wiring two or three TR series dampers to a zone, wire per
Method 3: If using 101 series dampers with a DTGE4 controller, wire
per method 3. Notice: 101 series dampers are required for all systems over 5 tons. Refer to Parts Selection Table, page 14.
method 1. Method 2: If wiring more than three TR series dampers to a zone, use method 2. This method requires a 24V ac, SPNO relay.
Method 1: Wiring Up to Three TR Series Dampers to a Zone
Method 2: Wiring More than Three TR Series Dampers to a Zone
Method 3: Wiring 101 Series Medium/Heavy Duty Dampers to a Zone
5
SYSTEM CONTROLLERS
The DigiTract 4-2 System Controller is the heart of the Digitract 4-2 zoning system. It is an auto changeover, home run system with a built in staging and capacity controller. The function of the System Controller is to receive calls from the zone thermostats, operate the HVAC system in either heat or cool mode, and close the zone damper(s) of the zones not calling for the operating mode. The mode of operation is determined by the first call received. If thermostats are calling for opposite modes, every 15 minutes it will change over to the other mode as long as there
SYSTEM CONTROLLER – GAS/ELECTRIC DTGE4-2
OPERATION
The System Controller will initially run in the mode requested by the first calling zone thermostat.
Cool mode – When running in the cool mode, the System Controller
energizes the compressor(s) and indoor blower. This is indicated by the corresponding Y and G LEDs illuminating. Dampers for the zones not calling for cool are powered closed and the dampers for the zones calling for cool are left open. This is indicated by the DPR LEDs. If the DPR LED is illuminated on the damper terminal strip and damper terminal board, the corresponding damper is closed. The system will continue to run in the cool mode until all calls are satisfied or changeover occurs. When all calls are satisfied or prior to changeover, the system will go into a purge mode.
Heat mode – When running in the heat mode, the System Controller
energizes the heat stage(s), indicated by the W LEDs illuminating. If the Fan Control Jumper is in the B position, the indoor blower will energize with heat, indicated by the G LED illuminating. Dampers for the zones not calling for heat are powered closed and the dampers for the zones calling for heat are left open. This is indicated by the DPR LEDs. If the DPR LED is on the damper terminal strip and damper terminal board, the corre­sponding damper is closed. The system will continue to run in the heat mode until all calls are satisfied or changeover occurs. When all calls are satisfied or prior to changeover, the system will go into a purge mode.
are opposing calls. The built in Capacity Controller maintains the supply air temperature within an operating range to prevent freeze ups and overheating. For heat pumps, the DTHP4 System Controller will also control the auxiliary heat to maintain an 88 degrees minimum coil leaving air temperature.
The DigiTract 4-2 is available in two models, Gas/Electric 2-Stage Heat/Cool and Heat Pump 3-Stage Heat/2-Stage Cool.
Changeover – While the system is operating in one mode, and the
System Controller receives a call for the opposite mode, the System Controller will continue to run in the current mode for 15 minutes or until all current calls are satisfied. Then the System Controller will go into a purge mode for 3 minutes, then change over to the new mode.
Purge mode – When all calls are satisfied or before changing
modes, the System Controller will go into a three minute purge cycle. During this mode, the compressor or heat will turn off and the indoor blower fan will continue to run. This is indicated by the W and Y LEDs off and the G LED on. The damper(s) of the last calling zones will remain open and all other damper(s) will be closed. This allows the supply air to adjust to room temperature before changeover or ventila­tion while providing a time delay to prevent short cycling. The DPR LEDs indicate which dampers are open and which are closed. If the DPR LED is on, the damper is closed. If the DPR LED is off, the damper is open.
Ventilation – When no zones are calling, all zone dampers are open.
During this time, if any thermostat has the fan switch ON then the indoor blower is energized (G made to R) and the G LED is on. This provides ventilation to all zones.
STATUS LEDS
Y1 Y2 G W1 W2 PWR DPR MODE FUNCTION
OFF OFF OFF OFF OFF OFF OFF Off Power off. OFF OFF OFF OFF OFF ON OFF On Power on, blower off, all zones satisfied. OFF OFF ON ON OFF ON 0 Vent Blower on, compressor(s) off, all zone dampers open. OFF OFF ON OFF OFF ON 1 Purge Blower on, compressor(s) off. Dampers with LED on are closed.
ON OFF ON OFF OFF ON 1 Y1 cool 1st stage cool, blower on. Dampers with LED on are closed.
ON ON ON OFF OFF ON 1 Y2 cool 2nd stage cool, blower on. Dampers with LED on are closed. OFF OFF A / B ON OFF ON 1 W1 heat 1st stage heat, blower on. Dampers with LED on are closed. OFF ON A/ B ON ON ON 1 W2 heat 2nd stage heat, blower on. Dampers with LED on are closed. OFF OFF ON OFF OFF FL 1 Cap cut out Blower on, all compressors off. Dampers with LED on are closed.
FL = Flashing A = On when JMPR1 is in Aposition B = OFF when JMPR1 is in B position 1 = One or more damper LED’s on 0 = All damper LED’s are off
6
SYSTEM CONTROLLER – GAS/ELECTRIC DTGE4-2
COMPONENTS
A. HVAC Unit/LAS Terminals – Connects to HVAC unit and
Leaving Air Sensor (LAS). ±: LAS terminals. The LAS monitors the leaving air
temperature.
W1: First stage heat. When energized (W1 made to R),
energizes first-stage heat.
W2: Second stage heat. When energized (W2 made to R),
energizes second-stage heat.
G: Blower. When energized (G made to R),
energizes the indoor blower.
Y1: First stage cool. When energized (Y1 made to R),
energizes first stage cooling.
Y2: Second stage cool. When energized (Y2 made to R),
energizes second stage cooling.
R: HVAC unit 24V power. Powers the DigiTract 4-2 board
and zone thermostats.
C: HVAC unit 24V power return.
B. Thermostat Terminals – Connects up to four zone
thermostats. W: Heat call. When energized (W made to R),
requests the Digitract 4-2 to run in heat mode. R: HVAC unit 24V power. Y: Cool call. When energized (Y made to R),
requests the Digitract 4-2 to run in cool mode. G: Blower Fan- When energized (G made to R), requests the
DigiTract 4 to turn on the indoor blower fan. C: HVAC unit 24V power return.
C. Damper Terminals – Connects dampers for up to four zones and
damper power supply. TR1/ TR2: 24V AC transformer terminals. This transformer powers only
the zone dampers.
1 1: Zone damper 1.
When energized, powers zone damper 1 closed.
2 2: Zone damper 2.
When energized, powers zone damper 2 closed.
3 3: Zone damper 3.
When energized, powers zone damper 3 closed.
4 4: Zone damper 4.
When energized, powers zone damper 4 closed.
D. Damper Status LEDs – On when corresponding zone damper is
being powered closed.
E. Board Number – This number indicates the circuit board number
and revision. May need to know this number if conferring with technical support.
F. Heat Mode Fan Control Selection Jumper – In the A position,
the blower is energized by the furnace when heat is energized (gas furnaces). In the B position, the blower is energized by the DTGE4-2 when heat is energized (electric furnaces).
+
Y2 W1
G
W2
Y1 R C
DIGITRACT 4-2 GE TWO STAGE 220108
E F
R8
R72
I
R10 R9 R5
W R Y G C
PWR
H
STAT 2
J
ON
-
Y1 G W1
A
STAT 1
W R Y G C
ZONE 1 THERMOSTAT
Vx.x
DPR1 DPR2 DPR3 DPR4
Y2
W2
STAT 3
B
W R Y G C
W R Y G CW R Y G C
ZONE 3 THERMOSTAT
JPR1
G
D
STAT 4
W R Y G C
G. Microcontroller – Responsible for activation and control of the
unit based upon thermostat input. Occasionally software upgrades may become available. If so, the Digitract 4-2 software can be field upgraded by changing this microcontroller.
H. HVAC System Status LEDs – Indicates what the DTGE4-2 is
energizing on the HVAC system. Y1: Compressor, yellow. On when the first-stage cool is energized. Y2: Compressor, yellow. On when the second-stage cool is energized. G: Blower, green. On when the indoor blower is energized. W1: Heat, red. On when first stage heat is energized. W2: Heat, red. On when second stage heat is energized. PWR: Power, orange. On when power at R and C and the Power
Switch is on. Flashing when in Capacity Control cut out mode.
See Status Lights section, page 6, for further information.
I. Leaving Air Sensor Potentiometer – Turn to calibrate the
leaving air sensor if required. See Calibration in Capacity Controller section.
J. Power Switch – When OFF, power from the HVAC unit transformer is
disconnected from the Digitract 4-2 and thermostats. When ON, power from the HVAC unit transformer is supplied to the Digitract 4-2 and the zone thermostats.
AB
C
TR1 TR2
1 1
2 2 3 3 4 4
7
Loading...
+ 19 hidden pages