Zonex System 2000 GEN II Installation And Application Manual

Installation and Applica tions Manual
System 2000
GEN II
A MODULATING SYSTEM
Vote Based Auto Changeover VAV
GEN II
QUICK START AND COMMISSIONING
Follow these Quick steps for a successful job
If you need additional information, please read the GEN II Manual
1. Install GEN II Controller in an easily accessible location for your customer.
2. Install an Independent 24 Volt 40 VA tr ansfor m er, and connec t to th e T R1 and T R2 ter m inals on the GEN II controller.
3. Install the LAT sensor in the supply air, ahead of any bypass takeoffs. Wire sensor to the S S terminals on the GEN II controller.
4. Install Dampers and Bypass Dampers.
5. Install all thermostat sub-bases.
6. Wire R & C Terminals from the GEN II Controller to the Thermostat wire).
7. Wire RX & TX Term inals from the GEN II Controller using Belden 8740 t wisted pair w ire to
first thermostat sub-base – only.
the
8. Damper wiring – connect RO, RC, MC wires from each therm ostat to its dam per with 18 GA thermostat wire.
9. Plug 1 MODSTAT into that sub-base.
10. Address that therm ostat to #1 – see Pages 10-13 f or MODSTAT installation, add ressing and operation.
11. Turn on GEN II Controller s witch “E”. Power light s h ou ld light up and then look at t he D ispl ay "O" on the GEN II Controller, and t he num ber 01 ap pears on the Dis play. T his indicat es you are communicating with the first thermostat.
12. If you don’t see the #1 and a 0 is displa yed, check the address . If the address is #01, t hen check wires for R&C polarity and RX TX for correct connections.
13. If #1 is displayed on the GEN II Controller, then daisy chain wires from Stat 01 to the next stat and address it #2; the n repeat the ON – Off switch operatio n and c onf ir m the #2 shows up on the display indicating the system is now communicating with 2 thermostats.
14. Continue adding MODSTATS, and conf irm communicatio n by repeating the O N – Off switch operation until all stats are wired and the total number of thermostats on your job shows up on the display on the GEN II Controller. (If you are adding stan d-alone units to the GEN II Controller, see #15. If not, skip to #16)
15. If there are any stand-alone units that are going to be managed by the GEN II Controller, install DIGICOM / DIGIHP stats at this tim e. Continue the RX & TX daisy chain from the last MODSTAT to the DIGICOM / DIGIHP and wire in the stand-alone unit at this time and address the DIGICOM / DIGIHP (see Pages 14-17 for installation, addressing and operation). Confirm communication by repeating the On – Off switch operation u ntil all stats are wired and the total nu mber of thermostats on your job shows up o n the display on the GEN II Controller.
16. Go to any MODSTAT and make a Cool Cal l. Look at the GEN II Co ntroller and conf irm Y1 (yellow LED) and G (green LED) lights are on.
17. Turn off the Cool Call to be sure Y1 and G turn off at GEN II Controller.
18. Repeat with Heat Call for W1 (red LED).
19. Wire GEN II Controller to A/C unit.
20. Set stat to ca ll for cool, and c heck r egister to be sure each dam per op ens and closes as you make and satisfy calls.
For Advanced Feature Configuration or additional operating information, review the attached
GEN II Manual.
first sub-base – only (18 ga.
GEN II
QUICK START AND COMMISSIONING
The GEN II is equipped with a Digital Display (O) on the GEN II controller that constantly displays Leaving Air Temperature from the unit. At startup, this dis p lay also reports the num ber
of thermostats communicating with the GEN II controller. The display and 3 buttons (N) beneath the display provide the installing contractor the ability to tailor the system to your specific application.
The GEN II controller is shipped from the factory configured for basic Gas/Electric operation. However, the following should be checked as part of the initial installation setup procedures:
1. EH jumper (A) is installed b y the fac tory on one pin for normal gas hea t operation where the fan is controlled by the HVAC system fan control. When a f an output is required from the GEN II controller on a call for heat, place the EH j umper over both pins for several seconds and then remove. Place the jumper tab on one pin.
2. O/B and HP jumpers (B&C) should both be on one pin or removed for GE operation.
3. PRIORITY jumper (D) should be on one pin. Note: If the Priority opp osing zone strateg y is to be used, this jumper pos ition will be changed after the initial system start-up is completed. See Advanced Feature Configuration.
4. Set the power switch (E) to ON.
5. Set the NIGHT DAY switch (L) to the DAY position.
6. Set the fan jumper (M) to AUTO for interm ittent operation or ON for c onstant ON operation in the Occupied mode.
7. Place the LOCKUNLOCK switch (P) in the UNLOCK position.
8. Place the TIME/TEMP jumper (Q) on the middle and upper pins to control Y2 and W 2 staging on run time and supply air temperature.
Table of Contents
Page
System Overview
General Sequence Gas Electric Operation
4 5
Heat Pump Operation
7 8
8
Zone Therm
12
.....13
Zone Thermostats
Advanced Feature Configuration
Zone Dampers
Bypass Dampers
System Overview Diagram ..................................................................................................................1
Controller ID Diagram ..........................................................................................................................3
Installation Controller ...........................................................................................................................3
GE Controller Configuration .................................................................................................................
GE Advanced Configuration ................................................................................................................5
H&C Cut-out Temperature ...................................................................................................................
Electric Heat Fan .................................................................................................................................5
2nd Stage cut in ....................................................................................................................................5
Controller ID Diagram ..........................................................................................................................6
Heat Pump Installation .........................................................................................................................
Basic Configuration ..............................................................................................................................
Heat Pump Advanced Configuration ...................................................................................................8
H&C Cut-out Temperature ...................................................................................................................
2nd Stage Cut-in ...................................................................................................................................9
ostat – ModStat
ModStat Installation ...........................................................................................................................10
Wiring Diagram ..................................................................................................................................10
ModStat Configuration ..................................................................................................................11-
Supplemental Heat Applications ...................................................................................................
DIGICOM / DIGIHP Installation ....................................................................................................14-15
DIGICOM / DIGIHP Configuration ................................................................................................16-17
Voltage Polarity .................................................................................................................................17
System Start and Test .........................................................................................................................18
Troubleshooting ...................................................................................................................................18
Gas Electric and Heat Pump .............................................................................................................19
Occupied/Unoccupied Fan ................................................................................................................19
Opposing Call Changeover ...............................................................................................................19
Priority Demand ................................................................................................................................19
Thermostat Security – LOCK ............................................................................................................20
Air Balance ........................................................................................................................................20
Default Thermostat Set Points ..........................................................................................................21
Time Clock (GCLK) ...........................................................................................................................21
Round Dampers ................................................................................................................................22
Rectangular Dampers .......................................................................................................................23
D-Fuser .............................................................................................................................................24
Sizing ................................................................................................................................................25
Slaving Zone Dampers .....................................................................................................................25
Bypass Dampers ...............................................................................................................................26
Slaving Bypass Dampers ..................................................................................................................27
Bypass Damper with Integrated Pressure Control........................................................................28-29
....................................................................................................................................1
of Operation ............................................................................................................2
...........................................................................................................................3
.............................................................................................................................6
– DIGICOM / DIGIHP
– Electronic
SYSTEM OVERVIEW
The SYSTEM 2000 GEN II is a commercial modulating or 2-p os iti on zone co ntr o l s ystem controlling 2-17 independent zones per unit. The G EN II controller is designed for Auto Change- over , multi­stage Heat Pump (2C/3H) and Gas Electric (2C/2H) applications.
For modulating applicat ions, the GEN II s ystem uses the Zonex ModStat, which controls the “ST” series, 3-wire, 24-volt, po wer open / power close round and rectan gular dampers. For 2-position damper applications, the GEN II system uses the Zonex MODS2 thermostat. The MODS2 thermostats control the T R round or TREC rectangular series, 2-wire, power close / spring open, low pressure dampers . The TR / TREC series dampers are designed f or systems 5 tons or less (2000 CFM).
Sophisticated, integrated software allows for a wide range of system control and changeover strategies, allowing the contractor to tailor the GEN II system to your specific application.
Additional features i nclude LED status indication of all system functions, digital LAT display, fully adjustable capacity control with on-board limit settings, and optional staging strategies. Night setback operation is standard, with selectable 2-hour override at each stat, along with a unique feature to remotely lock thermostats in the system.
The system provides the installing contractor with a simple startup diagnostic to minimize wiring errors and speed installation.
GEN II is rec ognized as the Industry's easi est zone control system to install and wire. The GEN II System operates over an unshielded two-wire data link, along w ith two 24 V power wires a ll daisy chained from st at to stat with no home run wiring required. Three wires from the s tat to actuator control a modulating damper in each zone.
The GEN II system does not require a computer to set up or operate.
1
System 2000 GEN II offers the following additional control features:
1. Set Cooling and Heating capacity cut-out set points
2. Adjustable timing to initiate 2
nd
stage operation
3. Adjustable opposing call changeover timing
4. Priority demand votes on a stat-by-stat basis
5. Provide default occupied and unoccupied set points on every stat
6. Open all dampers for air balancing
System 2000 GEN II components:
GEN II controller (includes integrated capacity control)
• Zone thermostats
• Power open / power close 24vac supply dampers
• Power open / power close 24vac bypass damper with static pressure control
• Communication cable (Belden 8740) twisted pair
• Time Clock (optional)
• 24vac 40va transformers: 1 to control system and dampers 1 for bypass damper and static pressure control
• Stand-alone thermostat – non-zoned system
GENERAL SEQUENCE OF OPERATION
When the GEN II controllers are po wered up, the t otal num ber of addressed ther m ostats (ModStat , MODS2, DIGICOM, DIGIHP) are determined and verified on the display. This confirms the controller is communic ating with all thermostats in the system. If there are no activ e heat or cool calls detected, the sup ply dampers will modulate to 5 0% open (ModStat) or full open (MODS 2) for ventilation mode. Ad ditional thermostats ma y be utilized to control stand-alone rooftop units with DIGICOM / DIGIHP thermostats. The system blower operat ion can be configured for constant ON or intermittent Auto. The controllers are shipped from the factory for Auto fan.
The System 2000 GEN II systems can be f ield configured for adjustable t ime based opposite cal l changeover, vote based majority changeover, or priority vote changeover by thermostat assignment. The GEN II controllers are shipped from the factory for 10-minute opposing call changeover. The GEN II controllers “poll” the thermostats once per minute to determine the thermostat demand s tatus for heat and cool. T he heat and cool chang eover functions wil l operate by the type of changeov er selected on t he controller. When the G EN II controllers change m odes, a 5-minute purge cycle is initiated before the changeover is completed.
On active heat or cool calls, the non-calling zones will modulate to the close position, or close 100% depending on the therm ostat being used. When the last calling zone is satisf ied in either heat or cool mode, the GEN II controllers will terminate the HVAC outputs after the next “poll”; and the blower output will be de-energized (unless contr oller is configured for cons tant fan) for a 5-minute purge cycle. During the purge cycle no heat or cool calls are recognized.
When the system is in the heat ing mode and calls for coolin g are received, an opposing c all timer strategy operates. T his timer is adjus table from 5–30 m inutes. The factory d efault is 10 minutes . At the end of the selected t i me period, if the oppos ing c all is 3 de grees a way from set point, heating is turned off. After a 5-m inute purge cycle, Cooling is turned on until the c ool call is satisfied. If necessary, GEN II will return to the heating mode. If all calls have been satisfied, dampers will modulate to the 50% open position for vent ilation. If th e opposing zone str ategy is not des ired, this feature may be disabled.
This mode may be enhanc ed by adding Priority votes to each thermostat in t he system, thereb y weighting certain zones more than others. This Priority mode allows you to select 0, 1, or 2 additional votes for a thermostat that has unusual loads, like a conference room.
2
LEGEND
TERMINAL FUNCTIONS / CONNECTIONS
GAS ELECTRIC OPERATION
TX / RX – Data Transmit / Receive S S – Leaving / Supply Air Sensor Input G – Fan Output
W2 – Auxiliary / Emergency Heat O/B – Reversing Valve Output Y2 – Stage 2 Cool Output Y1 – Stage 1 Cool Output R – 24vac from Unit Transformer
TC / TC – Time Clock Input for Occupied / Unoccupied Operation
TR1 / TR2 – 24vac Power Input / Common R / C – Stat Power Daisy Chain Stat to Stat (18 ga. Thermostat wire)
A EH Jumper (Set Up Fan Operation for
Electric Heat)
B O/B Jumper (Heat Pump Only –
Reversing Valve Operation)
C H/P Jumper (Jump for Heat Pump
Operation)
D Priority Jumper (Allows for Priority Vote
Setup)
E On / Off Switch F R C Power to ModStats (18 ga. Thermostat wire) G 24-Volt Transformer H TC – TC Time Clock Terminals I Unit Terminals J S S Terminals – Leaving Air Sensor
(LAT)
K RX – TX Communications Wire L Day / Night Switch M Fan Jumper (Continuous or Auto) N Up / Down / Set Buttons (High Limit,
Low Limit, Set)
O Digital Display (Leaving Air Temperature
and configuration)
P Lock / Unlock (Lock Thermostats) Q Staging Strategy (Time / Temperature or
Time Only)

General Installation Instructions

GEN II Controller
1. Install the GEN II controller on a n interior wall wher e the ambient tem perature is between 32°­120°F (0°- 48°C) non-condensing. This controller is to be installed in an accessible interior area; not in attics or above ceilings.
2. The controller is to be powered by a dedicated 24vac 40va transformer. The transformer secondary is wired to TR1 TR2 on the controller (G).
The secondary
voltage to the controller must be 24 to 28vac.
3
3. Install the leavi ng air s ensor (LAT ) in the s upp ly air , ahead of t he b ypass tak e-off. Sensor wires are connected to the S S terminals on the controller (J). The LAT sensor leads may be extended using standard 18/2 thermostat wire.
4. The leaving air sensor (LAT) is calibrated to the controller at the factory. However, the calibration should be checked as part of the system setup procedures. If adjustments are required, use the Blue potentiometer labeled R4 4 located in the upper lef t hand corner of the GEN II controller. Screw the pot clockwise to lower the display temperature and counter ­clockwise to raise the temperature. NOTE: The display will update every 10 seconds.
5. Confirm you have connected the RX TX communication wires and R and C from the thermostats to the con trolle r ( F&K), F = (R C), K = (TX RX). (Communication wire m axim um is 4,000 ft. from the Command Center to the farthest ModStat, DIGICOM or DIGIHP.)
6. Connect the output wires from the controller to the HVAC system using standard 18 ga. thermostat wire. The LAT sensor leads may be extended using standard 18/2 thermostat wire.
Gas Electric - Basic GEN II Controller Configuration
The GEN II is equipped with a Digital Display (O) on the GEN II controller that constantly displays Leaving Air Temperature from the unit. The display and 3 buttons benea th the displa y
provide the installing contractor the ability to tailor the system to your specific application. The GEN II controller is shipped from the factory configured for basic Gas/Electric operation.
However, the following should be checked as part of the initial installation setup procedures:
1. EH jumper (A) is installed b y the fac tory on one pin for normal gas hea t operation where the fan is controlled by the HVAC system fan control. When a f an output is required from the G EN II controller on a call for heat, place the EH j umper over both pins for several seconds and then remove. Place the jumper tab on one pin.
4
2. O/B and HP jumpers (B&C) should both be on one pin or removed, for GE operation.
3. PRIORITY jumper (D) should be on one pin. Note: If the Priority oppos ing zone strateg y is to be used, this jumper positi on will be changed after the initial system start-up is completed. See Advanced Feature Configuration.
4. Set the power switch (E) to ON.
5. Set the NIGHT DAY switch (L) to the DAY position.
6. Set the fan jum per (M) to AUTO for inter mittent operation or ON for constant ON o peration in the Occupied mode.
7. Place the LOCKUNLOCK switch (P) in the UNLOCK position.
8. Place the TIME/TEMP jumper (Q) on the m iddle and upper pins to c ontrol Y2 and W2 staging on run time and supply air temperature.
GEN II Gas Electric Advanced Feature Configuration

Gas Electric Capacity Control - Cool and Heat cut-out temperature adjust

The factory setting for the Cool and Heat cut-out temper atures is 45°- 145°F (7°- 62°C). T his can be easily changed with the following proced ur e:
1. Cool cut-out temp – Press the DN button (N); “C” will be displayed and then the cut-out temperature.
2. LOWER – Press the DN button; after the “ C” is displayed, continue to h old the DN button unti l the desired temperature is displayed; then release. NOTE: The controller will not change the Cool cut-out lower than 40°F (4°C).
3. RAISE – Press the DN but ton; after “C” is displayed, immediately release the DN button a nd press the UP button. Hold until the desired temperature reading is displayed, and release.
4. Press the DN button to verify the new cool cut-out temperature.
Heat cut-out temperature - Press and hold the UP button; after the “H” is displayed, use the same procedure as above to raise or lower the displayed temperature.

Electric Heat - Fan Configuration

EH jumper (A) is insta lled by the fac tory on one pin f or normal gas heat o peration wher e the fan is
controlled by the HVAC system fan control. When a fan output is required from the GEN II controller on a call for heat, place the EH jumper over both pins for several seconds and then remove. Place the jumper tab on one pin.

2nd Stage Heat and Cool Cut-in Configuration

The GEN II controller is set up at the fac tory to stage Y2 and W2 cut-in operation based on a 3­minute time delay and middle and upper pins on TIME/TEMP (Q), and the c ut-in delay set at 03 (3 m in) in the controller program. The cut -in temperatur es are fix ed in the con troller progr am at 57°F (13°C) and hig her for Y2 and 120°F (48°C) and lower for W2. The Y2 and W2 cut-in delay sequence can be field adjusted (see below).
supply air tem perature. This is done wit h a jumper which is place d on the

Adjust 2nd Stage Cut-in Time Delay

1. To increase the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (N) simultaneously. W hen 03 appears in the display, release the buttons and immediately press the UP button and hold until the desired de lay time is displayed, and r elease. The time delay is fully adjustable from 3 - 20 minutes . To verify the change, press and hold the SET and DN buttons simultaneously until the delay time is shown, and release.
5
2. To decrease the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (N)
TERMINAL FUNCTIONS / CONNECTIONS
(18 ga. Thermostat wire)
LEGEND
simultaneously. W hen delay time appear s in the displa y, release the butt ons and imm ediately press the DN button and hold u ntil the desired dela y time is displayed, and rele ase. To verify the change, press and hold the SET and DN buttons until the delay time is shown, and release.

Configure 2nd Stage Cut-in For Time Delay and Thermostat Demand Only

1. Place the 2nd stage configuration jumper (Q) on the middle and lower pins - TIME.
2. If the cut-in time del a y must be ch anged f rom the f actor y settin g of 03 (3 m in), f ollow the above procedures to raise or lower the time delay value.
3. Verify time delay value by pressing the SET and DN buttons simultaneously.
HEAT PUMP OPERATION
TX / RX – Data Transmit / Receive S S – Leaving / Supply Air Sensor Input G – Fan Output
W2 – Auxiliary / Emergency Heat O/B – Reversing Valve Output Y2 – Stage 2 Cool Output Y1 – Stage 1 Cool Output R – 24vac from Unit Transformer
TC / TC – Time Clock Input for Occupied / Unoccupied Operation
TR1 / TR2 – 24vac Power Input / Common R / C – Stat Power Daisy Chain Stat to Stat
A EH Jumper (Set Up Fan Operation for
Electric Heat)
B O/B Jumper (Heat Pump Only –
Reversing Valve Operation)
C H/P Jumper (Jump for Heat Pump
Operation)
D Priority Jumper (Allows for Priority Vote
Setup)
E On / Off Switch F R C Power to ModStats (18 ga. Thermostat wire) G 24-Volt Transformer H TC – TC Time Clock Terminals I Unit Terminals J S S Terminals – Leaving Air Sensor
(LAT)
K RX – TX Communications Wire L Day / Night Switch M Fan Jumper (Continuous or Auto) N Up / Down / Set Buttons (High Limit,
Low Limit, Set)
O Digital Display (Leaving Air Temperature
and configuration)
P Lock / Unlock (Lock Thermostats) Q Staging Strategy (Time / Temperature or
Time Only)
6
General Installation Instructions
GEN II Controller
1. Install the GEN II controller on a n interior wall wh ere the ambient tem perature is between 32°­120°F (0°- 48°C) non-condensing. This controller is to be installed in an accessible interior area; not in attics or above ceilings.
2. The controller is to be powered by a dedicated 24vac 40va transformer. The transformer secondary is wired to TR1 TR2 on the controller (G). The secondary voltage to the controller must be 24 to 28vac.
3. Install the LAT air sensor in the supply air between the indoor coil and electric strip heat elements.
4. The leaving air sensor (LAT) is calibrated to the controller at the factory. However, the calibration should be checked as part of the system setup procedures. If adjustments are required, use the Blue potentiometer labeled R44 l ocated in the upper left hand c orner of the GEN II controller. Screw the pot clockwise to lower the display temperature and counter ­clockwise to raise the temperature. NOTE: The display will update every 10 seconds.
5. Confirm you have connected the RX TX communication wires and R and C from the thermostats to the con trolle r ( F&K), F = (R C), K = (TX RX). (Communication wire m axim um is 4,000 ft. from the Command Center to the farthest ModStat, DIGICOM or DIGIHP.)
6. Connect the output wires from the controller to the HVAC system using standard 18 ga. thermostat wire. The LAT sensor leads may be extended using standard 18/2 thermostat wire.
Heat Pump operation “O” reversing valve
Cool Call – W hen a majority active cool call is received b y the GEN II controller, Y1, O /B and G LEDs are illuminated; and the out puts are energized (within 1.5 to 3 minutes ). After 3 minutes, if the leaving air tem perature is 58°F (14°C) or above, Y2 will e nergize for 2-stage system s. If the supply air temperature dro ps one degree below the Cool cut-out tem perature, Y1 and Y2 will de­energize for 4 minutes.
“B” reversing valve – Sequence of operation is the same: O/B is energized in the heat mode. Heat Call - When a majority active heat call is received by the GEN II controller, Y1 and G LEDs are
illuminated; and the out puts are energized (w ithin 1.5 to 3 minutes). If after 3 minutes the leaving air temperature is 94°F (34°C) or less, Y2 will en er gi ze. If after 6 minutes of run time the leaving air temperature is 91°F (32°C) or less, W 2 will energi ze. If the sup ply air tem perature ex ceeds 126°F (52°C), Y1, Y2 and W2 ( if energized) will drop ou t; and Y1 can then energ ize after a 4-minute time delay. NOTE: If the system fan is configured for “AUTO” on the GEN II c ontroller, the “G” output will be de-energ i zed in the t emperature cut-out mode.
When the last active call satis fies, the GEN II control ler goes into a 5-minute purge cycle with a ll supply dampers closing; then all dampers modulate open for ventilation.
Emergency Heat - The GEN I I emergency heat oper ation can be selected from any ModStat f or the entire control system . When the system operation mode is c hanged to Emergency Heat on a given ModStat, the GEN II controller will recognize the mode change on the next s ystem poll. The thermostat which was us ed to select Emergency Heat does not ha ve to make a heat call for the GEN II controller to respond to the change. Once the GEN II controller changes the mode to Emergency Heat, any ModStat in the system can make an emergency heat call. When the controller receives a heat c all in t his mode, the com pressor (s) are lock ed out a nd W 2 is energi zed. The G EN II controller will continue to make c onsecutive Emer gency Heat calls un til the ModStat(s ) have been changed back to the AUTO or HEAT mode.
7
To select Emergency Heat on any ModStat:
1. Press and hold the ModStat Menu button
2. When the mode disp lay indicates Emg, releas e the Menu button; and immediately press and hold the Select button to set the mode.
Heat Pump operation “B” reversing valve
By placing the O/B jum per (B) on both pins, the GEN II controller is c onfigured for “B” reversing valve operation. The operation and setup procedures are the s ame as with “O” mode reversing valve, except the reversing valve will be energized for heat operation.
GEN II Heat Pump Basic Configuration
The GEN II controller is shipped from the factory for Gas Electric operation. The controller must be field configured for Heat Pump operation. Heat Pump configuration:
1. Switch controller to OFF (E).
2. Set the O/B jumper (B) on one pin for “O” reversing valve (energizes for cool) or
set the O/B jumper (B) on both pins for “B”
reversing valve (energizes for heat).
3. Set the HP jumper (C) on both pins for Heat Pump operation.
4. Set the Priority jumper (D) on one pin.
5. Set the TIME / TEMP jumper (Q) on the middle and upper pins.
6. Set NIGHT / DAY switch (L) for DAY position.
7. Set LOCK / UNLOCK switch (P) to UNLOCK.
8. Switch the controller to ON (E).
9. Press the UP button (N), and verify the “H” (cut-out) temperature reads 126°F (52°C) on the controller display (O).
NOTE: The heat cut-out temperature must not be changed from the factory setting.
GEN II Heat Pump Advanced Feature Configuration

Heat Pump Capacity Control - Cool and Heat cut-out tempera tu re adjustment

When the GEN II controller is configured f or H e at P um p (H P jumper (C) on both pins ), the Cool and Heat cut-out temperatur es are 45°- 126°F (7°- 52°C). The cut-out tem peratures can be changed with the following procedure:
Heat cut-out temp – To eliminate the possibility of the Heat Pump tripping out on high head pressure or short cycling in the heat mode, the heat cut -out temperature shou ld never from the factory setting of 126°F (52°C).
1. Cool cut-out temp – Press the DN button (N); “C” will be displayed, then the cut-out temperature.
2. LOWER – Press the DN button. After the “C ” is displa yed, contin ue to hold t he DN butto n until the desired temperature is displayed; then release.
NOTE: The controller will not change the Cool cut-out lower than 40°F (4°C).
8
be chang ed
3. RAISE – Press the DN button. Af ter “C” is displa yed, immediatel y release the DN button, and press the UP button. Hold until the desired temperature reading is displayed; then release.
4. Press the DN button to verify the new cool cut-out temperature.

2nd Stage Heat and Cool Cut-in Configuration

The GEN II controller is set up at the fac tory to stage Y2 and W2 cut-in operation based on a 3­minute time delay and middle and upper pins on TIME/TEMP (Q), and the c ut-in delay set at 03 (3 m in) in the controller program. The cut -in temperatur es are fix ed in the con troller progr am at 57°F (13°C) and hig her for Y2 and 120°F (48°C) and lower for W2. The Y2 and W2 cut-in delay sequence can be field adjusted (see below).

Adjust 2nd Stage Cut-in Time Delay

1. To increase the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (N) simultaneously. W hen 03 appears in the display, release the buttons and immediately press the UP button and hold until the desired de lay time is displayed, and r elease. The time delay is fully adjustable from 3 - 20 minutes . To verify the change, press and hold the SET and DN buttons simultaneously until the delay time is shown, and release.
2. To decrease the Y2 and W2 cut-in delay, press and hold the SET and DN buttons (N) simultaneously. W hen delay time appear s in the displa y, release the butt ons and imm ediately press the DN button and hold u ntil the desired dela y time is displayed, and rele ase. To verify the change, press and hold the SET and DN buttons until the delay time is shown, and release.
supply air tem perature. This is done wit h a jumper which is place d on the

Configure Y2 and W2 cut-in for time delay and thermostat demand only

1. Place the 2
2. If the Y2 cut-in tim e delay must be changed from the factory setting of 03 (3 min), f ollow the above procedures to raise or lower the time delay value. NOTE: The cut-in delay timing for W2 (Aux Heat) is set for approximately 3 minutes in the control program and cannot be manually changed.
3. Verify time delay value by pressing the SET and DN buttons simultaneously.
nd
stage configuration jumper (Q) on the middle and lower pins - TIME.
9
Zone Thermostat - ModStat
Installation
Wiring
All 24-volt and comm unication wiring connections are made to term inal blocks on the thermostat sub-base. The com munication terminal b lock (RX TX/RX TX) is des i gne d as a j unc tion for two sets of 22 ga. solid cop per , t wist ed p air c om munications cable. The c a ble s ho uld b e d ais y c ha ine d f rom thermostat to thermostat (use Belden 8740).
1. Install the therm os tat s ub-bas e on an int er ior wal l a wa y fr om direct sunlight, suppl y a ir c urr ents , or any heat generating source. Mounting screws and anchors are provided. The sub-base may be installed on a vertical 2x4 electrical box.
2. Connect the control wires from the ModStat' s R & C, to the GEN I I controller (F). Verif y R & C polarity is the same on each thermostat (18 ga. Thermostat wire).
3. On the ModStat, connect the damper output wires from C-MC, RC and RO to the actuator motor terminals. NOTE: For MODS2, terminal RO is not used.
4. Connect the RX TX communicat ion wires on the right hand term inal block; there are 2 sets of RX TX terminals to make the daisy chain wiring easier.
NOTE: The communication wire must be twisted pair Belden 8740, 8450 (shielded) or 82442 (plenum rated).
10
Configuration
Addressing
Each thermostat must have a unique address from 1-17.
1. Press and hold the Menu button unti l you see the system mode displa y on the lo wer right beg in to change modes; then press and hold the Heat/Cool button with the Menu button.
2. When the displa y shows “address,” releas e t he Menu and Heat/Cool buttons, and pr ess th e UP or DN button until the correct address is displayed in the upper right of the display.
3. After setting the addr ess , th e ther mostat will automatic ally go back to norm al oper atio n; a nd the set point temperature will replace the address number just programmed.
Display Temperature Calibration Thermostats are calibrate d at the factory and shoul d require no further adjustm ent. However, the
display space temperature may be field calibrated by the following procedure:
1. Press and hold the Heat/Cool and Select buttons together; then press and release the UP button to increase the display temperature by one degree.
2. To lower the tem perature displa y, press the DN b utton once, af ter pressing the Heat/Cool and Select buttons. This makes a 1-degree change.
Adjusting Set Points
The Heat or Cool set po ints can be displayed b y pres si ng th e Heat/Cool butto n; t h e s et p oi nt w ill b e indicated on the upper right of the display.
The Heat and Cool set points can be individually set for the Occupied and Unoccupied modes.
Occupied Mode: H & C settings - Function switch (L) in the D AY position, or time clock in Occupied. Unoccupied Mode: H & C settings – Function s witch (L) in the NIGHT pos ition, or time clock in Unoccupied.
11
Heat - If “Heat Setting” is displayed on the top right of the display, simply press the UP or DN button to change the heat set point. If “Cool Sett ing” is displayed and you want to change the Heat set point, press the Heat/Cool button twic e to c han ge f r om “Cool Setting” to “Heat S etti ng”. Then press the UP or DN button to change the set point.
Cool - If “Cool Setting” is displayed on the top right of the display, simply press the UP or DN button to change the cool set p oint. If “Heat Setting” is displa yed and you want to change the Coo l set point, press the Heat/Cool button t wic e to c han ge f r om “Heat Setting” to “Cool S etti ng”. Then press the UP or DN button to change the set point.
Changing Mode
The thermostats are auto changeover, but specific modes may be selected. Auto mode is the default.
Heat only – Press and hold the Menu button and note the mode display begin to change. Press the Select button when Heat is displayed.
Emergency Heat - Press and hold the Menu button and note the mode displ ay begin to change. Press the Select button when Emg is displayed.
Cool only - Press and hold the Menu button and note the mode display begin to change. Press the Select button when Cool is displayed.
System Off - Press and hold the Menu button and note the mode displ ay begin to change. Pres s the Select button when Off is displayed.
Auto mode – Press and release the Menu button. Override
When the thermostat displ ays “Unoccupied” (top of display), a 2-hour temporary overri de may be initiated by pressing the O verride/Select button. W hen additional override time is required, press the Override/Select button again.
Reheat
The ModStat can be field c onfigured for reheat operatio n, including Fan Powered Box es. To set the ModStat for Reheat, pr ess and hold the Heat/Cool
and Select b uttons together and then press the Menu button; release all three buttons and the ° symbol will appear next to the heat and cool set point temperature display. NOTE: An air proving switch must be wired into the AUX output to protect the electric heating devices.
Heat Call – The ModStat will send a sig nal for dem and heating when the spac e tem perat ure drops 1° below the heat set point temperature. If the temperature drops 2° below the heat set point temperature, the AUX output will energi ze for auxiliar y heat. The therm ostat will end the active c all when the space temperature meets the heat set point.
When configured for R eheat, if the spac e temper ature drops below the hea t set point, the ModStat will modulate th e damper to 40% open. W hen the tem perature drops one more degre e, the AUX terminal energizes the duct heat strip. The heat call will terminate when the space temperature reaches the heat s et point temperature. The “AUX” output will de-energize, and the dam per will modulate closed. If the system goes into the ventilation mode, the damper will then modulate open.
12
SUPPLEMENTAL HEAT APPLICATIONS MODSTAT
SUBBASE
{twisted pair}
{18 ga. stat wire}
ModStat Terminal Designations TX – Data transmit RX – Data receive AUX – Reheat/AUX Heat Fan
RO – Run Open, damper RC – Run Closed, damper R – 24vac power input C-MC – 24vac power common
NOTE: A larger transformer may be needed to power fan relay and/or heat strip relay.
13
DIGICOM / DIGIHP THERMOST ATS
DESCRIPTION
The Zonex Systems DIGICOM (2H, 2C) and DIGIHP (3H, 2C) are microprocessor bas ed, auto changeover, stand-alone ther mostats used to control stand alone units with no dampers in the system . The DIGICOM is the Gas Electric version and has two-stage heat / cool outputs with selectable fan operat ion. The DIGIHP Heat Pum p thermostats have two­stage cool and three-s tage heat outputs with selectabl e fan. The D IGICOM and DIGIHP thermostats have a large, easy-to-read LCD display with a distinctive grey back light. The display backlight is continuous ly illuminated in the Occupied mode and goes off in the Unoccupied mode.
The DIGICOM and DIGIHP are very easy to configure through the system program or to make manual adjustments using the buttons located on the front cover.
These thermostats feature an onboard thermistor for precise temperature measurement. In the event of power loss, the H eat and Cool set point s are stored in a non-volatile memor y, without the need for battery backup.
The space ambient temperature is continually displayed with large, easy-to-read numbers. The DIGICOM temperature displa y range is 45° - 95°F (7°- 35°C) and the DIGIHP t emperature displa y range is 55°- 95°F (12°- 35°C). Fan Mode, H eat or Cool set points and operation m odes are all indicated on the display.
Programmed set points can be manuall y adjust ed at t he ther m ostat or elec tron icall y locked thr ough the system program to provi de limited manual s et point adjustment. Two-hour o verride is provided for after-hours temporary operation with a touch of a button.
INSTALLATION
Thermostat and terminal base
1. The thermostat is to be ins talled on the interior wall, away from drafts , supply air currents and
direct sunlight or any heat generating source.
2. To remove the thermos tat cover, gras p t he c over at the top and p ul l s traigh t of f; do not pivot the
cover from the base.
3. Install the thermos tat terminal base to the wall using the pro vided anchors and screws. The
thermostat can also be mounted on a 2x4 electrical box using two #6-32” screws.
Wiring
The Zonex System s DIGICOM and DIGIHP t hermostats have been specif ically designed to make wall mounting and wire connections very eas y. The thermostat terminal base has two separate terminal blocks: the left side terminal block is for the 24vac control circuits, and the right side terminal block is for the RX TX comm unication circuits. Ther e are two sets of RX TX terminals on the base to make daisy chain wiring from device to device straightforward and simple.
14
Wiring (Continued)
1. Use minimum 18-gauge AWG thermostat wire for the 24v ac contr ol cir cuits. T he load o n thes e
circuits must not exceed 1 amp. The voltage range on R and C must not exceed 28vac. Check Polarity before appl ying the transform er wire to R and C. Ref er to the Polarit y Check diagram on Page 17.
2. Connect the comm unicatio n wires to the RX TX terminals. There are 2 sets of RX TX terminals
for “daisy chain” installatio n of th is circuit. The comm unication wire spec ification is twiste d pair (Belden 8740) or shielded twisted pair wire (Belden 8450).
NOTE: When using s hielded twisted pair wire ( Belden 8450), just connect t he shield conductors together, as there is no electrical connection on the thermostat base ter minals. The shield will be landed on the GEN II controller on the G or TR2 terminal.
Blower Fan Relay
For electrical heat applications, which require a fan output on a call for heat, see Fig. 3.
DIGICOM
Fig. 1
DIGIHP
Fig. 2
Fig. 3
15
Configuration
1. Set the unique address for each thermostat from 01 to 20.
2. Press and hold the Menu button until you see th e system mode displa y on the lo wer r ight beg in
to scroll and change modes; then press and hold the Heat/Cool button with the Menu button.
3. When the display shows “address” and the set point temperature changes to the address
number, press the UP or DN button to raise or lower the number.
MAN UAL AD J U S T MEN T S Heat and Cool Set point Display
Press the Heat/Cool button to display the Heat or Cool set point temperatures. Temperature Set points
COOL Set point
1. Press the Heat/Cool button to display the Cool set point on the upper right.
2. Press the UP or DN buttons to change the Cool set point. HEAT Set point
1. Press the Heat/Cool button to display the Heat set point on the upper right.
2. Press the UP or DN buttons to change the Heat set point temperature. FAN Mode
To change the FAN operation to AUTO or On, press the UP and DN buttons together once to toggle fan operation.
HVAC System Mode To select Heat, Cool, Auto, Emergency Heat (HP only) or OFF, press and hold the Menu button; and when the desired m ode is displayed, press and ho ld the Select button; th en release
both to confirm mode. Override
When the system is in the Unoc cupied mode, the thermostat provides a 2-hour override for after ­hours system operat ion. T o s elect the 2-hour override, press the Select button a nd n ote “Override” indicated on the displa y, along with the b acklight com ing on. When additi onal override is required, press the Select button again.
Calibration When re-calibration is required, press and hold the Heat/Cool and Select butt ons simultaneously (the screen will flash) . Then pr ess the UP button once to incre ase tem peratur e 1° , or pres s the DN button once to decrease the temperature 1°. If additional calibration is required, repeat this step.
Reversing Valve Mode – Heating DIGIHP (O&B) is factory set at “O” and ca n be field configured for “B” re versing valve operation. For “B” mode reversing valve (reversing valve energized in the heat mode), press and hold the Heat/Cool and Select buttons; then press and release the Menu button once. Release the Heat/Cool and Select buttons. The ° symbol next to the set point display should disappear. (To set from “B” to “O”, reverse the procedure.)
THERMOSTAT OPERATION Display
The grey displa y backlight is constantly i lluminated in the Occupied m ode. The display backlight goes off when in the Unoc cupied mode. When in the Unoccupied mode, if an y button is pressed, the backlight will illum inate for 5 seconds. If the thermostat is placed in the override mode, the backlight will illum inate until the 2 hours times out. T o terminate overri de, press the Select button again.
COOL – DIGICOM / D IGIHP: The therm ostat will m ake a Y1 cool call when the s pace tem per ature rises 1° above the cool se t point. Y2 will energize wh en the space tem perature ris es 2° above the cool set point. When the room temperature is less than 2° above the cool set point, Y2 de-
16
energizes. Y1 de-energizes at set point. O or B is energized for the reversing valve circuit, depending on configuration. The G circuit is energized for fan.
HEAT – DIGICOM: The thermostat will make a W1 heat call when the space temperature is 1 degree below t he heat set point. W 2 will ener gize when t he sp ace t em perature i s 2 degrees below the heat set point. When the room temperature rises to within 2 degrees of the heat set point, W 2 de-energizes. W1 de-energizes at set point.
NOTE: The “G” fan circuit on the DIG ICOM thermostat is not energized in the Heat mode unles s the fan is set for ON operation.
HEAT − DIGIHP: The ther m ostat will mak e a Y1 heat call when th e space tem perature is 1 d egree below the heat set p oi nt. Y 2 will energize when the spac e temperature is 2 degrees bel o w the hea t set point. E (aux heat) will energize when the space temperature is 3 degrees below set point . When the room temperature rises to within 2 degrees of the heat set point, E (aux heat) de­energizes. When the room temperature rises to within 1 degree , Y2 de-energizes. Y1 de­energizes at set point.
Emergency Heat – DIGIHP: When Emergenc y Heat is selected on the DIGIHP thermostat on a call for heat, there is an output signal o n “E” for backup heat and “G” f or the fan. The compressor circuits “Y1” and “Y2” are lock ed out during heat calls until Auto, Heat or Cool mode is selected. The thermostat display will indicate when Emergency Heat has been selected.
DIGICOM – FAN op eration f or electric heat app lications : A pilot relay m ay be re quired to e nergize the fan for heat operation on electr ic heat applications. This relay is a 24vac coil – SPST and is field supplied. The coil is energized from W1 and C from the DIGICOM thermostat terminal base.
VOLTAGE POLARITY CHECK ON DIGICOM / DIGIHP
17
System Start and Test
1. Plug all thermostats into sub-bases. Turn GEN II power switch (E) to ON.
2. Choose any Thermostat and change its address from 25 to 1.
(See ModStat installation instructions – Configuration – Addressing).
3. Turn GEN II power switch OFF and the n ON. The Display sh ould flash 01 and the n show the
leaving air temperature. This confirms your successful wiring and communication with that thermostat.
4. If 01 is displa yed, change the next thermost at’s address from 25 to 2. Turn the GEN II power
switch OFF and then ON. The display should flas h 02 and then show the tem perature. Re­address thermostats one at a time.
5. After each stat is re-addressed, turn th e power switch off and then on. This will verify that the
re-addressed stat has been found by the GEN II Controller.
This procedure will sim plif y your instal lation a nd wil l confirm your wiring is cor rect and th at the GEN II controller can communicate over the 2-wire twis ted pair data link with every therm ostat in your system.
Troubleshooting
When stat #1 is not found:
1. Check remaining stats to verify that all addresses are 25.
2. Check all R & C wiring for proper color-to-color connections. Even if the stats lighted, all R
wires at the thermostat must be connected to the GEN II R terminal. All C wires must be connected to the GEN II C terminal. Confirm the daisy chain wiring is correct at this time.
3. Check RX & TX wires for proper color code and connections; polarity is imperative. All RX
connections must land on R X term inal o n the f ol lo win g thermostat, and all TX c onnecti ons must connect to TX terminal on each thermostat.
4. Check R & C wires for opens or shorts.
Checking the Daisy Chain for opens o r shorts:
Start from the GEN II board, and follo w RX & TX wires to the f irst sub-base. Remove the RX & TX wires going to the nex t s ub -bas e in th e l ink . Plug a s ta t int o th e first sub-base, and ad dr ess it as #1. Turn the GEN II power switch off, then on, to see if the display flashes.
1. If 01 is displayed, the first link of the daisy chain is OK. Reconnect the wires going to sub-
base.
2. Repeat these steps with a stat numbered 02. If the number 02 is displayed, then
Communication is confirmed.
When the correct number does not ap pear f or a link , that link is either shorted or open. A link of the daisy chain, which is open or shorted, must be repaired before the next thermostat is checked.
When the thermos tats are correctly addres sed, wired and linked, the total number of stats on your job connected to the GEN II Control board wi ll be disp layed when the board is turned on.
After the correct num ber of connected therm ostats is displayed, complete the wiring of AC unit or heat pump connections; then make heat and cool calls to the GEN II Controller.
18

Advanced Feature Confi guration - Gas Electric and Heat Pump

Occupied / Unoccupied fan operation

The factory setting for F AN operation is AUTO, with the F AN jumper (M) on the middle and lower pins. In this setting, the fan circuit on “G” is only energized on an acti ve cool call in Gas /Electric mode or on an activ e heat c all or cool call in He at Pum p mode. T his applies to both Oc cupied and Unoccupied modes. When the FAN jumper is in AUT O, there is no output on “G” with a n active heat call in Gas/Electric mode.
Constant Fan in the Occupied (DAY) mode – Place the FAN jumper (M) on the center and
upper pins on ON. T he fan output on “G” will be constant in the Occupie d (DAY) m ode and will revert to auto in the Unoccupied (NIGHT) mode.

Opposing Call Changeover

The GEN II controllers are configured at the factory for Opposing Call Changeover with a time delay setting of 10 minutes. W ith this configuration, any number of therm ostats can make a like active call (heat or cool). Dur ing this tim e, if a single th erm ostat m ak es an opposit e call, a at the next poll. This tim er starts a time delay operation to allow the initial calling therm ostats to satisfy. If the initia l active therm ostats do not completel y satisfy after 10 m inutes, the dam pers all close and the controller dro ps out the HVAC outputs and goes into a 3-minute pur ge cycle. When the purge cycle times out, the opposing thermostat call is initiated; and the appropriate HVAC outputs are energized, an d the supply dam per opens. The therm ostat with the opposing c all must now satisfy before the GEN II controller will recognize any of the initially calling thermostats.
The opposing call timer is factory adjusted for 10 minutes. However, the delay time can be field adjusted from 5 to 30 minutes. To increase the opposing call time delay:
1. Press the SET and UP buttons.
2. Release the SET button when the display changes, and continue to hold down the UP button.
3. Release the UP button when the desired time is displayed. To lower the time delay:
4. Press the SET and UP buttons.
5. Release the SET button, and immediately press and hold the DN (down) button until the desired time is indicated; then release. The Opposing Call feature can be disabled by performing steps 1 through 3 and then releasing the UP button when the display indicates 32. With this feature disabled, the GEN II c o n tr ol le rs wi ll operate changeover by majority vote from the zone thermostats.
timer is s tarted

Priority active Heat and Cool call operation

The GEN II controllers m ay be configure d in the field for major ity vote changeover but also assign multiple votes for selected thermostats to enhance the changeover operation for special requirements. Each thermostat repr esents one vo te for heat or c ool operati on; a m ajority of active calls will determine which mode the controller will operate in. With the Priority feature, any thermostat may be assigne d one or more additional votes to allo w it to ha ve priority to bring a mode changeover more quickly. To keep proper overall temperature control, this priority vote change should be limited to as few zones as possible. Follow the procedure to implement Priority vote operation:
1. Determine which thermostat address is to have an additional one or two votes.
2. Place the PRIORITY jumper (D) on both pins.
19
3. Press and ho ld t he SET and UP buttons (N), and the L ED disp lay will scroll through t h e number
of zones starting with 01.
4. W hen the display indicates the addr ess (01 to 17) of the thermostat you want to add votes to,
release both buttons and pres s the DN button. The display will scroll thr ough 00, 01, 02. To add one additiona l vote, release the DN button when the display indicates 01 (this assigns a total of 2 votes). To increase the votes b y two, press the DN button and wait unt il the indicates 02 and then release the DN button (this assigns a total of 3 votes maximum).
5. T o change the votes back to a single vote, press the DN button on the selected address an d
release when the display indicates 00.
6. To review the vote status of all of the thermostats in the system, pres s the UP button; and the
display will first i ndicate the address number starting with 01and then th e vote status for that address. 00 = 1 vote 01 = 2 votes 02 = 3 votes. Upon r eview, if stat #1 has 2 votes , the display will show Stat 01 followed by 02 signifying the number of Priority votes assigned to Stat 1. Stat 02 will appear followed b y a blank display, indicating onl y 1 vote; and Stat 03 will appear followed b y a blank scr een, indicating n o priorit y votes have been a dded to Stats 02 or
03.
7. Be certain to Place the PRIORITY jumper on one pin to put the contro ller back into normal
operation with the changes that were made.

Thermostat security - Set Point LOCK

display
The GEN II system provides the a bility to electronically lock all of the zone thermostats (global). When the thermostats are in the LOCK mode, there will be a padlock icon on each thermostat display. The LOCK m ode lim its the m anual chang ing of the heat and c ool set po int s to a m ax imum of 2° above or below the initial heat and cool set point temperatures.
To set the thermostats for the LOCK mode, simply change the switch position (P) from UNLOCK to LOCK. All of the thermostats will change to LOCK on the next system poll. To unlock, set the switch to the UNLOCK position; and the thermostats will drop the icon after the next system poll and revert to normal operation.

Air Balance - Force Dampers Open

When performing an air ba lance on the supply air outlets, the GE N II controller provides a uniq ue feature to simplif y this proc edure. T he GEN II controller will put all therm ostats in a cool ca ll whic h will open the dampers 100% and bring on the system blower.
1. Place the EH jumper (A) over both pins
2. Press the SET and UP buttons (N) simultaneously – T his puts a global cool set point of 58°F
(14°C) on all of the zone ther mostats, and the controller ener gizes th e “ G” fan out put on l y; Y1 is not energized.
3. When the air balance proc edure is completed, pres s the SET and DN buttons sim ultaneously,
which will assign 70°F (21°C) Heat and 75°F (23°C) Cool set points on all of the zone thermostats.
4. Press and hold the SET and DN buttons; and while holding these buttons, remove the EH
jumper tab and plac e it o n one pin. Rele ase the SET and DN buttons. This proc edure r eturns the GEN II controller to normal operation. For Electric Heat fan configuration, see Page 5.
20

Default Thermostat Set Point Programming

Global default set points can be established from the GEN II controller. The following procedure will provide a 75°F (23°C) Cool and 70°F (21°C) Heat occupied set point
along with Unoccup ied 58°F (14°C) Heat a nd 85°F (29°C) Cool set point for every thermostat in th e system. This handy feature minimizes visits to the thermostats. To establish these default set points:
1. EH jumper (A) - place the jumper over both pins.
2. Press the SET and DN button (N) simultaneously to engage default set points.
3. Remove the EH jumper, and place on one pin to put controller back into normal operation.
4. To view the unoccupied set points place the Night / Day switch (L) to the NIGHT position.
Following a poll, the t hermostat backlights will turn off ; and the unoccupied set points will be displayed.
Time Clock
The GCLK is a 24vac 7-Da y programmable time clock off ered by Zonex Systems, exclusivel y for the GEN II control s ys tem. This digital time clock will enable the c ontrol system to operate with “Global” Occupied and Un occupied schedules in a 7-day form at. The GCLK is powered from the GEN II c ontroller p ower suppl y, and there is a bac kup batter y to protect the tim e clock program for up to 100 hours.
Installation
The GCLK must be installed on an interior wall next to the GEN II controller. Both the GEN II controller and GCLK t ime clock must be easil y accessible to monitor stat us and to make program and function changes.
1. Remove the clear dust cover lens and loosen two screws on opposite corners of the clock
module.
2. Remove the housing that surrounds the time clock and the wire terminal cover.
3. Remove the clock m odule b y pulling stra ight out f rom the b ase. Instal l the bac king plat e to the
wall with 3 screws (provided).
4. The GCLK is powered from TR1 and TR2 on the GEN II c ontroller to terminals 1 and 2 on the
time clock terminal base.
5. The Normally Open s witch c ontacts on the tim e clock 3 an d 5 are wired to the TC term inals on
the GEN II controller.
6. Press the clock module back into place in the base, making certain that it is seated correctly.
7. Install the wire terminal cover and the clock housing with the 2 screws.
8. Install the clear dust cover lens in place.
Programming
See Programming and Conf iguratio n inclu ded with the G CLK.
21
ZONE DAMPERS
DAMPER MODEL
MAXIMUM
PRESSURE
SYSTEM SIZE
DUCT SIZE
STMPD Round Med. Pressure
1.75”
Any Size
18”
STMRTD Rect. Med. Press ure
1”
7.5 Tons
24”W x 20”H
STCD Rect. Heavy Duty
1.75”
Any Size
48”W x 48”H
D-FUSER
0.1”
Any Size
10”
DIAMETER
CFM
FPM
∆P “ WC
6”
110
540
.014
8”
250
700
.015
10”
410
750
.015
12”
660
850
.022
14”
1000
925
.035
16”
1450
1070
.036
18”
2000
1100
.036
L
W
D
ROUND DIM ENSION AL DATA
STMPD06
6
6”
10”
9”
STMPD08
8
8”
10”
11”
STMPD10
10
10”
12”
13”
STMPD12
12
12”
14”
15”
STMPD14
14
14”
16”
17”
STMPD16
16
16”
18”
19”
STMPD18
18
18”
20”
21”
MEDIUM PRESSURE (STMPD)
DAMPER TO MODSTAT WIRING
Zonex Systems zone dam pers are used in cooling/heating systems to provide room by room zone control. The damper is provided with a factory mounted actuator. Each zone damper is controlled by a zone thermostat. Mo re than one damper can be controlled by one zone thermostat. Use this table to determine which zone
Maximum Differential Pressure refers to the maximum static pressure drop in inches of water column between the input (upstream) of the zone damper and the output (downstream) when the damper is closed.
dampers to use. ROUND MEDIUM PRESSURE ZONE DAMPERS Zonex Systems round medium pressure zone dampers are
recommended for systems with a maximum differential static pressure up to 1.75”. This modulating power open/power close damper is manufactured from 20-22 gauge galvanized steel with rolled-in stiff ening beads for superior rigidity. Mechanica l minimum and maximum s et stops are pr ovide d and are easil y adj ustable. T he damper is elliptical, which allows the airflow to be tracked linearly. The damper pipe is f urnished with one c rimped end and one s traight end for easy installation. Do not install damper in an inverted position. A hat section supports a reversing 24vac, 60Hz, 2 VA motor. A magnetic c lutch allows for continu ous power to the motor and longer motor life. Motor drive time from full open to full close is 90 seconds.
ROUND MEDIUM PRESSURE DAMPER PART NUMBERS AND SIZES
PAR T # SIZE D L W
TYPICAL ROUND CAPACITIES
These air quantities were derived from a duct s izing chart 0.1” friction loss per 100’ of duct. All CFMs listed are approxim ate. For accurate selection, use duct sizing table or device.
DIFFERENTIAL
DUCT
NOMINAL
MAXIMUM
DUCT VELOCITY
MAXIMUM
DAMPER
22
D
H
MOTOR
D
2 ½”
48” MAXIMUM WIDTH
MEDIUM PRESSURE RECTANGULAR DIMENSIONAL DATA
Part Number Sizes available from 8” x 6” up to 24” x 20”
2½”
5”
H
RECTANGULAR ZONE DAMPERS
The rectangular zone dampers are available in either medium pressure or heavy dut y. For systems under 7.5 tons, use medium pressure dampers . For systems 7.5 tons or over, use heav y duty dampers. Motor dr ive time open and close is 90 seconds.
RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS (STMRTD)
Zonex Systems rectangular medium pressure dampers are recommended for systems under 7.5 tons with a m aximum differ ential static pressur e of 1”. These are fully m odulating, power open, power close damper s. They are constructed from heavy duty alum inum and sta inless stee l. The d am per is an op posed blade type that slips into a 3¼-inch wid e cutout in the existing d uct and attaches with screws via a duct mountin g plate. The duct mountin g plate is 5 inches wide. A hat section supports a r eversing 24vac, 60Hz, 2 VA motor. A magnet ic clutch allows for continuous po wer to the motor and longer m otor life. Two set screws connect the motor to the damper shaft, allowing quick motor replacement if necessary. Motor drive time from full open to full close is 90 seconds.
W
HEAVY DUTY RECTANGULAR DIMENSIONAL DATA
Part Number STCD W x H Sizes available from 8” x 8” up to 48” x 48”
RECTANGULAR HEAVY DUTY ZONE DAMPERS (STCD)
Zonex Systems rectangul ar heavy duty dampers ar e recommended for systems 7.5 tons or larger with a m aximum differential static pres sure of 1.75”. These are fully modulating, po wer open / power close dam pers made of 20 gauge “s naplock” steel frame with S & Drive duc t connections. Allo w a 16” gap in the duct for the damper. Formed steel blade stops incorporate a gasket for quiet operation and improved structural rigidity. Rectangular dampers under 10” in height incorporate a single blade design. Dampers 10” or over use opposed blade design. A full stall motor, drawing 2 VA, drives the motor from full open to full close in 90 seconds.
STMRTD W x H 2¼”
23
RECTANGULAR DAMPER SELECTION
Rectangular Damper Capacities*
WIDTH IN INCHES
8 10
12
14
16
18
20
22
24
26
28
30
32
8
300
400
500
610
710
820
925
1050
1175
1250
1400
1500
1600
10
400
540
680
825
975
1125
1300
1400
1590
1750
1975
2100
2175
12
500
680
850
1000
1200
1400
1600
1850
2000
2300
2550
2700
2850
14
610
825
1000
1250
1500
1750
2000
2250
2500
2900
3150
3425
3625
16
710
975
1200
1500
1800
2100
2450
2700
3000
3600
3950
4200
4425
18
820
1125
1400
1750
2100
2500
2850
3080
3600
4400
4600
4950
5100
20
925
1300
1600
2000
2450
2850
3400
3775
4000
4800
5500
5700
6000
22
1050
1400
1850
2250
2700
3080
3775
4300
4800
5100
6000
6350
6800
24
1175
1590
2000
2500
3000
3600
4000
4800
5400
6100
7000
7150
7600
26
1250
1750
2300
2900
3600
4400
4800
5100
6100
6700
7800
8400
8900
28
1400
1975
2550
3150
3950
4600
5500
6000
7000
7800
8400
9150
10000
30
1500
2100
2700
3425
4200
4950
5700
6350
7150
8400
9150
10000
11000
32
1600
2175
2850
3625
4425
5100
6000
6800
7600
8900
10000
11000
11250
* These air quantities were derived from duct sizing chart .1" friction loss per 100' of duct.
All CFMs listed are approximate.
For accurate selection use duct sizing table or device.
6”
Neck Vel
Throw 50 FPM
400
500
600
700
800
900 0.011
0.016
0.023
0.035
0.04
0.055 80
98
120
135
157
176
4’
4’
5’
6’
6’
7’
8”
Neck Vel
Throw 50 PM
400
500
600
700
800
900
0.019
0.03
0.045
0.056
0.041
0.093 140
170
207
247
280
315 5’
6’
7’
8’
9’
10’
10”
Neck Vel
400
500
600
700
800
900
0.029
0.045
0.066
0.09
0.12
0.146 218
273
330
382
438
497
6’
8’
9’
10’
11’
12’
24”
2”
12”
COLLAR: PLACE ON SIDE PLACE ON TOP
12”
AT NECK VELOCITIES UP TO 700 FPM
HEIGHT IN INCHES
D-FUSER ZONE DAMPER
Zonex Systems D-Fus er is a combination zone damper and diffuser. It mounts in a st andard 2’ x 2’ T-bar ceiling opening, providing for simple installation and easy maintenance access. The D-Fuser is a cone shaped fluidic nozzl e with a platen that m odulates up and do wn to control air f low. As the platen m oves up, the air volume is r educed; but the air velocity and throw rem ain constant. This keeps the air hugging the ceiling, which maximizes room air mixing and minimizes the “waterfall” effect. The D-Fuser is a fully modulating power open / power c lose damper using a 24vac 60Hz 2 VA motor. Motor drive tim e from full open to full close is 90 seconds . The D-Fuser connects to rou nd duct either on the side or top. Collars ar e available for 6”, 7”, 8”, 9” and 10” duct.
NC LESS THAN 30
P
CFM
P
CFM
P
CFM
Throw 50 FPM
24
SIZING ZONE DAMPERS
If the ductwork already exists, simply size the damper to fit the ductwork. For new systems or retrofit jobs:
A. Determine CFM from heat gain or loss calculations. B. Select damper size using either the round capacities chart, the rectangular capacities chart or by
using a duct sizing table or calculator.
C. Select a Zonex Systems damper to fit the duct size selected for that zone.
Make sure your zone dampers match the type specified in the table showing Maximum Differential Pressure. INSTALLATION NOTES
1. Do not exceed 700 FPM in a register/diffuser branch duct.
2. If a damper is installed within 3 feet of a register/diffuser, install sound attenuating flex duct between damper and outlet.
3. Zone dampers should be preceded by 2’ 4’ of straight pipe where possible.
4. In attic installations and hi gh humidity areas, the Zone x Systems damper s hould be insulated along with the ductwork. The hat sec tion on the round damper is delivered with insulation between the hat section and pipe. Therefore, i nsul ation should be app lied t o the r ound p ipe and be but ted aga inst the h at sec tion (do not insulate the motor). The motor generates enough heat so that no condensation will develop on it.
5. Remember to allow a 16” gap in the duct for heavy duty rectangular dampers.
6. Medium pressure rectangular dampers slide into a 3¼” wide cutout in the side of the preexisting ductwork.
7. Minimum open and close p ositioning is field adjustabl e on the actuator. T he dam per is shipped from the factory to close 100%.
NOTE: Dampers should not be installed with motor upside down in the 6:00 position. SLAVING UP TO THREE ZONE DAMPERS Up to three dampers can be direc tly controlle d by one therm ostat. T o wire two to three zone dam pers to one
thermostat, use the follo wing diagram shown. Rem ember to size the damper power tr ansformer for the total number of zone dampers. Each actuator draws 2 VA.
ZONE DAMPER ZONE DAMPER ZONE DAMPER
Mc Ro Rc Mc Ro Rc Mc Ro Rc
Mc Ro Rc
MODSTAT
SLAVING MORE THAN THREE ZONE DAMPERS
Use the following diagram when a thermostat will be controlling more than three zone dampers. Use an additional 24V transformer sized at 2VA per damper to power the slaved dampers.
25
BYPASS DAMPERS – ELECTRONIC
8”
560
10”
900
12”
1250
14”
1700
16”
2200
18”
2600
STBP08
8
8”
10”
11”
STBP10
10
10”
12”
13”
STBP12
12
12”
14”
15”
STBP14
14
14”
16”
17”
STBP16
16
16”
18”
19”
STBP18
18
18”
20”
21”
ROUND BYPASS SELECTION TABLE
4”
H
D
W
48” MAXIMUM WIDTH
RECTANGULAR BYPASS DAMPERS
D
L
W
ELECTRONIC BYPASS DAMPERS Bypass dampers are used to provide constant air delivery through the air handling unit. This is done by bypassing excess air f rom the supply duct back to th e return duct. As a zone is sat isfied, its zone damper closes. When this happe ns , the bypass damper opens j ust enoug h t o b ypass the ex ces s air. This will control static pressure and noise at the diffusers.
The Electronic Bypas s Da mper is used on any size s yst em over 5 tons. The da mper can be round (STBP) or rectangular (STCDBP) with integrated static pressure control; and multiple dampers can be slaved together.
SIZING ELECTRONIC BYPASS DAMPERS The bypass damper is to be sized for the total system CFM @ 1500 F PM. System CFM should be calculated at 400 CFM per ton. Example: A 5-ton system is rated at 2000 CFM (5x400 = 2000). When calculated at 1500 FPM, the bypass damper should be 16”. Never undersize the bypass damper.
ROUND BYPASS DAMPER SELECTION The Zonex Systems STBP damper is used for round bypass applications. When you know the bypass CFM requirements, use the ROUND BYPASS SELECTION TABLE to confirm the round damper size. NOTE: Multiple round dampers can be slaved from one static pressure control to provide the correct capacity. One large rectangular bypass damper may be used instead of multiple round dampers. See below.
RECTANGULAR BYPASS DAMPER SELECTION
The Zonex Systems STCDBP WxH damper is used for rectangular bypass applications. These dampers are also sized for the total system CFM rated at 1500 FPM. Multiple dampers can be slaved from a single static pressure control.
Diameter CFM
PART # SIZE D L W
SELECT FROM 8 x 8 thru 48 x 48
26
RECTANGULAR BYPASS SELECTION TABLE
WIDTH IN INCHES
8 10
12
14
16
18
20
22
24
28
32
36
40
44
48
8
667
833
1000
1167
1333
1500
1667
1833
2000
2333
2667
3000
3333
3667
4000
10
833
1042
1250
1458
1667
1875
2083
2292
2500
2917
3333
3750
4167
4583
5000
12
1000
1250
1500
1750
2000
2250
2500
2750
3000
3500
4000
4500
5000
5500
6000
14
1167
1458
1750
2042
2333
2625
2917
3208
3500
4083
4667
5250
5833
6417
7000
16
1333
1667
2000
2333
2667
3000
3333
3667
4000
4667
5333
6000
6667
7333
8000
18
1500
1875
2250
2625
3000
3375
3750
4125
4500
5250
6000
6750
7500
8250
9000
20
1667
2083
2500
2917
3333
3750
4167
4583
5000
5833
6667
7500
8333
9167
10000
22
1833
2292
2750
3208
3667
4125
4583
5042
5500
6417
7333
8250
9167
10083
11000
24
2000
2500
3000
3500
4000
4500
5000
5500
6000
7000
8000
9000
10000
11000
12000
28
2333
2917
3500
4083
4667
5250
5833
6417
7000
8167
9333
10500
11667
12833
14000
32
2667
3333
4000
4667
5333
6000
6667
7333
8000
9333
10667
12000
13333
14667
16000
36
3000
3750
4500
5250
6000
6750
7500
8250
9000
10500
12000
13500
15000
16500
18000
40
3333
4167
5000
5833
6667
7500
8333
9167
10000
11667
13333
15000
16667
18333
20000
44
3667
4583
5500
6417
7333
8250
9167
10083
11000
12833
14667
16500
18333
20167
22000
48
4000
5000
6000
7000
8000
9000
10000
11000
12000
14000
16000
18000
20000
22000
24000
HEIGHT IN INCHES
DAMPER
* * *
SLAVE
TO NEXT SLAVE BYPASS DAMPER IF APPLICABLE
RC RO MC
Bypass air in CFM. Calculated at 1500 FPM. Formula used: B = W x H / 144 x 1500, where B = Bypass air in CFM, W = damper width in inches, H = damper height in inches, 144 = 144 sq. inches per sq. ft., 1500 = 1500 FPM.
ROUND AND RECTANGULAR BYPASS DAMPER MOTORS
SLAVING BYPASS DAMPERS
Use only one Pressure Sens or when slaving two or more Bypass Dampers together . Connect the Pressure Se nsor to one damper as described above. Connect the slave dampers in parallel as shown. Up to 4 dampers can be slaved to one Sensor. The slaved dampers will self­synchronize each tim e the dampers reach full ope n or full close.
ACTUATOR
DAMPER
ACTUATOR
RC RO MC
RC RO MC
To Static P ressur e Control, as show n on the B ypass Wiring Diagram on the ne xt pa ge.
27
BYPASS DAMPER with INTEGRATED PRESSURE CONTROL
(Part # STBP or STCDBP)
Bypass Damper with Integrated Pressure Control is used to control bypass operations. The bypass damper modulates to maintain static pressure as zone dampers open and cl ose. The bypass system reduces air noise from the supply registers caused by excessive air velocity. If the system is configured for intermittent fan mode and the system satisfies, there will be a 3-minute delay to allow for system purge, after which the bypass damper will open to 25%, preventing noisy rush of air through supply registers when fan starts up on a call f or heat or cool. If the system is configured for fan continuous operation, the STBP (Round) or STCDBP (Rectangular) Electronic Bypass will monitor static pressure continuously, providing constant control of system static.
INTEGRATED PRESSURE CONTROL DESCRIPTION
A. Supply air tube B. 24vac R and C C. Damper Terminal RO, RC, MC D. LED lights E. Adjustable Potentiometer F. TP1 Test Point
5. Drill ¼” hole into the side of the supply duct 2’ after the bypass and before the 1
st
supply take­off. Mount pressure supporting block over ¼” hole, align hole in block with hole in duct. Use provided sheet metal screws.
6. Install air tube into supply air duct by slipping supplied plastic tubing into holes in support block and duct. Slip tube 3” into the duct. Pickup tubing fits snugly into provided hole.
7. Connect pressure tube from static air pickup to Integrated Pressure Control.
Fig. 1
BYPASS DAMPER INSTALLATION
1. Verify the bypass damper is sized properly to the system and not undersized. (Bypass damper sizing is recommended for 100% of system CFM.)
2. Bypass damper and controller are powered by a dedicated 24vac 40VA transformer.
3. Do not install the bypass damper outside.
4. Locate the Integrated Pressure Control (IPC) and air tube on the bypass damper.
Fig. 2
BYPASS DAMPER WITH INTEGRATED BYPASS CONTROL SETUP
1. Run all supply dampers to the full open position and have blower motor running at 100% fan speed. (See Note #1)
2. Manually close the bypass damper by pressing in the release lever on the motor side of the actuator. With the release lever pressed, rotate the damper actuator collar to close the damper and release the lever to lock the damper closed.
3. Quick Set Option: Turn the potentiometer on the damper control board to the full left position and slowly rotate RIGHT, until the “RC” RED LED turns on. Now rotate LEFT just slightly, until RC LED turns off. The IPC is ready for operation.
RC” RED LED means damper closing.
RO” GREEN LED means damper opening.
28
4. Static Pressure Option: The Integrated Pressure Control Board can be field configured for specif ied static pressure using a multi meter and the static pressure – voltage chart. (Exhibit A). This chart shows voltage (DC) to inches of W.C. (static pressure) relationship. Use a multi meter set on VDC and place the leads on the “C” terminal and “TP1” (test point one) next to the potentiometer. The Voltage reading translates to inches of W.C.
BYPASS CHECKOUT FOR STATIC PRESSURE CONTROLLER
1. Make cool call at the zone thermostat of the smallest zone.
2. Verify all zone dampers are closed except for calling zone.
3. Verify noise at zone registers is not excessive. Adjust the Integrated Pressure Control LEFT to lower noise (airflow) or RIGHT to increase airflow until too noisy.
BYPASS DAMPER WIRING DIAGRAM WITH INTEGRATED BYPASS CONTROL
Note # 1: To open all dampers, it may be necess ary
to remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats. This will modulate dampers fully open and lock out compressor.
On Zonex Systems GEN II and ModCom II, use air balance modes for simplified bypass setup.
29
System 2000
Quick Quote Web Site:
GEN II
Hot Line: (800) 228-2966
5622 Engineer Drive
Huntington Beach, CA 92649
Factory: (714) 898-9963
Fax: (714) 898-6802
Visit our Web Site http://www.zonexproducts.com
www.zonexproducts.com
PATENTED PRODUCT Part #GENIIMAN Zonex Systems reserves the right to discontinue, June 2014 or change at any time, specifications or designs without notice and without incurring obligations. Copyright 2013 by Zonex Systems
The easy way to Get Quotes Fast
Loading...