Zonex System 2000, System 1000 Design & Installation Manual

Design & Installation for
Zonex Systems
System 2000
2-20 Zone Auto Changeover
Part #101ASIM
Rev. September 2003
System 1000
2-7 Zone Manual Changeover
TABLE OF CONTENTS
System Operation.................................................................................................................................................................1
Components.........................................................................................................................................................................1
Component Selection Guide .................................................................................................................................................2
System 2000 System Controllers...........................................................................................................................................3
Gas/Electric (101ASSB).............................................................................................................................................3-5
Heat Pump (101AACBHP) .........................................................................................................................................5-7
Startup.................................................................................................................................................................................8
System Operation.................................................................................................................................................................9
Components.........................................................................................................................................................................9
Component Selection Guide ...............................................................................................................................................10
System 1000 Switching Centers
Gas/Electric (SYGE)..............................................................................................................................................11, 12
Heat Pump (SYHPA)..............................................................................................................................................12-14
Startup...............................................................................................................................................................................15
Zone Thermostats ...........................................................................................................................................................16, 17
Remote Sensors .................................................................................................................................................................17
Zone Dampers .......................................................................................................................................................................18
Round Zone Dampers..................................................................................................................................................18, 19
Rectangular Zone Dampers..........................................................................................................................................20, 21
Sizing Zone Dampers .........................................................................................................................................................22
Wiring Zone Dampers........................................................................................................................................................22
Damper Installation Notes..................................................................................................................................................22
Paralleling Zone Dampers..................................................................................................................................................23
Bypass Dampers ....................................................................................................................................................................23
Barometric ..................................................................................................................................................................23, 24
Electronic ....................................................................................................................................................................25, 26
Bypass Position Indicators ..........................................................................................................................................26
Paralleling Bypass Dampers........................................................................................................................................26
Bypass Damper Static Pressure Controller .......................................................................................................................27
Capacity Controllers .............................................................................................................................................................28
101CAPGE....................................................................................................................................................................29, 30
TRLAT..........................................................................................................................................................................31, 32
TRFPC................................................................................................................................................................................32
SYCAP ..........................................................................................................................................................................33, 34
101ALAS ............................................................................................................................................................................35
CAPL-2.........................................................................................................................................................................36, 37
CAPL-4.........................................................................................................................................................................38, 39
Capacity Controllers Installation.........................................................................................................................................40
Capacity Controllers, Setpoints, Calibration........................................................................................................................41
Important Diagrams
Five Wire Link....................................................................................................................................................................41
Transformer/Fuse Sizing ....................................................................................................................................................42
Application Schematics ................................................................................................................................................42, 43
SYSTEM 2000
The System 2000 is a light commercial/residential zone control system. It enables a single HVAC unit to be controlled by up to twenty zone (room) thermostats. System 2000 is a vote based, auto changeover system. The system operates on a first call, first served majority wins on changeover strategy. To provide economical, effective and simplified remote control and monitoring capability of one or more System 2000 zone control sys-
tems, the ZonexCommander may be used to manage up to 80 thermostat schedules. The ZonexCommander is a Window’s based thermal manage­ment system, which can integrate gas/electric and heat pump zone sys­tems to include stand alone HVAC systems. For modulating communi-
cating control, use the ZonexCommander (Plus).
System 2000
Zonex Systems Supplied Components
System Controllers ..............................................................Pages 3- 7
Zone Thermostats ...............................................................Pages 16-17
Zone Dampers ....................................................................Pages 18-23
Bypass Dampers .................................................................Pages 23-27
Capacity Controllers............................................................Pages 28-41
System 2000
Field Supplied Components
Thermostat Wire........................................................................Page 41
24V Transformers and Fuse.......................................................Page 42
CONCEPTUAL
DRAWING ONLY
Refer to System 2000
Controller Section for
Wiring Information
SYSTEM OPERATION
The System Controller communicates with the Zone Dampers and Zone Thermostats via a patented Five-Wire Link. The Five-Wire Link is daisy chained from damper to damper using standard five-conductor thermostat wire. The System Controller polls every zone every 120 sec­onds and registers the number of thermostats calling for heating and cooling. The System Controller then runs the HVAC/Heat Pump unit in the mode with the most calls. If the majority changes, the System Controller will automatically change over to the new mode of operation.
The Zone Dampers are open for the zones calling and closed for the zones not calling for the operating mode. When the HVAC/Heat Pump unit is not running, all Zone Dampers are open to provide ventilation if the indoor blower fan is running continuously.
While the unit is running, the Capacity Controller monitors the leaving air temperature from the unit and will cycle the HVAC/Heat Pump unit off and on to maintain the air temperature within a preset range to eliminate coil freeze-up and premature heat exchanger failure.
1
SYSTEM 2000 COMPONENT SELECTION GUIDE
Auto Changeover for 2 to 20 Zones
START
GAS ELECTRIC
System Controller
(101ASSB)
Capacity Controller
Single Stage(TRLAT) or (101CAPGE)
2-Stage (CAPL-2)
3- or 4-Stage (CAPL-4)
HEAT PUMP
System Controller
2 Stage Heat/Cool with Auxiliary Heat
(101AACBHP)
Capacity Controller
101ALAS (Included with Controller)
ZONE THERMOSTATS
Communicating Digital Programmable Auxiliary Heat
(DIGICOM) (101DIGI) (101PROG) for reheat/baseboard
COMMAND CENTER
(101CEC Communication Package,
one per 20 thermostats)
5 TONS AND UNDER OVER 5 TONS
Low Pressure Dampers Medium Pressure Dampers
Round (101ARZD size) up to .5” SP Round (101AMPD size) up to 1.75” SP
Rectangular (101EC W x H) up to .5” SP Rectangular (101MRTD W x H) up to 1” SP
ZONE DAMPERS
Heavy Duty Rectangular (101CD W x H) to 1.75” SP
(101DIGITS)
Optional Outdoor T-Stat (field supplied)
12 X (Number of Dampers) = VA for the 6 X (Number of Dampers) =VA for the
24V System Transformer (Field Supplied) 24V System Transformer (Field Supplied)
BYPASS DAMPERS
5 TONS AND UNDER
Barometric Bypass Damper
Round (101ABBD size) Rectangular RBB W x H
COMPLETE SYSTEM
Some Heat Pumps utilize Gas/Electric thermostats, typically units over 7.5 tons. For this application, use the Gas/Electric parts selection and field modify the capacity control heat cutoff setpoint to 118° F.
OVER 5 TONS
Electronic Bypass Damper
Round (STMPD size)
Rectangular (STCD W x H)
Static Pressure Controller (101ASPC)
24V, 40VA Independent Transformer
for bypass (Field Supplied)
Use heavy duty rectangular dampers on systems of 7.5 tons or larger
2
SYSTEM 2000 CONTROLLERS
Dimensions 7” x 7” x 2.5”
Gas Electric System Controller
SYSTEM 2000 CONTROLLERS – GAS/ELECTRIC 101ASSB
OVERVIEW
The 101ASSB is a Gas/Electric System Controller that will control up to 20 zones for the System 2000 zoning system. The System Controller selects the mode of operation based on a majority calls basis. It is used in conjunction with a Capacity Controller. The Capacity Controller controls the HVAC system staging. Capacity Controllers are available for one, two, three and four stage systems. Refer to Capacity Controller section (pg. 28) for further information.
The 101ASSB is a vote based, auto changeover System Controller. It polls each zone every 120 seconds, registering heat or cool calls. Majority wins, and the Controller operates the HVAC system in that mode until all calls are satisfied or it detects a majority of offsetting calls.
The System Controller should be located in an accessible, conditioned space. The Controller does not sense temperature; it simply receives data from the zone thermostats. The Controller communicates to the zone dampers and thermostats through a five-wire link. These five wires are daisy chained to each zone damper. This simple patented wiring process eliminates home run wiring.
OPERATION
When heating or cooling calls are sent to the System Controller, the controller will treat these calls as votes.
Heat Pump System Controller
(101ASSB)
HEAT CALLS– If the majority of calls are for heat, the System Controller
will turn on the heat. If the fan switch is set for auto, the bonnet control or a delay relay will start the fan. When all heating calls are satisfied or the majority changes to cooling, the gas valve will turn off.
CHANGEOVER – If the system is running in one mode and the majority of calls changes to the other mode, a timer will start. The System Con­troller will give the current operating mode another 4 minutes to try and satisfy the zone(s). It will then go into a 4-minute purge cycle before switching modes.
PURGE MODE – When a heat or cool call is satisfied or before chang­ing modes, the System Controller will go into a 4-minute purge cycle. The compressor or gas valve will turn off and the indoor blower will con­tinue to run. The dampers of any zone thermostat not satisfied in the previous mode will remain open. This allows the supply air to adjust to room temperature before changeover or ventilation while providing a time delay to prevent short cycling.
VENTILATION– When no zones are calling, all zone dampers open after the purge mode. This permits ventilation in all zones if the blower fan is on continuously.
with LAS Sensor
(101AACBHP)
COOL CALLS – If the majority of calls are for cooling, the System
Controller will turn on the compressor and fan. The air conditioner will continue to operate until all cooling calls are satisfied or the majority changes to heating.
3
RW1Y1G
TB2
ON
OFF
OFF
OFF
AUTO
ON
AUTO
TB1
TR2 TR1
1
TC2 TC11SYWRdBG
A
J
C
B
D
E
I
H
G
F
101ASSB
DELAY
HEAT
COOL
DAMPER
UNIT
J1
J2
SET BACK
FAN
HEAT
COOL
PWR
SYSTEM 2000 CONTROLLERS – GAS/ELECTRIC 101ASSB
COMPONENTS
The 101ASSB System Controller consists of the following:
A. TB1 (Terminal Block 1): Wires to daisy chain, transformer
and time clock. TC1, TC2 – Time clock switch terminals. Used for Select-Temp system only. S – Nite call. Used for Select-Temp system only. Y – Cool call. W – Heat Call. Rd – Damper close signal. B – 24V AC common. Same terminal as TR2. G – 24V AC hot. Same terminal as TR1 when PWR switch ON. TR2 – 24V AC common. TR1 – 24V AC hot.
B. Jumpers J1 and J2:
J1 – Not used. J2 – Not used for System 2000. Used for Select-Temp system only.
C. Microcontroller: Responsible for zone communication, activation
and control of outputs based upon zone demand and leaving air temperature. Occasionally software upgrades may become avail­able. If so, the 101ASSB software can be field upgraded by chang­ing this microcontroller.
D. Off board fuse: One amp. Protects Y and W terminals of TB1. E. Status lights: Refer to status light section for details. F. TB2 (Terminal Block 2): Wires to Capacity Controller and
HVAC unit. R – HVAC unit 24V AC power W1 – Heat enable Y1 – Cool enable G – Indoor blower fan enable
G. FAN switch:
AUTO – Turns on indoor blower fan when unit is running in cool mode. ON – Indoor blower fan runs continuously.
H. COOL and HEAT mode switches:
AUTO – Accepts calls from thermostats. OFF – Ignores calls.
I. Power switch. When on, applies 24V AC power to G of TB1. J. On board fuse. One amp. Protects 101ASSB board only.
STATUS LIGHTS
DELAY On when HVAC unit energized. Flashing when in purge/delay mode. HEAT* On in heat mode. COOL* On in cool mode. DAMPER When on, dampers of zones not calling for present mode are closed. UNIT On when HVAC unit energized.
*MODE LIGHTS TOGGLE BETWEEN HEAT AND COOL EVERY 120 SECONDS. THIS INDICATES THE SYSTEM CONTROLLER IS POLLING FOR HEAT OR COOL CALLS.
Delay Heat* Cool* Damper Unit
01000Heat, no calls HVAC unit off. All dampers open. 00100Cool, no calls HVAC unit off. All dampers open. 11011Heat call Heat energized. Heat calling zone dampers open.
10111Cool call AC energized. Cool calling zone dampers open. FLASH 1010Purge heat Blower fan on, HVAC unit off. Heat calling zone dampers open. FLASH 0110Purge cool Blower fan on, HVAC unit off. Cool calling zone dampers open.
Status Lights Mode Function
4
SYSTEM 2000 CONTROLLERS - GAS/ELECTRIC 101ASSB
Fused 24V AC Damper Transformer
1
7
6
TR2
TR1
SY WRdB G
TB1
DAISY CHAIN UP TO 20 ZONES
101ASSB
System Controller
TC2 TC
1
3
2
ZONE DAMPER
WY G RdBW2
WY R C RCW2 MC RO
Open
Close
DAMPER MOTORS
TB2
TB1
WY R C
ZONE
THERMOSTAT
DAMPER RELAY BOARD (P/N 101ARLY)
W1 Y1RG
TB2
TO CAPACITY CONTROLLER
AND HVAC UNIT (PG 28)
4
5
1
2
3
4
5
6
7
8
WIRING
If the heater does not turn on the blower fan, a blower fan relay must be installed. See page 43.
24V damper transformer. Requires in-line fuse. See table on page 42 for sizing trans­former and fuse.
Refer to page 41 for Five Wire Link wire sizing.
C terminal for hard wired electronic thermostats only.
Open motor not utilized on low pressure (spring open) dampers.
If using more than one damper per thermostat, refer to Slaving Zone Dampers section, page 23 and 44.
Do not remove factory installed jumper between TC1 and TC2. TC1 and TC2 are used for Select-Temp Zoning System only.
SYSTEM 2000 CONTROLLERS – HEAT PUMP 101AACBHP
The 101AACBHP Heat Pump Controller greatly simplifies coordination of single stage or two stage Heat Pumps with dampered zone systems. The Controller communicates to the zone dampers through a five wire link. These five wires are daisy chained to each zone damper. This simple patented wiring process eliminates home run wiring. The 101AACBHP
Overview
has a built-in capacity control system which uses an LAS (included with the Controller) for capacity control. Refer to the section on Capacity Control LAS for more information.
The Controller operates the Heat Pump using signals from each zone thermostat in the system. When heating or cooling calls are sent to the
Operation
controller, it treats these calls as votes. If the majority of calls are for cooling, the Controller will operate in the cool mode. The Heat Pump will continue to operate in the cool mode until the majority of calls shift to heating or all cooling calls are satisfied. If the majority of calls are for heating, the Controller will operate in the heat mode. The Heat Pump will continue to operate in the heat mode until the majority of calls shift to cooling or all heating calls are satisfied.
When using the 101ASSB controller in a heat pump application which utilizes G/E terminals, a fan relay must be installed, see page 43.
*The reversing valve is energized depending on the O/B jumper setting.
Second stage operation is based on the leaving air temperature of the unit. The LAS reports the discharge temperature to the Controller. Three minutes after initiating cooling, the Controller checks the LAS. If the discharge temperature is above 52 degrees, the second stage is turned on. Three minutes after initiating heating, the Controller checks the LAS. If the discharge temperature is below 114 degrees, the second stage is turned on.
The Heat Pump Controller is also set up to operate electric strip heat in the Heat Pump. The Controller monitors the air temperature leaving the Heat Pump coil. When there is a call for heat and the air leaving the coil is not above 85 degrees, the electric strip will turn on after an eight minute delay. This operation can be modified, if desired by an outdoor thermostat.
The Heat Pump Controller simplifies system wiring. The Controller terminals connect directly to the Heat Pump terminal strip. (Heat Pump thermostats are not used for this system). Relays, timers and other miscellaneous controls are not required.
5
SYSTEM 2000 CONTROLLERS – HEAT PUMP 101AACBHP
OPERATION (Continued)
The 101AACBHP Zonex Systems SYSTEM 2000 Heat Pump controller has a series of lights which indicate different operations. These are labeled “Heat,” “Cool,” “Damper,” “Pump,” “Rev. Valve,” “Y1 Cool”, “Y2 Cool,” “Y1 Heat” and “Y2 Heat.” The “Heat” and “Cool” lights indicate, when illuminated, the present mode of operation. These lights will momentarily toggle to the other mode every 120 seconds when polling. Polling is when the controller checks to see how many heat and cool calls are being made. If there are no calls, the “Heat” or “Cool” light will be on based on the last operating mode. The “Damper” light indicates that a thermostat is calling and that power is being supplied to the damper motors. The “Pump” light indicates that the first stage pump is operating. The “Rev. Valve” light indicates that the reversing valve is activated, or when it flashes, that a time delay is active. The “Y1” and “Y2” Cool and Heat lights are part of the Capacity control function included on the Heat Pump Controller. The Y2 Heat or Cool LED, when illuminated, indicates the Y2 compressor has cycled OFF, because the capacity control setpoint has been exceeded. When Y1 and Y2 heat or Cool LEDs are both illuminated, the controller will initiate a 4-minute temperature cut out, with both stages cycling off.
When power is first turned on, if there are no calls for cooling or heating, the “Heat” light will be the only light illuminated, with the exception of the “Rev. Valve” light. It will also be on if jumper J1 is removed (“B” operation). When there is a cooling or heating call, the “Damper” and “Heat” or “Cool” lights will turn on.
When the “Rev. Valve” light is not indicating a time delay by flashing, it will stay illuminated only when the reversing valve is operated.
HEAT – Reversing valve “O” Mode – When the controller receives an initial or consecutive call for Heat, the Rev Valve LED will flash; the Heat, Damper and Pump LEDs will illuminate. The first stage heat will energize on Y1, and the Rev Valve LED will continue to flash for at least 4 minutes. After 4 minutes from Y1, if the supply temperature is 95° or less, Y2 will energize and the Rev Valve LED will go OFF (Heat “B” mode will change the flashing Rev Valve LED to ON when Y2 energizes). The auxiliary heat will energize 4 minutes after Y2 and when the supply air temperature is 85° or less.
COOL – Reversing Valve “O” Mode – When the controller receives an initial or consecutive call for Cool, the Rev Valve LED will flash; the
Cool, Damper and Pump LEDs will illuminate. The first stage cool will energize on Y1 and O/B with the Rev Valve LED flashing for 8 minutes. After 8 minutes from Y1, if the supply air temperature is 60° or higher, Y2 second stage of cooling will energize. The Rev Valve LED will change from flashing to steady ON. (Cool “B” mode for Rev Valve LED will change from flashing to OFF after Y2 energizes.)
AUTO CHANGEOVER – If an existing mode is overridden by an opposite majority, the existing call will remain in operation for 4 minutes, and then the controller will go into a 2 minute purge with the existing dampers staying open. After the purge cycle has timed out, the system blower cycles OFF (when in the auto mode). The controller goes into a 2 to 4 minute delay, switching to the opposite mode, with the dampers making the opposite call opening. Y1 and Y2 are not energized during this delay. After this final delay times out, the controller energizes Y1 in the opposite mode.
If all zones satisfy, the “Pump” and “Damper” lights will go out. The “Heat” or “Cool” lights will be on based on the last mode of operation.
If your system includes auxiliary heat, it will be activated by the “W” terminal on the SYSTEM 2000’s Heat Pump Controller. Auxiliary heat will be activated when the following conditions are met. The “Heat” and “Damper” lights are on indicating a heat call; the “Pump” light is on and the “Rev. Valve” light is not flashing, indicating that first and second stage are activated; four minutes after the “Rev. Valve” light stops flashing the auxiliary heat will be activated if the leaving air temperature is below the Electric Heat setpoint (factory set at 85 degrees). The time delay before bringing on the auxiliary heat gives the second stage time to raise the leaving air temperature over 85 degrees. Even if the system is single stage, the controller will still delay the electric heat until after the second stage time delay is satisfied.
The reversing valve is controlled by the “O/BL” terminal. This terminal should be connected to the Heat Pumps terminal strip according to the unit manufacturers recommendations. Jumper J1 on the SYSTEM 2000 Heat Pump board needs to be adjusted to operate with the different manufacturers designs. The Heat Pump board is shipped from our factory ready to operate a heat pump unit which requires the “O” wire to energize the reversing valve in cooling. If the reversing valve needs to be activated for the “BL” terminal, jumper J1 needs to be removed from the Controller board. Refer to the Heat Pump Controller drawing on the previous page for the location of jumper “J1”. Remove the jumper from the board to activate the reversing valve using the “BL” terminal.
Warning: For heat pumps using standard gas/electric thermostats, do not use the 101AACBHP System Controller. Instead, use the
101ASSB System Controller and the CAPL-2 Capacity Controller.
6
SYSTEM 2000 CONTROLLERS – HEAT PUMP 101AACBHP
POWER UP, NO CALLS:
CALL (HEAT/COOL):
1ST STAGE
2ND STAGE
AUX. HEAT
DELAY IN MINUTES
STATUS LIGHTS: STATUS LIGHTS:
0
4*
8
DAMPER
OFF DAMPER
ON
ON
ON
REV. VALVE
NOTE 1 REV. VALVE
FLASH
NOTE 1
NOTE 1
HEAT*
ON HEAT
ON FOR HEAT
ON FOR HEAT
ON FOR HEAT
COOL*
OFF COOL
ON FOR COOL
ON FOR COOL
ON FOR COOL
PUMP
OFF PUMP
ON
ON
ON TB2: TB2: Y1 OFF Y1
ON
ON
ON Y2
OFF Y2
OFF
ON
ON G
OFF G
ON
ON
ON W
OFF W
OFF
OFF
NOTE 2
O/BL NOTE 1 O/BL
NOTE 1
NOTE 1
NOTE 1
MODE CHANGE: 1ST STAGE 2ND STAGE AUX. HEAT
STATUS LIGHTS:
O 4 8 10 12
DAMPER
ON ON ON ON ON
REV. VALVE
FLASH FLASH NOTE 1 NOTE 1
HEAT*
ON FOR HEAT ON FOR HEAT ON FOR HEAT ON FOR HEAT
COOL*
ON FOR COOL
ON FOR COOL
ON FOR COOL
ON FOR COOL
PUMP
OFF ON ON ON TB2: Y1
OFF ON ON ON Y2
OFF OFF ON ON G
OFF ON ON ON W
OFF OFF OFF NOTE 2 O/BL
NOTE 1 NOTE 1 NOTE 1 NOTE 1
DELAY IN MINUTES
NOTE 1: On if: a) In cool mode and reversing valve set for “O” operation (J1 jumper installed).
b) In heat mode and reversing valve is set for “BL” operation (J1 jumper removed).
NOTE 2:
On when in heat mode and supply air temperature below Electric Heat setpoint.Heat, Cool, and Fan switches in AUTO position. Capacity Controller lights off. Delay times are approximate.
*Momentarily toggles to opposite mode every 120 seconds.
CONTINUE
PREVIOUS
MODE
OPERATION
UP TO
20
ZONES
WYRC
BWY GRd
W Y R C RC MC RO
TB1
TB2
-
+
NC
W2
W2
FUSED 24 VOLT
TRANSFORMER
ELECTRIC HEAT
PUMP #2 PUMP #1
REV VALVE
FAN
Y1
G
Y2
W
R
O
BL
/
TO
HEAT
PUMP
101AACBHP HEAT PUMP
CONTROLLER
REV.
VALVE
HEAT
COOL
DAMPER
PUMP
Y1
Y2
Y1
Y2
HEAT
COOL
J1
ON
PWR
OFF
COOLHEAT
OFF
AUTO
OFF
ON
AUTO
FAN
HEAT ADJ TP3
COOL ADJ
TP2
ELECTRIC HEAT ADJ TP1
GROUND
GND
Y1
G
Y2
TB2 WR
O
BL
/
TC2
Y
W
BG
Rd TR1TR2STB1 TC1TEMP
-
+
J2
5
1
7
2
4
6
Zone
Thermostat
Zone
Damper
Relay Board
(101ARLY)
Motors
Close Open
DUCT
MOUNTED
LEAVING AIR
SENSOR
(101ALAS)
(PG 35)
1
2
3
4
5
6
7
8
OPERATION SUMMARY TABLE (EFFECTIVE HPC V1.04 8/02)
*NOTE:
Cool:Y2 delay on
make 8 min. Heat:Y2 delay on
make 4 min.
NOTES:
Refer to page 41 for 5 wire link wire sizing.
24V damper transformer. Requires in-line fuse. See table on page 42 for sizing transformer and fuse.
C terminal for hardwired electronic thermostats only.
J1 Reversing Valve Selection Jumper. Leave jumper in place to energize reversing valve in cool mode, “O” mode. Remove jumper to energize in heat mode, “B” mode. J2 is not used for System 2000.
If the heat pump does not include an outdoor thermostat, it is recommended that the “W” wire to the unit is run thru an optional outdoor thermostat with a manual override switch.
Do not remove the jumper wire from TC1 and TC2. Used for Select-Temp Zoning System only.
Open motor not utilized on low pressure (spring open) dampers.
If using more than one damper per thermo­stat, refer to Slaving Zone Dampers section, pages 23 and 44.
NOTE:
If the Heat Pump system does not have rev. valve inputs, use the 101ASSB (Gas/Electric Controller).
WIRING
7
SYSTEM 2000 SYSTEM STARTUP
Make sure the correct size fuse is installed in-line with the transformer powering the Controller.
For both Gas/Electric and Heat Pump Controllers
1. These system tests are to be done with all wiring to the air condi­tioning unit disconnected.
A. Be sure that the power switch to the Controller is in the “OFF”
position. For Gas/Electric remove “R,” “W1,” “Y1” and “G” wires from Terminal Strip 2 labeled (TB2).
B. Be sure that the power switch to the Controller is in the “OFF”
position. For Heat Pumps remove “R,” “W,” “Y2,” “Y1,” “O/BL” and “G” wires from Terminal Strip 2 labeled (TB2).
2. Check wiring of the 5 wire link to the dampers. All connections
must be made color to color.
3. If you are not using Zonex Systems supplied zone thermostats,
check each one to make sure it is an auto changeover type stat. Turn all thermostats to the OFF position. Check the Controller “HEAT” and “COOL” switches to be sure that both are in the “OFF” position. The “FAN” switch should be in the “AUTO” position. Observe the fuse on the Controller Board and transformer. Turn the power switch to “ON.” If the fuse blows, there is a wiring problem. If the fuse does not blow, turn the “HEAT” switch to “AUTO” and “COOL” switch to “AUTO.” If the fuse blows at any of these steps, find and repair the short in the wiring.
4. If the system is operating normally, the Heat light should be on for
the 101ASSB, and 101AACB-HP. Set the “HEAT” switch to “OFF”. Check the first zone by turning it on and setting it to call for cool­ing. If the call is received by the Controller, the “Damper” and “Cool” lights will turn on. If the lights come on, turn off the first stat and the “Damper” light should turn off. Test each stat this way to be sure that each one is capable of communicating with the Controller, and able to start and stop the air conditioner.
NOTE: “Heat” and “Cool” Led indicators will toggle every two min­utes to check opposite mode callers, regardless of heat and cool switch positions.
5. After cooling calls are tested, turn the cooling switch to “OFF” and set the heating switch to “AUTO”. Set the first zone to call for heat. If the call is received by the Controller, “Damper” and “Heat” lights will turn on. Test each thermostat to be sure that each properly communicates with the Controller for the heating sequence.
6. After all zones have been checked, turn the ON/OFF switch at the System Controller to OFF.
7. Before wiring the System Controller to your A/C unit or furnace, check the relays with a volt meter (set on 200 Ohms). Be cer­tain no continuity exists on the A/C unit terminal connections at the System Controller. Check between each terminal to the “R” termi­nal. There should be no continuity between the terminals. (If you do show continuity, your System Control board should be replaced.)
8. If no continuity exists from the test detailed above, connect the terminal to the A/C unit and the System Controller. Be certain all thermostats are now in the “OFF” position.
9. Turn the power switch to “ON” and the “HEAT” and “COOL” switch­es should be set to “AUTO”. Initiate a call for cooling from only one stat. After a time delay, both compressor and fan should be running. Turn off the cooling and initiate a heating call, (you may experience up to a 4 minute time delay). The heat should come on and after a short time delay the fan will be operated by the internal controls of the unit. On the Heat Pump controller, eight minutes on the ini­tial start of CAPL-2 after stage one starts, the LAS or capacity con­trol will control second stage operation.
10. After completing the system check and startup procedure, set the system up for normal operation.
8
SYSTEM 1000
System 1000 Zone Control enables a single HVAC unit to be controlled by up to seven zone (room) thermostats. System 1000 is a manual changeover system. This means that the mode of operation (heat/cool)
CONCEPTUAL DRAWING ONLY Refer to System 1000 Switching Center Section for Wiring Information.
is manually selected. For auto changeover capability select Zonex Systems System 2000.
4.25"
2.5"
1"
SYSTEM OPERATION
The user manually selects the mode (heat/cool) at the Switching Center. If any zone thermostat calls for the mode selected, the green call light turns on at the Switching Center, the HVAC/heat pump unit turns on, and all non-calling zone dampers close.
Once all zones are satisfied, the green call light turns off, the HVAC/heat pump unit shuts off and all dampers open. If the Switching Center fan switch is ON, the fan will continue to run to allow ventilation in all zones.
The Capacity Controller independently monitors the supply air temperature to prevent coil freeze up or overheating.
The Bypass damper will independently bypass any supply air not needed back to the return duct.
System 1000
Switching Center
System 1000
Zonex Systems Supplied Components
Switching Centers................................................................Pages 11-14
Zone Thermostats ...............................................................Pages 16-17
Zone Dampers ....................................................................Pages 18-23
Bypass Dampers .................................................................Pages 23-27
Capacity Controllers............................................................Pages 28-41
System 1000
Field Supplied Components
Thermostat Wire........................................................................Page 41
24V Transformer(s) and Fuse....................................................Page 42
9
SYSTEM 1000 – COMPONENT SELECTION GUIDE
Manual Changeover for 2 to 7 Zones
GAS ELECTRIC
Switching Center
(SYGE)
ZONE THERMOSTATS
Digital Programmable
(101DIGI) (101PROG)
CAPACITY CONTROLLERS
START
HEAT PUMP
Switching Center
(SYHPA)
2 Stage Heat/1 Stage Cool
ZONE THERMOSTATS
Digital Programmable
(101DIGI) (101PROG)
1 Stage
(TRLAT)
or
Digital Version
(101CAPGE)
Round (101ARZD size) up to .5” SP
Rectangular (101EC W x H) up to .5” SP
12 X (Number of Dampers) = VA for the
24V System Transformer (Field Supplied)
2 Stage
(CAPL-2)
5 TONS AND UNDER
Low Pressure Dampers
5 TONS AND UNDER
Barometric Bypass Damper
Round (101ABBD size) Rectangular RBB W x H
DIGITAL CAPACITY CONTROLLER
(SYCAP)
Optional Outdoor T-Stat (field supplied)
ZONE DAMPERS
OVER 5 TONS
Medium Pressure Dampers
Round (101AMPD size) up to 1.75” SP
Rectangular (101MRTD W x H) up to 1” SP
Heavy Duty Rectangular (101CD W x H) to 1.75” SP
6 X (Number of Dampers) =VA for the
24V System Transformer (Field Supplied)
BYPASS DAMPERS
OVER 5 TONS
Electronic Bypass Damper
Round (STMPD size)
Rectangular (STCD W x H)
Static Pressure Controller (101ASPC)
COMPLETE SYSTEM
Some Heat Pumps utilize Gas/Electric thermostats. For this type of Heat Pump, use the Gas/Electric parts selection and field modify the capacity control heat cutoff setpoint to 118° F.
10
24V, 40VA Independent Transformer
for bypass (Field Supplied)
Use heavy duty rectangular dampers on systems of 7.5 tons or larger
SYSTEM 1000 SWITCHING CENTERS – GAS/ELECTRIC SYGE
OVERVIEW
The SYGE Switching Center is a manual changeover, Gas/Electric System Controller. It can control up to 7 zone thermostats. Its function is to look for calls from the zone thermostats for the mode (heat/cool) selected. If a call is received, it sends a signal to close the dampers of all zones not calling and sends a signal to the HVAC unit to energize heating or cooling.
The Mode, Power and Fan control switches are located at the Switching Center. The Switching Center should be placed in a location that provides easy access to these switches.
The Switching Center is used in conjunction with a Capacity Controller. The Capacity Controller protects the evaporator coil from freezing and the heat exchanger from overheating. The Capacity Controller also controls staging for multistage HVAC systems. Refer to the Capacity Controller section (pg. 28) for more information.
COMPONENTS
1. 5 Wire Link Terminals – Daisy chain wires to zone dampers.
YD – Cool call input signal. Current flows in this terminal when Mode switch at COOL, Power switch ON and thermostat calling for cool. WD – Heat call input signal. Current flows in this terminal when Mode switch at HEAT and thermostat calling for heat. BD – 24V return. Same as TR2. GD – 24V hot. Same as TR1. RD – Unit on output signal. Energized (RD made to GD) when Switching Center acknowledges thermostat call. See 7.
2. Transformer Terminals – 24V AC transformer terminals. This
transformer powers the dampers, thermostats and Switching Center. It does not power the HVAC unit. That power comes from terminal R; see 3.
3. HVAC Unit Terminals – Connect to HVAC unit via Capac-
ity Controller. See Capacity Controller section for wiring information. W – Heat enable. Energized (W made to R) when Switch­ing Center acknowledges a heat call. See 7. Y – Cool enable. Energized (Y made to R) when Switch­ing Center acknowledges a cool call. See 7. R – HVAC unit 24V power. G – Fan enable. Energized when FAN switch is at ON posi­tion or when FAN switch is at AUTO position and Switch­ing Center acknowledges a cool call. See 7.
4. Mode Switch – Selects mode (heat/cool) to run system.
Switching Center will only respond to thermostats calling for mode selected.
HEAT
COOL
AUTO
FAN
OPERATION
The user manually selects the mode (heat/cool) at the Switching Center. Heat mode – If any zone thermostat calls for heat, electrical current flows in WD. The Switching Center senses this current, turns on the green Call light, energizes RD (RD made to GD) which tells the dampers of all zones not calling to close and energizes W (W made to R) which tells the HVAC unit to turn on heat. Cool mode – If any zone thermostat calls for cool, electrical current flows in YD. The Switching Center senses this current, turns on the green Call light, energizes RD (RD made to GD) which tells the dampers of all zones not calling to close, and energizes Y and G (Y and G made to R) which tells the HVAC unit to turn on cooling and the indoor blower fan. No calls – When no thermostats are calling, the green Call light is off, RD is not energized so all dampers are open, and W, Y are not energized so the HVAC unit is off. If the FAN switch is ON, then G is energized (G made to R), and the indoor blower fan will run. This allows ventilation in all zones.
5. Power Switch – When OFF the Switching Center will not respond to
thermostat calls. Power remains to all dampers and thermostats. The indoor blower fan will run if fan switch is on.
6. Fan Switch – Controls the indoor blower fan (G).
AUTO – Indoor blower fan turns on when air conditioner is on.
Note: In heat mode, furnace controls indoor blower fan.
ON – Indoor blower fan continuously on as long as Power switch is ON.
7. Call Light – On when Switching Center responds to a calling
thermostat.
1 2 3
ON
OFF
ON
YD WD BD GD RD TR1 TR2 W Y R G
4
SWITCHING CENTER
5
6
SYSTEM 1000
GAS/ELECTRIC
(SYGE)
GREEN CALL
LIGHT
7
11
YD
WD GDBDRD
LOGIC BOARD
160 OHMS
COOLHEAT
SWITCHING
CENTER
(SYHPA)
GREEN CALL LIGHT
OFF
K1
LOGIC BOARD
TR
1 TR2
POWER
K1
F U S E
3P3T
SWITCH
K1
COOL
HEAT
OFF
OFF
E.M. HEAT
ON
FAN
ONAUTO
OB
COOLHEAT
OFF
O/B Y
G R W2 E L C
E.M. HT LIGHT
(RED)
COMP. FAIL
(YELLOW)
SYSTEM 1000 SWITCHING CENTERS – GAS/ELECTRIC SYGE
2
3
4
5
1
WIRING
NOTES:
24V damper transformer. Requires in line fuse. See table on page 42 for sizing transformers and fuse.
Refer to page 41 for five wire link wire sizing.
C terminal for hard wired electronic thermostats only.
Open motor not utilized on low pressure (spring open) dampers.
If using more than one damper per thermostat, refer to Paralleling Zone Dampers section, pages 23 and 44.
SYSTEM 1000 SWITCHING CENTERS – HEAT PUMP SYHPA
SIMPLIFIED SCHEMATIC, SYHPA
SIMPLIFIED SCHEMATIC, SYGE
W
COOL
Y
R
G
HEAT
K1
ON
FAN
AUTO
LOGIC
BOARD
GREEN
CALL LIGHT
COOL
K1
WDYD GDBD RD
HEAT
POWER
160
OHMS
LOGIC
BOARD
SWITCHING CENTER
K1
OVERVIEW
The SYHPA Switching Center is a manual changeover, single stage cool, two stage heat, heat pump System Controller. It can control up to 7 zone thermostats. Its function is to look for calls from the zone thermostats for the mode (heat/cool) selected. If a call is received, it sends a signal to close the dampers of all zones not calling and sends a signal to the heat pump unit to energize heating or cooling.
The Switching Center is used in conjunction with a SYCAP Capacity Controller. The SYCAP cycles the heat pump on and off to maintain the leaving air temperature within a set range. Refer to the SYCAP in the Capacity Controller section (pg. 33) for more information.
12
TR1
TR2
SYSTEM 1000 SWITCHING CENTERS – HEAT PUMP SYHPA
The Mode, Power, Fan and Emergency Heat control switches are located at the Switching Center. The Switching Center should be placed in a location that provides easy access to these switches.
NOTE: If your heat pump is controlled by a gas/electric thermostat, use
an SYGE Switching Center. See SYGE Switching Center section, pg. 3.
OPERATION
The user manually selects the mode (heat/cool) at the Switching Center.
Heat mode – With the Mode switch set to HEAT, Fan switch set to AUTO,
EM HT switch set to OFF and Power switch set to ON, if any zone ther­mostat calls for heat, electrical current flows in WD. The Switching Cen­ter senses this current, turns on the green Call light, energizes RD (RD made to GD) which tells the dampers of all zones not calling to close and energizes Y, W2 and G (Y, W2 and G made to R). G turns on the indoor blower fan. Y controls the heat pump compressor and W2 controls auxiliary heat. Y and W2 are further controlled by the SYCAP Capacity Con­troller which makes and breaks Y and W2 to maintain a minimum and maximum leaving air temperature. See SYCAP under Capacity Controller section for further information. The reversing valve is energized (B made to R) if the reversing valve jumper is set to B.
Cool mode – With the Mode switch set to COOL, Fan switch set to AUTO,
EM HT switch set to OFF and Power switch set to ON, if any zone thermostat calls for cool, electrical current flows in YD. The Switching Center senses this current, turns on the green Call light, energizes RD
(RD made to GD) which tells the dampers of all zones not calling to close and energizes Y, and G (Y and G made to R). G turns on the indoor blow­er fan. Y controls the heat pump compressor. Y is further controlled by the SYCAP Capacity Controller which makes and breaks Y to maintain a minimum leaving air temperature. See SYCAP under Capacity Controller section for further information. The reversing valve is energized (O made to R) if the Reversing Valve jumper is set to O.
No calls – When no thermostats are calling, the green Call light is off,
RD is not energized so all dampers are open, and W2, Y are not energized so the HVAC unit is off. If the FAN switch is ON then G is energized (G made to R) and the indoor blower fan will run. This allows ventilation in all zones.
Emergency Heat – With the Mode switch set to HEAT, Fan switch set
to AUTO, EM HT switch set to ON and Power switch set to ON, if any zone thermostat calls for heat, electrical current flows in WD. The Switching Center senses this current, turns on the green Call light and red Emer­gency Heat light, energizes RD (RD made to GD) which tells the dampers of all zones not calling to close and energizes E (E made to R). What E is wired to depends on the make of your heat pump. Refer to the SYHPA wiring diagram for further information.
Note: Do not leave the Emergency Heat switch set to ON when the Mode switch is set to COOL. Doing so will energize E (turning on emergency heat) when a thermostat makes a cool call.
COMPONENTS
1. 5 Wire Link Terminals – Daisy chain wires to zone dampers.
WD – Heat call input signal. Current flows in this terminal when Mode switch is at HEAT and thermostat is calling for heat. YD – Cool call input signal. Current flows in this terminal when Mode switch is at COOL, Power switch is ON and thermostat is calling for cool. BD – 24V return. Same as TR2. GD – 24V hot. Same as TR1. RD – Unit on output signal. Energized (RD made to GD) when Switching Center acknowledges thermostat call. See 9.
2. Transformer Terminals – 24V AC transformer terminals. This
transformer powers the dampers, thermostats and Switching Center. It does not power the HVAC unit. That power comes from terminal R; see 3.
3. Heat Pump Unit Terminals – Connect to Heat Pump unit via SYCAP
Capacity Controller. O/B – Reversing Valve terminal. Energized (O/B made to R) in heat mode when O/B jumper is at B. Energized in cool mode when O/B jumper is at O. Y – Compressor enable. Energized (Y made to R) when Switching Center acknowledges a heat or cool call and Emergency Heat Switch OFF. G – Fan enable. Energized when FAN switch is at ON position or when FAN switch is at AUTO position, Emergency Heat Switch is OFF and Switching Center acknowledges a heat or cool call.
R – Heat Pump unit 24V power. E – Emergency Heat enable. Energized (E made to R) when Switching Center acknowledges a heat call and Emergency Heat switch is ON. See 6 and 9. W2 – Auxiliary Heat enable. Energized (W2 made to R) when Switching Center acknowledges a heat call and Emergency Heat switch is OFF. Sends signal to SYCAP. L – Compressor fail flag input terminal. If feature is provided by Heat Pump, when L is energized (L made to R), red light DL3 is illuminat­ed to signal compressor is not working. C – Heat Pump unit 24V power return.
4. Mode Switch – Selects mode (HEAT/OFF/COOL) to run system.
Switching Center will only respond to thermostats calling for mode selected.
5. Fan Switch – Controls the indoor blower fan (G) when the Emer-
gency Heat switch is OFF. AUTO – Indoor blower fan turns on when Heat Pump is on. ON – Indoor blower fan is continuously on as long as Power switch is ON.
6. Emergency Heat – Disables compressor (Y) and blower fan (G)
and energizes E (E made to R). This tells the Heat Pump to turn on auxiliary heat. Should only be used when Mode switch is in HEAT. If used when mode switch is in COOL, auxiliary heat will turn on when there is a cool call.
13
SYSTEM 1000 SWITCHING CENTERS - HEAT PUMP SYHPA
1
2
3
4
5
6
7
Daisy chain up to six additional zones
ZONE
THERMOSTAT
RYW
WYG Rd
W
Y
R
C
RO MC RC
TB2
C
W2
W2
TB1
DAMPER RELAY BOARD
(101ARLY)
FUSED 24V
DAMPER
TRANSFORMER
SYHPA
SWITCHING CENTER
RDBD GDWD YD
TR1 TR2
EGRYO/B W2LC
HEAT PUMP TERMINALS
EGRY
O/B
W2 LC
SYCAP
CAPACITY
CONTROL
(PG 33)
Y1Y1 W2W2 CR
3
4
5
7
B
2
6
1
CLOSE
MOTOR
OPEN
MOTOR
ZONE DAMPER
AUTO
FAN
ON
HEAT
OFF
COOL
OFF
ON
EM.
HT.
RDBD GDWD YD
O/B Y G R E W2 L C
OFF ON
DL2
DL3
DL1
O B
4
5
6
7
1
2
3
8
9
10
SYHPA
TR2 TR1
7. Reversing Valve Selection Jumper – Configures Switching Cen-
ter to energize reversing valve in cool mode or heat mode. Place on O and center pin to energize reversing valve in cool mode. Place on B and center pin to energize in heat mode.
8. Fuse – 1/10 amp. Protects WD and YD terminals.
9. Status Lights –
DL1 – Call light, green. On when Switching Center responds to a calling thermostat. DL2 – Compressor fail, yellow. On when L terminal is energized (L made to R). Indicates heat pump compressor is not functioning. DL3 – Emergency Heat, red. On when E terminal is energized (E made to R). Indicates emergency heat is on.
10. Power Switch – When OFF the Switching Center will not respond to
thermostat calls. The indoor blower fan will run if Fan switch is ON. Power remains to all dampers and thermostats.
WIRING
Open motor not utilized on low pressure (spring open) dampers.
C terminal for hardwired electronic thermostats only.
24V damper transformer. Requires in-line fuse. See table on page 42 for sizing transformer and fuse.
Refer to page 41 for Five Wire Link wire sizing.
If the heat pump does not include an outdoor thermostat, it is recommended that the “W2” wire to the heat pump unit is run thru an optional outdoor thermostat with a manual override switch.
If using more than one damper per thermostat, refer to paralleling zone dampers, pages 23 and 44.
If the heat pump does not have an emergency heat terminal, connect “E” of Switching Center to auxiliary heat terminal of heat pump. If the heat pump does not turn on the indoor blower fan in emergency heat mode, add blower fan relay as shown below.
EMERGENCY HEAT BLOWER FAN RELAY
If the heat pump does not energize the indoor blower fan when emergency heat is energized, add relay K1 as shown. Relay K1 is a 24VAC SPDT relay.
14
SYHPA
SWITCHING CENTER
GR E C
K1
K1
GR E C
HEAT PUMP TERMINALS
K1
SYSTEM 1000 STARTUP
When all wiring is completed to the dampers and the gas electric/heat pump unit, the following tests should be made:
Disconnect the R wire from the Switching Center.Check to be sure that there is 24 volt power between
terminals TR1 & TR2.
Set all thermostat switches to the OFF position. Set the Switching Center in the HEAT mode.Set the Switching Center ON/OFF switch to ON.
The green call light should be off at the Switching Center. If it is on, there is a thermostat calling or the WD wire is shorted.
Check all of the thermostats, if they are off, remove the WD wire
from the Switching Center. The green light should go off. If it does, find the short in the five wire link before re-connecting it. If the green light does not turn on, test each thermostat, one at a time. Turn on one thermostat, set it to call for heating, and the green light on the Switching Center should turn on. When you set this same thermostat for no heat, the green light at the Switching Center should turn off. Test each thermostat in this manner to
be sure all thermostats are properly wired. Now, set the Switching Center in the COOL mode. If the green light turns on with all thermostats off, there is a short in the YD wire. Correct the problem before proceeding.
Repeat the test of each thermostat in the cool mode. When a thermostat is calling, the green call light will turn on. Turning this thermostat off will turn off the green call light at the Switching Center.
GAS/ELECTRIC SYGE
Turn the ON/OFF switch off and reconnect the R wire. Be sure that all thermostats are off. Turn the ON/OFF switch ON. Decide if you want to test the heating or cooling system and set the HEAT/COOL switch to the desired position.
If you have set the switch to COOL, set one thermostat to call for cooling. The green light will turn on and the cooling system compressor and indoor fan will turn on. If it does not, check wiring between the Switch­ing Center and the unit.
If you have set the switch to HEAT, set one thermostat to call for heat. The green light will turn on and the furnace should start. The fan will start when the time delay or bonnet control turns it on. If the system does not turn on, check the wiring between the Switching Center and the furnace.
The Switching Center controls the furnace and air conditioner with relay contacts. The Switching Centers R,Y,W&G terminals operate exactly like a four wire thermostat. Trouble shooting the heating and air condition­ing equipment should be handled as though the Switching Center is a four wire thermostat.
HEAT PUMP (SYHPA) with the SYCAP
Check that the fuse on the SYHPA has not blown. If it has, check for shorts on the WD and/or YD wires on the five wire link and replace the 1/10 amp fuse.
Turn the POWER switch on the SYHPA and SYCAP OFF: Check all thermostats to be sure that they are off. Reconnect the R wire at the SYHPA. Check to be sure that the O/B jumper on the SYHPA is in the correct position for the heat pump. Turn the POWER switch on the SYHPA to ON.
To test the COOL mode, set the HEAT/COOL switch on the SYHPA to the COOL position. Set only one thermostat to call for cooling. The green call light on the SYHPA should turn on and the compressor will run. The indoor fan will start with the compressor. If the compressor or fan do not start, check the wiring between the SYHPA and the Heat Pump.
To test the HEAT mode, turn the POWER switch on the SYHPA to OFF. Turn all thermostats off. Set the MODE switch on the SYHPA to HEAT and then turn the POWER switch ON. Set one thermostat to call for heat. The green call light will turn on at the SYHPA and the compressor will turn on in the heat mode. The fan will turn on with the compressor. If the fan or compressor does not turn on, check the wiring.
When yellow DL2 is lit, there is a heat pump compressor failure (if “L” terminal has been wired).
When the “EM HT” switch is set to ON, the SYHPA will never power the “Y” or “G” terminal and will power the “E” terminal during a call. While the “EM HT” switch is set to ON, the red light labeled DL3 will turn on if there is a call. To test the Auxiliary/Electric heat, see the unit manufac­turers wiring diagrams and instructions.
SYCAP and Auxiliary/Electric Heat
To test the Auxiliary/Electric heat, turn the SYCAP switch ON. If the dis­play begins to toggle between “E” and “157”, the factory installed tem­perature sensor or its wiring to terminals ± is open. If the display toggles between “E” and “32”, the temperature sensor is shorted. Check con­nections + and – and the wire holding the sensor in the plenum for shorts.
During normal startup the supply air temperature should be displayed. Unless modified at this time, the SYCAP will operate at factory cut-out setpoints of 118 degrees F. for heat and 48 degrees F. for cooling. To modify these cut-out setpoints see “Determine the existing cut-out set­points on a CAP” in the Capacity Control section of this manual.
To test the Auxiliary/Electric heat disconnect the Y wire at the SYCAP or SYHPA. Set one stat to call for heat. If the supply air temperature is below the electric heat cut-in setpoint, and after a four minute time delay, DL2 and the Auxiliary/Electric heat will turn on.
After testing the SYCAP, replace the Y wire for proper heat pump operation.
Note: At temperatures below 38°F and above 125°F (heat pumps), the
display will toggle between “E” and the supply duct temperature. This is normal operation and provisions have been made to allow the heating and cooling to operate.
15
ZONE THERMOSTATS
Each zone requires a zone thermostat. This thermostat can be digital, mechanical, or programmable. All three types are available. Zonex Sys­tems thermostats have been specifically designed to work with Zonex Systems Zone Control systems. Attempting to use another manufacturer’s thermostat may create compatibility problems and cause nuisance calls. For trouble free installation, use only Zonex Systems supplied thermostats.
Digital Thermostats
Zonex Systems makes two Digital Thermostats for the System 1000/2000: 101DIGI – a single stage thermostat that can be used whenever auxil-
iary zoned heating is not required.
101DIGITS – a single stage cool, two stage heat thermostat. It should
be used when auxiliary zoned heating is needed.
101DIGI: This is a digital, dual setpoint, single stage zone thermostat, accurate to within one degree. The 101DIGI is auto changeover, is non power robbing, and is designed with a non-volatile memory to retain all programmed setpoints. The stat is operated by two push buttons to review and modify heat and cool setpoints. To avoid unauthorized setpoint mod­ifications, the 101DIGI has locking setpoint capability. There is also a zone On/Off switch. Under the cover there is a green and red light. When the green light is on the stat is calling for cooling. When the red light is on the stat is calling for heat. Following any call, the stat is designed with a two­minute minimum run time to prevent short cycling. It can be used with any of the System 1000/2000 Controllers. This thermostat can be ordered with a remote sensor (101DIGIRS). The 101DIGI Dimensions are: x 4-1/2”H x 1”D, the color is off white installation.
101DIGITS This is an auto changeover, electronic zone thermo­stat with auxiliary heat output. This dual setpoint thermostat has a large digital readout which displays cur­rent room temperature. Under the cover there are two red lights and one green light. When the green light is on, the thermostat is calling for cooling. When the red light labeled “D-1” is on, the the stat is call­ing for first stage heat. When the the red light labeled “HT2” is on, the stat is calling for second stage heat. This zone thermostat is designed for zones that require supplemental heat. This thermostat can be ordered with a remote sensor by adding RS to its part number. 101DIGITS dimen­sions are 2 7/8” W x 4 1/2” H x 1” D. Installation requires five wires.
101DIGI Thermostat Operation
Each digital thermostat has an “ON” / “OFF” switch located at the bottom. Typically, this thermostat should always be in the “ON” position. When the room is unoccupied, use this switch to take the zone out of your sys­tem by sliding it to the left to turn it off. When the room is occupied slide the switch to the right to turn it on. Assign the Heating and Cooling Set­points desired by using the following instructions:
. Requires four thermostat wires for
2-7/8”W
101DIGI Requires 4 Wires
101 DIGITS Requires 5 Wires
1. Determine the existing Set­points:
A. To determine the existing Heat
Setpoint, press and hold the top button marked until
>
the letter “H” appears and then release. The current heat setpoint will be displayed following the letter “H” (If the button is held down too long the Heat Setpoint will begin to increase). Approxi­mately two seconds after the button is released the current room temperature will be redisplayed.
B. To determine the existing Cool
Setpoint press and hold the low­er button marked until the
>
letter “C” appears and then release. The current Cool Setpoint will be displayed following the letter “C” (If the button is held down too long the Cool Setpoint will begin to decrease). Approximately two seconds after the button is released the current room temperature will be redisplayed.
2. Modifying the Setpoints:
A. To change the Heat Setpoint,
press and hold the top button until the Heat Setpoint is dis­played. Continue to press this button (the up button ) to
>
increase the Heat Setpoint or press and hold the bottom
>
button to reduce the Heat Setpoint to your desired comfort level in this room.
B. To change the Cool Setpoint,
press and hold the lower button until the Cool Setpoint is
>
displayed. Continue to hold this button to lower the Cooling Setpoint or press the top button to raise the Cool Setpoint
>
to your desired comfort level in this room.
Set up all of the zone thermostats in this way to provide room by room comfort control.
16
ZONE THERMOSTATS
REMOTE SENSOR BOARD
Temperature
Sensing
Thermistor
REMOTE SENSOR
COVER
TYPICAL
ZONE
THERMOSTAT
Wire Nut
Wire Nut
R
Shield to the "R" terminal
4.5" x 2.75"
3. Locking the Set points:
To avoid unauthorized setpoint modifications, the 101DIGI has locking setpoint capability. After the heat and cool setpoints have been selected, use the jumper located under the cover near the middle of the board labeled LCK to lock the setpoints. Slide the jumper over both terminals as shown in the diagram above. This will lock the setpoints in place. To modify the setpoints, the jumper must be to moved to the adjustable position.
DIGICOM
DIGICOM: The DIGICOM auto
changeover, communicating thermostat is used exclusively in ZonexCommander thermal management systems. Using a computer and the ZonexCommander software, all ther­mostats in the system can be programmed and viewed. The DIGICOM may be applied in stand alone unit control, from 1 to 80 split or pack­aged systems. When used with a modem, all ZonexCommander software functions can be controlled remotely. The DIGICOM requires 24V AC power from either the zone system or HVAC unit transformer, with the addition of a two conductor, twisted pair cable for communications. Dimensions: 2-7/8” W x 4-1/2” H x 1” D.
101PROG: Features a battery powered, 7-day programmable, auto changeover control for single stage heating and cooling applications. Thermostat can be programmed for up to four periods per day, and offers three operating modes: Manual, Automatic and Vacation. Blower operation is manual selectable for auto, on, or programmed for fossil fuel or electric heat, fan cycling. The oversized LCD display clearly shows the time, day of the week, space temperature, and selected operating mode. The 101PROG also provides for mode control through an optional telephone controller. Dimensions are 3.75”W x 5”H x 1”D. Color: White.
101PROG
ZONE THERMOSTATS – COMPATIBILITY
The 101ASSB gas/electric and 101AACBHP heat pump controllers are compatible with most thermostats, offering a wide thermostat selection to the installing contractor. NOTE: the 101AACBHP pump controller utilizes gas/electric thermostats. When using other than Zonex Systems thermostats, please refer to the following guidelines:
Electronic Thermostats: Digital thermostats requiring 24V AC power must be “Hard wired” with a separate R and C or common terminal. Power robbing type thermostats are not compatible. All types of battery operated thermostats may be used with any System 2000 control system.
Mechanical Thermostats: When using a mechanical thermostat, ensure the cooling compensator (anticipator) is removed, and the heating anticipator is shorted or set to its lowest setting.
ZONE THERMOSTATS – REMOTE SENSORS
The Zonex Systems digital thermostats can be ordered with a remote sen­sor. Remote sensors are useful if you would like to place the thermostat and sensor in different locations. Simply add “RS” at the end of the part number to order with a remote sensor; i.e.: “101DIGIRS”.
Please contact Factory Technical Support for additional thermostat compatibility information.
Wiring: The remote sensor must be wired with a minimum 18 ga., two conductor shielded cable, with a maximum length of 200 feet. The wires have no polarity. Use field supplied wire nuts to connect the sensor. Flare back and tape off the cable shield closest to the sensor. Connect the shield at the thermostat to the “R” terminal.
17
SYSTEM SIZE
5 TONS OR UNDER
UNDER 7.5 TONS
7.5 TONS OF LARGER
MAXIMUM
DIFFERENTIAL
PRESSURE
0.5" 1"
1.75"
ROUND DAMPER
LOW PRESSURE MEDIUM PRESSURE MEDIUM PRESSURE
RECTANGULAR DAMPER
LOW PRESSURE MEDIUM PRESSURE HEAVY DUTY
ZONE DAMPERS
Zonex Systems zone dampers are used in cooling/heating systems to provide room by room zone control. The damper is provided with a factory mounted relay board and zone actuator. Each zone damper is
Maximum Differential Pressure refers to the maximum static pressure drop in inches of water column between the input (upstream) of the zone damper and the output (downstream) when the damper is closed.
ROUND ZONE DAMPERS
There are two styles of round zone dampers, low pressure or medium pressure. For systems 5 tons or under with a maximum differential static
ROUND LOW PRESSURE ZONE DAMPERS
Zonex Systems round low pressure zone dampers can be used for systems up to 5 tons with a maximum differential static pressure of 0.5”. These are two position, spring open, power close dampers for very simple operation. Round damper sizes 9 inches and under are manufactured from 24 gauge galvanized steel. Sizes 10”, 12”, 14” and 16” are made from 20 - 22 gauge steel. All sizes are designed with rolled-in stiffening beads for superi­or rigidity. The damper pipe is furnished with one crimped end and one straight end for easy installation. A hat section supports a synchronous 24V AC 60Hz 12VA motor and terminal board. The motor is designed for contin­uous full stall operation. Special winding and heavy duty gearing provide for long motor life and easy spring open operation. A cross pin on the motor shaft provides positive direct drive to the damper blade shaft without a cou­pling or set screws, allowing for a quick and easy motor change if required. Motor drive time from full open to full close is 30 seconds. Since this is a spring open damper, in the event of power failure, the damper fails to the full open position.
controlled by a zone thermostat. More than one damper can be controlled by one zone thermostat; see Slaving Dampers. Use the table below to determine which zone dampers to use.
pressure of 0.5”, use low pressure dampers. Otherwise use medium pressure for up to 1.75” differential pressure on any system over 5 tons.
LOW PRESSURE (101ARZD)
ROUND MEDIUM PRESSURE ZONE DAMPERS
Zonex Systems round medium pressure zone dampers are recommend­ed for systems over 5 tons or with a maximum differential static pressure up to 1.75”. This power open / power close damper is manufactured from 20-22 gauge galvanized steel with rolled-in stiffening beads for superior rigid­ity. Mechanical minimum and maximum set stops are provided and easily adjustable. The damper pipe is furnished with one crimped end and one straight end for easy installation. A hat section supports a 35 lb./in. 24V, 6 VA power open, power closed actuator with a damper relay board interface. The actuator is designed for full stall operation, with a magnetic clutch to protect the internal gearing. The actuator is direct coupled to the damper shaft, which pro­vides positive operation and offers replacement ease if required. Drive time from full open to full closed is 60 seconds.
18
MEDIUM PRESSURE (101AMPD)
ZONE DAMPERS
ROUND LOW & MEDIUM PRESSURE DAMPER SIZES
ROUND LOW PRESSURE DAMPER
PART #
101ARZD06 101ARZD07 101ARZD08 101ARZD09 101ARZD10 101ARZD12 101ARZD14 101ARZD16
ROUND MEDIUM PRESSURE DAMPER
PART #
101AMPD06 101AMPD08 101AMPD10 101AMPD12 101AMPD14 101AMPD16 101AMPD18
SIZE DIAMETER (D) LENGTH (L)
6" 7" 8"
9" 10" 12" 14" 16"
SIZE DIAMETER (D) LENGTH (L)
6"
8" 10" 12" 14" 16" 18"
6" 7" 8"
9" 10" 12" 14" 16"
6"
8" 10" 12" 14" 16" 18"
10" 10" 10" 11" 12" 14" 16" 18"
10" 10" 12" 14" 16" 18"
23 1/2"
WIDTH (W)
9" 10" 11" 12" 13" 15" 17"
18 1/2"
WIDTH (W)
9" 11" 13" 15" 17" 19" 21"
W
D
L
TYPICAL ROUND CAPACITIES*
Duct
Diameter
6" 7"
8" 9"
10" 12" 14" 16"
18" 2000 1100 .036
Nominal
CFM
110 160
250 320
410
660 1000 1450
Duct Velocity
FPM
540 600
700 725
750 850 925
1070
Damper
P " WC
.014 .014
.015 .015
.015 .022 .035 .036
* These air quantities were derived from a duct sizing chart .1” friction loss per 100’ of duct. All CFMs listed are approximate. For accurate selection use duct sizing table or device.
19
ZONE DAMPERS
RECTANGULAR ZONE DAMPERS
The rectangular zone dampers come in either low pressure, medium pressure, or heavy duty. For systems 5 tons or under use low pressure. For systems under 10 tons use medium pressure dampers. For systems 10 tons or over use heavy duty dampers. Motor drive time open and close is 90 seconds, except for the low pressure damper which springs open.
RECTANGULAR LOW PRESSURE ZONE DAMPERS (101EC W x H)
Zonex Systems rectangular low pressure dampers can be used for systems up to 5 tons with a maximum differential static pressure of 0.5”. These are two position, spring open, power close dampers. They are constructed from heavy duty galvanized steel. The damper is a single blade type that slips into a 2-1/2” wide cutout in the existing duct and attaches with screws via a duct mounting plate. The duct mounting plate is 5” wide. The drive assembly supports a synchronous 24V AC 60Hz 12VA motor and ter­minal board. The motor is designed for continuous full stall operation. Spe­cial winding and heavy duty gearing provide for long motor life and easy spring open operation. A cross pin on the motor shaft provides positive direct drive to the damper shaft without a coupling or set screws. Motor drive time from full open to full close is 30 seconds. Since this is a spring open damper, in the event of power failure the damper fails to the full open position.
LOW PRESSURE (101EC W x H) RECTANGULAR DAMPER
RECTANGULAR MEDIUM PRESSURE ZONE DAMPERS (101MRTD W x H)
Zonex Systems rectangular medium pressure dampers are recommended for systems under 7.5 tons with a maximum differential static pressure of 1”. These are power open, power close dampers. They are constructed from heavy duty aluminum and stainless steel. The damper is an opposed blade type that slips into a 3-1/4” wide cutout in the existing duct and attaches with screws via a duct mounting plate. The duct mounting plate is 5” wide. The damper supports a 35 lb./in. 24V, 6 VA power open, power closed actuator with a damper relay board interface. The actuator is designed for full stall operation, with a magnetic clutch to protect the internal gearing. The actuator is direct coupled to the damper shaft, which provides positive operation and offers replacement ease if required.
RECTANGULAR HEAVY DUTY ZONE DAMPERS (101CD W x H)
Zonex Systems rectangular heavy duty dampers are recommended for systems 7.5 tons or larger with a maximum differential static pressure of
1.75”. These are power open, power close dampers made of 20 gauge “snap-lock” steel frame with S and Drive duct connections. Allow a 16” gap in the duct for the damper. Formed steel blade stops incorporate a gasket for quiet operation and improved structural rigidity. Rectangular dampers under 10” in height incorporate a single blade design. Dampers 10” or over use opposed blade design. A full stall motor, drawing 6 VA and a relay board control the damper position.
MEDIUM PRESSURE (101MRTD) AND
HEAVY DUTY (101CD) RECTANGULAR DAMPERS
20
LOW AND MEDIUM PRESSURE RECTANGULAR DAMPER DIMENSIONS
DEPTH
B 16"
A
WIDTH HEIGHT
16
B
MOTOR
48" MAXIMUM WIDTH
A
Rectangular dampers should operate at 1500 FPM. E.G. A 24" x 12" damper = 2 square feet. 2 square feet X 1500FPM = 3000 CFM.
4"
200 280 390 490
700 1090 1500 2000 2500 3000 3600 4000
630 960 1400 1850 2250 2300 3080
570 900 1220 1600 2000 2450 2850
500 770 1100 1400 1750 2100 2500
440 680 950 1200 1500 1800 2100
390 590 800 1000 1250 1500 1750
310 490 650 850 1000 1200 1400
250 390 510 650
6
8 10 12 14 16 18 20
81012 1416 18202224
HEIGHT IN INCHES
WIDTH IN INCHES
Part Number 101MRTD W x H Sizes available from 8” x 6” up to 24” x 20”
ZONE DAMPERS
W
Part Number 101EC W x H Sizes available from 8” x 8” up to 24” x 12”
2-1/2"
HEAVY DUTY RECTANGULAR DAMPER DIMENSIONS
Part Number 101CD W x H Sizes available from 8” x 8” up to 48” x 48”
Dampers listed below are standard sizes. For larger sizes and capacities, contact the factory.
5"
RECTANGULAR DAMPER CAPACITIES*
H
Motors on low and medium pressure dampers will be mounted on the Height (H) side. Bottom mount motors will be located on the Width (W) side. *These air quantities were derived from a duct sizing chart .1” friction loss per 100’ of duct. All CFMs listed are approximate. For accurate selection use duct
sizing table or device.
21
ZONE DAMPERS
FIVE WIRE LINK TO
SYSTEM CONTROLLER
TO
THERMOSTAT
TB2
WY
RC
RO MC
RC
W2
BWYG R
d
TB1
W2
Electronic stat
if applicable
OPEN MOTOR*
CLOSE MOTOR
*OPEN MOTOR NOT UTILIZED ON LOW PRESSURE (SPRING OPEN) DAMPERS.
SIZING ZONE DAMPERS
If the ductwork already exists, simply size the damper to fit the ductwork. For new systems or retrofit jobs:
a) Determine CFM from heat gain or loss calculations.
WIRING ZONE DAMPERS
b) Select damper size by using a duct sizing table or calculator.
c) Select a Zonex Systems damper to fit the duct size selected for that
zone.
For heavy-duty rectangular dampers: CW = RC (Run Closed) COM = MC (Motor Common) CCW = RO (Run Open)
1. Do not exceed 700 FPM in a register/diffuser branch duct.
2. If a damper is installed within 3 feet of register/diffuser, install sound attenuating flex duct between damper and outlet.
3. Zone dampers should be preceded by 2’-4’ of straight pipe where possible.
4. In attic installations and high humidity areas, the Zonex Systems damper should be insulated along with the ductwork. The hat sec­tion on the damper is delivered with insulation between the hat sec-
DAMPER INSTALLATION NOTES
For heavy-duty round dampers: CCW = RC (Run Closed) COM = MC (Motor Common) CW = RO (Run Open)
tion and pipe. Therefore, insulation should be applied to the round pipe and be butted against the hat section, (do not insulate the motor or relay board). Both motor and the relay board generate enough heat so no condensation will develop on the hat section.
5. Remember to allow a 16” gap in the duct for Heavy Duty rectangular dampers.
6. Low and Medium pressure rectangular dampers slide into a 3-1/4” wide cutout in the side of the preexisting ductwork.
22
TO THERMOSTAT
*
No connection
(- - - -) For power open/closed damper applications only.
FIVE WIRE LINK
TO
SYSTEM
CONTROLLER
DAMPER #2
RELAY BOARD
YRC
W
YRC
RO MC RC W
Rd B
WY
G
TB1TB2
W2
W2
DAMPER #1
RELAY BOARD
YRC
RO MC RC W
Rd B
W
YG
TB1TB2
W2
W2
* *
*
*
*
* *
*
*
*
*
YRC
RO MC RC W
Rd BW
Y
G
TB1TB2
W2
W2
* *
*
*
*
* *
*
*
*
*
DAMPER #3
RELAY BOARD
BYPASS DAMPERS – BAROMETRIC
INSTALLATION
The round barometric bypass damper can be installed in any position. This damper is factory set for horizontal installation and can be field modified for vertical installation. Do not run speed screws into damper housing. Screws may interfere with damper travel. Make sure counter weight is not obstructed in any way.
a) Install the bypass damper between the supply and return
plenums of the unit. It must be the first tap off the supply plenum.
b) Be sure the air flows through the damper in the proper direc-
tion as indicated by the arrow on the damper. Airflow is always from supply to return plenum. Be certain the damper shaft
is horizontal. c) Loosen counter weight with allen wrench. d) Loosen lever arm from damper shaft and allow to hang straight
down. e) Fully close damper by grabbing damper shaft on side attached
to lever arm and turning clockwise until it stops. f) While holding the damper fully closed, rotate the lever arm a
little to the right (facing the damper) and then screw in to
tighten to the damper shaft. Then tighten lock nut. g) Be sure the damper is being held closed by the counter weight.
Proceed to set up.
BAROMETRIC BYPASS SETUP
a) Turn off all thermostats. b) Turn on Switching Center/Controller and set fan switch to “ON”
position. Allow fan to run for 5 minutes to equalize pressure. Then make sure all dampers are open by checking for air flow out of each damper.
c) By moving counter weight up or down the lever arm, adjust it
so that the damper just wants to start opening.
d) If the damper cannot be held closed with the counter weight all
the way at the bottom of the lever arm, then hold the damper shaft, loosen the lever arm from the damper shaft, and rotate the lever arm further to the right and retighten. Repeat Step C.
e) The barometric bypass damper is now calibrated.
BAROMETRIC BYPASS STARTUP TEST
a) Have at least half of the zones call for either heating or cooling. b) Check to be sure the calling zone dampers are open, (air is
flowing).
c) Verify the bypass damper is open. Note, the damper may not
fully open.
d) If the open zones are not noisy, the bypass damper is set.
AIRFLOW
SHEET METAL
PIPE
AIRFLOW
BAROMETRIC
BYPASS
HORIZONTAL APPLICATION
A/C UNIT
RETURN
VERTICAL APPLICATION
SUPPLY
PLENUM
A/C UNIT
FURNACE
RETURN AIR GRILLE
OR
FURNACE
BAROMETRIC
BYPASS
OR
RETURN
AIR
PLATFORM
SUPPLY
PLENUM
AIRFLOW
ROOF TOP INSTALLATION Down Discharge Application
A/C UNIT
FURNACE
BAROMETRIC
SUPPLY
PLENUM
OPEN RETURN PLENUM BYPASS APPLICATION
To prevent bypass air from
flowing out the return grill,
use a short open ended
return air plenum to connect the bypass
damper to the unit.
RETURN AIR
GRILLE
SHEET METAL
BYPASS DAMPER
AIRFLOW
PIPE
AIR CONDITIONING
UNIT
OR
BYPASS
ROOF LINE
RETURN PLENUM
SUPPLY
DUCT
24
BYPASS DAMPERS – ELECTRONIC
ELECTRONIC BYPASS DAMPERS
Bypass dampers are used to provide constant air delivery through the air handling unit. This is done by bypassing excess air from the supply duct back to the return duct. As a zone is satisfied its zone damper closes. When this happens, the bypass damper opens just enough to bypass the excess air. This will control static pressure and noise at the diffusers.
The Electronic Bypass Damper can be used on any size system over. The damper can be round or rectangular and multiple dampers can be slaved together. The Electronic Bypass Damper consists of a medium pressure round or a heavy duty rectangular damper and a static pressure sensor.
SIZING ELECTRONIC BYPASS DAMPERS
When only the smallest zone is calling, the maximum amount of excess supply air will flow through the bypass damper.
CFM CALCULATION
To determine the proper size bypass damper: A) Calculate total air volume at 400 CFM per Ton. B) Calculate air volume of smallest zone in CFM . C) Calculate bypass CFM by subtracting the smallest zone air volume from the total.
(A - B = C).
ROUND BYPASS DAMPER SELECTION
When you know the bypass CFM requirement as determined in the “CFM calculation” section, use the ROUND BYPASS SELECTION TABLE. From the table, select the bypass damper with the CFM rating equal to or greater than the value calculated in step C of CFM Calculation.
Example: We know the smallest zone air volume is 400 CFM and we have a four ton system. Thus the air volume we need to bypass is (400 * 4) – 400 which equals 1200 CFM. Using the ROUND BYPASS SELECTION TABLE, we would select a 12 inch bypass since it can handle up to 1250 CFM of air.
ROUND BYPASS SELECTION TABLE
Diameter CFM
6 320
8 560 10 900 12 1250 14 1700 16 2200
RECTANGULAR & ROUND BYPASS DAMPER
WITH THE STATIC PRESSURE CONTROL
ROUND DIMENSIONAL DATA
PART # STMPD06 STMPD08 STMPD10 STMPD12 STMPD14 STMPD16
SIZE
6
8 10 12 14
16
D
L
6"
10"
8"
10"
10"
12" 14"
12" 14"
16"
16"
18"
L
D
W
W 9" 11" 13"
15" 17" 19"
Never exceed 16 inches for the round bypass damper. If you need to bypass more than 2200 CFM, either use a rectangular bypass or slave multiple round bypass dampers.
RECTANGULAR BYPASS DAMPER SELECTION
When you know the bypass CFM requirement as determined in the “CFM calculation” section, use the RECTANGULAR BYPASS SELEC­TION TABLE. From the table, select the bypass damper with the CFM rating equal to or greater than the value calculated in step C of CFM Calculation.
Example: We know the smallest zone air volume is 250 CFM and we have a 7-1/2 ton system. Thus the air volume we need to bypass is (400 X 7.5) -250) which equals 2750 CFM. Using the RECTANGULAR BYPASS SELECTION TABLE, we see the smallest damper we can use is a 12” x 22” or a 22” x 12”.
RECTANGULAR BYPASS DAMPERS
SELECT FROM 8 X 8 THRU 48 X 48
H
D
WIDTH HEIGHT
Part Number STCD W X H
DEPTH
H 16"W
25
48" MAXIMUM WIDTH
Rectangular bypass dampers should operate at 1500 FPM* E.G. A 24" x 12" damper = 2 square feet. 2 square feet X 1500FPM = 3000 CFM.
* FPM = Feet Per Minute
W
4"
24 28 32 36 40 44 48
8 2000 2333 2667 3000 3333 3667 4000 10 2500 2917 3333 3750 4167 4583 5000 12 3000 3500 4000 4500 5000 5500 6000 14 3500 4083 4667 5250 5833 6417 7000 16 4000 4667 5333 6000 6667 7333 8000 18 4500 5250 6000 6750 7500 8250 9000 20 5000 5833 6667 7500 8333 9167 10000 22 5500 6417 7333 8250 9167 10083 11000 24 6000 7000 8000 9000 10000 11000 12000 28 7000 8167 9333 10500 11667 12833 14000 32 8000 9333 10667 12000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 24000
8 10 12 14 16 18 20 22
8 667 833 1000 1167 1333 1500 1667 1833 10 833 1042 1250 1458 1667 1875 2083 2292 12 1000 1250 1500 1750 2000 2250 2500 2750 14 1167 1458 1750 2042 2333 2625 2917 3208 16 1333 1667 2000 2333 2667 3000 3333 3667 18 1500 1875 2250 2625 3000 3375 3750 4125 20 1667 2083 2500 2917 3333 3750 4167 4583 22 1833 2292 2750 3208 3667 4125 4583 5042 24 2000 2500 3000 3500 4000 4500 5000 5500 28 2333 2917 3500 4083 4667 5250 5833 6417 32 2667 3333 4000 4667 5333 6000 6667 7333 36 3000 3750 4500 5250 6000 6750 7500 8250 40 3333 4167 5000 5833 6667 7500 8333 9167 44 3667 4583 5500 6417 7333 8250 9167 10083 48 4000 5000 6000 7000 8000 9000 10000 11000
WIDTH IN INCHES
HEIGHT IN INCHES
BYPASS DAMPERS – ELECTRONIC
RECTANGULAR BYPASS SELECTION TABLE
Bypass air in CFM. Calculated at 1500 FPM. Formula used: B = W X H / 144 X 1500, where B = Bypass air in CFM, W = damper width in inches, H= damper height in inches, 144 = 144 sq. inches per sq. ft., 1500 = 1500 FPM.
BYPASS POSITION INDICATOR
SLAVING BYPASS DAMPERS
Use only one Pressure Sensor when slaving two or more Bypass Dampers together. Connect the Pressure Sensor to one damper as described above. Connect the slave dampers in parallel as shown. Up to 4 dampers can be slaved to one Sensor. The slaved dampers will self syn­chronize each time the dampers reach full open or full close.
DAMPER
ACTUATOR
To Static Pressure Controller As Shown On The Bypass Wiring Diagram On The Next Page.
ROUND AND RECTANGULAR
BYPASS DAMPER MOTORS
SHAFT END MARKING IS PARALLEL
WITH DAMPER BLADE. DAMPER TRAVEL
IS 60° ON ROUND BYPASS AND 90°
ON RECTANGULAR BYPASS
CW
CCW
Note: Clockwise to close on rectangular bypass and counterclockwise on round bypass.
RC RO MC
**
***
RC MC
RO
N/C COM N/O
101ASPC
Static
Pressure Control
SLAVE
DAMPER
ACTUATOR
*
RC RO MC
26
TO NEXT SLAVE BYPASS DAMPER IF APPLICABLE
RC RO MC
BYPASS DAMPER – STATIC PRESSURE CONTROLLER
The Static Pressure Controller controls a standard medium pressure round damper (STMPD) or the heavy duty rectangular damper (STCD) by maintaining constant static pressure in the duct downstream of the bypass takeoff. As the zone dampers close, the static pressure increases. When this happens, the static pressure controller opens the bypass damper to bring the static pressure back to the setpoint.
STATIC PRESSURE CONTROLLER DESCRIPTION
A: Mounting tabs. B: Supply air barb. C: Reference air, “LOW”, barb. D: Diaphragm must be
mounted vertically. E: Pressure adjusting screw. F: Normally closed, N/C, terminal. G: Normally open, N/O, terminal. H: Common, COM, terminal.
BC
D
E
A
F
G
H
STATIC PRESSURE CONTROLLER INSTALLATION
a. Select location for pressure sensor tube. Location should be in sup-
ply duct, downstream of bypass takeoff, upstream of any zone
dampers and perpendicular to the air flow. b. Drill 5/16” hole at selected location for pressure sensor tube. c. Mount Static Pressure Controller near the drilled hole with the
diaphragm of the sensor vertical. The controller must be mounted
on a stable, non vibrating surface. d. Attach 5/16” pressure sensor tube, supplied, to the barb of the Sta-
tic Pressure Controller located closest to the mounting tabs. The oth-
er barb, labeled “LOW”, is left open if the Controller is in the
conditioned building. If the Controller is located outside the build-
ing, another tube, not provided, must be connected between the
“LOW” barb and a location inside the building. e. Remove the terminal cover and wire as shown in the wiring
diagram. f. Reattach terminal cover. Installation is complete. Proceed to Static
Pressure Controller Setup.
AIR
C
CONDITIONER
O
AIRFLOW
Insert the tube into the side of the duct, approximately
1
3. Make sure the tube is perpendicular to the air flow.
I
L
MOTOR
WINDOW
STOPS
AIRFLOW
STATIC
PRESSURE
SENSOR
BYPASS DAMPER
1
STATIC PRESSURE CONTROLLER SETUP
Note: 24V ac may be read on both terminals (RO & RC to MC) due to
voltage bleeding thru the motor windings. Disconnect the RO or RC wire to determine which wire is energizing the motor.
a. Ensure all dampers are open and blower is running on high speed.
Zonex Systems recommends de-energizing the bypass damper when the blower fan turns off. If not installed as recommended, when the blower fan turns off the bypass will fully close. Then when the blower fan turns back on, there could be excessive air supplied to the calling zone, causing exces­sive air noise until the bypass is able to open sufficiently. An alterna­tive wiring diagram is provided using an additional static pressure sensor to deenergize the bypass damper.
Alternative Wiring
b. Verify bypass damper is Closed
. Bypass dampers using a square motor have a grey release lever on the bottom/side of the damper (near motor) to manually open or close the damper.
c. At 101ASPC Static Pressure Controller, remove the NO wire from the
micro switch. Connect A/C voltmeter (or test light) to COM and NC terminals of static pressure controller. Zero V ac
(no light) should
be present, ensuring a connection is made between COM and NC. If 24V ac is present (light on), turn adjustment screw on 101ASPC Sta­tic Pressure Controller clockwise (CW) until connection is made and 0V ac (no light) is obtained. Do Not Overtighten Adjusting Screw.
d. Verify bypass damper is Closed. Slowly back out adjusting screw
(CCW) until 24V ac (light on) is present ensuring no connection between COM and NC. STOP. Slowly turn adjusting screw in (CW) until 0V ac (no light) is present. STOP. Bypass damper should be on verge of opening but still closed with all zone dampers open and the blower fan on high speed.
e. If the bypass damper sizing and duct design are correct, this
completes the bypass damper setup. Connect all wires and proceed to Bypass Checkout.
BYPASS CHECKOUT FOR STATIC PRESSURE CONTROLLER
a. Make a cool call at the zone thermostat of the smallest (damper size) zone. b. Verify all zone dampers are closed except for calling zone. c. Verify noise at zone register is not excessive. Adjust static pressure
controller CCW to lower noise (airflow) or CW to increase airflow until too noisy.
27
P/N GE/HP
#
STAGES
ECONO
CNTRL
CUT-IN SET-POINT LEAVING
AIR
COMPRESSOR
MIN. RUN
FAN
CONTROL
101CAPGE
GE 1 HT, 1 CL NO NO FULL RANGE
YES
NO NO
TRLAT
GE 1 HT, 1 CL NO NO
4 HT, 4 CL
NO NO YES
CAPL-2
GE 2 HT, 2 CL YES YES FULL RANGE YES YES YES
CAPL-4
GE 4 HT, 4 CL YES YES FULL RANGE YES YES YES
SYCAP
HP 2 HT, 1 CL NO NO FULL RANGE YES NO NO
TRFPC
GE
1 CL
NO NO FULL RANGE NO NO NO
CAPACITY CONTROLLERS
An HVAC system is sized to handle the load of an entire home or building. Because of this, when all the zones are not calling, the load to the HVAC system can diminish below its designed capacity. Left unchecked, the A/C coil could freeze up causing compressor slugging or the furnace could overheat causing premature heat exchanger failure. To compensate for this, a Capacity Controller is needed.
The basic function of the Capacity Controller is to monitor the leaving air temperature and cycle the unit on and off to maintain a leaving air temperature within set parameters. Zonex Systems offers six unique capac­ity controllers to meet all your application needs: TRLAT, 101CAPGE, CAPL­2, CAPL-4, SYCAP and TRFPC.
CAPACITY CONTROLLER SELECTION
Select the Capacity Controller best suited for your application based on the following table and feature list.
GE/HP – Gas/Electric or Heat Pump. For Gas/Electric HVAC systems,
select GE. For heat pumps select HP unless heat pump uses GE thermostats (no external reversing valve control), then select GE.
# STAGES – Maximum number of HVAC system heat and cool stages.
ECONO CNTRL – This feature allows the economizer to operate as an
additional stage of cooling when outdoor air conditions are acceptable. May be used with HVAC systems that utilize an economizer.
CUT-IN – This advanced feature separates the cut-in setpoint from the
cut-out setpoint. This permits better staging and leaving air temperature control. Example: Without this feature, in cool mode with a cut-out setpoint of 48 degrees, the compressor will turn off if the leaving air drops below 48 and, after a time delay, turn back on when the air rises above
48. With this feature, if the cut-out is 48, the cut-in will be 58. If the air drops below 48 the compressor will turn off. It will not turn on, howev­er, until the air temperature rises above 58 and a time delay has elapsed. This gives longer compressor running times and maintains a more com­fortable leaving air temperature.
FEATURE LIST
SETPOINT – Number of setpoints available for heat and cool.
LEAVING AIR DISPLAY– Digitally displays the leaving air temperature.
This is useful for troubleshooting and system monitoring.
COMPRESSOR MIN. RUN – Runs the compressors a minimum of
four minutes whenever they are energized. This ensures proper oil return and increased compressor life.
FAN CONTROL – Runs the indoor blower fan during capacity cut-out.
This ensures the heat exchanger properly cools down and the AC coil warms up during capacity cut-out. It also provides better zone tem­perature control by providing conditioned air during capacity cut-out periods. This feature is not provided or necessary for heat pumps because blower fan is continuously energized as long as there is a call. This fea­ture is also not necessary if blower fan is run continuously.
28
CAPACITY CONTROLLERS – 101CAPGE
OVERVIEW
The 101CAPGE is a Gas/Electric Capacity Controller that digitally displays leaving air temperature. It should be utilized for single stage applications. For multistage HVAC systems, use either the CAPL-2 or CAPL­4 Capacity Controller.
The Zonex Systems 101CAPGE capacity controller protects both the air conditioner and furnace. It simply measures the leaving air temperature. If the air gets too cold (drops below the cool cutout setpoint), it breaks the “Y” connection, disengaging the compressor. If the air gets too warm (rises above the heat cutout setpoint), it breaks the “W” connection, de­energizing the furnace. To prevent short cycling, the compressor or fur­nace cannot reenergize for at least four minutes after cutout. The heat­ing and cooling cutout setpoints can be changed by the installer.
The 101CAPGE has a three digit LED display and two push buttons. Normally the leaving air temperature is displayed. When the push but­tons are pressed the cut-out setpoints are displayed.
OPERATION
The 101CAPGE has three modes of operation: in range, out of range and enable mode.
In Range – If the leaving air temperature is between the cool and heat cutout setpoints and the 101CAPGE is not in cutout time delay, light DL1
is off and relay K1 is made, permitting the System Controller to energize the compressor or furnace. The leaving air temperature is displayed on the digital display during this time.
Out of Range – If the leaving air temperature drops below the cool cutout setpoint or rises above the heat cutout setpoint, light DL1 is lit and the relay contacts between Y1 Y1 and W1 W1 break, de-energizing the compressor or furnace. Four minutes after the leaving air temperature has returned within operating range light DL1 is turned off and the relay contacts close, making Y1 Y1 and W1 W1 and energizing the fur­nace or compressor. The leaving air temperature is displayed on the digital display during this time.
Enable Mode – On the digital display, “E” followed by the leaving air temperature indicates that the 101CAPGE is in the Enable Mode. The purpose of this mode is to ensure the furnace can turn on in a cold building and the air conditioner can turn on in a hot building. Enable Mode is entered if the leaving air temperature is below the cool cutout setpoint or above the heat cutout setpoint for more than eight minutes. The relay contacts are made during this mode, enabling the furnace or air conditioner to run. After the leaving air temperature has returned within operating range the 101CAPGE will return to normal operation, displaying only the leaving air temperature.
COMPONENTS
The 101CAPGE consists of the following:
Digital Display – Three digit LED. Normally displays the leaving
A.
air temperature of the HVAC unit. When “E” is displayed, it indicates 101CAPGE is in Enable mode; refer to OPERATION section. When the UP/DN buttons are pressed, the cutout setpoints are displayed. Refer to the Setpoint Calibration section for reading and adjusting the setpoints.
B. Microcontroller – Activates and controls outputs based
upon leaving air temperature comparison with programmed set­points. Occasionally software upgrades may become available. If so, the 101CAPGE software can be field upgraded by changing this microcontroller.
Cut-out Indicator Lights – DL1 light is on when relay K1 is
C.
energized. See E.
D. Thermometer Calibrator – Calibrates the leaving air tempera-
ture thermometer. Turn clockwise to lower temperature. Turn coun­terclockwise to raise. Refer to CALIBRATION section for com­plete calibration information.
E. Relays K1 and K2 – DPDT, NC relays. When K1 is energized, it
breaks contact between Y1 Y1 and W1 W1 terminals.
G
961205-C
K
C
DL1
E
UP
J
DN
ON
I
OFF
TR1 TR2
H
A
CAPGE V3.4
B
D
R11
+-
F
Leaving Air Sensor (LAS) Terminals – Leaving air tempera-
F.
Y1 Y1 W1W1
ture sensor is connected to the 101CAPGE here. Red to + and white to –. The sensor monitors the leaving air of the HVAC system. If pre­ferred, the 101CAPGE can be mounted up to 500 feet from the sen­sor. See INSTALLATION section for further information.
29
System Controller (101ASSB)
Switching Center (SYGE)
101CAPGE
K1aK1b
H V A C
U N
I
T
Y
W
C
G
R
R G WY
Y1Y1
W1W1
TR1TR2
Without Fan Relay
With Fan Relay
K1aK1b
H V A C
U N
I
T
Y1Y1W1W1TR1TR2
SPDT, 24V
AC Relay
Y
W
C
G
R
101CAPGE
System Controller (101ASSB)
Switching Center (SYGE)
R G WY
4
2
5
1
3
CAPACITY CONTROLLERS – 101CAPGE
G. HVAC/System Controller Interface Terminals– Y1 controls
the A/C compressor and W1 controls the furnace. W1 controls the first stage furnace and W2 controls second stage. One Y and W connect to the System Controller, the other Y and W connect to the HVAC unit. It does not matter which W/Y connects to the System Controller and which connects to the HVAC unit. See WIRING section for detailed wiring instructions.
Power Source Terminals – Connect to 24V AC power source.
H.
Recommend using either the HVAC unit transformer or the System Controller transformer. 101CAPGE uses less than 2 VA of power. See WIRING section for detailed wiring instructions.
101CAPGE WIRING
The 101CAPGE is installed as detailed in the Capacity Controllers installation section, Page 40. The following wiring diagrams show how to wire the 101CAPGE to the System Controller and the HVAC unit. Terminals TR1 and TR2 of the 101CAPGE can be wired either to R and C of the HVAC Unit or to TR1 and TR2 of the System Controller.
There are two ways of wiring the 101CAPGE: without a fan relay and with a fan relay.
I.
Power Switch – When off, the display is off, the 101CAPGE is
disabled and the relay contacts are closed. The HVAC unit can run at this time but will not have capacity control protection. When the switch is on, the display is on and the 101CAPGE is operational.
J. Setpoint Adjustment – Use the UP/DN buttons to view and change
the cut-out setpoints. Refer to the Setpoints, Calibration section (Page
41) for reading and adjusting the setpoints.
Board Number – This number indicates the circuit board number
K.
and revision. You may need to know this number if conferring with technical support.
Use the “Without Fan Relay” drawing if the indoor blower fan will be running continuously or the furnace keeps the indoor blower fan on for at least three minutes after the heat call is removed (W de-energized).
Use the “With Fan Relay” drawing if the indoor blower fan will not be running continuously and the furnace does not keep the indoor blower fan on for at least three minutes after the heat call is removed (W de-energized). The relay is a SPDT, 24V AC.
30
CAPACITY CONTROLLERS – TRLAT
GE
O
HP B
CONTROLLER UNIT
+ -
ONOFF
SW1 SW2 SW3 SW4
WYRO/B G C W YRO/B G C
D E L A Y
P W R
B
A
G
E
F
C
D
OVERVIEW
The Zonex Systems TRLAT is a single stage Gas/Electric or Heat Pump Capacity Controller. However, the heat pump feature is not compatible with the Zonex Systems System 1000/2000 Zoning Systems so we will only address the Gas/Electric features. If you have a heat pump that uses heat pump controls refer to the SYCAP for System 1000 and LAS for System 2000.
The TRLAT Capacity Controller protects both the air conditioner and furnace. It simply measures the leaving air temperature. If the air gets too cold (drops below the cool cutout setpoint), it breaks the “Y” connection, disengaging the compressor, If the air gets too warm (rises above the heat cut-out setpoint), it breaks the “W” connection, de-energizing the furnace. To prevent short cycling, the compressor or furnace cannot reenergize for at least four minutes after cut-out. The heating and cooling cut-out setpoints can be changed by the installer.
OPERATION
Cool mode: If the leaving air temperature drops below the TRLAT
cooling setpoint (field settable to 41, 44, 47 or 50 degrees Fahrenheit), the Y (Controller) breaks from Y (Unit) and makes to G. This turns off the compressor and keeps the indoor blower fan running to warm up the evaporator. Four minutes after the leaving air temperature rises above the cooling setpoint, Y (Controller) makes to Y (Unit) and breaks to G. This restarts the compressor and returns indoor blower fan control to the Switching Center/Controller.
COMPONENTS
A. Status Lights:
DELAY (red): On when compressor or furnace is disabled. PWR (yellow): On when TRLAT is powered.
B. Jumpers:
GE/HP: For gas/electric systems, place jumper on GE and center pin. For heat pumps, place jumper on HP and center pin.(Digitract Systems only) O/B: For heat pumps, if reversing valve is energized in cool mode, place jumper on O and center pin. If reversing valve is energized in heat mode, place jumper on B and center pin.
C. Unit terminal block: Connects to HVAC unit. O/B – Reversing
Valve; R – 24V AC hot; G – Blower fan; C – 24V AC rtn; W – heat; Y – compressor. See WIRING section for detailed wiring instructions.
D. Controller terminal block: Connects to System Controller. Terminal
designations same as for Unit terminal block. See WIRING section for detailed wiring instructions.
E. Leaving Air Sensor (LAS) Terminals: Leaving air temperature sensor
is connected to the TRLAT here. Red to + and white to –. The sensor monitors the leaving air of the HVAC system. If preferred, the TRLAT can be mounted up to 500 feet from the sensor. See INSTALLATION section for further information.
Heat mode: If the leaving air temperature rises above the TRLAT heating setpoint (field settable to 125, 140, 150 or 160 degrees Fahrenheit), the W (Controller) breaks from W (Unit) and makes to G. This turns off the heater and keeps the indoor blower fan running to cool down the heater. Four minutes after the leaving air temperature drops below the heating setpoint, W (Controller) makes to W (Unit) and breaks to G. This restarts the heater and returns indoor blower fan control to the heater or Switching Center/Controller.
Cut-out disable: The cool cutout is disabled in heat mode. The heat cutout is disabled in cool mode. This permits the heat to turn on in a cold building and the air conditioner to turn on in a hot building. For heat pumps, this also prevents the compressor from cycling off when the heat pump is in defrost mode. The O/B (Controller) input tells the TRLAT which mode of operation (heat or cool) is active.
NOTE: For GE systems, a jumper wire (factory installed) must be connected between O/B (Controller) and W (Controller).
F. Jumper wire: Factory installed. Must be connected between O/B
(Controller) and W (Controller) for GE systems and removed for heat pumps.
G. Setpoint Select: Sets the heat and cool cutoff setpoints. See SETPOINT
SETUP, TRLAT section.
31
CAPACITY CONTROLLERS – TRLAT
SETPOINT SETUP, TRLAT
A four pole dip switch is used to designate the desired heat and cool cutoff setpoints. Using the table to right, set the switch positions to correspond to the cutoff temperatures desired. For heat pumps, the heat cutoff point is 118 degrees and unchangeable.
Cool
SW1 SW2 On On 50 Deg F On Off 47 Deg F Off On 44 Deg F Off Off 41 Deg F
SW3 SW4 On On 125 Deg F On Off 140 Deg F Off On 150 Deg F Off Off 160 Deg F
Cut-out
Heat
Cut-out
TRLAT WIRING
System 1000 Switching Center (SYGE)
System 2000 Controller (101ASSB)
RG WY
1
O/B R G
C W
TRLAT
O/B R G C
R G
HVAC UNIT
The TRLAT is installed as detailed in the Capacity Controllers Installation section, page 40. Wire as shown above.
WARNING
1
Jumper wire (factory installed) must be connected for GE applications between W (Controller) and O/B (Controller). If not, the TRLAT will not shut off the heater when the heat setpoint is exceeded.
W
C W
CONTROLLER
Y
UNIT
Y
Y
CAPACITY CONTROLLERS – TRFPC
OVERVIEW
The TRFPC is an inexpensive no frills single stage air conditioning only Capacity Controller. It will simply interrupt power to the air conditioning compressor when the supply air temperature drops below 47 degrees Fahrenheit and re-energize when the temperature rises above 47 degrees. This setpoint is non-adjustable. It has no control for preventing compressor short cycling. If your air conditioner does not have a non-recycle timer, we highly recommend adding one when using this Capacity Controller to prevent short cycling.
OPERATION
The TRFPC will interrupt power to the air conditioning compressor when the supply air temperature drops below 47 degrees Fahrenheit and re-energize when the temperature rises above 47 degrees. This setpoint is non-adjustable. The TRFPC is powered by the “Y” terminal. Thus, the TRFPC will operate only when there is a call for cooling (24V at “Y”). A green status light is provided. When on, the compressor can run (relay closed). When off, the “Y” circuit is broken, disengaging the compressor.
WIRING
The TRFPC is installed as detailed in the Capacity
System Controller (101ASSB)
Switching Center (SYGE)
R G WY
Controllers installation section, page 40. The fol­lowing wiring diagrams show how to wire the TRFPC to the System Controller and the HVAC
R
H V
G
A C
C
U
W
N I
Y
T
unit. Terminal C of the TRFPC must be wired to
C
YOUTYIN
the HVAC unit’s trans­former common.
TRFPC
Note: A non recycle timer on the air conditioner is strongly recommended
to prevent short cycling.
32
CAPACITY CONTROLLERS - SYCAP
OVERVIEW
The SYCAP is a single stage cool, two stage heat Heat Pump Capacity Controller. It works in conjunction with the System 1000 SYHPA Switching Center only. Its function is to control the heat pump coil leaving air temperature within a set operating range.
When the heat pump is running, the SYCAP keeps the heat pump coil leaving air temperature within operating range by turning the heat pump compressor off for a minimum of four minutes if the air temperature gets too cold in cool mode or too hot in heat mode. The SYCAP will also turn on the heat pump auxiliary heat if the coil leaving air temperature is not hot enough in heat mode. The compressor is kept off for a minimum of four minutes to prevent short cycling.
OPERATION
The SYCAP has two relays (K1 and K2) and two corresponding status lights (DL1- red and DL2- green). Relay K1 is a normally closed relay. When energized, it breaks the connection between Y1 Y1 which disables the heat pump compressor. Relay K2 is a normally open relay. When energized, it makes the connection between W2 W2 which enables the heat pump auxiliary heat.
There are three adjustable setpoints on the SYCAP: Heat Cut-out, Cool Cut-out, and Auxiliary Heat Cut-in. The Heat Cut-out Setpoint is the maximum allowable leaving air temperature in heat mode. If the air temperature rises above this setpoint in heat mode, the compressor is disabled for a minimum of four minutes. The Cool Cut-out setpoint is the minimum allowable leaving air temperature in cool mode. If the air temperature drops below this setpoint in cool mode, the compressor is disabled for a minimum of four minutes. The Auxiliary Heat Cut-in temperature is the minimum allowable leaving air temperature in heat mode. Four minutes after the heat pump compressor has been turned on, if the coil air temperature cannot rise above this setpoint, the auxiliary heat is enabled. The auxiliary heat is disabled when the air temperature rises nine degrees above the Auxiliary Heat Cut-in setpoint.
The SYCAP knows which mode of operation it is in by monitoring the W2 signal from the SYHPA Switching Center. If W2 is energized, it knows the SYHPA is making a heat call.
The following is a detailed operation description of each mode.
IN RANGE, HEAT MODE – If the SYHPA Switching Center is making
a heat call and the leaving air temperature is below the Heat Cut-out setpoint and above the Auxiliary Heat Cut-in, relays K1 and K2 are de-energized, red light DL1 is off and green light DL2 is off. The leaving air temperature is displayed on the digital display.
COOL CUT-OUT – If the SYHPA is making a cool call and the leaving
air temperature drops below the Cool-Cut-out setpoint, the connection between Y1 Y1 breaks, red light DL1 turns on, and the Heat Pump compressor is disabled. Every four minutes after Y1 is broken, the leaving air temperature is checked. If the temperature rises above the cool cut-out setpoint, Y1 Y1 is made, red light DL1 turns off and the compressor is re-enabled.
HEAT CUT-OUT – If the SYHPA is making a heat call and the leaving air
temperature rises above the Heat Cut-out setpoint, the connection between Y2 Y2 breaks, red light DL1 turns on, and the Heat Pump compressor is disabled. Every four minutes after Y2 is broken, the leaving air temperature is checked. If the temperature drops below the heat cut-out setpoint, Y2 Y2 is made, red light DL2 turns off and the compressor is re-enabled.
AUXILIARY HEAT CONTROL – Four minutes after the SYHPA initiates
a heat call, the leaving air temperature is continuously checked. If the air temperature does not rise above the Auxiliary Heat Cut-in setpoint, green light DL2 turns on, the connection between W2 W2 is made, and the Heat Pump Auxiliary heat is enabled. When the leaving air temperature rises nine degrees above the auxiliary heat cut-in setpoint, green light DL2 turns off, W2 W2 is broken, and the auxiliary heat is disabled.
SYCAP Components
The SYCAP consist of the following:
A. Digital Display – Three digit LED. Normally displays the coil
leaving air temperature of the heat pump. When “E” displayed, indicates SYCAP is in Enable mode; refer to OPERATION section. When the UP/DN buttons are pressed, the cutout setpoints are displayed. Refer to the Setpoint Calibration section for reading and adjusting the setpoints.
B. Microcontroller – Brains of the SYCAP and where the program
resides. Occasionally, software upgrades may become available. If so, the SYCAP software can be field upgraded by changing this micro­controller.
C. Status Lights – Red light DL1 is on when relay K1 is energized.
Green light DL2 is on when relay K2 is energized. See E.
D. Thermometer Calibrator – Calibrates the leaving air temperature
thermometer. Turn clockwise to lower temperature. Turn counter­clockwise to raise. Refer to CALIBRATION section for complete calibration information.
E. Relays K1 and K2 – SPST relays. Relay K1 is a normally closed
relay. When energized, it breaks contact between Y1 Y1. Relay K2 is a normally open relay. When energized, makes contact between W2 W2 terminals.
F. Leaving Air Sensor (LAS) Terminals – Leaving air temperature
sensor is connected to the SYCAP here. Red to + and white to –. The sensor monitors the coil leaving air of the heat pump. If preferred, the SYCAP can be mounted up to 500 feet from the sensor. See INSTALLATION section for further information.
G. Heat Pump/Switching Center Interface Terminals – Y1
controls the heat pump compressor. W2 controls the heat pump auxiliary heat. One Y1 and W2 connect to the Switching Center, the other Y1 and W2 connect to the heat pump. It does not matter which W2/Y1 connects to the Switching Center and which connects to the heat pump. See WIRING section for detailed wiring instructions.
33
CAPACITY CONTROLLERS - SYCAP
UP
DN
RC+-
DL1
K1
A
K
J
B
D
I
H
G
F
DL2
C
Y1 Y1 W2W2
K2
E
90107C
ON
OFF
H. Heat Pump Power Terminals – Connect to heat pump 24V AC
power source. R is 24 V hot. C is 24 V rtn. Cannot be connected to any other power source. SYCAP uses less than 2 VA of power. See WIRING section for detailed wiring instructions.
I. Power Switch – When off, the display is off, the SYCAP is disabled
and K1 relay contacts are made. The heat pump compressor can run at this time but will not have capacity control protection. The auxiliary heat cannot run. When the switch is on, the display is on and the SYCAP is operational.
J. Setpoint Adjustment – Use the UP/DN buttons to view and
change the cut-out setpoints. Refer to the Setpoints, Calibration section (Page 41) for reading and adjusting the setpoints.
K. Board Number – This number indicates the circuit board num-
ber and revision. You may need to know this number if con­ferring with technical support.
WIRING
The SYCAP is installed as detailed in the Capacity Controllers Installation section, page 40. Wire as diagrammed below. The W2 terminal from the SYHPA Switching Center must be wired to the SYCAP Capacity Controller even if the Heat Pump does not have auxiliary heat. The SYCAP determines the mode of operation based on this signal.
Terminals R and C of the SYCAP must be wired to terminals R (24V hot) and C (24V rtn) of the Heat Pump system transformer.
34
Switching Center (SYHPA)
RGW2YO/B E L C
O/B
H
Y
E A
G
T
R
P
E
U
M
W2
P
L
C
CR
SYCAP
W2W2
Y1Y1
K1K2
CAPACITY CONTROLLERS - 101ALAS
Deg. F. DC Volts Deg. F. DC Volts Deg. F. DC Volts
40 2.775 70 2.942 100 3.109 41 2.781 71 2.948 101 3.114 42 2.787 72 2.953 102 3.120 43 2.792 73 2.959 103 3.125 44 2.798 74 2.964 104 3.131 45 2.803 75 2.970 105 3.137 46 2.809 76 2.975 106 3.142 47 2.814 77 2.981 107 3.148 48 2.820 78 2.987 108 3.153 49 2.825 79 2.992 109 3.159 50 2.831 80 2.998 110 3.164 51 2.837 81 3.003 111 3.170 52 2.842 82 3.009 112 3.175 53 2.848 83 3.014 113 3.181 54 2.853 84 3.020 114 3.187 55 2.859 85 3.025 115 3.192 56 2.864 86 3.031 116 3.198 57 2.870 87 3.037 117 3.203 58 2.875 88 3.042 118 3.209 59 2.881 89 3.048 119 3.214 60 2.887 90 3.053 120 3.220 61 2.892 91 3.059 121 3.225 62 2.898 92 3.064 122 3.231 63 2.903 93 3.070 123 3.237 64 2.909 94 3.075 124 3.242 65 2.914 95 3.081 125 3.248 66 2.920 96 3.087 126 3.253 67 2.925 97 3.092 127 3.259 68 2.931 98 3.098 128 3.264 69 2.937 99 3.103 129 3.270
Deg. F. DC Volts
130 3.275 131 3.281 132 3.287 133 3.292 134 3.298 135 3.303 136 3.309 137 3.314 138 3.320 139 3.325 140 3.331 141 3.337
OVERVIEW
The 101ALAS works with the System 2000 Heat Pump System Controller (101AACBHP). The 101ALAS provides leaving air temperature readings to the System Controller, which allows it to make capacity control decisions.
OPERATION
The 101ACBHP System Controller has four status lights that represent capacity control. The heat Y1 and Y2 red lights indicate heating opera­tion and the cool Y1 and Y2 green lights indicate cooling operation. Heat­ing or cooling will be initiated depending on the position of the revers­ing valve. When one of the lights turns on, the leaving air temperature in the duct, sensed by the LAS, has exceeded one of the capacity control set­points. The light will indicate which stage will be turned off. The sec­ond stage factory default cut-in temperature for heating is 95 degrees, and for cooling 60 degrees. If the setpoint is exceeded, a stage light will illu­minate, the stage will be shut down, and a four-minute time delay will begin. After the four minute delay, if the leaving air temperature has recov­ered to an acceptable temperature, the stage which was shut down will restart. If the temperature has not recovered, the time delay will contin­ue. If both first and second stage setpoints are exceeded by the leaving air, then a four-minute time delay per stage will go into effect.
MODIFYING SETPOINT ADJUSTMENT
The Heat Pump Controller is designed so that it is possible to modify the cut-in setpoints for cooling, heating (and electric heat on the Heat Pump Controller). If necessary, locate the potentiometer associated with its test point on the diagram above. “GND” is the common ground test point, TP2
is the cool test point and TP3 is the heat test point. (TP1 is the electric heat test point on the Heat Pump Controller). Clip the leads of a digital volt meter, set to 20 volts DC, between the potentiometer test point that needs to be modified and the ground test point. Rotate the correspond­ing potentiometer until the meter reads the proper voltage according to Table 2 below.
101ALAS
+
GROUND
ELECTRIC HEAT ADJ TP1
COOL ADJ TP2
HEAT ADJ TP3
1
GND
TB2 WRO
TB1
Y1
+
Y2
HEAT
J1
Y1
COOL
TC2 Y W B GRd TR1TR2S
TC1TEMP
J2
Y2
Y2
101AACBHP HEAT PUMP
CONTROLLER
REV.
VALVE
Y1
/
BL
ON
PWR OFF
OFF
COOLHEAT
AUTO
OFF
AUTO
G
FAN
ON
WIRING
The 101ALAS is installed as detailed in the Capacity Controllers
1
Installation Section, page 40. The + or – terminals of the LAS are wired to the + or – terminal of the 101AACBHP using two conductor 18 gauge thermostat wire.
LAS VOLTAGE CONVERSION CHARTS
TABLE 1: CAPACITY CONTROL
STAGE CUT-IN TEMPERATURES*
Cooling
Second Stage 60 GND & TP2 2.887
Heating
Second Stage 95 GND & TP3 3.081 Electric Heat 85 GND & TP1 3.025 Discharge Duct
Temperature –– LAS + & – per table #2
*The Y2 cut-out temperature is 10° fixed below the cut-in temperature
in cooling, and 10° above in heating. The Y1 cut-out temperature is 15° fixed below the cut-in temperature in cooling, and 25° above in heating.
TABLE 2: TEMPERATURE TO VOLTAGE CONVERSION CHART
35
CAPACITY CONTROLLERS – CAPL-2
YINY1Y2G
I N
WIN W1W2 R C
24V PWR
24V RTN
HEAT 1
HEAT 2
ECONOMIZER
COMP 1
COMP 2
FAN
Y
G
W
R
LAS
SENSOR
+
-
CAPL-2
HVAC UNIT
+ –
SYGE Switching Center
101ASSB System Controller
G O
U T
*Lennox L Series Units may require a direct connection from YIN to the Economizer.
*
OVERVIEW
The Zonex Systems CAPL-2 is a combination staging and capacity control device for use with gas/electric units and heat pumps that use standard gas/electric thermostats. It can stage an economizer, two stages of cooling and up to two compressors and two stages of heat. The CAPL-2 monitors the leaving air temperature and stages the cooling or heating to maintain the leaving air temperature within a fixed range. Controlling the staging based on the leaving air temperature ensures the supply always matches the load. This is essential with a zoning system since the load varies sub­stantially as the number of zones calling varies.
Cool Mode – When there is a cool call, if the leaving air is above the cool cut-in temperature, the CAPL-2 turns on the next stage compressor after a time delay. If the air gets too cold, it turns off the last stage compressor after that compressor has run a minimum of four minutes. As long as there is a cool call, when a compressor turns off it will stay off for a minimum of four minutes if the jumper is on ECON and when a compres­sor turns on it will run a minimum of four minutes. This prevents short cycling and ensures sufficient compressor oil return. When the cool call is removed, all compressors are immediately turned off.
Heat Mode (Gas/Electric) – If the leaving air is below the heat cut­in temperature, it turns on the next heat stage after a time delay. If the air gets too warm, it turns off the last heat stage after a time delay. When the heat call is removed, all heat stages turn off immediately.
Heat Mode (Heat Pump) – When there is a heat call, if the leaving air is below the heat cut in temperature, the CAPL-2 turns on the next stage heat after a time delay. If the air gets too warm, it turns off the last stage heat after that stage has run a minimum of four minutes. As long as there is a heat call, when a heat stage turns off, it will stay off for a minimum of four minutes and when a heat stage turns on it will run a minimum of four minutes. This prevents short cycling and ensures sufficient compressor oil return. When the heat call is removed, all compressors are immediately turned off.
SEQUENCE OF OPERATION
The following sequence of operation assumes the cool cut-out setpoint is 48 degrees Fahrenheit and the heat setpoint is 150 degrees for gas/electric units and 118 degrees for heat pump units. For any other cut-out settings, add or subtract the difference to the values stated. Example: If your actual cool cut-out is 50 degrees, add 2 degrees to each temperature value stated under the Cooling Call section. All temperatures are in degrees Fahrenheit.
COOLING CALL (cool setpoint 48): As long as there is a cooling call
(YIN energized), the following will occur.
ECONOMIZER:
• As long as there is a cooling call the economizer, if available, is enabled and outside air is supplied based on enthalpy. The Economizer selection jumper must be on ECON if there is an economizer. If no economizer, place jumper on ECOFF.
COMPRESSOR STAGING ON:
• If the leaving air is 58 degrees or greater and no compressors are
running, compressor one will turn on within six minutes. If compressor one is running, compressor two will turn on within eight minutes.
COMPRESSOR STAGING OFF:
• If the leaving air is between 48 and 52 degrees and compressor two is running, compressor two will shut off after running a minimum of four minutes. Compressor one will shut off after it has been on a minimum of four minutes and compressor two has been off a minimum of six minutes.
• If the leaving air is 48 degrees or less, then all compressors will turn
off after the last compressor running has run for at least four minutes.
NO STAGING:
• If the
HEATING CALL (Gas/Electric)
Heat setpoint may be field modified to compensate for local temperatures
leaving air is equal to or greater than 52 and less than
58 degrees, then no compressor staging will occur.
(The factory heat setpoint is 150.
WIRING – CAPL-2
36
CAPACITY CONTROLLERS – CAPL-2
and field conditions. For example, in milder climates setting may be as low as 110 to 115 degrees. In more severe climates up to 150 degrees.) As long as there is a heating call (WIN energized), the following will occur.
HEAT STAGING ON:
• If the leaving air is 130 degrees or less and heat one is off, heat
one will turn on within four minutes. If heat one is on, heat two will turn on within ten minutes.
HEAT STAGING OFF:
• If the leaving air is between 145 and 150 degrees and heat two
is running, heat two will turn off. Heat one will turn off after 150 Degree setpoint is exceeded
If the leaving air is 150 degrees or greater then all heat stages
will turn off and the indoor blower fan is energized until heat one turns back on or until the heat call is satisfied.
NO STAGING: If the leaving air is greater than 130 and less than
or equal to 145 degrees, then no heat staging will occur.
COMPONENTS
The CAPL-2 consists of the following:
A. Digital Display – Three digit LED. Normally displays the leaving air temperature of the HVAC unit. When the UP/DN buttons are pressed, the cut-out setpoints are displayed. Refer to the Setpoint Calibration section for reading and adjusting the setpoints.
B. Microcontroller – Activates and controls outputs based upon leaving air temperature comparison with programmed setpoint. Occasionally soft­ware upgrades may become available. If so, the CAPL-2 software can be field upgraded by changing this microcontroller.
C. Thermometer Calibrator – Calibrates the leaving air temperature thermometer. Turn clockwise to lower temperature. Turn counterclock­wise to raise. Refer to CALIBRATION section for complete calibration infor­mation.
D. Economizer Selection Jumper:
ECON – Place here if you have an economizer. ECOFF – Place here if no economizer.
E. Leaving Air Sensor (LAS) Terminals – Leaving air temperature sensor is connected to the CAPL-2 here. Red to + and white to –. The sensor monitors the leaving air of the HVAC system. If preferred, the CAPL-2 can be mounted up to 500 feet from the sensor. See Installation section for further information.
F. HVAC/System Controller Interface Terminals – Y IN – Cool call input, Economizer output; Y1 – Compressor 1; Y2 – Compressor 2; G – Indoor blower fan; W IN – Heat call input; W1 – Heat 1; W2 – Heat
2. See Wiring section for detailed wiring instructions. G. HVAC Power Terminals – Connect to HVAC system 24V AC power
source. R is 24 V hot. C is 24 V rtn. Cannot be connected to any other power source. CAPL-2 uses less than 2 VA of power. See Wiring section for detailed wiring instructions.
HEATING CALL (Heat Pump) (heat setpoint 118). As long as there
is a heating call (WIN energized), the following will occur:
HEAT STAGING ON:
• If the leaving air is 98 degrees or less and heat one is off, heat
one will turn on within four minutes. If heat one is on, heat two will turn on within eight minutes.
HEAT STAGING OFF:
• If the leaving air is between 113 and 118 degrees and heat two
is on, heat two will shut off after running a minimum of four min­utes. Heat one will turn off after it has been on a minimum of four min­utes and heat two has been off a minimum of six minutes.
• If the leaving air is 118 degrees or greater then all heat stages will
turn off after the last heat stage running has run for at least four min­utes.
NO STAGING:
• If the leaving air is greater than 98 and less than or equal to 113 degrees, then no heat staging will occur.
H. Status Lights – ECONO – On during cool call. Indicates economiz-
er enabled; Y1 – On when first stage compressor energized; Y2 – On when second stage compressor energized; Y3 – On when third stage compressor energized; Y4 – On when fourth stage compressor energized; FAN – On when indoor blower fan energized by System Con­troller or CAPL-2 (G energized); W1 – On when first stage furnace energized; W2 – On when second stage furnace energized; W3 – On when third stage furnace energized; W4 – On when fourth stage furnace energized.
I. Power Switch – When off, the display is off, the CAPL-2 is disabled and the relay contacts are closed. The HVAC unit can run at this time but will not have staging control or capacity control protection. When the switch is on, the display is on, and the CAPL-2 is operational.
J. Board Number – This number indicates the circuit board number and revision. May need to know this number if conferring with technical support.
K. Heat Pump/Gas Electric selection jumper – Place at GE position for gas/electric units.
ECON
E C O N O
Y1 Y2
UP
L
DN
HP
GE
D
H
F A N
W1 W2
GOUT
F
Place at HP position for heat pump units that use gas/electric thermostats.
L. Setpoint Adjust­ment – Use the UP/DN
buttons to view and change the cutout set­points. Refer to the Set­points, Calibration sec­tion (Page 41) for read­ing and adjusting the set-
s.
point
37
A
B
R4
ECOFF
C
E
Y IN Y1 Y2 GINRCWIN W1 W2
-
+
J
K
990616B
ON
OFF
I
G
CAPACITY CONTROLLERS – CAPL-4
OVERVIEW
The Zonex Systems CAPL-4 is a combination staging and capacity control device in one. It can stage an economizer and up to four compres­sors and up to four stages of heat. The CAPL-4 monitors the leaving air temperature and stages the cooling or heating to maintain the leaving air temperature within a fixed range. Controlling the staging based on the leaving air temperature ensures the supply will always match the load. This is essential with a zoning system, since the load varies sub­stantially as the number of zones calling varies.
Cool mode – When there is a cool call, if the leaving air is above the cool cut-in temperature, the CAPL-4 turns on the next stage compressor after a time delay. If the air gets too cold, it turns off the last stage compressor after that compressor has run a minimum of four minutes. As long as there is a cool call, when a compressor turns off it will stay off for a minimum of four minutes and when a compressor turns on it will run a minimum of four minutes. This prevents short cycling and ensures sufficient compressor oil return. When the cool call is removed, all compressors are immediately turned off.
Heat mode – If the leaving air is below the heat cut-in temperature, it turns on the next heat stage after a time delay. If the air gets too warm, it turns off the last heat stage after a time delay. When the heat call is removed, all heat stages turn off immediately.
OPERATION
The following sequence of operation assumes the cool cut-out setpoint is 48 and the heat is 150 degrees Fahrenheit. For any other cut-out settings, add or subtract the difference to the values stated. Example: If your actu­al cool cut-out is 50 degrees, add 2 degrees to each temperature val­ue stated under the Cooling Call section. All temperatures are in degrees Fahrenheit.
NO STAGING:
If the leaving air is equal to or greater than 52 and less than 58° then no compressor staging will occur.
HEATING CALL (heat setpoint 150). As long as there is a heating call (WIN energized), the following will occur.
HEAT STAGING ON:
If the leaving air is 130° or less, the next heat stage will turn on within four minutes. As long as the air temperature remains within this range the next higher heat stage will turn on every four minutes.
HEAT STAGING OFF:
If the leaving air is between 145 and 150° the highest heat stage on will shut off within four minutes. As long as the air temperature remains within this range the next highest heat will stage off every four minutes.
If the leaving air is 150° or greater then all heat stages will turn off.
COMPONENTS
The CAPL-4 consist of the following:
A. Digital Display – Three digit LED. Normally displays the leaving air temperature of the HVAC unit. When the UP/DN buttons are pressed, the cut-out setpoints are displayed. Refer to the Setpoint Calibration section for reading and adjusting the setpoints.
B. Microcontroller – Activates and controls outputs based upon leav­ing air temperature comparison with programmed setpoints. Occasion­ally software upgrades may become available. If so, the CAPL-4 software can be field upgraded by changing this microcontroller.
COOLING CALL (cool setpoint 48): As long as there is a cooling call (YIN energized), the following will occur.
ECONOMIZER:
As long as there is a cooling call the economizer, if available, is enabled and outside air is supplied based on enthalpy.
COMPRESSOR STAGING ON:
If the leaving air is 58° or greater, the next compressor will turn on within four minutes. As long as the air temperature remains within this range the next higher compressor will stage on every four minutes.
COMPRESSOR STAGING OFF:
If the leaving air is between 48 and 52°, the highest compressor stage on will shut off within four minutes. As long as the air temperature remains within this range the next highest running compressor will stage off every four minutes.
If the leaving air is 48° or less then all compressors will turn off after the last compressor running has run for at least four minutes.
38
A
C
+
D
R4
-
B
E C O N O
Y1 Y2 Y3 Y4 G
Y1 IN Y1 Y2
Y3
Y4
UP
J
DN
G
W1 IN
990407A
SW1
G
W1 W2W3 W4
W3
W1W2
W4
I
ON
H
RC
F
E
CAPACITY CONTROLLERS - CAPL-4
C. Thermometer Calibrator – Calibrates the leaving air temperature
thermometer. Turn clockwise to lower temperature. Turn counter­clockwise to raise. Refer to CALIBRATION section for complete calibra­tion information.
D. Leaving Air Sensor (LAS) Terminals – Leaving air temperature sensor is connected to the CAPL-4 here. Red to + and white to –. The sensor monitors the leaving air of the HVAC system. If preferred, the CAPL­4 can be mounted up to 500 feet from the sensor. See INSTALLATION section for further information.
E. HVAC/System Controller Interface Terminals – Y IN – Cool call input, Economizer output; Y1 – Compressor 1; Y2 – Compressor 2; Y3 – Compressor 3; Y4 – Compressor 4; G – Indoor blower fan; W IN – Heat call input; W1 – Heat 1; W2 – Heat 2; W3 – Heat 3; W4 – Heat 4. See WIRING section for detailed wiring instructions.
F. HVAC power terminals – Connect to HVAC system 24V AC power source. R is 24 V hot. C is 24 V rtn. Cannot be connected to any other power source. CAPL-4 uses less than 2 VA of power. See WIRING section for detailed wiring instructions.
WIRING – CAPL-4
G. Status Lights – ECONO – On during cool call. Indicates economizer
enabled; Y1 – On when first stage compressor energized; Y2 – On when second stage compressor energized; Y3 – On when third stage compressor energized; Y4 – On when fourth stage compressor energized; FAN – On when indoor blower fan energized by System Controller or CAPL-4 (G energized); W1 – On when first stage furnace energized; W2 – On when second stage furnace energized; W3 – On when third stage furnace energized; W4 – On when fourth stage furnace energized.
H. Power Switch – When off, the display is off, the CAPL-4 is disabled and the relay contacts are closed. The HVAC unit can run at this time but will not have staging control or capacity control protection. When the switch is on, the display is on and the CAPL-4 is operational.
I. Board Number – This number indicates the circuit board number and revision. May need to know this number if conferring with technical support.
J. Setpoint Adjustment – Use the UP/DN buttons to view and change the cut-out setpoints. Refer to the Setpoint, Calibration section (Page 41) for reading and adjusting the setpoints.
24V RTN
24V PWR
HEAT 4 HEAT 3 HEAT 2 HEAT 1
FAN
HVAC UNIT
COMP 4 COMP 3 COMP 2 COMP 1
ECONOMIZER
LAS
SENSOR
+ –
-
+
G
W
Y
R
101ASSB System Controller
Y1 IN Y1 Y2 Y3 Y4 G W1 IN W1 W2W3W4 R C
CAPL-4
39
C A P A C
I T Y
Sensor
Protect sensor wire from sharp edges by using grommet or tape.
C
O
N T R
O
L L E R
CAPACITY CONTROLLERS – INSTALLATION
A. Select location to place sensor. For gas/electric HVAC systems, sen-
sor must be in leaving air duct, preferably as far from the coil/heat exchanger as possible but not past the bypass tap. For heat pumps, sensor must be placed between coil and auxiliary heat. If heat pump does not have auxiliary heat, place sensor as specified for gas/electric system. See Figure 1.
B. Cut or drill a hole in selected location large enough to fit sensor
through.
C. For 101CAPGE, TRLAT, SYCAP, CAPL-2 and CAPL-4, determine if
Capacity Controller will be mounted integral with sensor or remote from sensor. Mounting sensor remotely enables you to place the Capacity Controller in a location easily visible and serviceable.
D. For the 101ALAS, TRFPC, or if mounting any other model with the
sensor integral with Capacity Controller, place sensor through hole made in duct and mount Capacity Controller to duct with screws. Use grommet or tape to protect sensor wire from sharp edges. See Figure 2.
GAS/ELECTRIC
C
O
I
AIRFLOW
BYPASS RETURN
L
Figure 1. Sensor Location
HEAT PUMP
E. If mounting sensor remotely, refer to Figure 3 and do the following:
1. On Capacity Controller, loosen + and – terminal screws and disconnect sensor.
2. Remove circuit board screws and pull circuit board away from casing.
3. Pull sensor out of casing.
4. Reattach circuit board to casing with screws previously removed.
6. Place sensor in hole made in duct and secure with tape, wire tie or cable clamp. Use grommet or tape to protect sensor wire from sharp edges.
7. Select location for Capacity Controller and mount with screws.
8. Wire sensor to Capacity Controller, red to + and white to –. If less than 200 feet, use separate 18 gauge, two conductor wire. If over 200 feet, use separate two conductor shielded wire and connect shield to TR2 or C terminal of Capacity Controller.
Place sensor in supply duct, as far from coil/heat exchanger as possible but not past Bypass tap.
BYPASS
TAP
C
O
AIRFLOW
BYPASS RETURN
L
Place sensor in heat pump between coil and auxiliary heat
Figure 2. Capacity Controller Mounted with Sensor
H
A
E
I
U X
A T
+ -
White to – Red to +
BYPASS
TAP
Circuit board screws (qty. 3)
If using shielded wire, connect shield to TR2 or C
Secure sensor with tape, cable clamp or wire tie
White Red
Protect sensor wire from sharp edges by using grommet or tape.
Figure 3. Capacity Controller with Remote Sensor
40
CAPACITY CONTROLLERS – SETPOINTS, CALIBRATION
WIRE LENGTH
NUMBER OF
ZONE
DAMPERS
50' 100' 150' 200' 1 18 GA 18 GA 18 GA 18 GA 2 18 GA 18 GA 18 GA 18 GA 3 18 GA 18 GA 18 GA 18 GA 4 18 GA 18 GA 18 GA 18 GA 5 18 GA 18 GA 18 GA 18 GA 6 18 GA 18 GA 18 GA 16 GA 7 18 GA 18 GA 18 GA 16 GA 8 18 GA 18 GA 16 GA 16 GA 9 18 GA 18 GA 16 GA 14 GA
10 18 GA 18 GA 16 GA 14 GA 11 18 GA 16 GA 16 GA 14 GA 12 18 GA 16 GA 14 GA 14 GA 13 18 GA 16 GA 14 GA 12 GA 14 18 GA 16 GA 14 GA 12 GA 15 18 GA 16 GA 14 GA 12 GA 16 18 GA 14 GA 14 GA 12 GA 17 18 GA 14 GA 12 GA 12 GA 18 18 GA 14 GA 12 GA 12 GA 19 18 GA 14 GA 12 GA 12 GA 20 18 GA 14 GA 12 GA 12 GA
The following applies to the
101CAPGE, CAPL-2, CAPL-4 and SYCAP Setpoints:
There are two cut-out setpoints, one for heat and one for cool. The digital display normally displays the leaving air temperature of the HVAC/heat pump unit. By pressing the UP and DN buttons, the setpoints can be viewed and changed.
Cool Setpoint – To read the cool cut-out setpoint, press the DN button until “C” appears and then release. The number that follows is the cool cut-out setpoint. After a couple of seconds the leaving air temperature will be redisplayed. To change the setpoint, press the bottom or down button until the “C” is displayed, then immediately after the setpoint is displayed press and hold the UP/DN button till setpoint is at the desired value.
Zonex Systems’s patented Five Wire Link is one of the most important ele­ments of the System 1000/2000 zoning system. Extra care should be made to ensure the wiring is done correctly. The color code must be strictly fol­lowed. Ensure the stripped wire leads are not touching each other at the ter­minal blocks. If putting two wires into one terminal block, use the same gauge wire for both and ensure they are seated properly.
You must ensure the wire is sized properly to match the power needs of the number of dampers installed. The more dampers used, the greater the current draw and the greater the voltage loss on the Five Wire Link. If too much voltage is lost on the Five Wire Link, there will not be enough voltage at the zone dampers to properly operate them. To ensure the correct wire size, use the following table. Select the row matching the number of zone dampers you have. Move across horizontally to the column that matches the distance from the System Controller to the farthest damper. Use the wire size specified at the row/column intersection.
To reduce wire size, you can run more than one Five Wire Link Daisy Chain. Example: If you have 10 dampers, and the maximum distance is 200 feet, you would need 12 GA wire. If instead, you used two Five Wire Links with 5 dampers on each, you would now only need 18 GA wire for each daisy chain. Multiple daisy chains are wired color to color at the System Controller.
NOTE: Never use less than 18 GA wire on the 5 Wire Link.
Heat Setpoint – To read the heat cut-out setpoint, press the UP button
until “H” appears and then release. The number that follows is the heat cut-out setpoint. After a couple of seconds the leaving air temperature will be redisplayed. To change the setpoint, press the top or up button until the “H” is displayed, then immediately after the setpoint is displayed press and hold the UP/DN button till setpoint is at the desired value.
Auxiliary Heat Setpoint – For the SYCAP only, to read the auxiliary heat setpoint, press the UP and DN buttons simultaneously until “E” appears and then release. The number that follows is the auxiliary heat setpoint. After a couple of seconds the leaving air temperature will be redisplayed. To change the setpoint, immediately after the setpoint is displayed press and hold the UP/DN button till the setpoint is at the desired value.
CALIBRATION
The digital display normally displays the leaving air temperature of the internal thermometer. This thermometer is factory calibrated. If calibration is ever required, turn the Thermometer Calibrator clockwise to lower the temperature. Turn counterclockwise to raise.
FIVE WIRE LINK
41
WIRING THE ZONE DAMPER
For Duct Supplemental Heat Applications
K1 = RELAY DPDT
W Y
R C
RC
K1
DAMPER
MOTOR
B
K1 A
MC RO
TO FIVE
WIRE
LINK
SAIL OR PRESSURE
SWITCH
MAKE AND BREAK
ELECTRIC HEAT
CIRCUIT
NOTE: CONTACT "K1 A" IS ONLY REQUIRED FOR DUCT
HEATER APPLICATIONS TO FORCE DAMPER TO THE OPEN POSITION
Rd
G
Y
W
THERMOSTAT
1 STAGE COOL 2 STAGE HEAT
R
YW
1 W2 C
K1 B
TO
A/C UNIT
OR FURNACE
G
R
Time Clock Switch
RG
SWITCHING CENTER
OR
SYSTEM CONTROLLER
W
RC
C
Y
T-STAT
TRANSFORMER / FUSE SIZING
Transformer/fuse sizing:The 24V transformer
connected to TR1 and TR2 of the Switching Center/System Controller powers the zone dampers, zone thermostats and Switching Center/System Controller. The power rating of the transformer must be sufficient to power the number of dampers used. Also, a properly rated in line fuse must be used on the secondary of the transformer. To determine the power rating of the transformer and the amperage rating of the fuse, use the table above.
Note: If using both spring open and power open dampers, size as if all dampers are spring open.
NUMBER LOW PRESSURE MED. PRESSURE/HEAVY DUTY
OF (SPRING OPEN) DAMPERS (POWER OPEN) DAMPERS
DAMPERS XFMR PWR FUSE SIZE XFMR PWR FUSE SIZE
1 12 V A 1 AMP 6 V A 1 AMP 2 24 V A 2 AMP 12 VA 1 AMP 3 36 V A 2 AMP 18 VA 1 AMP 4 48 V A 3 AMP 24 VA 2 AMP 5 60 V A 3 AMP 30 VA 2 AMP 6 72 V A 4 AMP 36 VA 2 AMP 7 84 V A 5 AMP 42 VA 3 AMP 8 96 V A 5 AMP 48 VA 3 AMP
9 108 V A 6 AMP 54 VA 3 AMP 10 120 VA 6 AMP 60 V A 3 AMP 11 132 VA 7 AMP 66 V A 4 AMP 12 144 VA 7 AMP 72 V A 4 AMP 13 156 VA 8 AMP 78 V A 4 AMP 14 168 VA 9 AMP 84 V A 5 AMP 15 180 VA 9 AMP 90 V A 5 AMP 16 192 VA 10 AMP 96 VA 5 AMP 17 204 VA 10 AMP 102 VA 5 AMP 18 216 VA 11 AMP 108 VA 6 AMP 19 228 VA 11 AMP 114 VA 6 AMP 20 240 VA 12 AMP 120 VA 6 AMP
APPLICATION SCHEMATICS
TYPICAL SETBACK/SETUP WIRING FOR ALL SWITCHING CENTERS AND SYSTEM CONTROLLERS
For continuous fan operation in the occupied mode and intermittent operation during unoccupied periods, leave the System Controller/ Switching Center fan switch in the “ON” position.
Time Clock Switch:
Closed – Occupied Open – Unoccupied
42
TB1
TR2TR1 B W Y GRD
FUSED 24 VOLT
TRANSFORMER
TO ADDITIONAL ZONES
SYSTEM
CONTROLLER
YW1 W2
TO BASE BOARD CONTACTOR
**
*
DAMPER
RELAY
BOARD
NOTE:
FACTORY WIRED.
WYR CR
C MC RO
W2
BWYGR
dW2
R
C
THERMOSTAT 1 STAGE COOL 2 STAGE HEAT
(101DIGITS)
CENTRAL & AUXILIARY
BASE BOARD HEAT WIRING
H V A C
U N
I
T
SPDT, 24V
AC Relay
C
G
R
System Controller (101ASSB)
Switching Center (SYGE)
RG
W
4
2
5
1
3
APPLICATION SCHEMATICS
BLOWER FAN RELAY
If the heater does not turn on the indoor blower fan when heat is on, you must add a blower fan relay as shown below. The relay will energize the fan signal “G” when the heat signal “W” is energized.
*
The Blower Fan Mode (AUTO/ON) is usually selected at the System Controller/Switching Center. If preferred, the Fan Mode can be selected at one zone thermostat using this diagram. The thermostat needs to have a fan switch.
ECONOMIZER INTERFACE FOR SWITCHING CENTERS AND SYSTEM CONTROLLERS NOT UTILIZING THE CAPL-2 OR CAPL-4.
ECONOMIZER
ENTHALPY
CONTROL
COMPRESSOR
101ASSB
& SYGE
Y
Y Y
101CAPGE OR TRLAT ONLY
W
ZONE FAN CONTROL
C
R
WY W
2
TB2
WY G
R
Auto
On
ZONE THERMOSTAT
(SADIGI)
(101PROG)
Note: Leave the fan switch in the "AUTO" position at the Switching Center or System Controller.
101AACB-HP
ENTHALPY
CONTROL
ECONOMIZER
Y1
COMPRESSOR
#1
Y2
COMPRESSOR
#2
RELAY
SWITCHING CENTER
G
SYSTEM CONTROLLER
ECONOMIZER
BW
d
R
DAMPER
G
RELAY
Y
BOARD
W2
TB1
OR
ENTHALPY
CONTROL
AC UNIT
43
G
R
SYHPA
Y
SYCAP
Y Y
COMPRESSOR
SLAVING MULTIPLE DAMPERS
YRCRO MC RC W2
Rd B
WY
GW2
W
W
NC NC NC NC
NC
NC NC NC NC NC
NC
NC
TO THERMOSTAT: Wires used vary per application
FIVE
WIRE LINK TO
SWITCHING
CENTER
or
CONTROLLER
DAMPER #1
TB1
TB2
DAMPER #2
TB1TB2
DAMPER #3
TB1
TB2
SPDT RELAY
24 Volt
Transformer
DAMPER
MOTOR
#1
Size Transformer
12VA Per Spring Return Damper
and 6VA Per Power Open /
Power Close Damper
To
Additional
Dampers
NC
No connection
(- - - -) For power open / power close dampers only
YRC
RO MC RC
W2
Rd B
WY
GW2
W
W
YRCWW2
YRCRO MC RC W2
Rd B
WYGW2
W
W
Damper Relay
Board
Damper Relay
Board
Damper Relay
Board
NC NC NC NC
NC
NC NC
NC NC NC
NC
NC
For Controller Transformer. (Transformer connected to TR1 and TR2 of the Central Controller) add 6VA for each relay used.
1
1
LINE
VOLTAGE
24 V
R
HEATING/COOLING AUTO CHANGE OVER WITH DUCT STAT
Mechanical
Room Stat
Duct Stat set at
65 degrees
R
WY
Y
W
HEATING/COOLING AUTO CHANGE OVER WITH
RELAY
PARALLEL THE RELAY WITH GAS
VALVE W WIRE ON HEATER
W
Y
R
LINE
VOLTAGE
24 V.
STAT
B
W
Y
G Rd
W
YRC
RO MC RC
TB2
TB1
DAMPER
RELAY
BOARD
W2
W2 B
W
Y
G Rd
W
YRC
RO
MC
RC
TB2
TB1
DAMPER
RELAY
BOARD
W2
W2
C
C
*
*
* "C" Terminal used for electronic thermostats
COOLING ONLY DAMPER
Y
R
STAT
LINE
VOLTAGE
24 V.
B
WY
G Rd
WYRCRO MC RC
TB2 TB1
DAMPER
RELAY
BOARD
W2
W2
C
*
W
Each zone thermostat can control more than one damper. To determine when to use this application drawing, refer to Slaving Zone Dampers section on page 23.
PROPER BYPASS INSTALLATION WITH ECONOMIZER
When sizing a bypass damper, compute the system total air volume at 400 CFM/Ton and subtract the CFM of the smallest zone. The balance of the air can be bypassed at any one time. Refer to the Round and Rectangular damper CFM Charts. Choose the bypass closest to your CFM to bypass.
1. Outside Air Intake
2. Mixing Damper for Outside Air & Return Air
3. Pressure Relief of Outside Air from Building
4. Barometric Damper to Prevent Return Air Pressurization
5. Modulating Bypass Damper
WIRING A STAND ALONE DAMPER
When no system controller is used, use Zonex Systems’s Digital, Auto Changeover Stand Alone Modulating Thermostat (SAMOD) in con­junction with an ST Series round or rectangular damper.
Listed below are some non-modulating solutions to stand alone applications if it is not possible to use a SAMOD.
44
SYSTEM 1000/2000 TERMINAL DESCRIPTIONS
Daisy Chain, 5 or 6 Wire Link:
1. GD/G Hot wire, 24V. Hot when Switching Center/Controller TR1 is hot. For System 2000, turning Controller Power switch off will remove power from GD. The Power switch will not remove power from GD on System 1000.
2. BD/B 24V return (chassis ground). Measure all Daisy Chain voltages in reference to this terminal.
3. RD Hot when the Switching Center/Controller recognizes a thermostat call. Damper light on Switching Center/ Con­troller is on when RD is hot.
4. YD/Y Cool call, hot when cool call recognized by Switching Center/Controller. For System 1000: 5V to 16V (1 to 7 zones calling). For System 2000: 212 mv to 3.64V (1 to 20 zones calling). There should never be 24V on this terminal when the System 1000 Switching Center green light is on and the mode switch is at “Cool” or when the System 2000 Controller’s “Damper” and “Cool” lights are on. If there is, you have a short to either RD or GD.
5. WD/W Heat call, hot when heat call recognized by Switching Center/Controller. Voltages the same as for YD. There should never be 24V on this terminal when the System 1000 Switching Center green light is on and the mode switch is at “Heat” or when the System 2000 Controller’s “Damper” and “heat” lights ar on. If there is, you have a short to either RD or GD.
6. W2 Second stage heat call. 24V when second stage of zone thermostat is calling. Only used with System 1000 SYHPA.
Damper Relay Board:
1. TB2: a. MC
b. RC Run Closed. 24V when damper motor closing.
c. RO Run Open. 24V when damper motor opening.
d. R 24V hot. Same as GD.
e. C 24V return. Same as BD.
f. W Thermostat heat call. See below how to determine
g. Y Thermostat cool call. See below how to determine
h. W2 Second stage thermostat heat call. Same as W2 on
2. TB1: Daisy Chain. See Daisy Chain, 5 or 6 Wire Link above.
Motor common. Return for 24V damper motor(s). Motor voltages measured in reference to this termi­nal.
if a zone is calling.
if a zone is calling.
Daisy Chain.
SYSTEM 1000/2000 TROUBLE SHOOTING
To determine if a zone is calling:
On Damper Relay board, measure voltage from W to W and Y to Y (TB1 to TB2). If the voltage is at least 8 volts for System 1000 or 20 volts for System 2000, that zone is calling. If voltage is between W and W, zone is calling for heat. If between Y and Y, zone is calling for cool. To take this reading, RD must also be powered which means the Switching Center/Controller has recognized the call (Damper light on). Note: Do not test for a call by measuring the voltage from Y to C or W to C on TB2. The system utilizes pull up resistors which can give you false readings.
If Controller/Switching Center transformer fuse is blowing:
1. Check for short on five wire link between RD and B or between G and B.
2. Check for short on thermostats between R and C.
If Controller circuit board fuse is blowing (System 2000 only):
Make sure that the voltage between TR1 and TR2 is not less than 24 V or more than 30 V. If voltage is okay, replace Controller. If volt­age is not within range, be sure you have the correct transformer and that the primary voltage is adequate. If primary voltage is okay and transformer is correct size, replace transformer.
If Controller off circuit board fuse is blowing (System 2000 only):
You have a short on the five wire link between either Y and G, W and G, Y and Rd, or W and Rd.
If System 1000 SYHPA Switching Center circuit board fuse is blowing:
You have a short on the five wire link between either YD and GD, WD and GD, YD and RD or WD and RD.
45
Zonex Systems
System 2000
2-20 Zone Auto Changeover
System 1000
2-7 Zone Manual Changeover
Hot Line: (800) 228-2966
5622 Engineer Drive
Huntington Beach, CA 92649
Factory: (714) 898-9963 • Fax: (714) 898-6802
Visit our Web Site http://www.hvaccomfort.com
E-mail us at calecon@hvaccomfort.com
PATENTED PRODUCT Zonex Systems reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Copyright 2003 by Zonex Systems, Inc.
Zoning
Part #101ASIM
Rev. September 2003
Loading...