Zonex ZonexCommander, ZonexCommander Plus Installation Manual

Page 1
Installation and Applications Manual
Part #ZCMAN
ZonexCommander
ZonexCommander
(Plus)
Network All Your HVAC Equipment
for Stand-Alone HVAC and Zoned Systems
Rev. Oct 2014
1
Page 2
Table of Contents Page
Commander System Overview.....................................................................................................................................................................................3
System Selection Criteria.............................................................................................................................................................................................3
ZONEXCOMMANDER
ZONEXCOMMANDER (PLUS)
Unit Relay Module (RMOD)
OPTIONAL COMPONENTS
ZONE DAMPERS
Component Descriptions.........................................................................................................................................................................................4-5
Concept Drawing................................................................................................................................................................................................6
Component Selection Guide................................................................................................................................................................................7
Sequence Of Operation.......................................................................................................................................................................................8
Installation Instructions......................................................................................................................................................................................9
DIGICOM / DIGIHP Thermostats ................................................................................................................................................................10-11
Command Center – ZonexCommander.............................................................................................................................................................12
Wiring Overview ..............................................................................................................................................................................................13
Concept Drawing .............................................................................................................................................................................................14
Component Selection Guide..............................................................................................................................................................................15
Wiring Overview ..............................................................................................................................................................................................16
Sequence Of Operation ...............................................................................................................................................................................17-18
Command Center – ZonexCommander (Plus) .................................................................................................................................................19
Installation Instructions....................................................................................................................................................................................20
ModStat Thermostat and Supplemental Heat Applications............................................................................................................................21-22
Sequence Of Operation.............................................................................................................................................................................23
RMOD Terminal Diagram ........................................................................................................................................................................24
Description / Installation..........................................................................................................................................................................25
Wiring Overview – RMOD ........................................................................................................................................................................26
RMOD To Unit Wiring Diagram.................................................................................................................................................................27
SENDCOM – Communicating Duct Temperature Sensor .............................................................................................................................28-29
Communicating Relay Module (RLYCOM).........................................................................................................................................................30
Round Dampers ...............................................................................................................................................................................................31
Rectangular Dampers..................................................................................................................................................................................32-33
D-Fuser ...........................................................................................................................................................................................................33
Sizing................................................................................................................................................................................................................34
Slaving..............................................................................................................................................................................................................34
Bypass Dampers .........................................................................................................................................................................................35-36
Static Pressure Controller. ...........................................................................................................................................................................37-38
System Start-Up – Commander Software Review ........................................................................................................................................39-48
Trend And Data Logging Operation ..............................................................................................................................................................49-50
Troubleshooting....................................................................................................................................................................................................51
Operating Schedule..............................................................................................................................................................................................52
2
Page 3
COMMANDER SYSTEM OVERVIEW
SYSTEM SELECTION CRITERIA
Are you using zone dampers on this job?
NO, control your stand-alone equipment with a ZonexCommander. YES, use a ModCom or a ZonexCommander (Plus).
Stand-Alone Unit Applications
ZONEXCOMMANDER
1. How many units are on this project?
2. Are units Gas Electric or Heat Pump?
3. Are there any generic loads to control (pumps, lights, or fans)?
4. Is a Network/Internet communication required?
5. Proceed to the ZonexCommander Component Selection Guide, and insert the above answers to develop a bill of materials for your control system composed of stand-alone RTUs or split systems.
1. How many zones are on each unit?
2. How many stand-alone units are in this application?
3. What size dampers are needed?
4. What size and how many bypass dampers are needed?
5. Are there any generic loads to control and schedule (pumps, fans or lights)?
6. Is Network/Internet communication required?
7. Proceed to the ZonexCommander (Plus) Component Selection
This manual covers the design and installation for the ZonexCommander systems. ZonexCommander is a communicating Windows-based DDC system designed to remotely control 1 – 80 RTUs, split systems or zones. The systems can control stand-alone HVAC equipment, zoned units with fully modulating or two-position zone dampers and auxiliary equipment such as exhaust fans, lighting or other generic loads scheduled via the ZonexCommander software.
Zonex is designed to network one or multiple zoned units on one two-wire twisted pair for remote communications over the Internet in buildings too large for multiple programmable thermostats but too small for a full blown energy management system.
1. ZonexCommander – Controls stand-alone HVAC equipment 1-80 units
constant volume and VAV systems.
following features to enhance control and management of the facility remotely or on-site as follows: – On-site or remote control of all HVAC equipment – Remotely collect and view temperature data, RA/SA from any unit – Monitor or change every thermostat remotely, individually or globally – Schedule each thermostat for two occupied and two unoccupied
periods per day – Remotely lock thermostats individually or globally – Vacation scheduling for 20 events of up to 30 days in duration – Provide scheduled occupied and unoccupied operation of generic
devices (pumps, lights, fans, and more) – Print reports for thermostat setpoints, zone or room temperatures – Trend logging capability
– Remote system control with simple Windows operating software
To select the proper Zonex system for your application please answer the following questions:
Two versions of the product are available:
2. ZonexCommander (Plus) – designed to centralize control of multiple
Communications with these systems are accomplished with a computer
connected directly to the system or over the Internet. A dedicated on-site computer is not required to operate any ZonexCommander.
Systems utilize Zonex Windows-based software and provide the
– Alarming
ZONEXCOMMANDER (PLUS) – for Multiple Zoned and
Stand-Alone Units
Guide.
3
Page 4
ZONEX COMPONENT DESCRIPTIONS
providing remote communication with all RTUs or splits in your system. The ZonexCommander eliminates the need to continually set
building. ZonexCommander bridges the gap between ineffective stand-alone thermostats and expensive and complex automation systems.
COMMAND CENTERS
The Command Center is a microprocessor based digital communicating controller. Each Command Center supports up to 20 devices (thermostats
ZonexCommander ZonexCommander (Plus)
The Command Centers communicate with the computer through the RS-232 link, and communications with thermostats or devices communicate through the RS-485 link using a daisy chained two-wire twisted pair (Belden 8740).
not affected by power interruptions.
The Command Centers are powered by dedicated 24vac 40va, field supplied transformers. Each Command Center must have its own
Part #CETCIP
network device, for 20 communicating devices.
The ZonexCommander automates and networks 1-80 HVAC units,
and reset multiple programmable thermostats located throughout yourr
Please review integral components of the Zonex Systems below.
and RLYCOM relay modules).
A unique Command Center exists for each communicating Zonex System::
Each Command Center maintains Day, Date, Time and Year with battery backup. All Occupied, Unoccupied and Vacation schedules, device name tags and addresses are programmed into non-volatile memory, which is
transformer power supply.
ZONEXCOMMANDER COMMAND CENTER
CETCIP – ZonexCommander Communications Package with TCIP
COMCIP – Command center with TCIP – adds 20 additional com-
municating devices for larger systems.
ZONEXCOMMANDER (PLUS) COMMAND CENTER
ZPTCIP – ZonexCommander (Plus) Communications Package with
TCIP network device for internet communications, for 1-4 RMODs
with 20 communicating devices. Includes system operating software.
CZNXIP Command Center with TCIP – supports 4 additional
RMODs and another 20 additional communicating devices.
ZonexCommander (Plus) is designed to provide centralized control
for multiple zoned HVAC systems. Each Command Center supports up
to 20 devices (ModStat, MODS2, DIGICOM thermostats and
RLYCOMs). Each ZPTCIP Command Center controls up to four
RMOD controllers, each controlling one HV AC unit. CZNXIP Com-
mand Centers via TCIP device provide expansion capability to
support up to 16 HVAC units with 80 zones. The thermostats are allo-
cated to the RMOD controller through ZonexCommander (Plus)
software.
RMOD – UNIT RELAY MODULE
For use with ZonexCommander (Plus) systems only
Each Command Center can support 4 RMODs. Each Universal RMOD
controls a zoned GE or
HP unit with on-board
capacity control. The
RMOD communicates
with the Command
Center and thermostats
assigned to that RMOD.
Each thermostat can
send a heat or cool call
to the RMOD. The RMOD
polls the number of heat
or cool calls every
minute and energizes
the unit based on our
control algorithm of
first call first served, majority wins on changeover..
THERMOSTATS
The DIGICOM and DIGIHP thermostats are used to control stand-
alone Gas Electric (2H/2C) or Heat Pump (3H/2C) HVAC systems.
4
Page 5
ZONEX COMPONENT DESCRIPTIONS
Commander software and have a manual two-hour override. When the thermostats are “locked,” the setpoints can be adjusted locally by
The Heat / Cool setpoints and address assignments are stored in
non-volatile memory to insure recovery in the event of a power inter­ruption. Thermostats are powered with 24vac, and communication is through the RS-485 twisted pair (Belden 8740) communication wire.
COMMUNICATION WIRE SPECIFICATION RS-485
The Commander System sends and receives data from the Command Center to all communicating devices through a 2-conductor twisted pair RS-485 link (Belden 8740). The communication wire has a maximum run length of 4,000 L Ft. The communication link is a vital component of any DDC system, and it must be installed correctly using the correct wire for the specific application.
For standard applications the basic twisted pair (Belden 8740) wire is used, which is daisy chained to each communicating device. For installations with any potential for electrical interference such as caused
shielded twisted pair (Belden 8450) should be used to insure clean communications.
OLAT - 5vdc OUTSIDE AIR SENSOR
The LAT Thermistor sensor assembly is provided with the Zonex­Commander and ZonexCommander (Plus) Command Centers to
provide the Outside Air Temperature which is displayed on the System screen of the ZonexCommander/Commander (Plus) program.
COMPUTER SPECIFICATIONS A dedicated on-site “control” computer is not required. All of the
ZonexCommander Family of control systems are accessed by Windows
OPTIONAL DEVICES
SENDCOM Sensor
The SENDCOM is a microprocessor based communicating air duct
device is used to display Supply and
requires a SENDCOM to display Return and Supply air temperature for that particular system. This data is transmitted to and displayed on the Commander software.
The SENDCOM is designed for installation on the supply duct, with a remote sensor for the return duct. The SENDCOM does not use a dedicated address on the communication link; it piggybacks a thermostat address and displays data when that thermostat number
temperature.
device equipped with two SPDT relays, which are used for controlling fans, pumps, blowers, lighting, etc. The
devices to be cycled ON and OFF by programmed schedules in the Commander software. Status is displayed on the REVIEW screen for
dedicated address from 01 to 20. The load applied to the relay
mode and de-energize in the Unoccupied mode.
TCIP Network Device
The ModStat (modulating) and MODS2
(2-position) are zone thermostats, which
control zone dampers.
The Zonex thermostats are microprocessor
based, auto changeover, digital commu-
nicating thermostats. The thermostats
have a large, easy-to-read LCD display
with a distinctive grey backlight. The
display is designed to clearly indicate
space temperature from 57°to 92°, heat and cool
setpoints, system status, override and thermostat address.
The factory set Heat and Cool setpoints are 70° and 75°, and the factory
set address is 25. Thermostats can be electronically "locked" by the
no more than 2° above or below the locked setpoints.
based Laptop or Desktop computers using Windows 7, 8,XP or Vista
operating systems. Our systems can be easily accessed with a direct
connected computer or the optional TCIP device for Internet or
Ethernet access.
Communicating Supply and Return Air Temperature Sensors
temperature sensor. This optional
Return air on stand-alone HVAC systems. Each stand-alone HVAC system
is selected by double clicking over that thermostat's current room
RLYCOM
The RLYCOM is a communicating
by large transformers, VFDs, ballasts and other electrical devices,
LAT – 5vdc TEMPERATURE SENSORS
LAT sensors are used on the RMOD and SENDCOM devices
for Return and Supply Air temperature sensing. The Supply
and Return sensors provide data to the RMOD and
CMod for proper system capacity control and HI/LO limiting. The SENDCOM has a supply sensor, which is factory installed in the
enclosure for supply plenum installation; and the remote return sensor is included for field installation on the return plenum.
ModCC /
RLYCOM enables these auxiliary
verification. Each RLYCOM uses a
contacts must not exceed one amp at 24vac. The RLYCOMis designed to switch 24vac circuits only. The relays energize in the Occupied
The TCIP device provides communication with the Commander
System through the Internet or Ethernet Network using an assigned
IP address and Port Forwarding.
The Network device includes the iServer with power supply, installation software and the Commander Network version
operating software.
5
Page 6
ZonexCommander is a DDC system for automating and networking new and existing stand-alone HVAC systems and mechanical devices. Gas Electric and Heat Pump HVAC units are controlled with communicating thermostats while mechanical devices are controlled with a relay device (RLYCOM). Each of these devices can be scheduled through the simple Windows-based ZonexCommander software and communicate to the Command Center via a daisy-chained 2-wire twisted pair communications link.
ZONEXCOMMANDER CONCEPT DRAWING
Twisted Pair Communications Wire (Belden #8740)
DIGICOM or DIGIHP Thermostat
Standard 18-ga. Thermostat Wiring to Unit
1
2
3
4
ZonexCommander Command Center (Part #CETCIP)
6
Page 7
ZONEXCOMMANDER COMPONENT SELECTION GUIDE
SYSTEM
NUMBER OF THERMOSTATS
Up to 20
from above)
THERMOSTATS
Gas/Electric
Heat Pump
DIGICOM
(2H/2C)
DIGIHP (3H/2C)
ZonexCommander
Remotely control 1-80 stand-alone rooftops or split systems
COMMUNICATING ACCESSORIES (Optional)
STAND-ALONE
EQUIPMENT
COMMAND CENTER
21 to 80
additional 20 Thermostats
Stand-Alone Equipment
SENDCOM
Duct Temperature Sensor
(1 per HVAC unit)
Communicating
Relay Device
RLYCOM
CETCIP Communications package
Includes: Command Center, software, TCIP Device, cables and LAT Sensor
(Use 1 – CETCIP
1 – CETCIP Communications Package
1 – COMCIP Command Center per
7
Page 8
SYSTEM OVERVIEW
ZonexCommander is a DDC system for automating and networking new and existing stand-alone HVAC systems and mechanical devices.
The ZonexCommander networks 1-20 RTUs, AHUs, Heat Pumps, or split systems per Command Center with an expansion capability of up to 80 units.
Gas Electric and Heat Pump HVAC units are controlled with communicat­ing thermostats (DIGICOM / DIGIHP), while mechanical devices are controlled with a relay device (RLYCOM). Each of these devices can be scheduled through the simple Windows-based ZonexCommander software and communicated to the Command Center via a daisy-chained 2-wire twisted pair communications link (Belden 8740).
The Command Center has available inputs for outside air temperature display; and, with the addition of a SENDCOM sensor, each unit’s Return Air and Supply Air temperature is remotely displayed on the Commander software. This information may also be trend logged via the Zonex- Commander Trending Program, included with your Commander software.
ZonexCommander allows you to instantly communicate and remotely control every unit in your system.
OPERATION
The ZonexCommander Command Center polls all devices every minute to register information on operation in the Command Center. DIGICOM and DIGIHP thermostats place calls to HVAC units based on thermostat setpoint.
Cool Call
The DIGICOM and DIGIHP thermostats will initiate a Y1 cool call when the space temperature rises 1° above the Cool setpoint. The fan will also be energized on “G.” On 2-stage systems, Y2 will be energized when the space temperature rises 2° above the Cool setpoint. Y1 and Y2 will remain energized until the active cool call is satisfied at setpoint.
When the DIGIHP thermostat is configured for “O” reversing valve on an active cool call, “O” will energize on call for cool and will remain energized until a heat call is made. When the DIGIHP is configured for “B” reversing valve, there is no signal from the O/B terminal on an active cool call.
Heat Call
The DIGICOM and DIGIHP thermostats will initiate a 1st stage heat call (W1 or Y1 & G) when the space temperature drops 1° below the Heat setpoint. 2nd stage heat is energized (W2 or Y2 & G) when the space temperature drops 2° below the Heat setpoint. The DIGICOM thermostat does not energize “G” for fan on a heat call unless the thermostat has been configured for FAN ON in the Occupied mode.
On the DIGIHP thermostat, when the temperature drops 3° below the heat setpoint, the auxiliary heat will be energized on W2 and G, along with Y1 and Y2. When Emergency Heat is selected, Y1 and Y2 are de-energized; and W2 and “G” are energized.
When the DIGIHP thermostat is configured for “O” reversing valve on an active heat call, the O/B output will be de-energized. When the DIGIHP
is configured for “B” reversing valve on a call for heat, “B” will energize the reversing valve and will remain energized until a call for cool is made.
Occupied/ Unoccupied
A schedule for Occupied and Unoccupied operation is made through the ZonexCommander Windows-based software. This schedule will communicate with thermostats to reset temperature setpoints of thermostats for occupied and unoccupied time. Each thermostat can have its own occupied and unoccupied schedule and thermostat setpoints. The Zonex- Commander Windows-based software allows for seven-day programmability with two occupied and two unoccupied time periods per day.
Thermostat Lock Feature
The DIGICOM / DIGIHP thermostats can be electronically locked either individually or globally through the ZonexCommander program. When a thermostat is in the Lock mode, the address number on the left column of the Review screen on the Zonex software will be in red. The thermostat will also display the Lock mode with a padlock symbol on the upper left of the LCD display. When in the Lock mode, the thermostat can be locally controlled providing heating or cooling changes ±2° from Heat or Cool setpoint. The 2-hour override is operational in the Lock mode.
Schedule Override
The DIGICOM / DIGIHP thermostats provide a 2-hour override in the Unoccupied mode. When the thermostat goes into the Unoccupied mode, the backlight automatically goes off, and Unoccupied is displayed. When the Select button on the thermostat is pressed in the Unoccupied mode, the backlight energizes and the 2-hour override to Occupied begins. To terminate the 2-hour override, press the Select button again, which returns the thermostat to the Unoccupied mode.
schedule input on the Commander software. When the Command Center
Center sends an Unoccupied call, the RLYCOM de-energizes. Manual
SENDCOM SENDCOMs work in conjunction with their assigned thermostats. To
review SENDCOM information, double click on an assigned thermostat’s current room temperature. Supply and Return air temperatures will appear on the REVIEW page for this SENDCOM, if a SENDCOM was installed in this application.
ZONEXCOMMANDER SEQUENCE OF OPERATION
RLYCOM
The RLYCOM energizes and de-energizes two SPDT relays based on the
sends an Occupied call, the RLYCOM energizes. When the Command
changes are performed from the Toggle button on the RLYCOM. When the red LED is illuminated, the RLYCOM is energized. Multiple RLYCOMS may be utilized to control additional devices or loads.
8
Page 9
3. When the installation calls for an on-site, direct connected computer, the Command Center must be located within 10’ of the computer if the
4. Install a 24vac 40va dedicated transformer for each individual Command Center, and wire to terminals “G” and “B.” (See Fig. 1)
6. A single air sensor (OLAT) is supplied to display the Outside Air
Temperature on the System screen of the Commander program. It
7. The twisted pair communication wire (Belden 8740) is to be daisy chained to each communicating device, which is controlled by the specific Command Center. When multiple Command Centers are used, each Command Center is to have a dedicated communication loop. The communication loop is polarity sensitive on RX and TX. Wire nuts are never to be used on the communication wire. When splicing wire, use screw type terminal strips or solder.
NOTE: for systems with potential electrical interference, such as large transformers, VFDs, etc, shielded twisted pair (Belden 8450) may be used for the communications loop.
ZONEXCOMMANDER INSTALLATION INSTRUCTIONS
Fig.1
CETCIP Command Center
1. Install the CETCIP Command Center on a wall or mounting board
in a dry interior space where the ambient temperatures will be between
32° and 125° non-condensing.
2. When installing multiple Command Centers, mount all boards together on the same surface. NOTE: 120vac outlets are required for the TCIP iServer device power supplies.
USB cable is used. The TCIP device requires an Ethernet cable,
which is field provided.
should be installed where it will not be in direct sunlight. If the sensor
leads must be extended, simply use standard 18/2 thermostat wire,
and connect to the S S terminals on the Command Center.
NOTE: Power supply voltage on G and B should be 24 to 28vac.
5. For system TCIP configuration, you must provide a 120vac outlet for the power supply.
9
Page 10
DIGICOM / DIGIHP THERMOSTATS
DESCRIPTION
The Zonex Systems DIGICOM and DIGIHP are microprocessor based, auto changeover, stand-
The DIGICOM and DIGIHP are very easy to configure through the system program or to make manual adjustments using the buttons located on the front cover.
These thermostats feature an onboard thermistor for precise tempera­ture measurement. In the event of power loss, the Heat and Cool set­points are stored in a non-volatile memory, without the need for bat­tery backup.
The space ambient temperature is continually displayed with large,
Programmed setpoints can be manually adjusted at the thermostat or electronically locked through the system program to provide limited manual setpoint adjustment. Two-hour override is provided for after-hours temporary operation with a touch of a button.
INSTALLATION Thermostat and terminal base
1. The thermostat is to be installed on an interior wall, away from drafts, supply air currents and direct sunlight or any heat generating source.
2. To remove the thermostat cover, grasp the cover at the top and pull straight off; do not pivot the cover from the base.
3. Install the thermostat terminal base to the wall using the provided anchors and screws. The thermostat can also be mounted on a 2x4 electrical box using two #6-32” screws.
Wiring
The Zonex Systems DIGICOM and DIGIHP thermostats have been specifically designed to make wall mounting and wire connections very easy. The thermostat terminal base has two separate terminal blocks: the left side terminal block is for the 24vac control circuits, and the right side terminal block is for the RX TX communication circuits. There are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple.
1. Use minimum 18-gauge AWG thermostat wire for the 24vac control circuits. The load on these circuits must not exceed 1 amp. The voltage range on R and C must not exceed 28vac.
2. Connect the communication wires to the RX TX terminals. There are 2 sets of RX TX terminals for “daisy chain” installation of this circuit. The communication wire specification is twisted pair (Belden 8740) or shielded twisted pair wire (Belden 8450).
NOTE: When using shielded twisted pair wire (Belden 8450), just connect the shield conductors together, as there is no electrical connection on the thermostat base terminals. The shield will be landed on the Command Center on the G or TR2 terminal.
Fig. 1
DIGICOM
DIGIHP
Fig. 2
Fig. 3
Blower Fan Relay For electrical heat applications, which require a fan output on a call for heat. (See Fig 3.)
alone thermostats used to control stand-alone units
with no dampers in the system. The DIGICOM the Gas Electric version and has two-stage heat / cool outputs with selectable fan operation. The
DIGIHP
Heat Pump thermostats have two-stage
cool and three-stage heat outputs with selectable fan. The DIGICOM and DIGIHP thermostats have a large, easy-to-read LCD display with a distinctive gray backlight. The display backlight is
continuously illuminated in the Occupied mode and goes off in the Un-
occupied mode.
easy-to-read numbers. The DIGICOM temperature display range is 57°to 90°F., and the DIGIHP temperature display range is 57°to 90°F. Fan mode, Heat or Cool setpoints and operation modes are all indicated
on the display.
is
RG
W1
H
R
10
V A
G
C
C
U N I T
2
5
1
SPDT, 24V
AC Relay
4
3
Page 11
Configuration
1. Set the unique address for each thermostat from 01 to 20.
2. Press and hold the Menu button until you see the system mode
display on the lower right begin to scroll and change modes; then press and hold the Heat/Cool button with the Menu button.
3. When the display shows “address” and the setpoint temperature
MANUAL ADJUSTMENTS Heat and Cool Setpoint Display
Press the Heat/Cool button to display the Heat or Cool setpoint temperatures.
Temperature Setpoints COOL Setpoint
1. Press the Heat/Cool button to display the
Cool setpoint on the upper right.
2. Press the UP or DN buttons to change the
Cool setpoint.
HEAT Setpoint
1. Press the Heat/Cool button to display the
Heat setpoint on the upper right.
2. Press the UP or DN buttons to change the
Heat setpoint temperature.
FAN Mode
To change the FAN operation to AUTO or ON, press the UP and DN buttons together, once to toggle fan operation.
HVAC system mode
To select Heat, Cool, Auto, Emergency Heat (HP only) or OFF, press and
hold the Menu button; and when the desired mode is displayed, press and hold the Select button; then release both to confirm mode.
Override
When the system is in the Unoccupied mode, the thermostat provides a 2-hour override for after-hours system operation. To select the 2-hour
override, press the Select button and note “Override” indicated on the display, along with the backlight coming on. When additional override is
required, press the Select button again.
Calibration When re-calibration is required, press and hold the Heat/Cool and
Select buttons simultaneously (the screen will flash). Then press the UP
button once to increase temperature 1°, or press the DN button once to decrease the temperature 1°. If additional calibration is required, repeat this step.
THERMOSTAT OPERATION Display
The grey display backlight is constantly illuminated in the Occupied mode. The display backlight goes off when in the Unoccupied mode. When in the Unoccupied mode, if any button is pressed, the backlight will illuminate for 5 seconds. If the thermostat is placed into the override mode, the backlight will illuminate until the 2 hours times out. To terminate override, press the Select button again.
COOL – DIGICOM / DIGIHP: The thermostat will make a Y1 cool call when the space temperature rises 1° above the cool setpoint. Y2 will energize when the space temperature rises 2° above the cool setpoint. When the room temperature is less than 2°from setpoint, Y2 de-energizes. Y1 de-energizes at setpoint. O or B is energized for the reversing valve circuit, depending on configuration. The G circuit is energized for fan.
HEAT – DIGICOM: The thermostat will make a W1 heat call when the space temperature is 1° below the heat setpoint. W2 will energize when the space temperature is 2° below the heat setpoint. When the room temperature rises to within 2° of the heat setpoint, W2 de-energizes. W1 de-energizes at setpoint.
NOTE: The “G” fan circuit on the DIGICOM thermostat is not energized in the Heat mode unless the fan is set for ON operation.
HEAT – DIGIHP: The thermostat will make a Y1 heat call when the space
space temperature is 2° below the heat setpoint. E (aux heat) will energize when the space temperature is 3° below setpoint. When the room temperature rises to within 2° of the heat setpoint, E (aux heat) de-energizes. When the room temperature rises to within 1°, Y2 de-energizes. Y1 de-energizes at setpoint.
Emergency Heat – DIGIHP: When Emergency heat is selected on the DIGIHP thermostat, on a call for heat, there is an output signal on “E”
for backup heat and “G” for the fan. The compressor circuits “Y1” and “Y2” are locked out during heat calls until Auto, Heat or Cool mode is selected. The thermostat display will indicate when Emergency Heat has been selected.
DIGICOM – FAN operation for electric heat applications: A pilot relay may be required to energize the fan for heat operation on electric heat applications. This relay is a 24vac coil – SPST and is field supplied. The coil is energized from W1 and C from the DIGICOM
thermostat terminal base.
DIGICOM / DIGIHP THERMOSTATS
changes to the address number, release Heat/Cool and Menu buttons
and press the UP or DN button to raise or lower the number.
Reversing Valve Mode
DIGIHP (O&B) is factory set at "O" and can be field configured for "B"
reversing valve operation. For "B" mode reversing valve (reversing valve
energized in the heat mode), press and hold the Heat/Cool and Select
buttons; then press and release the Menu button once. Release the Heat/
Cool and Select buttons. The ° symbol next to the set point display
should disappear. Repeat steps above to go back to "O."
temperature is 1° below the heat setpoint. Y2 will energize when the
11
Page 12
COMMAND CENTER – ZONEXCOMMANDER
LEGEND
1
DATE AND TIME BACKUP BATTERY
SENSOR CALIBRATION:
2
R12 OUTSIDE AIR (OA)
POWER LED INDICATOR
3
MAIN CONTROL CHIP ZONEXCOMMANDER
4
5
COMMUNICATION RS-485 TWISTED PAIR (POLARITY SENSITIVE) (BELDEN 8740)
6
USB COMPUTER
OUTDOOR AIR SENSOR TERMINAL
7
TERMINALS G AND B, 24VAC 40VA INPUT
8
9
ON/OFF SWITCH
12
Page 13
ZONEXCOMMANDER WIRING OVERVIEW
ROOFTOP UNITS: UP TO 20 PER COMMAND CENTER
13
Page 14
ZONEXCOMMANDER (PLUS) CONCEPT DRAWING *
The ZonexCommander (Plus), ZPTCIP, is a DDC system for automating multiple zoned HVAC systems, stand-alone HVAC units and mechanical
devices. The universal RMOD controls both Gas Electric and Heat Pump units with onboard capacity control. The modulating/two-position
thermostats (ModStat and MODS2) are used to communicate calls for heat and cool, as well as modulate dampers based on zone demand.
The ZonexCommander (Plus) system can be applied to existing HVAC systems or new installations providing central control of HVAC operations
using Windows-based ZonexCommander (Plus) software.
* Concept Drawing Only. See Wiring Schematic on Page 16
14
Page 15
ZONEXCOMMANDER (PLUS) COMPONENT SELECTION GUIDE
15
Page 16
ZONEXCOMMANDER (PLUS) INSTALLATION WIRING DIAGRAM
NOTE: Each Command Center supports up to 4 RMODs and a maximum of 20 communicating devices. When the application requires more than
Fig. 2
Fig. 1
ELECTRIC HEAT FAN CYCLING AUXILIARY BLOWER FAN RELAY
When W1 is energized from the DIGICOM, ModCC or RMOD, the fan circuit (G) is not energized. For applications requiring the blower to be cycled
The W1 output signal is connected to the heating device input terminal and the coil of the fan relay. This is required for electric heat and gas furnaces with no fan control. (See Fig. 2)
4 RMODs or more than 20 communicating devices, additional Command Center(s) will be required. There must be separate communications circuit (twisted pair Belden 8740) for each Command Center (channel). (See Fig. 1)
All RX communication wires must be connected to the RX terminals.
All TX communication wires must be connected to the TX terminals. The RX and TX wires should never intersect.
on a W1 heat output, a field supplied, 24-volt coil SPDT relay must be used.
16
H
R V A
G C
C U N I T
BLOWER FAN RELAY
RG
W1
2
5
1
SPDT, 24V
AC Relay
4
3
Page 17
ZONEXCOMMANDER (PLUS) SEQUENCE OF OPERATION
SYSTEM OVERVIEW
for communication and control with the zoning and stand-alone
provides interface between the communicating system and a Windows-
modulating zones totaling 20 system devices. Twenty thermostats are available to be allocated to the 1-4 RMODs associated with each Command Center. Communication is accomplished through a two-conductor twisted pair RS-485 link (Belden 8740), which is daisy chained between all system communicating components.
OPERATION
The ZonexCommander (Plus) Command Center polls every minute. When the Command Center polls, it goes to each ModStat to gather information on whether it is making a cool call, heat call or no call. Based on this information the Command Center then sends calls for cool, heat or no call to RMOD and ModStats.
ModStat/MODS2 Cool Call
If room is one or more degrees above setpoint, a call for cool will be made to the Command Center. If a majority of thermostats assigned to the same RMOD is calling for cooling, the Command Center will communicate to RMOD to make a call for cool. Command Center will also send a mode call to all thermostats assigned to this RMOD for cool. This tells ModStat what the system mode is so that damper control may be made. If the room is calling for cooling and the RMOD is in the cool mode, the ModStat will modulate the dampers calling and closed to sat­isfy room demand. If the room temperature is two or more degrees above setpoint, the damper will be between 100% and 0% open, based on room load desire. If using a MODS2 with a two-position damper, the damper will be open. When call is satisfied, the damper will close.
Heat Call ModStats will place a call for heat if room temperature is two or more degrees
below setpoint. When the Command Center polls, if there is a majority call for heat from ModStats that are assigned to the same RMOD and the system is not in cooling mode, then the Command Center will communicate a call for heat to the RMOD and a heat call will be initiated. If there is a current call for cooling and a majority heat call has been received, a changeover sequence will begin. After two minutes the cool call will end,
a two-minute purge will start, and at the end of the purge a heat call will be made. The Command Center will communicate a heat mode call to the
is two degrees or more below room temperature, ModStat will modulate the damper to 100% open. If the room temperature is within two degrees of setpoint, the ModStat will control the damper from 100% open to 0% open based on deviation of setpoint. If using a MODS2
in the heat mode,
the damper will be open.
Auxiliary Heat
the AUX heat output will energize initiating auxiliary heat.
RMOD
When heating or cooling calls are sent to the RMOD Relay Module by the thermostat, the RMOD will treat these calls as votes to determine mode of
Cool Mode
If the majority of calls are for cooling, the RMOD will energize Y1 and G for 1st stage cooling. After four minutes, the RMOD will check the leaving air temperature. If the leaving air temperature is 10° above cutout
compressor safety.
Heat Mode
If the majority of calls are for heating, the RMOD will energize W1 for 1st stage heating. After four minutes, the RMOD will check the leaving air temperature. If the leaving air temperature is 15° below high limit cutout (145° - 15° = 130°F), then W2 will energize. W2 will stage off at 5° below temperature cutout (145° - 5° = 140°F), and W1 will stage off on high temperature at 145°F.
Changeover
If the system is running in one mode and the majority of calls change to the other mode, a timer will start. The RMOD will give the current operating mode another four minutes to try to satisfy the zone(s). It will then go into the purge cycle before switching modes to the majority.
The ZPTCIP is the primary Command Center, which provides a source
thermostats, along with various communicating devices. The ZPTCIP
based PC computer over the Internet. Included with the ZPTCIP are a TCIP driver, Operating Software, Cables, and Sensor.
The ZPTCIP Command Center manages 1 to 4 HVAC systems with
The CZNXIP controller is the ZPTCIP Command Center without software
to expand communication for an additional 20 devices per each CZNXIP Command Center. When using additional CZNXIP Com-
mand Centers, an additional TCIP device and an individual IP
address must be used for interface communications.
RMOD, and ModStats will control dampers. If the room temperature
If the space temperature drops 2°F below the Heat setpoint temperature,
operation. Adjustable factory limits are 45°F cool and 145°F heat.
(45° + 10° = 55°F), then Y2 will energize. Y2 will stage off 4° above cutout (45° + 4° = 49°F) and Y1 will stage off on low temperature at 45°F. A four-minute off delay between operations is provided for
17
Page 18
ZONEXCOMMANDER (PLUS) SEQUENCE OF OPERATION
Purge Mode
When a heat or cool call is satisfied or before changing modes, the RMOD will go into a three-minute purge cycle. The call for heat or cool will be removed, and the dampers will remain in their last position to allow time for air to adjust to room temperature before going into ventilation mode or changeover.
Fan Operation
Fan operation in the ZonexCommander (Plus) is controlled by the RMOD. The fan jumper on RMOD allows for the option of fan continuous in Occupied and intermittent in Unoccupied. Fan intermittent can be selected in both Occupied and Unoccupied modes. Place fan jumper in desired position.
Ventilation
When no zone is calling for heat or cool, the dampers will open 50%. This permits ventilation in all zones if the blower fan is on continuously.
COMMUNICATION FAILURE
If the RMOD cannot communicate with any of the thermostats, it will control the HVAC unit based on return air temperature. The RMOD will try to maintain 70°F heat and 75°F cool return air.
TEMPERATURE LIMITS AND STAGING
The RMOD monitors the leaving air temperature for staging and Hi /Low
145° F. Staging is based on the limit settings.
Gas Electric & Heat Pump
Example:
Gas Electric Heating W2 cut-in temperature is high limit minus 15° F (145° – 15° =
130° F). The W2 cut-out is cut-in plus 10° F (130° + 10° = 140° F). Example: Adjustable high limit = 145° W2 Cut-in = 130° F (high limit minus fifteen) W2 Cut-out = 140° F (cut-in plus ten) W1 cut out = 145°
Heat Pump Heating – When the RMOD is configured for HP operation, the high
cut-out is automatically set to 121°.
• W2 energizes when the SA temperature is 88° or less after 4 minutes of run time. W2 de-energizes when the SA temperature rises to 100°.
• Y2 energizes when the SA temperature is below 100° after 2 minutes of run time and de-energizes above 115°.
• Y1 cuts out for 4 minutes when the SA temperature is above 120°.
TEMPERATURE LIMIT ADJUSTMENT
Low Limit –
1. Push DN button until display shows C.
2. Current setpoint will be displayed.
3. Push UP or DN button until desired setpoint is displayed.
4. Release button.
1. Push UP button until display shows H.
2. Current setpoint will be displayed.
3. Push UP or DN button until desired setpoint is displayed.
4. Release button.
operation. A shorted sensor or wiring will display low temperature, and
RLYCOM
The RLYCOM energizes and de-energizes the two SPDT relays based on
the schedule input on the Commander software. When the Command
Center sends an Occupied call, the RLYCOM energizes. When the
Command Center sends an Unoccupied call, the RLYCOM de-energizes.
When the red LED is illuminated, the RLYCOM is energized.
Supply and Return Air Temperature Display
System supply and return air temperatures can be read from each RMOD
and the REVIEW screen of the ZonexCommander (Plus) program. On the REVIEW screen simply double-click on the Current
Room Temperature of
address 1, 2, 3, 4. The address number is displayed on the left hand
column. The Read
Sensors Screen will appear with the supply and return
temperatures for the specific RMOD.
Address: 1 = RMOD 92
2 = RMOD 93 3 = RMOD 94 4 = RMOD 95
SENDCOM sensor.
SENDCOM
On the ZonexCommander (Plus) system, the supply and return
temperatures from the stand-alone DIGICOM and DIGIHP thermostats are provided by the SENDCOM. One SENDCOM is installed for each stand-alone system. When assigning addresses for the stand-alone thermostats and SENDCOMs, you must start at #75 through #90 (5 through 20). The first 4 address numbers on the program are for
SENDCOMs associated with the 4 RMODs only. Pay particular attention to this issue. Each RMOD has a SENDCOM associated with it. If 4
RMODs are utilized with 1 Command Center, the information from those SENDCOMs will be retrieved on the Zonex software from thermostat
locations 1, 2, 3, or 4.
limit. The adjustable factory low limit is 45° F and the high limit is
Cooling Y2 cut-in temperature is low limit plus 10°F (45°+ 10°= 55°F). The Y2 cut-out is cut-in minus 8°F (55° – 8° = 47°F).
Adjustable low limit = 45°F Y2 Cut-in = 55°F (low limit plus ten) Y2 Cut-out = 47°F (cut-in minus eight)
High Limit –
NOTE: The RA and SA air sensors (P# LAT) must be installed for unit
an open sensor or wiring will display high temperature.
Manual changes are performed from the Toggle button on the RLYCOM.
To obtain this information from stand-alone equipment, include a
18
Page 19
COMMAND CENTER – ZONEXCOMMANDER (PLUS)
LEGEND
DATE AND TIME BACKUP
1
SENSOR CALIBRATION:
2
3
4
5
6
7
8
9
R12 OUTSIDE AIR
POWER LED I NDICATOR
MAIN CONTROL CHIP ZONEX COMMANDER (PLUS)
COMMUNICATION RS-485 TWISTED PAIR (POLARITY SENSITIVE) (BELDEN 8740)
USB COMPUTER
SENSOR TERMINAL OA (OUTSIDE AIR) ONLY
TERMINALS G AND B, 24VAC 40VA INPUT
ON/OFF SWITCH
BATTERY
19
Page 20
3. If the installation calls for an on-site computer to be directly
4. Install a 24vac 40va dedicated transformer for each individual
Command Center, and wire to terminals “G” and “B.” Power supply voltage on G and B should be 24 to 28vac.
6. The only sensor connected to the Command Center is the Outside Air
Sensor (OA), which is Part # OLAT. The Outside Air Sensor is not polarity sensitive.
The outside air temperature is displayed on the SYSTEM screen in the
7. The twisted pair communication wire (Belden 8740) is to be daisy chained to each communicating device, which is controlled by the
each Command Center is to have a dedicated communication loop.
The communication loop is polarity sensitive on RX and TX. Wire
nuts are never to be used on the communication wire. When
making connections, use screw type terminal strips or solder.
NOTE: for systems with potential electrical interference, such as
large transformers, VFDs, etc, use shielded twisted pair (Belden
8450) for the communications loop.
ZONEXCOMMANDER (PLUS) INSTALLATION INSTRUCTIONS
Fig. 1
ZPTCIP/CZNXIP Command Centers
1. Install the Command Center on a wall or mounting board in a dry interior space where the temperatures will be between 32-125°
non-condensing.
2. When additional Command Centers are used, mount all together on the same wall or mounting board.
connected to the Command Center, the computer must be located within 10 feet of the Command Center.
5. For system TCIP configuration, you must provide a 120vac outlet for the power supply.
ZONEXCOMMANDER (ZPTCIP / CZNXIP)
Commander program.
specific Command Center. When multiple Command Centers are used,
20
Page 21
DESCRIPTION
The LCD ModStat is available for the ZonexCommander
The unique grey display backlight is constantly illuminated in the Occupied mode. The display backlight will go out in the Unoccupied mode. If any button is pressed while the thermostat is in the Unoccupied mode, the backlight will illuminate for 5 seconds. The backlight will also be illuminated when the thermostat is in the 2-hour override mode.
INSTALLATION Thermostat and terminal base
1. The thermostat is to be installed on an interior wall, away from drafts, supply air currents and direct sunlight or any heat generating source.
2. To remove the thermostat cover, grasp the cover at the top and pull straight off; do not pivot the cover from the base.
3. Install the thermostat terminal base to the wall using the provided anchors and screws. The thermostat can also be mounted on a 2x4 electrical box using two #6-32” screws.
WIRING
The Zonex Systems ModStat and MODS2 thermostats have been specifically designed to make wall mounting and wire connections very easy. The thermostat terminal base has two separate terminal blocks: the left side terminal block is for the 24vac control circuits, and the right side terminal block is for the RX TX communication circuits. There are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple.
1. Use minimum 18-gauge AWG thermostat wire for the 24vac control circuits. The load on the auxiliary heat circuit must not exceed 1 amp at 24vac. The voltage range on R and C must not exceed 28vac.
2. Connect the communication wires to the RX TX terminals. There are 2 sets of RX TX terminals for “daisy chain” installation of this circuit. The communication wire specification is: twisted pair (Belden 8740) or shielded twisted pair wire (Belden 8450). Refer to manual (ZCMAN). NOTE: When using shielded twisted pair wire (Belden 8450), just connect the shield conductors together, as there is no electrical connection on the thermostat base terminals. The shield will be landed on the Command Center on the G or TR2 terminal.
3. On the ModStat, connect the damper control wires from MC, RC and RO to the actuator terminals. For MODS2, connect MC and RC to the damper motor.
4. Auxiliary Heat – The ModStat and MODS2 provide a 24vac signal
gized when the space temperature is 2° below the heat setpoint. The signal is de-energized at setpoint temperature.
CONFIGURATION Addressing (1-20). Each thermostat must have a unique address from 1 to 20.
1. Press and hold the Menu button until you see the system mode display
on the lower right begin to scroll and change modes; then press and hold the Heat/Cool button with the Menu button.
2. When the display shows “address,” release the Menu and Heat/Cool buttons; and press the UP or DN button until the correct address is displayed in the upper right of the display.
3. After setting the address, the thermostat will automatically go back to normal operation; and the setpoint temperature will replace the address number just programmed.
Manual Operation - Adjusting Setpoints
The Heat or Cool setpoints can be displayed by pressing the Heat/Cool button; the setpoint will be displayed on the upper right of the display.
Heat – If “Heat Setting” is displayed on the top right of the display, simply press the UP or DN button to change the heat setpoint. If “Cool Setting” is displayed and you want to change the Heat setpoint, press and hold the Heat/Cool button twice to change from “Cool Setting” to “Heat Setting.” Then press the UP or DN button to change the setpoint.
Cool – If “Cool Setting” is displayed on the top right of the display, simply press the UP
or DN button to change the cool setpoint. If “Heat Setting”
is displayed and you want to change the Cool setpoint, press and hold the Heat/Cool button twice to change from “Heat Setting” to “Cool Setting.” Then press the UP or DN button to change the setpoint.
Changing Mode
The thermostats are auto changeover, but specific modes may be selected. Auto mode is the default.
Heat only – Press and hold the Menu button, and note the mode display begin to change. Press the Select button when Heat is displayed.
Cool only – Press and hold the Menu button, and note the mode display begin to change. Press the Select button when Cool is displayed.
System Off – Press and hold the Menu button, and note the mode display begin to change. Press the Select button when Off is displayed.
Auto mode – Press and release the Menu button.
Override
When the thermostat displays “Unoccupied” (top of display), a 2-hour temporary override may be initiated by pressing the Override/Select button. When additional override time is required, press the Override/Select button again.
Display Temperature Calibration
Thermostats are calibrated at the factory and should require no further adjustment. However, the display space temperature may be field cali­brated by the following procedure:
1. Press and hold the Heat/Cool and Select buttons together; then press
2. To lower the temperature display, press the DN button once, after pressing the Heat/Cool and Select buttons. This makes a 1°change.
ModStat / MODS2 THERMOSTATS
(Plus) DDC control system. It is also utilized
with the System 2000 GEN II product. The ModStat
version drives medium pressure, power open / power
close dampers for modulating applications. The
MODS2 version drives low pressure, power close / spring open dampers for 2-position systems, which are 2000 CFM or less.
output on the "AUX” terminal for Auxiliary Heat. This signal is ener-
5. Reheat - The ModStat can be field configured for Reheat applications,
including Fan Powered VAV boxes. The terminal base provides a 24 volt output on terminal “AUX” for the heat elements and the fan relay circuit (if applicable).
NOTE: An Air Proving Switch must be wired into the “AUX” output to protect the electric heating devices.
and release the UP button to increase the display temperature by 1°.
21
Page 22
ModStat / MODS2 THERMOSTATS
ModStat Terminal Designations: TX – Data transmit RX – Data receive
RO – Run Open, damper RC – Run Closed, damper R – 24vac power input C-MC – 24vac power common
MODSTAT
GENERAL OPERATION Ventilation – No active Heat or Cool calls
With no active calls, the ModStat or MODS2 will open the damper for blower ventilation.
Cool Call – The ModStat and MODS2 will send a signal for demand cooling when the space temperature exceeds the cool setpoint temperature by 1°. The thermostat will end the active call when the space temperature meets the cool setpoint.
Heat Call – The ModStat and MODS2 will send a signal for demand heating when the space temperature drops 1° below the heat setpoint temperature. If the temperature drops 2° below the heat setpoint tem-
will end the active call when the space temperature meets the heat setpoint.
When configured for Reheat, if the space temperature drops 1° below
modulate the damper open. The heat call will terminate when the space
system goes into the ventilation mode, the damper will then modulate open.
Reheat - The ModStat can be field configured for Reheat operation by pressing the Heat/Cool and Select buttons together, and then press the Menu button and release all three buttons. The Heat/Cool set­point display will show the ° symbol to verify Reheat configuration.
SUPPLEMENTAL HEAT APPLICATIONS
perature, the “AUX” output will energize for auxiliary heat. The thermostat
the heat setpoint, the ModStat will energize the “AUX” output and
temperature reaches the heat setpoint temperature. The “AUX” output will de-energize, and the damper will modulate closed. If the
Note 1: Sail switch or pressure switch
should be used to prove fan operation.
NOTE: A larger transformer may be needed to power fan relay and/or heat strip relay.
22
SUBBASE
AUX – Reheat/AUX Heat Fan
Page 23
OPERATION
When heating or cooling calls are sent to the RMOD Relay Module by the thermostat, the RMOD will treat these calls as votes to determine mode
When configured for Heat Pump operation, the cut-out is automatically
COOL CALLS
If the majority of calls are for cooling, the RMOD will energize Y1 and G for 1st stage cooling. After 4 minutes, the RMOD will check the leaving
provided for compressor safety.
HEAT CALLS
If the majority of calls are for heating, the RMOD will energize W1 for 1st stage heating. The RMOD will bring on additional stages in 3-minute increments. See Gas Electric and Heat Pump staging.
CHANGEOVER
If the system is running in one mode and the majority of calls changes to the other mode, a timer will start. The RMOD will give the current operating mode another 4 minutes to try to satisfy the zone(s). It will then go into the purge cycle before switching modes to the majority.
PURGE MODE
When a heat or cool call is satisfied, or before changing modes, the RMOD will go into a 3-minute purge cycle. The call for heat or cool will be removed, and the dampers close.
VENTILATION MODES
The RMOD can be field configured for FAN Constant in the Occupied mode or FAN Automatic. When all zones are satisfied, dampers will modulate to 50% open.
EMERGENCY HEAT
Selected by the on-board switch or remote switch.
COMMUNICATION FAILURE
If the RMOD loses communications, it will then control the HVAC unit based on the return air temperature. The RMOD will maintain 70°F heat and 75° F cool as measured by the MIX Air sensor in the return air.
TEMPERATURE LIMITS AND STAGING
The RMOD monitors the leaving air temperature for staging and Hi /Low
145° F. Staging is based on the limit settings.
Gas Electric & Heat Pump
Example:
Gas Electric Heating W2 cut-in temperature is high limit minus 15° F (145° - 15°
= 130° F). The W2 cut-out is cut-in plus 10° F (130° + 10° = 140° F). Example: Adjustable high limit = 145° F W2 Cut-in = 130° F (high limit minus fifteen) W2 Cut-out = 140° F (cut-in plus ten) W1 cut out = 145°
Heat Pump Heating – When the RMOD is configured for HP operation, the high
cut-out is automatically set to 121°.
• W2 energizes when the SA temperature is 88° or less after 4 minutes of run time. W2 de-energizes when the SA temperature rises to 100°.
• Y2 energizes when the SA temperature is below 100° after 2 minutes of run time and de-energizes above 115°.
• Y1 cuts out for 4 minutes when the SA temperature is above 120°.
TEMPERATURE LIMIT ADJUSTMENT
The high and low cut-out temperatures are field adjustable.
HVAC unit operation.
RMOD SEQUENCE OF OPERATION
of operation. Adjustable factory limits are 45°F cool and 145°F heat.
set for 121° heat.
air temperature. If the leaving air temperature is above 55° F, then Y2 will energize. Y2 will stage off at 47° F and Y1 will stage off on low temperature at 45° F. Four-minute minimum run and four-minute off delays are
limit. The adjustable factory low limit is 45° F and the high limit is
Cooling Y2 cut-in temperature is low limit plus 10°F (45°+ 10°= 55°F). The Y2 cut-out is cut-in minus 8° F (55° – 8° = 47° F).
Adjustable low limit = 45° F Y2 Cut-in = 55° F (low limit plus ten) Y2 Cut-out = 47° F (cut-in minus eight)
NOTE: The RA and LV AIR sensors (P# LAT) must be installed for
23
Page 24
RMOD TERMINAL DIAGRAM
TERMINAL DESIGNATIONS
TX – Data transmit RX – Data receive
RA – Return air sensor
Gas/Electric G – Fan output W2 – Stage 2 heat output W1 – Stage 1 heat output Y2 – Stage 2 cool output Y1 – Stage 1 cool output R – 24vac from HVAC unit transformer
Heat Pump G – Fan output W2 – Aux heat output O/B – Reversing valve signal Y2 – Stage 2 compressor Y1 – Stage 1 compressor R – 24vac from HVAC unit transformer
R – 24vac power input C – 24vac power common
LV AIR – Supply Air sensor input
R45 – RA calibration R52 – LV AIR calibration
LEGEND
LEAVING AIR TEMPERATURE DISPLAY, TO DISPLAY RETURN TEMP,
1
HOLD BOTH HEAT/COOL BUTTONS
2
SENSOR CALIBRATION:
R52 SUPPLY AIR TEMP R45 RETURN AIR TEMP
3
HEAT (UP) / COOL (DN) / ADDRESS BUTTON
MAIN CONTROL CHIP
4
2-PIN SELECTABLE HEAT PUMP/GAS ELECTRIC (JUMPED FOR HEAT PUMP)
5
O/B MODE SELECT (JUMPED “O” OUTPUT IN COOLING)
6
STATUS LEDs - PWR1, Y1, Y2, W1 and O/B, W2, G
FAN JUMPER:
7
CENTER AND TOP = ON CENTER AND BOTTOM = AUTO FAN
8
EMERGENCY HEAT SWITCH, USED IN HP MODE ONLY
9
TO HVAC UNIT TERMINALS
10
ON/OFF SWITCH
11
SENSOR TERMINALS RA AND LV AIR MUST BE INSTALLED.
24
Page 25
DESCRIPTION
The Zonex Systems RMOD is a microprocessor based digital communi­cating HVAC Relay Module for the ZonexCommander (Plus) system. The RMOD controls Gas/Electric 2-stage heat and cool, as well as Heat Pump, 2-stage cool and 3-stage heat, based on supply air temperature. The RMOD provides high and low limits to protect HVAC system components.
Each RMOD can communicate with up to 20 thermostats. There can be up to 4 RMOD controllers per Command Center; however, each Command Center controls up to 20 thermostats. The total number of thermostats cannot exceed 20 on each Command Center.
The RMOD and corresponding ModStats must be configured into the ZonexCommander (Plus) system before the RMODs will communicate. See Installation Guide.
INSTALLATION
RMOD circuit board
The RMOD can be installed with the Command Center or in the HVAC unit it is controlling. It must be protected from the elements in an area where the temperature range is from 25° to 125° non-condensing. DO NOT install the Command Centers or RMODs in close proximity to large transformers, VFDs, or any device that produces electrical energy fields.
1. Install the RMOD where it can be properly accessed.
3. The RMOD is shipped from the factory to operate in the Gas Electric
mode. For Heat Pump operation, place the HP jumper tab over both pins.
4. For Heat Pump “O” reversing valve operation the O/B jumper tab is on one pin. For reversing valve “B” operation, place the jumper tab over both pins.
intermittent fan. For Constant FAN in the Occupied mode, place the jumper tab over the middle and upper pins (ON).
of the bypass
take-off.
bypass take-off (Gas Electric), or between the indoor coil and strip heat elements (Heat Pump AHU).
Addressing & Calibration
button until the correct address appears, and release.
2. Energize the FAN only and check RMOD display calibration.
adjust calibration.
4. Return air temperature is displayed when the UP and DN buttons are
holding down these buttons.
Wiring
8740).
any other ac voltage wiring; it must be run completely separate. Use
switch to the EM terminals on the RMOD.
The RMOD is ready to be configured in the ZonexCommander (Plus) program. See Installation Guide.
RMOD UNIT DESCRIPTION / INSTALLATION
HVAC UNIT CONTROLLER
2. The RMOD is powered by the Command Center transformer by daisy chaining the 24vac from Command Center to the RMOD. You will need to properly size the transformer to the total number
of dampers on the system.
3. When the sensor leads are too short, you may extend the wire with 18 AWG thermostat wire.
1. Set the address for the RMOD (92, 93, 94 or 95) by switching the RMOD to ON from S1, and press the ADR button. To change the address from 92, continue to hold the ADR button; and press the UP
3. Constant display indicates supply air temperature. Rotate R52 to
pressed simultaneously. Rotate R45 to adjust the calibration, while
1. Connect the twisted pair communication wires to RX and TX (Belden
NOTE: The twisted pair communication wire cannot be installed with
shielded twisted pair (Belden 8450) if there is any potential
for electrical interference.
2. Connect the Return Air sensor to the RA terminal screw block.
3. Connect the Supply Air sensor to the LV Air terminal screw block.
5. Set the FAN jumper tab (JPR1) on the center and lower pin (AUTO) for
Sensors – Supply and Return (LAT)
1. Install the RA sensor (LAT) in the return duct, ahead
2. Install the LV AIR sensor (LAT) in the supply duct ahead of the
4. Connect the RMOD outputs to the HVAC system.
5. If Emergency Heat is to be controlled by a remote switch, wire a SPST
25
Page 26
RMOD WIRING OVERVIEW
All RX communication wires must be connected to the RX terminals.
All TX communication wires must be connected to the TX terminals.
The RX and TX wires should never intersect.
26
Page 27
RMOD (RELAY MODULE) TO UNIT WIRING DIAGRAM
• Minimum 18 AWG thermostat wire.
• Y2 & W2 terminals are not used for gas/electric single stage units.
• SA (supply air sensor) controls low and high temperature limits and heat/cool staging.
• RA (return air sensor) controls unit operation in communication failure mode.
• Keep sensor wires and power wires separate.
NOTE: Shorted wiring or sensors cause a low temperature reading. Open wiring or sensors cause a high temperature reading.
• Use 18 AWG. for RA & LV.
• Part# LAT for all sensors.
27
Page 28
SENDCOM DESCRIPTION
DESCRIPTION
The Zonex Systems SENDCOM is a microprocessor based, communicating air duct temperature sensor. The SENDCOM is used to display the discharge air and return air temperature of a single HVAC unit. The temperatures are displayed within the ZonexCommander software on the REVIEW page. Double Click on Current Room Temp where a SENDCOM is attached to display duct temperatures.
SENDCOM Communicating Duct Temperature Sensor – Part # SENDCOM
SENDCOM
1. The SENDCOM communicates both supply and return temperatures,
and is mounted directly to the supply trunk or plenum of the HVAC unit.
2. The SENDCOM must be mounted in a dry, protected atmosphere not
subject to the elements.
3. Locate the position of the SENDCOM enclosure with the attached supply air sensor, on to the supply duct or plenum.
4. Drill a 1/4” hole for the sensor and attach the SENDCOM assembly so that the sensor fits through the 1/4” hole.
5. Attach the SENDCOM assembly to the duct or plenum with the sheet metal screws provided.
6. Locate the position in the return duct or plenum for the return sensor and drill a 1/4” hole.
sheet metal screws, and extend the sensor wire to the SENDCOM
8. Connect the shield conductor of the return air sensor lead wire to – on the RA terminal block.
9. Connect 24 volts using 18 AWG wire minimum, to the “R” and “C” terminals of the SENDCOM. Power can be taken from the HVAC unit
10. Connect the communication wire to RX and TX. The communication wire must be separate from any 24-volt or higher wiring.
NOTE: After setting the address switches, cycle power to the
SENDCOM to set the address.
TERMINAL FUNCTIONS
7. Install the sensor assembly labeled LAT SENSOR with the provided
RA terminal block.
control transformer.
11. Each SENDCOM must be addressed to the corresponding stand
alone thermostat. Determine the thermostat address to which
the SENDCOM is applied and add 70 to that address. Press and hold the ADR button, and then press the UP or DN button to raise or
lower the displayed address number (see Page 29).
28
Page 29
12. Set the individual SENDCOM address to correlate to the thermostat
for that HVAC unit.
EXAMPLE: If the DIGICOM or DIGIHP thermostat has an address of 01, to address the SENDCOM, add 70 to the address number of thethermostat. This makes the SENDCOM address 71. If the address on the DIGICOM or DIGIHP is 02; add 70 to make the SENDCOM address 72, etc. Applications with ZonexCommander (Plus) will not use SENDCOMs to see supply and return air temperatures. These are reported from the RMODs and will be seen on address 1, 2, 3, and 4 current room temperatures. On ZonexCommander (Plus) systems a SENDCOM cannot be addressed for thermostats 1, 2, 3, or 4, so start addressing any stand alone equipment in a ZonexCommander (Plus) system at 75.
13. The SENDCOM is calibrated at the factory but can be field calibrated
tiometer for return air.
SENDCOM DESCRIPTION
171 272 373 474 575 676 777 878
979 10 8 0 11 8 1 12 8 2 13 8 3 14 8 4 15 8 5 16 8 6 17 8 7 18 8 8 19 8 9 20 9 0
ADDRESSING
Determine the thermostat address to which the SENDCOM will be
by adjusting the R2 potentiometer for Supply Air or the R10 poten-
THERMOSTAT
ADDRESS SENDCOM
TENS ONES
applied, and add a value of 70.
29
Page 30
RLYCOM DESCRIPTION
DESCRIPTION
The Zonex Systems RLYCOM is a communicating relay module, which provides programmed on and off schedules for auxiliary devices such as blowers, fans, lighting, etc. As with the communicating thermostats, the Commander Schedule program provides up to 4 Occupied/Unoccupied events per day for each RLYCOM, including vacation days. The control status of the RLYCOM is displayed on the REVIEW screen of the Commander program.
The RLYCOM consists of 2 SPDT relays for controlling auxiliary devices such as lighting, blowers, etc. The relay contacts are designed for 24vac circuits only, with a maximum one amp load. Power for the RLYCOM is provided by a separate 24vac 40va transformer.
The RLYCOM requires a unique address from 01 to 20 (except Zonex Commander (Plus) 05-20). Communication is through the RS-485 twisted pair wire.
OPERATION
When the RLYCOM is in the Occupied mode, the on-board relays are energized. In the Unoccupied mode, the relays are de-energized. The mode status is displayed on the REVIEW screen of the Commander program and on the RLYCOM circuit board. On the Commander
is displayed with a RED “0” in the Unoccupied Heat column. Unoccupied mode is displayed with a BLUE “0” in the Cool Unoccupied column. The mode is displayed on the RLYCOM circuit board with the red PWR LED. When the LED is illuminated, the device is in the Occupied Mode. When the LED is OFF, the RLYCOM is in the Unoccupied mode. The mode can
The SPDT relays are dry contacts for maximum 2 amp 24-volt circuits only.
RLYCOM Communicating Relay Module – Part# RLYCOM
The RLYCOM address is selected by simultaneously pressing the
ADDR button and either the UP or DN button to raise or lower the
address.
program the RLYCOM is displayed with a row of 0’s. Occupied mode
be changed manually at the RLYCOM by pressing the Toggle button. The mode can also be changed from the Commander program from the
SYSTEM tab.
30
Page 31
Zonex Systems zone dampers are used in cooling/heating systems to provide room by room zone control. The damper is provided
zone damper is controlled by a zone thermostat. More than one damper can be controlled by one zone thermostat. Use this table to determine which zone dampers to use.
ROUND MEDIUM PRESSURE ZONE DAMPERS
Zonex Systems round medium pressure zone dampers are recommended for systems with a maximum differential static pressure up to 1.75”. This modulating power open/power close damper is manufactured from 20-22 gauge galvanized steel with rolled-in stiffening beads for superior rigidity. Mechanical minimum and maximum set stops are provided and easily adjustable. The damper is elliptical, which allows the airflow to be tracked linearly. The damper pipe is furnished with one crimped end and one straight end for easy installation. Do not install damper in an inverted position.
ROUND MEDIUM PRESSURE DAMPER PART NUMBERS AND SIZES
TYPICAL ROUND CAPACITIES
These air quantities were derived from a duct sizing chart 0.1” friction loss per 100’ of duct. All CFMs listed are approximate. For accurate selection use duct sizing table or device.
MEDIUM PRESSURE (STMPD)
MODSTAT
ZONE DAMPERS
Maximum Differential Pressure refers to the maximum static pressure drop in inches of water column between the input (upstream) of the zone damper and the output (downstream) when the damper is closed.
DAMPER TO MODSTAT WIRING
with a factory mounted actuator. Each
STMPD ROUND MEDIUM PRESSURE 1.75” ANY SIZE 18”
STMRTD RECT. – MED. PRESSURE
DAMPER MODEL
STCD RECT. – HEAVY DUTY 1.75” ANY SIZE 48”W x 48”H
D-FUSER 0.1” ANY SIZE 10”
A hat section supports a reversing, 24vac, 60Hz, 2 VA motor. A magnetic clutch allows for continuous power to the motor and longer motor life. Motor drive time from
full open to full close is 90 seconds.
MAXIMUM
DIFFERENTIAL
PRESSURE
1” 7.5 TONS 24”W x 20”H
MAXIMUM
SYSTEM SIZE
MAXIMUM
DUCT SIZE
ROUND DIMENSIONAL DATA
PAR T #
L
D
W
STMPD06 STMPD08 STMPD10 STMPD12 STMPD14
STMPD16
STMPD18
SIZE
6
8 10 12 14
16
18
D
6"
8" 10" 12" 14" 16"
18" 20" 21"
L
10" 10" 12" 14"
16" 18"
W
11" 13" 15" 17" 19"
9"
Duct
Diameter
10” 12” 14” 16”
6” 8”
Nominal
CFM
110 250 410
660 1000 1450
Duct Velocity
FPM
540 700 750 850 925
1070
18” 2000 1100 .036
Damper
ΔP
WC
"
.014 .015 .015 .022 .035 .036
31
Page 32
MEDIUM PRESSURE RECTANGULAR DIMENSIONAL DATA
Part Number STMRTD W x H Sizes available from 8” x 6” up to 24” x 20”
HEAVY DUTY RECTANGULAR DIMENSIONAL DATA
Part Number STCD W x H Sizes available from 8” x 8” up to 48” x 48”
Zonex Systems rectangular heavy duty dampers are recommended for systems
7.5 tons or larger with a maximum differential static pressure of 1.75”. These are power open, power close dampers made of 20 gauge “snap­lock” steel frame with S & Drive duct connections. Allow a 16 inch gap in the duct for the damper. Formed steel blade stops incorporate a gasket for quiet operation and improved structural rigidity. Rectangular dampers under 10” in height incorporate a single blade design. Dampers 10” or over use opposed
RECTANGULAR ZONE DAMPERS
The rectangular zone dampers come in either medium pressure or heavy duty. For systems under 7.5 tons use medium pressure dampers. For systems 7.5 tons or over use heavy duty dampers. Motor drive time open and close is 90 seconds.
RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS
Zonex Systems rectangular medium pressure dampers are recommended for systems under 7.5 tons with a maximum differential static pressure of 1”.
MEDIUM PRESSURE (STMRTD) AND HEAVY DUTY (STCD) RECTANGULAR DAMPERS
ZONE DAMPERS
RECTANGULAR HEAVY DUTY ZONE DAMPERS
These are fully modulating power open, power close dampers. They are constructed from heavy duty aluminum and stainless steel. The damper is an opposed blade type that slips into a 3-1/4 inch wide cutout in the existing duct and attaches with screws via a duct mounting plate. The duct
mounting plate is 5 inches wide. A hat section supports a reversing 24vac, 60 Hz, 2 VA motor. A magnetic clutch allows for continuous
power to the motor and longer motor life. Two set screws connect the motor
to the damper shaft, allowing quick motor replacement, if necessary.
Motor drive time from full open to full close is 90 seconds.
blade design. A full stall motor, drawing 2 VA, drives the motor from full open to full close in 90 seconds.
2-1/4”
W
2-1/2"
MOTOR
B
16
WIDTH HEIGHT
A
5"
H
48” MAXIMUM WIDTH
DEPTH
B 16”
2.5”
A
32
Page 33
6” Neck Vel 400 500 600 700 800 900
ΔP 0.011 0.016 0.023 0.035 0.04 0.055
CFM 80 98 120 135 157 176
Throw 50 FPM 4’ 4’ 5’ 6’ 6’ 7’
8” Neck 400 500 600 700 800 900
ΔP 0.019 0.03 0.045 0.056 0.041 0.093
CFM 140 170 207 247 280 315
Throw 50 FPM 5’ 6’ 7’ 8’ 9’ 10’
10” Neck Vel 400 500 600 700 800 900
ΔP 0.029 0.045 0.066 0.09 0.12 0.146
CFM 218 273 330 382 438 497
Throw 50 FPM 6’ 8’ 9’ 10’ 11’ 12’
D-FUSER ZONE DAMPER
Zonex Systems D-Fuser is a combination zone damper and diffuser. It mounts in a standard 2’ x 2’ T-bar ceiling opening, providing for simple installation and easy maintenance access. The D-Fuser is a cone shaped fluidic nozzle with a platen that modulates up and down to control air
and throw remain constant. This keeps the air hugging the ceiling which maximizes room air mixing and minimizes the “waterfall” effect.
ZONE DAMPERS
RECTANGULAR DAMPER CAPACITIES*
Dampers listed below are standard sizes. For larger sizes and capacities contact the factory.
*
These air quantities were derived from a duct sizing chart .1” friction loss per 100’ of duct. All CFMs listed are approximate. For accurate selection use duct sizing table or device.
AT NECK VELOCITIES UP TO 700 FPM
NC LESS THAN 30
flow. As the platen moves up, the air volume is reduced but the air velocity
The D-Fuser is a fully modulating power open, power close damper
using a 24vac 60Hz 2 VA motor. Motor drive time from full open to
full close is 90 seconds. The D-Fuser connects to round duct either on
the side or top. Collars are available for 6", 7", 8", 9" and 10" duct.
COLLAR:
12”
12”
2”
24”
PLACE ON SIDE OR TOP
33
Page 34
SIZING ZONE DAMPERS
If the ductwork already exists, simply size the damper to fit the ductwork. For new systems or retrofit jobs:
a) Determine CFM from heat gain or loss calculations. b) Select damper size using either the round capacities chart, the
rectangular capacities chart or by using a duct sizing table or calculator.
c) Select a Zonex Systems damper to fit the duct size selectedfor
that zone. Make sure your zone dampers match the type specified in the table showing Maximum Differential Pressure.
INSTALLATION NOTES
1. Do not exceed 700 FPM in a register/diffuser branch duct.
2. If a damper is installed within 3 feet of register/diffuser, install sound attenuating flex duct between damper and outlet.
3. Zone dampers should be preceded by 2’-4’ of straight pipe where possible.
4. In attic installations and high humidity areas, the Zonex Systems damper should be insulated along with the duct work. The hat section on the round damper is delivered with insulation between the hat section and pipe. Therefore, insulation should be applied to the round pipe and be butted against the hat section, (do not insulate the motor). The motor generates enough heat so that no condensation will develop on it.
5. Remember to allow a 16-inch gap in the duct for Heavy Duty rectangular dampers.
6. Medium pressure rectangular dampers slide into a 3
1
4-inch wide
cutout in the side of the preexisting ductwork.
NOTE: Dampers should not be installed with motor upside down in the 6:00 position.
Up to three dampers can be directly controlled by one thermostat. To wire two to three zone dampers to one thermostat, use the following diagram shown. Remember to size the damper power
SLAVING MORE THAN THREE ZONE DAMPERS
Use the following diagram when a thermostat will be controlling more than three zone dampers. Use an
power the slaved dampers.
ZONE DAMPERS
SLAVING UP TO THREE ZONE DAMPERS
transformer for the total number of zone dampers. Each actuator
draws 2 VA.
7. Minimum open and close positioning is field adjustable on the
actuator. The damper is shipped from the factory to close 100%.
ZONE DAMPER
RC
ZONE DAMPER
MC R O
RCMC R O
ZONE DAMPER
MC R O
RC
additional 24V transformer sized at 2VA per damper to
34
MC R O RC
MODSTAT
SIZE TRANSFORMER AT
2VA PER DAMPER
Page 35
ELECTRONIC BYPASS DAMPERS
Bypass dampers are used to provide constant air delivery through the air handling unit. This is done by bypassing excess air from the supply duct back to the return duct. As a zone is satisfied its zone damper closes. When this happens, the bypass damper opens just enough to bypass the excess air. This will control static pressure and noise at the diffusers.
The Electronic Bypass Damper is used on any size system over 5 tons. The damper can be round or rectangular and multiple dampers can be slaved together. The Electronic Bypass Damper consists of a medium pressure round or a heavy duty rectangular damper and a static pressure sensor.
SIZING ELECTRONIC BYPASS DAMPERS
The bypass damper is to be sized for the total system CFM @1500 FPM. System CFM should be calculated at 400 CFM per ton. Example: A 5-ton system is rated at 2000 CFM (5x400 = 2000). When calculated at 1500 FPM, the bypass damper should be 16”. Never undersize the bypass damper.
ROUND BYPASS DAMPER SELECTION
The Zonex Systems STMPD damper is used for round bypass applications. When you know the bypass CFM requirements, use the ROUND BYPASS SELECTION TABLE to confirm the round damper size. NOTE: multiple round dampers can be slaved from one static pressure control to provide the correct capacity. One large rectangular bypass damper may be used instead of multiple round dampers. See below.
RECTANGULAR BYPASS DAMPER SELECTION
The Zonex Systems STCD WxH damper is used for rectangular bypass applications. These dampers are also sized for the total system CFM rated at 1500 FPM. Multiple dampers can be slaved from a single static pressure control.
RECTANGULAR & ROUND BYPASS DAMPER
WITH THE STATIC PRESSURE CONTROL
BYPASS DAMPERS – ELECTRONIC
Diameter CFM
8” 560 10” 900 12” 1250 14” 1700 16” 2200 18” 2600
ROUND BYPASS SELECTION TABLE
PART # SIZE D L W STMPD08 8 8" 10" 11" STMPD10 10 10" 12" 13" STMPD12 12 12" 14" 15" STMPD14 14 14" 16" 17" STMPD16 16 16" 18" 19" STMPD18 18 18" 20" 21"
L
D
W
RECTANGULAR BYPASS DAMPERS
SELECT FROM 8 X 8 THRU 48 X 48
H
D
WIDTH HEIGHT
35
H 16”
W
PART # STCD W x H
48" MAXIMUM WIDTH
W
DEPTH
4"
Page 36
Bypass air in CFM. Calculated at 1500 FPM. Formula used: B = W X H / 144 X 1500, where B = Bypass air in CFM, W = damper width in inches, H= damper height in inches, 144 = 144 sq. inches per sq. ft., 1500 = 1500 FPM.
BYPASS POSITION INDICATOR
SLAVING BYPASS DAMPERS
Use only one Pressure Sensor when slaving two or more Bypass Dampers together. Connect the Pressure Sensor to one damper as described above. Connect the slave dampers in parallel as shown. Up to 4 dampers can be slaved to one Sensor. The slaved dampers will self synchronize each time the dampers reach full open or full close.
24 28 32 36 40 44 48
8 2000 2333 2667 3000 3333 3667 4000
10 2500 2917 3333 3750 4167 4583 5000
12 3000 3500 4000 4500 5000 5500 6000
14 3500 4083 4667 5250 5833 6417 7000
16 4000 4667 5333 6000 6667 7333 8000
18 4500 5250 6000 6750 7500 8250 9000
20 5000 5833 6667 7500 8333 9167 10000
22 5500 6417 7333 8250 9167 10083 11000
24 6000 7000 8000 9000 10000 11000 12000
28 7000 8167 9333 10500 11667 12833 14000
32 8000 9333 10667 12000 13333 14667 16000
36 9000 10500 12000 13500 15000 16500 18000
40 10000 11667 13333 15000 16667 18333 20000
44 11000 12833 14667 16500 18333 20167 22000
48 12000 14000 16000 18000 20000 22000 24000
8 10 12 14 16 18 20 22
8 667 833 1000 1167 1333 1500 1667 1833
10 833 1042 1250 1458 1667 1875 2083 2292
12 1000 1250 1500 1750 2000 2250 2500 2750
14 1167 1458 1750 2042 2333 2625 2917 3208
16 1333 1667 2000 2333 2667 3000 3333 3667
18 1500 1875 2250 2625 3000 3375 3750 4125
20 1667 2083 2500 2917 3333 3750 4167 4583
22 1833 2292 2750 3208 3667 4125 4583 5042
24 2000 2500 3000 3500 4000 4500 5000 5500
28 2333 2917 3500 4083 4667 5250 5833 6417
32 2667 3333 4000 4667 5333 6000 6667 7333
36 3000 3750 4500 5250 6000 6750 7500 8250
40 3333 4167 5000 5833 6667 7500 8333 9167
44 3667 4583 5500 6417 7333 8250 9167 10083
48 4000 5000 6000 7000 8000 9000 10000 11000
WIDTH IN INCHES
HEIGHT IN INCHES
BYPASS DAMPERS – ELECTRONIC
RECTANGULAR BYPASS SELECTION TABLE
ROUND AND RECTANGULAR
BYPASS DAMPER MOTORS
DAMPER
ACTUATOR
**
***
RC RO MC
To Static Pressure Controller As Shown On The Bypass Wiring Diagram On The Next Page.
36
SLAVE
DAMPER
ACTUATOR
*
RC RO MC
TO NEXT SLAVE BYPASS DAMPER IF APPLICABLE
RC RO MC
Page 37
BYPASS DAMPER WITH INTEGRATED PRESSURE CONTROL
Bypass Damper with Integrated Pressure Control is used to control bypass operations. The bypass damper modulates to maintain static pressure as zone dampers open and close. The bypass system reduces air noise from the supply registers caused by excessive air velocity. If the system is configured for intermittent fan mode and the system satisfies, there will be a 3 -minute delay to allow for system purge, after which the bypass damper will open to 25%, preventing noisy rush of air through supply regist ers when fan starts up on a call for heat or cool. If the system is configured for fan continuous operation, the STBP (Round) or
STCDBP (Rectangular) Electronic Bypass will monitor static pressure continuously, providing constant control of system static.
INTEGRATED PRESSURE CONTROL DESCRIPTION
A. Supply air tube B. 24vac R and C
C. Damper Terminal RO, RC, MC D. LED lights
E. Adjustable Potentiometer F. TP1 Test Point
2. Bypass damper and controller are powered by a dedicated 24vac 40VA transformer.
3. Do not install the bypass damper outside.
4. Locate the Integrated Pressure Control (IPC) and air tube on the bypass damper.
5. Drill ¼” hole into the side of the supply duct 2’ after the bypass and before the 1 pressure supporting block over ¼” hole, align hole in block with hole in duct. Use provide d sheet metal screws.
6. Install air tube into supply air duct by slipping supplied plastic tubing into holes in support block and duct. Slip tube 3” into the duct. Pickup tubing fits snugly into provided hole.
7. Connect pressure tube from static air pickup to Integrated Pressure Controller (port closest to you).
st
supply take-off. Mount
Fig. 1
BYPASS DAMPER INSTALLATION
1. Verify the bypass damper is sized properly to the system and not undersized. (Bypass damper sizing is recommended for 100% of system CFM.)
Fig. 2
BYPASS DAMPER WITH INTEGRATED BYPASS CONTROL SETUP
1. Run all supply dampers to the full open position and have blower motor running at 100% fan speed. (See Note #1)
2. Manually close the bypass damper by pressing in the release lever on the motor side of the actuator. With the release lever pressed, rotate the damper actuator collar to close the damper and release the lever to lock the damper closed.
37
Page 38
BYPASS DAMPER WITH INTEGRATED PRESSURE CONTROL
3. Quick Set Option: Turn the potentiometer on the damper control board to the full left position and slowly rotate RIGHT, until the “RC” RED LED turns on. Now rotate LEFT just slightly, until RC LED turns off. The IPC is ready for operation.
RC” RED LED means damper closing.
RO” GREEN LED means damper opening.
4. Static Pressure Option: The Integrated Pressure Control Board can be field configured for specified static pressure using a multi meter and the static
pressure – voltage chart. (Exhibit A). This chart shows voltage (DC) to inches of W.C. (static pressure) relationship. Use a multi meter set on VDC and place the leads on the “C” terminal and “TP1” (test point one) next to the potentiometer. The Voltage reading translates to inches of W.C.
BYPASS CHECKOUT FOR STATIC
PRESSURE CONTROLLER
1. Make cool call at the zone thermostat of smallest zone.
2. Verify all zone dampers are closed except calling zone.
3. Verify noise at zone registers is not excessive. Adjust the Integrated Pressure Control LEFT to lower noise (airflow) or RIGHT to increase airflow until too noisy.
BYPASS DAMPER WIRING DIAGRAM WITH INTEGRATED BYPASS CONTROL
Note #1: To open all dampers, it may be necessary to
remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats. This will modulate dampers fully open and lock out compressor.
On Zonex Systems balance modes for simplified bypass setup.
GEN II
and
ModCom II
, use air
38
Page 39
6. Please answer the questions as the Installation Wizard is loading.
7. When the Wizard has completed the loading process, confirm the Zonex icon is located on the Desktop: NOTE: A second icon with our trending or Zonex charts icon will also reside on your desktop.
ZonexCommander and ZonexCommander (Plus)
1. Connect USB cable to computer and USB plug on Command Center.
2. Start with Commander program closed, and switch on the Command Center with on/off switch. Verify Command Center is on by the power LED. “Found new hardware” wizard should appear on computer screen.
3. Insert the Driver CD into the CD drive on computer, and follow the installation wizard prompts to install. A. Can Windows connect to Windows Update to search for software?
Select “YES, this time only”
B. “This Wizard helps you install software for: ZonexCommander.
What do you want the wizard to do?” Select: “Install the software
automatically”
C. When the message “ZonexCommander has not passed Windows
logo testing…” Click “Continue Anyway”
D. When the wizard has finished installing the software for the
ZonexCommander, Zonex Commander (Plus), the message “Completing the Found New Hardware Wizard” will appear.
4. Remove the Driver CD from computer.
with COM1, 2, 3 or 4.
it to an open COM1, 2, 3 or 4.
plug on the Command Center.
Center.
Common Ground Phasing procedure. See below.
SYSTEM START-UP PROCEDURE
Installing System Software
1. Place Systems Software Master CD in the CD drive.
2. Click on My Computer.
3. Click on the CD or DVD RW drive; i.e., “D” or “E.”
4. Double click on the Commander..exe file.
5. Click on OK to start the Installation Wizard.
USB Driver Installation for Windows XP and Vista
5. Proceed to Assigning COM Port Instructions (below).
USB Driver Installation for Windows 7777 and 8
1. With the ZonexCommander (Plus) Command Center in the OFF
position, connect the USB cable to the Commander board and USB
port on the computer. Turn on the Command Center. The message,
“New Hardware Found” will appear., followed by “Device Driver
software was not successfully installed.”
2. Click on the
Hardware and Sounds. Locate and click on Device Manager.
Select Other Devices
and note the COM Port assigned. Right click on ZonexCom-
mander,
3. Insert the USB Driver CD into the computer drive, and note which
drive is being used.
Start
menu and select
, and locate the ZonexCommander listing
and then click on
Control Panel
Properties.
. Then select
4. Under the
select “Browse My Computer for Driver Software.”
5. Select the Drive which has the CD installed; and click on
warning may appear; click on
6. After installation, a message will appear, stating “Windows has
successfully updated driver . ”
7. Remove the Driver CD from computer..
8. Proceed to Assigning COM Port Instructions (below).
Assigning COM Port Instructions for Windows 777, 8, XP and Vista
1. From the computer desktop, right click on MY COMPUTER.
2. Select PROPERTIES.
3. Select Hardware on System Properties page.
4. Select Device Manager.
5. On Device Manager page, find COM & LPT ports and expand by clicking on the + next to COM & LPT.
6. ZonexCommander or ZonexCommander (Plus)
7. If the COM assignment is higher than 4, you must manually change
8. Reboot computer.
9. Once computer has restarted, select the ZonexCommander or
ZonexCommander (Plus) icon on display; and click on Connect Now.
10. Select COM1, 2, 3 or 4 from connection settings window.
11. When Connection Successful window appears, click OK.
Continue with system setup and configuration steps in Zonex­Commander Installation manual.
General Tab for properties, click on
“Install the software anyway.
Update Drivers;;;
Next.
should be listed
Connecting to the System
Direct Connect - Computer connected directly to a single Command
Center.
NOTE: It is recommended to first set up and configure a new system
with a direct connected computer (laptop or desktop), and verify oper-
ation.
Setup
Zonex Commander/Commander (Plus) (CETCIP / ZPTCIP)
1. With the Command Center switched OFF and the Commander
program closed, connect the 6’ USB cable to computer and USB
2. Switch the Command Center ON, and then bring up the Commander system program on the computer.
3. Remove the insulating tag from the backup battery on the Command
4. With all components wired, addressed and powered up, perform the
A
39
Page 40
Program Screens
The Zonex software provides 6 tabbed screens for System status and configuration. If you are installing ZonexCommander (Plus) to control multiple zoned units, your software is equipped with 7 tabs:
Welcome Tab Use to connect to the system. Review Tab Display total number of thermostats and devices, along with current space and heat/cool setpoint temperatures. Schedule Tab Assign Occupied and Unoccupied events for each thermostat and RLYCOM in the system. Set Temp Tab Enter Occupied and Unoccupied, Heat and Cool temperatures remotely for selected thermostats. System Tab To access or set the Day, Date, and Time – display Outside air on all systems, Mixed air (return) and Leaving air (supply)
temperature warning alert and temperature trending.
Vacation Tab Assign up to 20 vacation/holiday events for each thermostat and RLYCOM. Zoned Units Tab Used only with ZonexCommander (Plus), allocates thermostats to their respective units when multiple units are included in the system.
SYSTEM START-UP PROCEDURE
COMMON GROUND PHASING PROCEDURES
1. With the ModStats powered up, set voltmeter to the AC scale.
2. Separate the thermostat circuit board and cover from the terminal base.
3. Place one meter probe on the RX terminal and the other probe on the R terminal - note the voltage reading.
4. Keeping one probe on RX, place the other meter probe on terminal C and note the voltage reading.
5. The lowest voltage reading must be on the RX to C terminals.
6. If the low voltage reading is measured on RX to R, reverse the R and C wires on the thermostat terminal base.
7. If erratic voltages are read, contact Technical Support.
temperatures on SYSTEMS TAB – Number of thermostats and devices (RLYCOM) – Override for Occupied / Unoccupied modes – Enter names or tags for thermostats and other devices – Thermostat lock feature –
40
Page 41
Accessing the Systems
WELCOME Screen – Fig. 1
Double click on the Zonex icon to open the program’s WELCOME screen
(see Fig. 1)
Setting a Password (Optional)
If a password is required, it may be entered now or at a later time. If you do not require a password and do not need to add or modify a device, proceed to Connecting to the Zonex System section below.
1. Click on the Password Maintenance button on the lower right side
of the WELCOME screen. (see Fig. 2)
2. Enter your new password. The password must not exceed 30 characters and spaces. NOTE: the password only affects the computer on which it is entered.
3. Re-enter your password in the Verify box.
4. Click on OK to store the password. NOTE: Your password should be retained elsewhere. If it is lost, the program will have to be re-installed and all information re-entered.
Adding, Modifying or Deleting Records
To add or change a project name, phone number or IP address:
1. Add a record:
a. Click on the Connect Now button from the WELCOME screen. b. Verify that the Connection Settings window appears (see Fig. 3).
c. Click on Commander Job and Installation Contacts button. d. Verify that the Contacts window appears (see Fig. 4).
e. Click on Records. f. Click on ADD (see Fig. 5); and enter new project name, phone
number for the dedicated phone line to this job or IP address and port number, if applicable. Multiple facilities may be accessed from this software.
g. Click on File; then click on Save. h. Click on Exit to return to the WELCOME Tab.
SYSTEM START-UP PROCEDURE
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
41
Page 42
2. Modify an existing record:
a. Click on the Connect Now button from the WELCOME screen. b. Verify that the Connection Settings window appears. c. Click on Commander Job and Installation Contacts button. d. Verify that the Contacts window appears (see Fig. 4). e. Use the Scroll buttons (<< or >>) at the bottom right of the
Contacts screen to locate the record to be modified.
f. Click inside the field to be changed, and revise data. g. Click on File; then click on Save. h. Click on Exit to return to the WELCOME Tab.
3. Delete a record:
a. Click on the Connect Now button from the WELCOME screen. b. Verify that the Connection Settings window appears. c. Click on Commander Job and Installation Contacts button. d. Verify that the Contacts window appears (see Fig. 4). e. Use the Scroll buttons (<< or >>) at the bottom right of the
Contacts screen to locate the record to be deleted.
f. Click on Records. g. Click on Delete. h. Click on File; then click on Save. i. Click on Exit to return to the WELCOME Tab.
Connecting to the Zonex System
1. Click on the Connect Now button from the WELCOME screen
(see Fig. 6).
2. Verify that the Connection Settings window appears (see Fig. 7).
4. Click on the Connect button (see arrow in Fig. 7). The screen then
displays: Please wait while system is loading (see Fig. 8). The connection should complete within 30 seconds and is verified when the Connection Successful window appears.
5. Click on OK in the Connection Successful window (see Fig. 9).
SYSTEM START-UP PROCEDURE
Fig. 8
Fig. 6
Fig. 7
Fig. 9
For International systems equipped with Celsius thermostats, you may now select a Celsius temperature display by clicking the box labeled "Click here for Celsius." If you are not using Celsius thermostats, please ignore this step. Each time you enter the program, this step must be ini­tiated to display Celsius Temperatures.
3. Click on the appropriate COM port or TCP/IP network connection.
42
Page 43
System Setup and Configuration
SYSTEM Screen – Fig. 10
Stats
2. Select the total number of system devices (up to 20 thermostats and
RLYCOMs on the Command Center communication buss).
3. The program is equipped with a System Alarm Deviation function,
establish out of range temperature criteria from 3-10°. Whenever a thermostat exceeds the selected deviation from its heating or cooling setpoints, the current temperature will be highlighted in Yellow on the REVIEW Screen. If this feature is not required, select 00 to disable the alert; otherwise, select the temperature deviation.
4. Click on Send Settings to place this information into memory.
Date/Time
will appear on the upper right of the screen.
2. Click on the right or left arrownext to the month and year to select
the current month or click on today’s date.
3. Click on current day to highlight in gray.
4. Click on the Select Hour and Select Minute down arrow buttons
to select time.
5. Click on the AM or PM radio button.
6. Click on Send Settings to place this information into memory.
7. Verify setting by clicking on the Clock Setting button on the top left
of the screen.
SYSTEM START-UP PROCEDURE
Fig. 10
1. Click on the SYSTEMS Tab, and click on the radio button next to
Stats (see Fig. 11).
1. Click on the Date/Time radio button (see Fig. 12), and a calendar
Fig. 12
Fig. 11
or System warning alert (see Fig. 11), which allows the user to
43
Page 44
SYSTEM START-UP PROCEDURE
Stat Name
Do not exceed 20 characters and spaces on each entry.
2. Click on Send Settings after typing each address to place it into
memory. Confirm that entries have been saved by clicking on the REVIEW Tab; then return to the SYSTEMS Tab to continue labeling the thermostats.
Occupied Mode
2. Select Global, and click on Send Settings. This is to ensure all
devices are in the Occupied mode for the start-up. Settings can be changed to Unoccupied Mode after initial setup.
Lock/Unlock Thermostats
2. Select the thermostat from the drop down menu, or click on Global to
lock or unlock all thermostats, or select an individual address to lock.
3. Click on Send Settings to place this information into memory.
4. Confirm your lock/unlock request by returning to the REVIEW Tab. If the thermostat number you selected is Red, it is locked; if it is Black, it is unlocked. If necessary, repeat the sequence above to change to desired setting.
Reviewing System Data
1. Click on the REVIEW Tab at the top of the screen to verify thermostat,
2. Verify that the number of thermostats and devices (upper left of screen) is correct.
3. Occupied and Unoccupied temperature setpoints and space temperatures should be displayed in each address row.
NOTE: If any thermostat shows “0” across the row, there is no com­munication with that thermostat. See the Troubleshooting section.
1. Click on the Stat Name radio button (see Fig. 13), and enter 1. Click on the Lock/Unlock radio button to lock or unlock thermostats individual thermostat names, RLYCOM, or SENDCOM designations. remotely (see Fig. 15).
Fig. 13
1. Click on the Occupied Mode radio button (see Fig. 14).
Fig. 15
Fig. 14
SYSTEM Screen – Fig. 16
RLYCOM and SENDCOM communications (see Fig. 16).
Fig. 16
44
Page 45
SYSTEM START-UP PROCEDURE
4. RLYCOM devices, if utilized, control generic loads and will be displayed with a Red “0” when energized and a Blue“O” when off.
a. A Red “0” should appear in the Unoccupied Heat column, which
indicates the RLYCOM is energized. (During setup, all devices were set to Occupied mode.)
c. If all of the RLYCOM “0’s” are Black, the device is not commu-
nicating. See the Troubleshooting section.
5. To test the RLYCOM operation and communications, switch to the Unoccupied mode and verify the result, as follows:
a. Note the address number of the RLYCOM to be tested.
b. Click on the SYSTEM Tab, and click on the Unoccupied mode
radio button.
c. When the address window appears, select the address assigned to
the RLYCOM being tested.
d. Click on Send Settings.
e. Return to the REVIEW Tab, and verify the RLYCOM has changed
to a Blue “0” in the Unoccupied column. The power light on the RLYCOM should be off.
f. After testing, you may wish to adjust the mode back to the
original setting.
6. SENDCOM communications are used to display RA/SA temperatures from stand-alone units.
a. Place the cursor directly over a Current Room Temperature
thermostat number with a SENDCOM attached; and double click
b. The Read Sensors window will appear, displaying Discharge
and Return Air temperatures. If a single “0” is displayed for both sensors, or if the temperature appears to be incorrect, see the Troubleshooting section.
7. For multiple Command Centers repeat the above steps in this section for each Command Center.
Additional Information Displayed on the REVIEW Screen
1. Click on the thermostat number to confirm that the thermostat is in
This feature is not available with a RLYCOM. Its status is indicated by a Red “0” for either ON or HOT (Occupied) and a Blue “0” (for OFF or de-energized.).
2. Click on a thermostat name to display Schedules after they have been
3. Click on the Legend button for an explanation of activities displayed
b. A Blue “0” in the Unoccupied Cool column indicates the
RLYCOM is either off or de-energized.
the Occupied or Unoccupied mode (see Fig. 18).
Fig. 18
entered (see Fig. 19).
on it (see Fig. 17).
Fig. 17
Fig. 19
on the REVIEW Screen (see Fig. 20).
Fig. 20
45
Page 46
SYSTEM START-UP PROCEDURE
4. The REVIEW Screen is dynamic and automatically updates every three
minutes. To initiate an immediate update, click on the Refresh Thermostat button.
5. To print a copy of the REVIEW Screen, which displays all current temperature data, as well as a date and time stamp, click on the Print button.
Thermostat Management
Everything the on-site user can perform at the thermostat can be performed remotely on the SET TEMP screen. The SET TEMP screen displays a thermostat feature, which allows the Heat and Cool setpoints to be changed on individual or all (global) thermostats, for either Occupied or Unoccupied modes.
1. Click on the SET TEMP Tab.
2. To change temperature setpoints on all thermostats, click on the
3. To change an individual thermostat, click on the Individual radio button.
NOTE: When the Individual radio button is selected, a window will appear with a down arrow button:
a. Click on the down arrow button to display thermostat address
numbers and names, and click on an address.
b.After selecting the desired address, the current Occupied and
Unoccupied temperature setpoints for that thermostat will be
4. After the Individual or Global radio button has been selected,
click on either the Occupied or Unoccupied mode radio button.
5. Click on either the Heat or Cool radio button.
6. To change the temperature, click on the Up or Down buttons on
the thermostat until the desired temperature is displayed.
7. Click on the Send to Thermostat button to place information
into memory.
8. After adjusting setpoints, click on the REVIEW TAB to confirm entries have been saved. If a change did not occur, repeat the sequence above.
Scheduling the System
The ZonexCommander software provides up to four scheduled events each day, for each thermostat. To assign Occupied and Unoccupied schedules:
1. Click on the SCHEDULE Tab.
2. Under Select Thermostat at the top left of the screen, click on the
down arrow button; and select a thermostat from the drop down menu.
SET TEMP Screen – Fig. 21
Fig. 21
Global radio button (see Fig. 22); or,
displayed (see Fig. 23).
Fig. 23
SCHEDULE Screen – Fig. 24
Fig. 22
Fig. 24
46
Page 47
SYSTEM START-UP PROCEDURE
3. Event times can be entered separately for each day or for the entire
week. Click on the All Week radio button. This allows a complete schedule to be assigned to one thermostat for every day of the week. (If, after the week’s schedule has been set, you would like to change one day, see No. 6 below for instructions.)
4. To enter the time schedules on the selected thermostat or RLYCOM address, use the down arrow buttons in each Hour, Minute and AM or PM field to make your selections.
You must make an entry into each time event. If there is no difference in time between the Occupied and Unoccupied modes, select NC (“No Change”) in the appropriate fields.
EXAMPLE: Thermostat 01 will be in the Occupied mode from 6:30 AM until 5:00 PM –
a. Under Day Occupied select 6 in the hour field, 30 in the minute
field, and then AM.
b. Under Day Unoccupied select NC in the hour field (this denotes
“No Change”).
c. Under Night Occupied select NC in the hour field (this denotes
“No Change”).
d. Under Night Unoccupied select 5 in the hour field, 00 in the
minute field, and then PM.
e. Click on Set Schedule to program the schedule into memory.
f. Repeat this process for each thermostat and RLYCOM address.
5. To copy the same schedule to another thermostat or RLYCOM:
a. Click on the Copy Schedule to Thermostat radio button, and
select the destination thermostat address.
b. Click on Set Schedule to copy the schedule to the destination
thermostat.
6. Thermostats and RLYCOMs can have individual schedules for every day of the week. To assign a schedule for one day:
a. Select the thermostat or RLYCOM address from the pull down
menu under Select Thermostat.
b. Click on the radio button next to the day of the week to be
scheduled. Schedule each day individually. After each day’s schedule is entered, click on the Set Schedule button.
7. The schedules can be printed from the SCHEDULE screen:
a. Click on either the Individual or Global radio button below
the Print button. The Global selection will print the schedules for all thermostats and RLYCOMs, and the Individual selection will print a copy of the SCHEDULE screen displayed.
b. Click on Print
. It is recommended that this information be printed
following the start-up of the system.
8. The Individual schedules can also be viewed on the REVIEW screen:
a. Click on the REVIEW Tab.
Vacation Scheduling
The vacation schedule provides 20 separate Unoccupied events for up to 30 days. This feature is designed to maximize your energy savings by placing the thermostat(s) into a 24-hr Unoccupied mode for 1 to 30 days.
To set an event:
1. Click on the VACATION Tab at the top of the screen, and verify all
thermostat and RLYCOM addresses are listed under the column,
2. To enter an Unoccupied day event, click on the down arrow
button in the field showing the event numbers [“Select 1-20”]. Begin by selecting 1 for the first event.
3. Select the Month, Day, and Duration of the event by using the down arrow buttons in the appropriate fields.
4. Click on Set Vacation Schedule.
5. Verify that the event Month, Day and Duration appear in the list on the left side of the screen.
6. Repeat steps 1 – 4 to set each vacation date, using the next available event number.
VACATION Screen – Fig. 25
Fig. 25
Thermostats below on Vacation Schedule (see Fig. 26).
b. Click on the thermostat name (see Fig. 19).
Fig. 26
47
Page 48
To clear an event:
1. Click on the down arrow button in the event number [“Select 1-20”]
field, and select the event number.
2. Click on the down arrow button in the Month field.
3. Click on Clear.
4. Click on Set Vacation Schedule.
To override an event, if you have signage or other units that will operate during a vacation period:
1. In the Thermostats below on Vacation Schedule column, click
on each thermostat address that you wish to override. Notice that, when you click on an address, it moves to the Override Vacation
2. Click on Confirm Override.
To print the Vacation event schedule:
1. Click on the Print button.
Allocating Thermostats to Specific Units for use with ZonexCommander (Plus) only
The ZONED UNITS screen is only applicable to ZonexCommander (Plus) software. It is used to configure, allocate and display thermostats assigned to their specific RMOD controllers. Each Command Center can support up to four RMODs. The RMODs are designated as Units #92 – #95.
1. Click on the ZONED UNITS Tab.
2. Verify that all thermostat/device address numbers appear in the
3. Select the RMOD #92 radio button, and highlight the thermostat address numbers to be assigned to that RMOD (one or more addresses may be highlighted). NOTE: When DIGICOM, DIGIHP thermostats or RLYCOM devices are part of the installation, they must be addressed above #05 (5).
4. Click on Add.
5. It is important to confirm that the correct thermostats are assigned to
6. Repeat steps 1-5 to allocate thermostats to each RMOD.
7. If an address has been assigned in error, simply highlight the address number and click on the Remove button. This returns the thermostat to the Add/Remove column. Reassign the address to the appropriate unit.
8. After all addresses have been assigned to the corresponding RMOD, click on the Set Zoned Units button on the lower left of the screen.
9. Repeat these procedures for each RMOD #93, #94 and #95 when
10. When the hourglass returns to the arrow cursor on the ZONED UNITS
screen, close the ZonexCommander (Plus) program on the computer; and recycle power on the Command Center and RMOD(s).
11. Bring up the ZonexCommander (Plus) program again, and direct-
connect to the system.
12. Go the the REVIEW screen, and verify all termostats are indicating
temperatures.
SYSTEM START-UP PROCEDURE
Schedule column (see Fig. 27).
Fig. 27
Add/Remove left column (see Fig. 28).
that RMOD (see Fig. 29).
Fig. 29
applicable (see Fig. 30).
ZONED UNITS Screen – Fig. 28
Fig. 28
Fig. 30
48
Page 49
13. Double left click on the Current Room Temperature of thermostat
confirms communication with the RMOD.
14. Double left click on the Current Room Temperature on thermostat
15. Click on the ZONED UNITS screen, and verify any DIGICOM, DIGIHP and RLYCOM addresses remaining in the Add/Remove column.
on the Print Units button.
17. RMOD configuration is complete
Activating Trend Logging Data
Trending Thermostat Data
Historical data must be developed in order to trend thermostat information.
1. Click on the SYSTEM Tab.
2. Underneath Use Log File, in the lower right corner of the SYSTEM screen, click on the New radio button to open a new trend log.
3. Click on the Logging button.
4. If you have SENDCOM Sensors in your system:
a. Click on the box labeled Enable RA/SA Sensors (SENDCOM)
Logging. This will open another box, which lists all thermostats
b. Click on thermostats with SENDCOM Sensors to move them to
the right column for inclusion in the trending data.
5. The program must be named and then saved onto your C drive
C:\Program Files\ Zonex Systems.
6. After the logging commences, you may minimize the Zonex program
in order to use other computer functions; but do not turn off the computer or trending program during data collection. This will cause the logging function to cease. Typically, 2-3 days of logging information polled at 20-minute intervals provides you with sufficient data to establish a trend.
Displaying Trending Data
Trending data is displayed in a separate Zonex program called Zonex
Software. A Zonex Trends icon should reside on your Desktop.
1. Click on the Zonex Trends icon.
2. Click on the Select Log file, and retrieve the saved data file. (Using
our example above, we would select C:\Program Files\Zonex Systems; then click on Log Zones).
TREND AND DATA LOGGING OPERATION
#1, to bring up RMOD 92 Supply and Return temperatures. This
#2 for RMOD 93, #3 for RMOD 94 and #4 for RMOD 95.
16. To print the ModStat to RMOD listings for future reference, click
System Requirements: Windows 7,8, XP or Vista are required
to trend log. Not compatible with Windows 95 or 98.
SYSTEMS Screen – Fig. 31
in your system (see Fig. 32).
(see Fig. 33). For example, we saved a file named Log Zones in
Fig. 33
Fig. 31
Trends (see Fig. 34). This program was initially loaded with the Zonex
Fig. 34
Fig. 32
49
Page 50
TREND AND DATA LOGGING OPERATION
3. When the file is retrieved, use the drop down box to select your
4. The data logging program logs data on every thermostat in your
system every 20 minutes. Use the pull down box to select the thermostat you want to analyze.
Enter the From/To date and time range you want to review.
6. You also have the option of viewing the saved data every 20 minutes or hourly; select one option.
7. Click on the Continue button. The trending program will provide
you with a Trend Analysis Chart reflecting the temperatures of the desired thermostat vs. the heating and cooling setpoints during the trending period.
8. The chart displays temperatures from 40-100º in 2º increments on the
9. Different presentations may be prepared by selecting options
listed in the Chart Type drop down box. The initial chart is displayed as a 2d line.
10. A correlation exists between the number of data points and the rows of data displayed. Reducing the number of rows allows you to zoom in on the data.
11. To print the Trending Chart, click on the Print button; or save it in your computer as a bitmap (.bmp), which can be e-mailed easily.
12. To generate additional data for other thermostats in the system, click on the X button located at the top of the page to return to Page 1 of the Trending program. Then select another thermostat you wish to analyze by using the drop down arrow, and the data will be retrieved quickly.
13. After the data is collected, if you would like to trend Return and Supply air from each unit:
a. If you are using SENDCOM sensors in your system, click on the
Discharge/Return Air Temps button on the graphing page associated with that thermostat.
b.If you are using a ModCom System, the system’s RA/SA will be
shown as the last entry in the pull down thermostat box. To display, click on the Discharge/Return Air Temps button on the graphing page. If you are using SENDCOM sensors with stand-alone equipment, that information will follow its thermostat number.
14. Temperature points on the trend lines can be highlighted by double clicking on any of the lines (additional data points will appear). By clicking inside each small box, the temperature at that data point will be displayed at the bottom of the graph with its value at that point. Data points will be displayed for any SENDCOM assigned to that specific thermostat number.
installation name, thermostat number, and date and time range;
then click the Continue button (see Fig. 35). Multiple buildings
can be accessed via the trending program, and files can be saved
under various names.
Fig. 35
5. A calendar resides in the trending software package (see Fig. 36).
Y axis, and dates and times are displayed on the X axis (see Fig. 37).
Fig. 37
Fig. 36
50
Page 51
TROUBLESHOOTING COMMON PROBLEMS
ZonexCommander Will Not Connect
Direct Connect
1. System will not connect; error message, “
operation. Please try again.”
A. Verify ZonexCommander Command Center is
energized.
B. Verify that the USB cable is installed between the
ZonexCommander Controller and the computer.
C. Verify the correct COM port is assigned to the
computer
D. Close all running programs except the Zonex-
Commander. Uninstall USB Driver; reinstall
following USB Installation procedures on Page 39 9 of Installation and Applications Manual.
2. System will not connect; error message, “
port number. Please try again.”
A. Verify the correct COM port is assigned on the
computer.
B. Change COM port assignment in Computer
Device Manager to port 1-4.
Error on
Invalid
Network Connection
1. System won’t connect on the network,
Timed Out.”
A. Verify the network cable is installed to the Network
ISERVER Device.
B. Check cable from the ISERVER to the Zonex-
Commander Controller.
C. Verify the ISERVER Network device is powered
and energized. D. Check the IP Address being used to connect. E. Check the configuration of the ISERVER and
verify the baud rate of 4800.
“System
Communicating Devices Not Responding
ModStat, DIGICOM and DIGIHP
1. When trying to read the thermostats, the REVIEW
screen shows “0” for temperature. A. Verify device is powered up. B. Verify device has the correct address. C. Verify communication wire is in correct polarity on
terminals RX & TX.
D. Verify communication wire is properly connected
from ModStat/DIGICOM/DIGIHP thermostats to Command Center with no disconnected or broken connections. Wire nuts are not to be used.
E. Check polarity of R & C to the thermostats
(Common Ground Phasing).
SENDCOM
1. SENDCOM reporting “0” on Read Sensors window. A. Verify device is powered up.
B. Verify device has the correct address. For
corresponding thermostat address, add 70.
C. Verify communication wire is in correct polarity on
terminals RX & TX.
D. Verify communication wire is properly connected
from the SENDCOM(s) to the communication link with no disconnected or broken connections.
Wire nuts are not to be used. E. Verify C/F jumper position. F. Verify the R & C polarity (Common Ground
Phasing).
RLYCOM
1. RLYCOM indicates all black zeroes (“0”) on REVIEW screen and does not switch from computer schedule.
A. Verify device is powered up.
B. Verify device has the correct address (01 to 20). C. Verify communication wire is in correct polarity on
terminals RX & TX.
D. Verify communication wire is properly connected
from the RLYCOM(s) to the communication link, with no disconnected or broken connections. Wire nuts are not to be used.
E. Check polarity of R & C (Common Ground
Phasing).
Programming and System Setup Problems
1. Thermostat names disappear after entering.
A. When entering thermostat names or ID, do not
exceed 20 characters, including spaces.
B. After entering each name or ID, click on Send
Settings button.
2. Cannot manually change address or set points on the thermostats.
A. Thermostat is electronically locked. B. Thermostat can only be unlocked from the
computer on the SYSTEM screen.
3. Thermostat display is blank.
A. Verify thermostat 24 volt power, verify 24-28vac
measured from “R” to “C” on circuit board.
4. System goes into Unoccupied during the day.
A. Go to the SYSTEM screen and verify that the Day,
Date and Time are correct.
B. Verify Occupied and Unoccupied times are correct
from the SCHEDULE screen.
C. Verify Vacation schedule entries.
51
Page 52
OPERATING SCHEDULE
For additional questions on programming and technical support, please call Zonex Systems at (800) 228-2966, M-F 6:30 AM-5:00 PM PST.
DAY OCC DAY UNOCC NIGHT OCC NIGHT UNOCC
DAY ADR NAME H C H C H C H C
MON TUES WED
THUR
FRI
SAT
SUN
MON TUES WED
THUR
FRI
SAT
SUN
MON TUES WED
THUR
FRI
SAT
SUN
MON TUES WED
THUR
FRI
SAT
SUN
MON TUES WED
THUR
FRI
SAT
SUN
MON TUES WED
THUR
FRI
SAT
SUN
MON TUES WED
THUR
FRI
SAT
SUN
52
Page 53
Page 54
Hot Line: (800) 228-2966
www.zonexcontrols.com
The easy way to Get Quotes Fast
5622 Engineer Drive
Huntington Beach, CA 92649
Factory: (714) 898-9963 • Fax: (714) 898-6802
PATENTED PRODUCT Zonex Systems reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Part #ZCMAN
ZonexCommander
(Plus)
Network All Your HVAC Equipment
for Stand-Alone HVAC and Zoned Systems
Designed to centralize
control of multiple
constant volume VAV
systems
ZonexCommander
Visit our Web Site http://www.zonexproducts.com
Copyright 2014 by Zonex Systems.
52
Rev. Oct 2014
Loading...