Zonefirst ZD Series, ZDSP, ZDBP User Manual

Page 1
©2017 ZONEFIRST® | 6 Aspen Drive – Randolph, NJ. 07869-1103 | Telephone: 201-794-8004 | Fax: 201-794-1359
www.zonefirst.com | info@zonefirst.com
Controlling Your Comfort Room by Room
The ZD series are extruded aluminum parallel blade dampers compete with a Power Open Power Close Plug-In Motor. These dampers are shipped complete and ready for installation. The lightweight ZD can be installed in any position in any properly sized duct. These dampers are rated for duct pressure up to
2.0” W.C.
Dampers are available all in even sizes from 8x8 to 36”x24. All dampers are 1/4” undersized from their listed size. Dampers are ordered as ZDSP for side mount, width by height, as the motor and end plate will be on the smaller dimension, for typical insertion into the side/shorter dimension of the duct. The ZDBP denotes bottom mount and is ordered height by width. The motor and end plate are on the longer dimension for typical insertion into either the bottom or top of the duct. Dampers are ordered as ZDSPwwhh or ZDBPhhww, using 2 digits for each dimension. All ZD dampers are shipped in the Open position ready for installation.
A 12 Volt DC damper motor, Model MP12M, powers the damper closed and open. The MP12M motor wires by simply plugging the motor in using the modular cord, supplied with each damper. The modular cord is a 25’ length of standard four (4) conductor telephone wire with RJ11 jacks on each end. The motor is complete with 2 jacks allowing you to daisy chain up to 10 dampers per zone.
The MP12M motor has been tested to over 1,000,000 cycles to provide long life. Even replacing the motor is a simple less than one (1) minute change by l oosening the setscrew holding the motor onto the damper, slide the motor off the damper shaft, place a new one on and secure with the screw.
The MP12M motor also has a two-color Light Emitting Diode (LED) to indicate the damper position. When the LED is GREEN the damper is Open. When the LED is RED the damper is Closed. When the LED is not lit the motor is typically moving between open and closed. The motor cycles between open and closed in less than 5 seconds
Actuator & 25’ of modular cord included with each damper
Minimum Position Adjustment
Simply open the cover to minimum position setting. With a screwdriver, loosen the setscrew and adjust your setting to desired
position.
ZONE DAMPER
With MP12M Plug-In Motor
Model: ZDSP & ZDBP
ZDSP Side
Mount
ZDBP-Bottom Mount
Dimensional Drawing (nominal)
Damper Specifications
Construction – Aluminum Mill Finish, Mitre Angles
Linkage – Zinc plated linkage arms, Delrin bushings
Dimensions – 8”x8” to 36”x24” in 2” increments, 1/4” undersized.
Custom sizes also available
Motor Voltage – 12VDC, 0.100A
Torque – 7.0 in/lbs, 112.0 in/oz, 0.79NM
Temperature Rating - 0 F to 150 F Operating, -13 F to 150 F Storage
Humidity – 5% to 95% Non-Condensing
Damper Timing – Nominal 5 Sec. Powered Open-Closed \
Connection - Modular RJ11, 2 Ports
Duct Pressure – Maximum 2”W.C.
Page 2
©2017 ZONEFIRST® | 6 Aspen Drive – Randolph, NJ. 07869-1103 | Telephone: 201-794-8004 | Fax: 201-794-1359
www.zonefirst.com | info@zonefirst.com
NOT USED POSITIVE (+)
NEGATIVE (-)
POSITIVE (+) NOT USED
-12VDC
VDC
-12VDC
NOT USED POSITIVE (+)
NEGATIVE (-)
POSITIVE (+) NOT USED
+12VDC
VDC
+12VDC
INSTALLATION
1. Cut a 4-inch (102-millimeter) opening in one side of the air
duct at the location selected. Ensure the opening is cut fully to the top and bottom air duct seams.
2. Slide the damper into the cut opening of the air duct. Ensure the electric actuator is mounted toward the top of the air duct.
3. Secure the damper mounting plate to the air duct with the sheet metal zip screws provided.
Side Mount:
CHECKOUT
To checkout the operation of the dampers the control panel needs to be operating. I t is recommended that each damper be checked before installing into the duct.
To check the damper, plug the damper into a zone on the control panel. Each zone of the panel has an LED that will be Green when the damper is to be open. When the panel LED is off, the damper will close and the damper LED will turn RED.
All dampers are 100% factory tested with the cord provided with each damper.
OPEN CLOSE
The damper shaft is square however the motor has a small triangular shape that also indicates the position of the damper. If the LED does not light, this will indicate the damper is either opening or closing. The damper may be closed and the LED not lit Red as the damper may have stopped short of full closed due to the roundness of the damper.
Bottom Mount:
TROUBLESHOOTING
If the damper LED does not light and the motor is not moving when plugged into the control panel, unplug and retry plugging in again. Until the motor moves and the LED lights. Make sure the cord is not pinched or broken.
The motor is powered by 12VDC from the panel. Check the connector on the panel for 12VDC as shown below.
MOTOR
PLUG
The power to the dampers can be checked with a voltmeter measuring 12VDC. Check the
and any wire the same way by checking the inside negative pair of wires with the outside positive pair of wires.
+12VDC
VDC
-12VDC
VDC
POSITIVE (+)
NEGATIVE (-)
POSITIVE (+) NOT USED
DAMPER OPEN
MOTOR
PLUG
NOT USED POSITIVE (+)
NEGATIVE (-)
POSITIVE (+) NOT USED
DAMPER CLOSED