Zodiac Pool Systems Legacy LRZ Millivolt Installation And Operation Manual

Installation and Operation Manual
Legacy™ Pool and Spa Heater
Model LRZ Millivolt
INSTALLATION AND
OPERATION MANUAL
ENGLISH
Natural Gas or LPG
WARNING
FOR YOUR SAFETY: This product must be installed and serviced by a contractor who is gas safe registered and HWB1 certified. Before installing this product, read and follow all warning notices and instructions that accompany this product. Failure to follow warning notices and instructions may result in property damage, personal injury, or death. Improper installation and/or operation can create carbon monoxide gas and flue gases which can cause serious injury, property damage, or death. For indoor installations, as an additional measure of safety, Zodiac Pool Systems, Inc. strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces. Improper installation and/or operation will void the warranty.
WARNING
The GAS SAFETY (INSTALLATION AND USE) REGULATIONS 1998 as amended, place statutory requirements on gas users.
This heater is certified to European requirements for use only as a swimming pool or spa heater. The heater must not be used for any other purpose and must be installed and serviced by a qualified professional. The heater must be operated strictly in accordance with the user's instructions and applicable laws.
If the heater is installed in a room, it must be separated from a living space, and adequate air supply and ventilation must be provided and maintained.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
If these instructions are not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
Read this manual in its entirety. If these instructions are not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
H0316500 Rev F
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Table of Contents
ENGLISH
Page 3
Section 1. General Information .................... 5
1.1 Introduction .................................................... 5
1.2 Consumer Information and Safety ................. 5
1.2.1 Spa/Hot Tub Safety Rules ........................ 5
1.2.2 Swimming Pool Energy Saving
Tips ........................................................... 6
1.3 Warranty ........................................................ 6
1.4 Codes and Standards .................................... 6
1.5 Technical Assistance ..................................... 6
1.6 Materials Installer Must Provide .................... 6
1.6.1 Materials for All Applications ..................... 6
1.6.2 Materials for Special Applications ............. 6
1.7 Specications ................................................ 7
1.7.1 GeneralSpecications .............................. 7
1.7.2 PerformanceSpecications ...................... 7
1.7.3 Dimensions ............................................... 7
Section 2. Installation Instructions .............. 7
2.1 Introduction .................................................... 7
2.2. Statutory Information ..................................... 8
2.3 General Installation Requirements ................ 9
2.4 Field Assembly ............................................. 9
2.5 Location Requirements ................................. 9
2.5.1 Introduction ............................................... 9
2.5.2 Clearances ............................................... 9
2.5.3 Flooring ..................................................... 10
2.5.4 Outdoor Installation .................................. 10
2.5.5 Indoor for Natural Gas Installation
Only .......................................................... 11
Section 5. Water Connections ...................... 14
5.1 Water Piping .................................................. 14
5.2 Hydraulic Head Loss ..................................... 14
5.3 Check Valve Installation ................................ 14
5.4 Automatic Flow Control Valve ....................... 14
5.5 Reversible Water Connections ...................... 15
5.6 Connections at Heater ................................... 17
5.7 Pressure Relief Valve .................................... 17
5.8 Auxiliary Components, Chlorinators, Ozone
Generators, and Sanitizing Chemicals .......... 19
Section 6. Electrical....................................... 19
6.1 Main Power ................................................... 19
6.2 Earth Bonding ................................................ 19
6.3 Auxiliary Time Clock Wiring ........................... 20
Section 7. Commissioning ............................ 21
7.1 Heater Start-Up ............................................. 21
Section 8. Operating Instructions ................ 21
8.1 Normal Operation .......................................... 21
8.2 Start-Up ......................................................... 22
8.3 Lighting and Shutdown Procedures .............. 22
8.3.1 Lighting the Heater ................................... 22
8.3.2 Relighting the Heater ................................ 24
8.3.3 Shut-Down Procedure .............................. 24
8.4 Turning the Heater On/Off and
Setting the Temperature Control ................... 24
Section 3. Venting.......................................... 11
3.1 Combustion Air Supply .................................. 11
3.2 Flue System Type B11 (Indoor) ..................... 11
3.3 Vent Pipe Sizing and General Installation .... 12
3.3.1 Outdoor Installations ................................. 12
3.3.2 Indoor Installations (Natural Gas ONLY) .. 12
3.3.3 Inspection and Replacement of Existing
Vent System with New Components ........ 13
Section 4. Gas Connections ......................... 13
4.1 Gas Supply and Piping .................................. 13
4.2 Burner Pressure ............................................ 14
4.3 Special Precautions for LPG ......................... 14
Section 9. Maintenance ................................. 25
9.1 Water Chemistry ............................................ 25
9.2 Seasonal Care ............................................... 25
9.2.1 Spring and Fall Operation ......................... 25
9.2.2 Winterizing ................................................ 25
9.2.3 Spring Start-up ......................................... 26
9.3 Inspection and Service .................................. 26
9.3.1 Owner Inspection ...................................... 26
9.3.2 Professional Inspection ............................ 26
Section 10. Troubleshooting ........................ 28
10.1 General Heater Troubleshooting ................... 28
Page 4 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Table of Contents (Continued)
Section 11. Professional
Maintenance and Service ........ 30
11.1 General Information ....................................... 30
11.2 Natural-Draft Combustion System ................. 30
11.3 Heater Components and Their Operation ..... 30
11.4 Electrical Troubleshooting ............................. 31
11.4.1 Gas Valve ................................................. 31
11.4.2 Pilot Generator ......................................... 33
11.4.3 Fusible Link .............................................. 33
11.4.4 Fireman Switch and External ...................
Interlocks .................................................. 33
11.4.5 Limit Switches ........................................... 34
11.4.6 Water Pressure Switch ............................. 34
11.4.7 Temperature Control Circuit ...................... 34
11.4.7.1 ON/OFF Toggle Switch ..................... 34
11.5 Adjusting the Water Pressure Switch ............ 35
11.6 Temperature Rise .......................................... 35
Section 12. Replacement Parts .................... 36
12.1 Ordering Information ..................................... 36
12.2 Parts List ....................................................... 37
12.3 General Exploded View ................................. 38
12.4 Detailed Exploded View ................................ 39
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 5
Section 1. General Information
1.1 Introduction
This manual provides installation and operation instructions for the Legacy Model LRZ millivolt pool and spa heaters. Read these installation and operation instructions completely before proceeding with the installation. The installation must be conducted by a
qualied professional. While the entire manual should be read by both the qualied professional installer
and the user, Sections 2 through 7 of this manual are
intended for the qualied professional installer. The
Operating instructions for the user begin in Section 8. Consult the Zodiac factory, or local factory representa­tive, with any questions regarding this equipment. The instructions cover two (2) types of heaters as follows:
1. Type A (ueless) for outdoor installations only.
2. Type B11 ue for outdoor and indoor installations,
but must not be installed in a living space.
The Legacy model LRZ millivolt heater is a self contained standing pilot unit and requires no external power.
The Legacy Model LRZ millivolt heater
is specically designed for heating fresh water
swimming pools and spas, and with proper installation and care, will provide years of reliable service. Do not use the heater to maintain pool or spa water tempera­ture below 21°C (70°F). Do not use it as a heating boiler or general service water heater. Consult your dealer for the appropriate Zodiac products for these applications.
NOTE “Fresh water swimming pools and spas”
include systems that utilize saltwater chlorine generator units, such as the Jandy AquaPure® Electronic Chlorine Generator. Please ensure that the salt content of the pool/spa does not
exceed4000ppmandwaterowrateiswithin
110-470 lpm.
1.2 Consumer Information and Safety
The Legacy Model LRZ millivolt heater is designed and manufactured to provide many years of safe and reliable service when installed, operated and maintained according to the information in this manual and the installation codes referred to in later sections. Throughout the manual safety warnings and cautions
are identied by the "
comply with all of the warnings and cautions.
1.2.1 Spa/Hot Tub Safety Rules
Elevated water temperature can be hazardous. Consult heater operation and installation instruc­tions for water temperature guidelines before setting temperature.
" symbol. Be sure to read and
WARNING
1. Spa or hot tub water temperature should never exceed 40°C (104°F). Thirty-eight degrees Celsius (38°C [100°F]) is considered safe for a healthy adult. Special caution is recommended for young children.
2. The drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could lead to unconsciousness, and subse­quently result in drowning.
3. Pregnant women take note! Soaking in water above 38.5°C (102°F) can cause fetal damage
during the rst three (3) months of pregnancy
(which could result in the birth of a brain­damaged or deformed child). If pregnant women are going to use a spa or hot tub, they should make sure the water temperature is below 38°C (100°F) maximum.
4. The water temperature should always be checked with an accurate thermometer before entering a spa or hot tub. Temperature controls may vary by as much as 1°C (1°F).
5. Persons with a medical history of heart disease, diabetes, circulatory or blood pressure problems should consult their physician before using a hot tub or spa.
6. Persons taking any medication which induces drowsiness (e.g., tranquilizers, antihistamines, or anticoagulants) should not use spas or hot tubs.
7. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experi­ence and knowledge, unless they have been given supervision or instruction concerning use of appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
8. Prolonged immersion in hot water can induce hyperthermia.
Hyperthermia occurs when the internal body
temperature reaches a level several degrees above the normal body temperature of 37°C (98.6°F). Symptoms include dizziness, fainting, drowsiness, lethargy, and an increase in the internal body temperature. The effects of hyperthermia include:
Lack of awareness of impending hazard
Failure to perceive heat
Failure to recognize need to leave spa
Physical inability to leave spa
Fetal damage in pregnant women
Unconsciousness resulting in a danger of
drowning
Page 6 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
1.2.2 Swimming Pool Energy Saving Tips
Zodiac Pool Systems, Inc., ("Zodiac") offers the
following recommendations to help conserve fuel and minimize the cost of operating your pool heater
without sacricing comfort.
1. The American Red Cross recommends a maximum water temperature of 25°C (78°F).
Use an accurate pool thermometer. A difference
of 2°C (4°F), between 26°C and 28°C (78°F and 82°F), will use as much as 40% more gas.
2. Carefully monitor the water temperature of your pool in the summertime. You can reduce heater usage due to warmer air temperatures.
3. Find the proper setting on the pool heater temper­ature control and use the Set Point Lockout feature to discourage further adjustments.
4. Set the pump time clock to start the pump no earlier than 6:00 AM during the pool heating season. This is the time when nightly heat loss balances.
5. If the pool is only going to be used on weekends, reduce the heater temperature control setting by 8 or 10 degrees during the week. Reset it to the 25°C (78°F) level a day or so before you plan to use the pool.
6. During the winter or when on vacation for longer than a week, shut down the heater by following the shutdown instructions found on the inside of the heater.
7. Where possible, shelter the pool from prevail­ing winds with well-trimmed hedges or other landscaping, cabanas, or fencing.
8. Always use a pool cover when practical. Besides providing a valuable safety feature, a pool cover will reduce heat loss, conserve chemicals, and
reduce the load on lter systems.
1.3 Warranty
The Legacy Model LRZ millivolt heater is sold
with a limited factory warranty. Details are specied
on the back cover of this manual.
Make all warranty claims to an authorized Zodiac
representative or directly to the factory. Claims must include the heater serial number and model (this infor­mation can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
The warranty does NOT cover damage caused
by improper assembly, installation, operation or eld modication. Also, damage to the heat exchanger by
corrosive water is NOT covered by the warranty. See Section 9.1 for maintaining proper pool water chemistry.
NOTE Keep this manual in a safe place for future reference when inspecting or servicing the heater.
1.4 Codes and Standards
The Legacy Model LRZ millivolt heater has
been tested and certied by GL Industrial Services for compliance with the Gas Appliance Directive (GAD;
2009/142/EC) and the latest version of European Standard, BSEN 656. In addition, the product has also been found to be in compliance with the essen-
tial requirements of the Low Voltage Directive (LVD;
2006/95/EC), and the Electromagnetic Compatibility
Directive (EMC Directive; 2004/108/EC).
All Zodiac heaters must be installed in accor­dance with the local building and installation codes as per the utility or authorities having jurisdiction.
Any changes to the heater, gas controls, gas
orices, wiring, draft hood, vent cap, or improper
installation may void the warranty. If change is required to any of the above, consult the factory.
1.5 Technical Assistance
Consult your local Zodiac distributor with any
questions or problems involving the specications,
installation, and operation of your Zodiac equipment.
1.6 Materials Installer Must Provide
1.6.1 Materials for All Applications
The following items are needed and are to be supplied by the installer for all Legacy Model LRZ millivolt heater installations:
1. The correct size gas pipe to supply gas from the
meter to the heater (see Section 4.1).
2. A manually operated gas cock to be installed in
the gas line outside of the heater jacket.
3. Plumbing items needed to provide a sediment
trap (drip leg) in the gas line between the manual
gas cock and the heater (see Section 4.1).
1.6.2 Materials for Special Applications
In addition to the items listed above, the follow-
ing items are needed for special applications:
1. A factory authorized draft hood and any vent pipe needed for indoor installations. See Section
3.3.2. Draft hoods are available from any Zodiac distributor.
2. Primer and cement suitable for cementing PVC pipe to the CPVC Zodiac unions supplied with the heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 7
3. A noncombustible platform for installation
Section 2. Installation Instructions
on combustible surfaces (see Section 2.5.3). Noncombustible bases are available from your
2.1 Introduction
Zodiac distributor.
4. A factory approved vent cap for all outdoor installations where wind conditions may cause downdrafting. Approved vent caps are available from your Zodiac distributor. See Section 12.2,
"Parts List", of this manual for the correct part
number.
1.7 Specications
1.7.1 GeneralSpecications
1. Installation Location:
Certied for use: Natural Gas: Indoor and Outdoor LPG: Outdoor Only
Refer to Table 1.
2. Minimum Clearance From Combustible Material
See Table 4.
1.7.2 PerformanceSpecications
The Legacy Model LRZ millivolt heater perfor-
mance specications are shown in Table 2.
1.7.3 Dimensions
This product must be installed and serviced by a
contractorwhoislicensedandqualiedinpool
equipment. Improper installation or maintenance can cause nausea or asphyxiation from carbon
monoxideinuegaseswhichcouldresultinsevere
injury, or death. For indoor installations, as an ad­ditional measure of safety, Zodiac strongly recom­mends installation of suitable Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces. The heater may only be installed in a room which complies with the appro­priate ventilation requirements and which is sepa­rate from living areas.
Install the Legacy Model LRZ millivolt heater, vent caps and draft hoods in accordance with the procedures in this manual, local codes and ordinances, and in accordance with the latest edition of the appro-
priate national code (see Section 1.4 "Codes and Standards").
All gas-red products require correct installation
to assure safe operation. The requirements for pool heaters include the following:
1. Field assembly (if required)
WARNING
2. Appropriate site location (clearances) and ooring
See Figure 1 for a diagram showing the heater's
exterior dimensions and dimensions to critical connec-
3. Sufcient combustion and ventilation air
4. Properly sized gas meter and piping
tions on the heater.
Table1.GeneralSpecications
LRZ
125 175 250 325 400
Water Capacity (L) 0,81 0,95 1,16 1,35 1,57
Minimum Water Flow (l/min) 75,7 75,7 94,6 113,6 113,6
Maximum Static Head (bar) 5,1 5,1 5,1 5,1 5,1
Maximum Outlet Temp (C) 40 40 40 40 40
Dry Weight (kg) 60 67 78 88 100
Gas Connection 3/4 in Bsp
Water Inlet Connection 2" unthreaded PVC
Water Outlet Connection 2" unthreaded PVC
Electrical Supply
IP Rating IPX4
Flue Types Flue Type A (Flueless) for Outdoor Installations Only
Appliance Category: Natural Gas I2H LPG I3P
Inlet Pressure (mbar) Natural Gas G20 LPG G31 @ 37 mbar
Note: The LPG heat inputs apply up to an altitude of 600 m. Above this altitude, de-rate the heat input by 4% for every 300 m.
(Rc 3/4)
or CPVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
Flue Type B11 (with Vent Cap for High Wind Areas) For Outdoor Installation Only
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
Flue Type B11 (with Draft Hood) for Indoor Installation Only
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
Page 8 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
1041 mm
1000 mm
A
Outdoor Flueless Heater Configuration Indoor Open Flue Configuration with Draft Hood
Heater Width
Model
125 384 150 441 413
175 460 150 457 613
250 578 175 464 641
325 683 200 479 673
400 822 230 546 699
Dim "A"
mm mm mm mm
Vent Diameter
194 mm
333 mm
95 mm
Venting Dimensions
Dimension "H"
406 mm
127 mm 203 mm
Outdoor Flue Configuration with Vent Cap
Outdoor
264 mm
Indoor
Dimension "H"
H
724 mm
Figure1. GeneralConguration
5. Proper electrical wiring (if required)
6. Adequate water ow
This manual provides the information needed to meet these requirements. Review all application and installation procedures completely before continuing the installation.
2.2. Statutory Information
It is the law that all gas appliances are to be installed only by competent persons (e.g., registered
members of Gas Safe) in accordance with the Gas Safety (Installation and Use) Regulations, latest
published version of BS6798, BS5440 Pt. 1 and Pt. 2, BS6891, and BS5482 Pt. 2. Failure to install appliances correctly could lead to prosecution.
The Legacy heater, as supplied, has been tested
and certied by Gas Appliance Directive (GAD;
2009/142/EC) and the latest version of European
Standard, BSEN 656 for use with natural and LPG
gases. Legacy heaters are only permitted to be installed
in the open air or in a room which is separated from living rooms and provided with appropriate ventilation directly to the outside.
WARNING
TheLegacyheateriscertiedtoEuropeanrequire­ments for use only as a swimming pool or spa heater. The Legacy heater must not be used for any other purpose and must be installed and serviced
byaqualiedprofessional.TheLegacyheatermust
be operated strictly in accordance with the manufac­turer's instructions. If the Legacy heater is installed in a room, adequate air supply and ventilation must be provided and maintained. Never store any materials within the area of the heater or ventilation openings.
It is important that no external control devices
(e.g., ue dampers, economizers, etc.) be directly
connected to the Legacy heater unless covered by these installation and servicing instructions or other-
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Table2.LRZMPerformanceSpecications
LRZ M Size (In BTU Input)
125 BTU 175 BTU 250 BTU 325 BTU 400 BTU
Nat. Gas
Heat Input Gross (kW) 40,7 40,7 56,9 56,9 81,5 81,5 105,9 105,9 130,3 130,3
Heat Input Net (kW) 36,7 36,7 51,3 51,3 73,4 73,4 95,4 95,4 117,4 117,4
Heat Output (kW) 28,6 28,6 41,1 41,1 58,7 58,7 76,8 76,8 95,1 95,1
Max. Burner Pressure (mbar)
3
Gas Rate (m
Gas Rate (m
Flue Gas Volume
4.5% CO2, 120C (l/sec) 32,1 -- 44,9 -- 64,1 -- 83,9 -- 102,8 --
Flue Gas Volume
4.5% CO2, 120C (l/sec) G30 -- 32,3 -- 45,3 -- 70,3 -- 91,4 -- 106,4
Injector Diameter (mm and marking)
/h) G20 3,5 -- 4.9 -- 7 -- 9,1 -- 11,2 --
3
/h) G30 -- 1,05 -- 1,48 -- 2,3 -- 2,99 -- 3,47
9 22,4 9 22,4 9 22,4 9 22,4 9 22,4
(2,26)
Marked
43
LPG
(1,51)
Marked
53
Nat. Gas
(2,26)
Marked
43
LPG
(1,51)
Marked
53
Nat. Gas
(2,26)
Marked
43
LPG
(1,51)
Marked
53
ENGLISH
Nat. Gas
(2,26)
Marked
43
LPG
(1,51)
Marked
53
Page 9
Nat. Gas
(2,26)
Marked
43
LPG
(1,51)
Marked
53
wise recommended in writing by Zodiac, if in doubt please ask. Any direct connection of a control device
not approved by Zodiac, could invalidate the Gas Appliance Directive (GAD) certication, the normal
Legacy heater warranty, and could also violate appli­cable gas safety regulations.
2.3 General Installation Requirements
The Legacy heater must be installed by compe-
tent persons (e.g., registered member of Safe Gas).
The Legacy heater must be installed in accordance
with the relevant requirements of the Gas Safety Regulations, current I.E.E. Regulations, Model Water Bylaws, local Water Authority Bylaws, and any
relevant requirements of local gas region, local author­ity, and relevant British Standard Codes of Practice and Building Regulations.
2.4 Field Assembly
The Legacy Model LRZ millivolt heater is
shipped from the factory with the top assembly in
the low-prole ueless Type A conguration for
outdoor installation. The Legacy Model LRZ millivolt
heater is design certied for indoor installation when equipped with a draft hood and Type B11 ue, which must be installed without modication.
Check the rating plate on the heater or the Parts List (Section 12) of this manual for the correct Zodiac draft hood or vent cap part number. See instructions supplied with the draft hood or vent cap for instal-
lation and attachment. When the draft hood is used,
locate the heater so as to be in the same atmospheric pressure zone as the combustion air inlet to the heater.
2.5 Location Requirements
2.5.1 Introduction
CAUTION
When pool equipment is located below the pool surface, a leak from any component can cause
largescalewaterlossorooding.Zodiaccannotbe responsibleforsuchwaterlossoroodingorresult-
ing damage.
The Legacy Model LRZ millivolt heater may be installed indoors or outdoors as outlined in later sections. Location of the heater below or above the pool water level affects operation of its water pressure switch. See sections on water piping and heater start­up for more information about this.
Avoid placing the heater in locations where it can cause damage by water or condensate leakage. If this is not possible, provide a suitable drain pan to catch and divert any leakage. The pan must not restrict the
air ow around the heater.
All criteria given in the following sections
reect minimum clearances as stated in the national
standards. However, each installation must also be evaluated, taking into account the prevailing local conditions such as wind speed and direction, proxim­ity and height of walls that may block ventilation, and proximity to public access areas.
2.5.2 Clearances
The heater must be placed to provide clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces (see Table 3).
Page 10 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
At least 457 mm access must be available in front of the heater for burner removal and access to the igniter.
If the heater is to be installed in a garage, or similar structure, all burners and burner ignition devices must have a minimum 457 mm clearance
above the oor.
This heater must be installed at least 1.52 m from the inside wall of a pool unless the heater is separated from the pool by a solid fence, wall or other permanent solid barrier.
2.5.3 Flooring
The heater must be installed on a level surface
of noncombustible construction or on re-resistant slabs or arches. Noncombustible ooring is dened as ooring material and surface nish not capable of
being ignited and burning and with no combustible materials against the underside. Acceptable materials are those consisting entirely of a combination of steel, iron, brick, tile, concrete, slate, glass or plaster. Do not install the heater directly on a combustible wood or
carpet oor without placing a noncombustible platform between the oor and the heater.
The heater can be installed on a combustible oor
if a noncombustible base assembly, available from Zodiac, is used. See the heater rating plate or the Parts List (Section 12) of this manual for the appropriate base part number. Heaters must never be installed
directly on carpeting.
As an alternative to the Zodiac noncombustible base plate, the heater may be placed on a combustible surface when there is a platform under the heater made of hollow masonry no less than 102 mm thick, covered with sheet metal at least 24 gauge thick and extend­ing beyond the full width and depth of the heater by at least 153 mm in all directions. The masonry must be laid with ends unsealed, and joints matched to provide free circulation of air from side to side through the masonry (see Figure 2). If the heater is installed in a
carpeted alcove, the entire oor of the alcove must be
covered by a noncombustible panel.
2.5.4 Outdoor Installation
The Legacy Model LRZ millivolt heater can be installed in the low-prole Type A ueless congu­ration as received from the factory. Alternately, the heater may be installed outdoors using a Type B11 vent cap. This vent cap is used in high wind installa­tions. No draft hood is required for this type of outdoor installation.
Locate the heater in an open, unroofed area. Do not install the heater under a deck. Do not locate the heater below or adjacent to any doors, glass openings, louvers, grills, etc., which connect in any way with an inhabited area of a building, even though the access might be through another structure (e.g., a garage or utility room). There must be a minimum of 2 m horizontally or 2 m vertically between the heater and any door, glass opening, or gravity inlet into a build­ing. See Figure 3.
The top surface of the heater must be at least
0.91 m above any forced air inlet, or intake ducts located within 3.0 m horizontally.
If the heater is installed under an overhang, there must be a minimum clearance of 1.5 m above the top of the heater and the structure should not overhang the heater more than 0.30 m. The area under the overhang must be open on three (3) sides. This prevents combus­tion gases from being diverted into living areas through doors, windows, or gravity inlets.
Sheet Metal Min. Thickness 24 Ga
Table 3. Minimum Heater Clearances
From Combustible Surfaces
SIDE OF HEATER MINIMUM CLEARANCE
Millimeters
BLANK 203
REAR 150
PIPING 355
TOP 1120
FRONT 457
Note: Clearances listed in Table 4 are manufacturer's tested
values. These are given as minimum values. Where local
codes apply, and values are different than those listed in Table 4, use the greater value to ensure safe operation.
Hollow Concrete Block Platform
153mm
Notes:
1. Blocks must provide a solid base and be braced so they cannot slip out of place.
2. Air openings in blocks must be arranged to provide un­restricted opening through entire width or length of base.
3. Sheet metal must be at least 24 ga. and extend 153 mm beyond the heater jacket on all sides.
Figure 2. Noncombustible Platform
153mm
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
2m
2m
2m
ENGLISH
Page 11
If the heater is installed close to a structure, protect it from rain water runoff with rain gutters on the roof or other measures. Do not locate the heater near irrigation sprinkler systems that could spray water
on it. Water from sprinklers may cause damage to
controls and electronic components.
Avoid locations where wind deection off nearby structures might cause downdraft conditions. Where
downdraft conditions exist, locate the heater at least
0.91 m from vertical surfaces (e.g., nearby buildings and walls).
2.5.5 Indoor for Natural Gas Installation Only
The Legacy heater can be installed indoors using
the draft diverter available from Zodiac, and a Type
B11 ue system complying with the national and
local applicable standards in addition to the Building Regulations (see Section 2).
Section 3. Venting
The applicable codes, standards and Zodiac, require that the heater be properly vented as outlined in this manual. Proper ventilation of exhaust and
combustion air are essential for the safe and efcient
operation of the heater.
3.1 Combustion Air Supply
The heater location must provide sufcient air
supply for proper combustion and ventilation of the surrounding area.
In general, the room in which a heater is installed should be provided with two (2) permanent air supply
openings; one within 305 mm of the ceiling, the other within 305 mm of the oor. All indoor installations
must have uninterrupted openings to outside air for
combustion, ventilation, and dilution of ue gases
from inside the building (see Figure 4 and Table 4). Zodiac, does not recommend indoor installations that do not provide combustion air from outside the build­ing.
Figure 3. Outdoor Heater Installation
Table 4. Ventilation Requirements
Positions of Air Vents Air Vent Areas
(Air Direct From Outside)
2
High Level 270 cm
excess of 60 kW total rated input
Low Level 540 cm
excess of 60 kW total rated input
plus 2.25 cm2 per kW in
2
plus 4.5 cm2 per kW in
Exhaust Fans or Vents: Any equipment which exhausts air from the room where the heater is installed can deplete the combustion air supply or reverse the natural draft action of the venting system.
This could cause ue products to accumulate in the
room. Additional air must be supplied to compensate for such exhaust.
The information in Table 3 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by quali-
ed engineers.
The heater must be completely isolated and protected from any source of corrosive chemical fumes such as those emitted by trichlorethylene, perchloro­ethylene, chlorine, etc.
WARNING
Do not store any chemicals, cleaners, or other cor­rosive material near combustion air openings or in the room. Avoid locating appliance vents in the vi­cinity of combustion air openings. Failure to prevent corrosive materials from mixing with combustion air can result in reduced heater life and unsafe heater operation.
3.2 Flue System Type B11 (Indoor)
Connect the draft diverter to a Type B11 ue
system of at least the same diameter, and end at least
0.6 meters above the highest point of the roof or other object that is within 3.05 m of the vent. Install a certi-
ed terminal which allows a full equivalent opening for ue products (see Figure 4). There must be at least 600 mm of vertical ue above the drafthood. Bends in the ue should not exceed 45° to the vertical.
To make sure the heater operates safely and satis-
factorily, the ue system must be able to completely
remove combustion products at all times. The number
of bends and lengths of horizontal ue pipe used
should be kept to a minimum in order to reduce gas
ow resistance.
Compliance with all national and local applicable installation codes and regulations should be strictly observed.
The ue design should avoid the formation of
excessive quantities of condensate. For this reason, it
is recommended that all ues be insulated and lined.
For brick or similar structures, a stainless steel rigid
or exible ue liner (Grade 304/316) may be used in
conjunction with a 50 mm (minimum) thick layer or
Page 12 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
vermiculite or perlite granules between the liner and the inner skin of the chimney body.
Liners should be sealed at both top and bottom.
Drainage points should be provided at the bottom of
all vertical ue sections. Drain pipes should be:
1. No less than 25 mm inside diameter.
2. Made from acid condensate resistant material (e.g., stainless steel).
3. Positioned so that pipe runs and discharge points
are not subject to the effects of frost and ue
gases cannot leak into the boiler room.
3.3 Vent Pipe Sizing and General
Installation
3.3.1 Outdoor Installations
For outdoor installations, exhaust venting consid-
erations will determine the placement of the heater (See Section 2.5.4). If the heater cannot be placed so as to meet the requirements stated in Section 2.5.4, a Type B11 vent pipe and cap may be added to the heater to move the exhaust vent opening to a position
that complies with the requirements. When the heater
is installed in areas of high wind or when unavoidably installed near a vertical obstruction where downdraft­ing may occur, it may be desirable to add a vent cap directly to the top of the heater. In all cases, vent pipes and caps must be of the same diameter as the exhaust outlet of the heater. Approved vent caps may be obtained through your Zodiac distributor.
VENT TERMINATED AT LEAST 600 mm ABOVE ANY OBJECT WITHIN 3.1 m
3.1 m
LISTED FLUE TERMINAL
3.3.2 Indoor Installations (Natural Gas ONLY)
WARNING
Vent pipe diameter must be as required by appli­cable local gas appliance installation codes such as BS 5440. Undersized pipe can result in inadequate venting and oversize pipe can result in vent conden­sation. In either case the result can be release of combustion products to the indoors. This can cause serious injury or death by carbon monoxide poison­ing or asphyxiation.
All indoor installations and outdoor shelter installations require a factory approved draft hood and Type B11 venting. The draft hood must be installed
without modication. All vent installations must be
made in accordance with all local, state or provincial codes and with:
Avoid long horizontal runs of the vent pipe, and 90° elbows, reductions and restrictions. Horizontal runs should have at least a 20 mm rise per meter in the
direction of ow.
Avoid terminating heater vents near air condi­tioning or air supply fans. The fans can pick up
exhaust ue products from the heater and return them
inside the building, creating a possible health hazard.
Do not locate the vent terminal where ue
products could strike against building materials and cause degradation.
Vent opening should be well away from trees
or other obstructions that would prevent free air ow
to and from vent terminal. Do not terminate the vent under decks, stairways, or car ports.
Be sure to support all venting so that connec­tions will not separate and so that the weight of the vent pipe does not rest on the heater draft hood. All connections should be made with rustproof sheet metal screws. Do not weld or fasten the vent pipe to the heater draft hood. The draft hood and heater top must be easily removable for normal heater service and inspection.
6.35 mm minimum pitch per meter of horizontal pipe
NOTE
Use approved roof jack.
Figure 4. Indoor Installation Venting or Outdoor Shelter Venting
AT LEAST 600 mm OF VERTICAL FLUE ABOVE THE DRAFT HOOD
NON-COMBUSTIBLE
BASE
BENDS SHOULD NOT EXCEED 45°
DRAFT HOOD
4)
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 13
The draft hood outlet is to be connected to an unobstructed vent pipe of the same diameter, terminat­ing outside the building. The vent must terminate at least 0.6 m above the highest point of the roof or other object that is within 3.05 m of the vent termination. The vent pipe must have a listed vent cap which allows
a full equivalent opening for ue products (see Figure
4). The top of the vent cap must be at least ve (5) feet
in vertical height above the draft hood outlet.
Double wall or equivalent vent pipe is recom­mended.
IMPORTANT NOTE: Do not use sheet metal screws at
the snap lock joints of gas vents.
When venting multiple appliances through one
common duct, each appliance must have its own vent temperature limit switch. All vent limit switches must be wired in series so as to prevent any appliance from
ring in the event of a blocked vent. Refer to national
and local installation codes for more information on multiple venting.
3.3.3 Inspection and Replacement of Existing Vent System with New Components
If the Legacy heater is being installed to replace an existing pool heater, it is recommended that a new appropriate venting system be installed with the new heater. However, if an existing venting system must be used, be sure to carefully inspect the venting system to ensure that it is in good condition and continues to be appropriate for the Legacy heater. Replace any parts that are not in good and serviceable condition with new parts before completing the pool heater installa­tion.
Section 4. Gas Connections
such as "The Gas Safety (Installation and Use) Regulations" (Statutory Instrument 1998 No.
2451).
2. Check the gas supply to be sure that it is the same as the gas indicated on the heater's rating plate.
3. If there is any doubt regarding the capacity of any existing service pipes or the size required for new service pipes then the advice of the gas supplier should be requested. Installation
pipework should be tted and tested for gas
soundness. Zodiac recommends the gas inlet pipe sizes listed in Table 5.
4. Use the gures in Table 5 to size the gas inlet
piping from the gas meter to the heater. Check all local codes for compliance before installing the heater.
Table 5. Pipe Size Requirements*
Distance from Gas Meter
Heater
Size
125 20 25 25
175 25 25 32
250 25 32 32
325 32 32 40
400 32 40 40
0-15 m 15-30 m 30-60 m
mm mm mm
5. Before operating the heater, test for gas sound-
ness. Do not use a naked ame.
6. If the gas supply pressure is less than required, check for undersized pipe between the meter and
the heater, a restrictive tting, or an undersized gas meter. Gas supply pressures to the heater are
listed in Table 2.
4.1 Gas Supply and Piping
Review the following general instructions before
continuing the installation.
WARNING
The Legacy Model LRZ pool and spa heaters are designed for use with either natural gas or LPG. Check the rating plate on the inner panel to be sure that the heater is designed to use the type of gas being supplied. DO NOT ATTEMPT TO CONVERT
THIS HEATER FOR USE WITH ANY OTHER TYPE OF FUEL.
CAUTION
Permanent damage to the gas valve will occur if the following procedures are not followed.
1. Gas piping installation must be in accordance
with all applicable local rules and regulations
Inlet Gas Pressure Test Port
Gas Cock
Burner Pressure Point
Figure 5. Fitting a Gas Service Cock
Page 14 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
4.2 Burner Pressure
Conrm that gas supply pressure is correct. If
the gas supply pressure is less than required, check for undersized pipe between the meter and the heater, a
restrictive tting, or an undersized gas meter. Gas inlet
pressures to the heater, when it is operating, are listed in Table 2.
CAUTION
Burner gas pressure for the Legacy Model LRZ natural gas heaters should be set to the values listed in Table 2.
The burner pressure may be checked by connect­ing a manometer to the pressure port on the burner. Refer to Figure 5. The pressure will be zero when the
heater is not running. When the heater is operating the
burner gas pressure should be the values listed in Table 2.
If the burner pressure indicated above is not correct, check the gas train for possible problems.
Check the meter, gas line, gas ttings, and gas shut off
for under sizing. Check the gas valve inlet for excess pipe dope, if all is correct, then it may be necessary to adjust the gas valve regulator. To adjust the burner gas
pressure, rst remove the slotted cap next to the inlet pressure port on the inlet side of the gas valve. Under
the slotted cap is a slotted plastic screw which increas­es the burner pressure when turned clockwise and decreases the burner pressure when turned counter­clockwise. After measurements, and adjustments if necessary, have been made, make sure to replace the test point plugs on the inlet and burner pressure ports, and the cap on the burner pressure adjustment screw. It is extremely important to replace these parts before leaving the installation. Failure to do so can result in damage to property or injury or death. With the heater ring, the pressure must be within the range shown in Table 2. Also check the pressure with the heater off.
4.3 Special Precautions for LPG
LPG is heavier than air and can therefore more
readily collect or “pool” in enclosed areas if provision for proper ventilation is not made. Installation of pool heaters in enclosed areas such as pits is not recom­mended.
Consult any local code and re protection author­ities about specic installation restrictions in your area.
Section 5. Water Connections
5.1 Water Piping
Figure 6 illustrates typical piping for pool equip-
ment in pool/spa combination pools.
For normal installations, do not install a shutoff valve or any kind of variable restriction in the water piping between the heater outlet and the pool/spa. In special installations where a shut-off valve, diverter valve or other variable restriction is required in the plumbing between the heater outlet and the pool, Zodiac recommends the installation of a pressure relief valve on the heater (see Section 5.7).
Arrangement of pool system components other than as illustrated in these diagrams can affect the operation of the heater’s water pressure switch. Location of the heater above or below the pool water surface can also affect operation of the switch. In general, the pressure switch can be adjusted to accom­modate this effect if the heater water connections are no more than 1.8 m below the pool water surface and no more than 4.5 m above it. See instructions for pressure switch adjustment (Section 5.7) in the heater start-up section of this manual for more information about this.
Note that when pool equipment is located below the pool surface a leak can result in large scale water
loss or ooding. Zodiac cannot be responsible for such water loss or ooding or the damage caused by either
occurrence.
For special installations such as water connec­tions below the water level of the pool, or for other questions consult your local Zodiac dealer.
5.2 Hydraulic Head Loss
To verify that the minimum ows required
for the heater are met, a hydraulic head loss curve is shown in Figure 7. This should be checked when installing this heater into a new or existing piping system. This should also be consulted when installing a new pump.
5.3 Check Valve Installation
WARNING
A check valve can interfere with the proper operation of certain Suction Vacuum Release System (SVRS) products. To avoid possible en­trapment hazard, serious injury, or death, make sure to review the operation/owners manual of your particular SVRS product before installing the check valve.
The heater must be protected from back-siphon­ing of water, which can result in dry starts. If there is any chance of back-siphoning, provide a check valve
between the pool and the lter pump inlet.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Figure 6. Typical Piping Installation
AQUAPURE
ENGLISH
MANUAL BY-PASS DETAIL
MANUAL BY-PASS IS USED WHEN FILTRATION RATE EXCEEDS 125 GPM
Page 15
5
4.5
4
3.5
3
2.5
2
Pressure Drop (m H2O)
1.5
1
0.5
0
0 100 2 00 300 4 00 500
Figure 7. Hydraulic Head Loss Curve
LRZ400
LRZ325
LRZ175
LRZ250
LRZ125
When an automatic chemical feeder is installed
in the plumbing, it must be installed downstream of the heater (see Section 5.7). A check valve must be installed between the heater and the chemical feeder to prevent back-siphoning of chemically saturated water into the heater where it will damage the components.
5.4 Automatic Flow Control Valve
The inlet/outlet header of the Legacy Model LRZ
millivolt heater comes equipped with an automatic
ow control valve. The automatic ow control valve maintains the proper ow through the heater at rates up to approximately 475 lpm. If the lter system ow
rate is higher than approximately 475 lpm, install a manual bypass valve (see Figure 6), then perform a temperature rise test (see Section 11.6) and adjust the ow using the bypass valve until the proper tempera­ture rise is obtained.
LRZ Pressure Drop vs Flow
Water Flow (L PM)
5.5 Reversible Water Connections
The Legacy Model LRZ millivolt heater is
shipped with water connections on the right side,
but can be modied in the eld to provide left-side
water connections. This procedure involves remov­ing the heat exchanger headers and reinstalling them on opposite ends of the tube assembly. Some of the heater wiring must be disconnected and re-routed, so this procedure must be done only by a trained service technician. Heat exchanger reversals are generally done before the installation of power and water to the heater. If you need to reverse the heat exchanger on a previously installed heater be sure that all electri­cal power, the gas supply and water supply have been turned off before starting the procedure. These instruc­tions have been written to include the steps needed when reversing the water connections on an existing installation. If you are reversing the headers on a new installation, some steps will be ignored.
Page 16 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Water connection reversal is illustrated in Figures
8 and 9. Proceed as follows:
1. For an existing installation, drain the heater by removing the two (2) drain plugs on the inlet/ outlet header and the drain plug on the return header.
2. Remove the heater front panel (door).
3. Remove the I/O header side cover plates, top and bottom. See Figure 10.
4. Remove the return header side cover plates, top and bottom. See Figure 10.
5. Tag and disconnect the black high limit wire leading to the pressure switch (PS) and the black wire on the Fireman's switch terminal which leads to the high limit switch.
6. Remove the water temperature sensor nut from the inlet/outlet header and remove the sensor.
7. Tag and disconnect the black and white wires from the water pressure switch.
CAUTION
In order to prevent property damage or injury, en­sure that the wiring is handled and routed carefully so as not to cause any damage to it. Additionally, be careful not to create any kinks in the water pressure switch copper tubing when handling the header.
8. For an existing installation, remove the coupling nuts from the header and disconnect the water supply from the heater.
9. Remove the 10 bolts and washers from the inlet/ outlet header and remove the header from the tube assembly.
10. Remove the 10 bolts and washers from the return header and remove the header from the tube assembly.
11. For an existing installation, remove the tube gaskets and clean the header's mating surface of any corrosion or debris. Replace the tube gaskets with new ones. Do not use any metal tools on the header surface. Scratches may compromise the seal integrity.
WARNING
To avoid product failure which can cause property damage, serious personal injury or death, install the inlet/outlet header with the high limit devices on the bottom.
Figure 8. Water Connections as Shipped
DO NOT
INTALL THE INLET/OUTLET HEADER UPSIDE-DOWN
THE HIGH LIMIT DEVICES MUST BE ON THE BOTTOM
NOTE: When reversal is complete the water temperature sensor wires and the syphon loop tube will exit the inlet/outlet header at the back of the heater and the drain plugs are facing down.
Bypass Assembly
Figure 9. Water Connections Reversed
VENT TOP
RETURN HEADER SIDE COVER PLATES TOP AND BOTTOM
LEFT SIDE PANEL
®
CONTROL PANEL
FRONT PANEL
(DOOR)
BASE
TOP PANEL
REAR PANEL
IN/OUT HEADER SIDE COVER PLATES TOP AND BOTTOM
RIGHT SIDE PANEL
Figure10. LegacyPanelIdentication
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 17
12. Place the inlet/outlet header over the bolts and gasketed tubes on the left side of the tube assem­bly. Make sure the high limit devices are on the bottom. Refer to Figure 9. Align the bolt and tube holes in the header with the bolts and tubes in the header bar and slide the assembly together.
13. Thread on the 10 bolts and washers and hand tighten.
14. Place the return header over the bolts and gasket­ed tubes on the right side of the tube assembly. Align the bolt and tube holes in the header with the bolts and tubes in the header bar and slide the assembly together.
15. Thread on the 10 bolts and washers and hand tighten.
16. Use a torque wrench to tighten the bolts on each
header to 4 ft-lbs. The bolts must be tightened in the sequence indicated in Figure 11.
CAUTION
Failure to tighten the header as indicated in step 16 may cause the header to leak or become perma­nently damaged from warping.
17. Remove the 3/4 inch button plug located in the left side panel below the inlet/outlet header and replace with the 3/4 inch wire grommet from the right side panel below the return header. The high limit leads were routed through this grommet prior to removal in step 5. Install the 3/4 inch plug in the opening where the 3/4 inch wire grommet was removed.
18. Reconnect the white wire on the pressure switch (PS) and the white wire on the Fireman's switch terminal.
19. Reinstall the temperature sensor in the inlet/ outlet header and tighten the nut.
20. Reconnect the black and white wires to the water pressure switch.
21. Use plastic wire ties to refasten the temperature
sensor, high limit switch and water pressure switch wires to each other. Bundle the wires near the control panel and fasten them with a wire tie.
CAUTION
In order to prevent property damage or injury, be sure that none of the wires are in contact with a sharp edge or a hot surface.
22. Install the return header side cover plate on the right side of the unit.
23. Install the I/O header side cover plates, top and bottom on the left side of the unit.
24. Replace the front panel (door).
5.6 Connections at Heater
The Legacy Model LRZ millivolt heater has a
standard 2 inch water header and coupling design.
With this feature, only nominal 2 inch PVC or CPVC
may be connected to the heater. However, by installing the appropriate pipe adapters and two (2) short pieces of 2 inch plastic pipe (supplied by the installer), any
size existing pipe may be tted to the heater.
To connect a section of 2 inch PVC or CPVC
pipe to the heater, rst slip a coupling nut onto the
pipe. Then prepare the end of the pipe with the proper PVC/CPVC primer and glue. Follow the manufac­turer’s instructions provided with the primer and glue for preparation procedures and curing times. Apply
the slip-t side of the coupling to the end of the pipe.
Allow the glue to cure completely. Set the o-ring into the groove on the face of the coupling. Slide the coupling nut up to the coupling and tighten it to the threaded connection on the header (see Figure 12).
5.7 Pressure Relief Valve
A pressure relief valve (PRV) is recommended in
all installations, and is mandatory in any installation
in which the water ow can be shut off between the
heater outlet and the pool/spa.
A pressure relief valve is not supplied with the
Legacy Model LRZ millivolt heater. However, it is recommended that a pressure relief valve be installed and may even be required by local codes.
7
3
2
8
6
4
1
9
5
10
Figure 11. Header Bolt Tightening Sequence
O-RING
COUPLING
COUPLING
Figure 12. Piping to Heater
PVC OR CPVC PIPE
NUT
Page 18 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Be sure to check any applicable installation codes in your area to determine whether a pressure relief valve is required. See Section 12.2 (Parts List) of this manual for the appropriate kit part number.
The pressure rating of the valve should be at or below the lowest working pressure of any component in the system. The maximum working pressure of this heater is 5.1 bar.
Follow these steps to install a pressure relief valve:
1. To protect the threads while drilling, screw the
brass adapter (included with the Zodiac PRV
kit) into the blind threaded hole on the top of the
inlet/outlet header.
2. Using the countersink in the center of the blind
hole as a guide, drill a 6.4 mm (1/4 inch) hole
through the plastic (see Figure 13).
3. Open the hole by reaming it with a 9.5 mm (3/8
inch) drill bit.
4. Open the hole again by reaming it with a 12.7
mm (1/2 inch) drill bit.
CAUTION
Initially drilling a 12.7 mm (1/2 inch) hole without reaming may cause the bit to "grab" on the plas­tic. This may cause personal injury or damage the plastic header.
TEMPORARILY INSTALL
START WITH A 1/4" BIT
THEN OPEN HOLE WITH
A 3/8" BIT THEN OPEN
HOLE WITH A 1/2" BIT
Figure 13. Drill Hole for Pressure Relief Valve
PRESSURE RELIEF
VALVE HAND
TIGHTEN ONLY
RUBBER WASHER
BRASS ADAPTER TO
PROTECT PLASTIC
THREADS
BRASS ADAPTER
5. Remove the brass adapter and clean the cuttings
out of the hole.
6. Install the rubber washer at the bottom of the
hole (see Figure 14).
7. Thread the adapter into the hole and tighten so
that it seals against the rubber washer.
8. With a permanent marker, place a mark on the
adapter so that the mark faces the same direction
as the water connections on the header.
9. Remove the adapter from the hole.
10. Coat the threads of the pressure relief valve
(PRV) with an appropriate metal to metal thread
sealant.
11. Install the adapter on the PRV and tighten using
two (2) wrenches. Use the mark made earlier on
the adapter to orient the PRV to the desired direc-
tion in relation to the water connections on the
header.
12. Reinstall the adapter, with the PRV, into the
plastic threaded hole and tighten it until the mark
on the adapter is once again facing the same
direction as the water connections on the header.
Figure 14. Pressure Relief Valve Installation
CAUTION
Do not use any pipe compound or pipe dope on the threads of the adapter or any part that comes in contact with the plastic headers. These compounds may damage the header over a period of time.
CAUTION
In order to prevent property damage, do not over­tighten. Overtightening may crack the header.
DO NOT TIGHTEN WITH A WRENCH. Overtightening may crack the header. Route the discharge piping so that discharge from the pipe does not endanger anyone near the heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 19
Refer to your local installation codes for more detailed information. The valve setting should be at or below the maximum working pressure of any
component in the lter system. The maximum working
pressure of the Legacy Model LRZ millivolt heater is
5.1 bar.
5.8 Auxiliary Components,
Chlorinators, Ozone Generators, and Sanitizing Chemicals
The Legacy Model LRZ millivolt heater is manufactured with materials that are not compatible with high concentrations of ozone, chlorine, bromine, or other sanitizing chemicals. Heater damage caused by excessive chemicals or improper ozonization is not covered by the Zodiac warranty. Be sure to adhere to the following:
When ozone is injected upstream of the heater,
install an offgas mixing chamber, or an ozone
bypass system between the heater and the ozone
injector to prevent ozone and air from entering
the heater.
When chemical feeders are used, plumb the
feeder downstream of the heater and install
an in-line check valve between the heater and
the feeder (a minimum of 450 mm is required
between the heater and the check valve).
Wire any electrical chemical feeder so that it
cannot operate unless the lter pump is running.
If the feeder has an independent clock control,
synchronize it with the lter clock.
Never deposit chemicals directly in the pool
skimmer.
Section 6. Electrical
WARNING
This product must be installed and serviced by a
contractorwhoislicensedandqualiedinpool
equipment by the jurisdiction in which the product will be installed where such state or local require­ments exists. In the event no such state or local requirement exists, the installer or maintainer must
beaprofessionalwithsufcientexperienceinpool
equipment installation and maintenance so that all of the instructions in this manual can be followed exactly. Before installing this product, read and fol­low all warning notices and instructions that accom­pany this product. Failure to follow warning notices and instructions may result in property damage, personal injury, or death.
CAUTION
Label all wires prior to disconnection when servic­ing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
6.1 Main Power
The Legacy heater does not require an external source of electrical power to operate. The power for the gas valve and safety circuit are generated by a thermopile. The thermopile generates a millivolt signal
when heated by the pilot ame. Figure 15 shows the
internal electrical wiring diagram and schematic of the heater.
6.2 Earth Bonding
CAUTION To prevent premature failure of the appliance result­ing from stray voltages and voltage differentials, the heater must be bonded to other equipment which is part of the pool plumbing system with a solid copper wire not smaller in diameter than 8 AWG (10mm2).
Zodiac requires that the appliance be connected
to an "earth bonding loop" that includes all electrical
equipment in the system and on the equipment pad. Earth bonding lugs must be connected with a solid
copper wire not smaller than 8 AWG (10mm
2
). Failure
to do so will void warranty.
Additionally, all metallic components of a pool
structure, including reinforcing steel, metal ttings
and above ground components be bonded together (forming an “earth bonding grid”) with a solid copper
conductor not smaller than a 8 AWG (10mm
2
).
Page 20 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
TH
BK
TP
R
W
TP/TH
GAS VALVE
EARTH BONDING LUG
W
GENERATOR
PILOT
PILOT
WR
Figure 15. Legacy Wiring Diagram
W
ROLL-OUT SWITCH
(FUSIBLE LINK)
W
R
W
240°C (464°F)
TEMPERATURE
IGNITER
VENT
LIMIT
TEMPERATURE CONTROL
BK
BK
HIGH LIMIT
W
W
FIREMAN SWITCH
BK
W
52°C
(126°F)
®
HIGH LIMIT
42°C
(108°F)
PRESSURE SWITCH
BKBK
BK - BLACK R - RED W - WHITE
H0321000 Rev E
BK
The equipment and/or appliances associated with the pool water circulating system, including, but not limited to, pump motors and heaters must also be bonded together as part of the equipotential bonding grid. Zodiac provides a special labeled earth bonding lug on the right side of the heater to accommodate this requirement. Consult your local applicable installation codes/regulations for additional requirements that may apply.
6.3 Auxiliary Time Clock Wiring
If you install a time clock to control the lter
pump operation, it is recommended that the time clock have its own low voltage (Fireman’s) switch to turn off the heater before turning off the pump. The switch should shut off the heater about 15 minutes before
the lter pump shuts off. This will allow for a more efcient operation by removing any residual heat
contained in the heat exchanger back to the pool.
To install a time clock auxiliary switch into the heater wires (see Figure 16):
1. Remove heater door.
2. Remove the factory installed wire between termi-
nals 1 and 2 on the terminal strip (see Figure 16).
3. Connect the wires from the time clock auxiliary
switch to the two (2) terminals. Use 14 AWG (2,5
2
) stranded copper wire with a temperature
mm rating of 105°C (221°F) or greater.
The length of the wire between the heater and the time clock should not exceed 4.57 m. The contact points of the time clock switch should be silver, or a low resistance alloy.
BLACK BLACK
OR CONTROL
ROLL-OUT SWITCH
(VENT FUSIBLE LINK)
Figure 16. Time Clock Wiring or Control Connection
VENT TEMPERATURE LIMIT
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 21
Section 7. Commissioning
7.1 Heater Start-Up
1. When the heater has lit, remove the service door
and check all gas connections for soundness with
leak detection uid.
2. Check the manifold (burner) pressure setting and adjust as necessary (see Table 1).
3. Start the adjustment procedure with the heater cold, on full load, and with the temperature control set at maximum. This will ensure, as far as possible, that thermostatic shutdown does not interfere while the pressure is being checked and adjusted.
4. Remove the blanking screw in the manifold (burner) setting pressure test nipple (see Figure
17) and securely connect a suitable gas pressure gauge.
5. Light the heater and allow it to operate for about 15 minutes to stabilize the burners.
6. Check the pressure and adjust it for the appro­priate heater size. Refer to Table 2. The burner pressure setting adjuster is found on the gas control (valve).
7. Remove the dust cover over the adjuster and, using a screwdriver, turn the screw beneath clockwise to increase or anti-clockwise to decrease the pressure. Replace the dust cover
when nished.
8. Turn off the burner, disconnect the gas pressure gauge, and replace the blanking screw in the burner setting pressure test nipple.
9 Relight and check for gas soundness.
10. For heaters installed with a draft hood, perform a spillage test in accordance with BS.5440:1 to check for spillage of combustion products from the heater draft diverter.
11. Check that the main burner responds correctly to
manual ON/OFF operations of any controls tted
in the gas control circuit.
12. Check the operation of the ame failure safety
device using the following steps:
a. Extinguish the main burner and pilot burner
by turning off the main gas inlet cock.
b. Check that the ame failure device is heard
to close within one (1) minute.
c. Wait three (3) minutes, then turn on the gas
and re-light the pilot.
13. With the pump running, check for water leaks in
the heat exchanger or water piping.
14 Adjust the water pressure switch according to the
procedure in Section 11.5.
15. Perform a temperature rise test acording to the procedure in Section 11.6.
16. Ret the service door and return all controls to
the required settings.
Pressure Test Nipple with Blanking Screw
Figure 17. Lighting the Pilot
Inlet Gas Pressure Test Point
Burner Pressure Adjustment
Section 8. Operating Instructions
8.1 Normal Operation
WARNING
Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in
uegaseswhichcouldresultinsevereinjury,or
death. For indoor installations, as an additional measure of safety, Zodiac strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces.
The Legacy model LRZ millivolt heaters are
capable of automatic operation based on a call for heat at a preset temperature. The heater has an inter­nal safety system which allows operation in a variety of conditions and prevents operation when certain adverse conditions are encountered.
When the heater's pilot is lit and the pilot
generator is providing a millivolt signal to the safety
circuit, water is owing through the heater, and the
temperature of the water entering the heater is below
Page 22 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
the temperature control setting, an operating cycle is initiated by the automatic control. The temperature control circuit is closed, activating the gas valve and
the gas valve is opened. Gas ows through the burners,
is mixed with air in the combustion chamber, and is ignited by the pilot. Operation will continue until the temperature of the water entering the heater reaches the temperature control setting.
If ignition is unsuccessful, or if the ame fails
during normal operation, the temperature control circuit opens and shuts off the gas valve.
8.2 Start-Up
CAUTION
Do not use this heater if any part has been under water.Immediatelycallaqualiedservicetechni­cian to inspect the heater and replace any part of the control system and any gas control which has been under water.
CAUTION
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the heater.
CAUTION
Do not attempt repairs on the gas controls or appli­ance. Tampering is dangerous and voids all warran­ties.
CAUTION
Keep all objects off the top of the heater. Blocking
airowcoulddamagetheheater,andmayvoidthe
warranty.
WARNING
Vent pipes, draft hoods, and heater tops get hot! These surfaces can cause serious burns. Do not touch these surfaces while the heater is in opera­tion. Adding a vent cap reduces the temperature on the top.
WARNING
For your safety, when starting the heater, keep your
headandfacewellawayfromthelowerrebox
opening to prevent any risk of personal injury.
Be sure that there is water in the pool and that the
surface level is above the skimmer or other inlet of the
pool’s lter system.
Conrm that pool water is owing normally through the pool system and equipment. With any new pool or spa installation, operate the lter pump
with the heater off long enough to completely clean the water. This will remove any installation residue
from the water. Clean the lter at the end of this
operation before starting the heater. Start the heater in accordance with the Operating Instructions section of this manual, with particular attention to the light­ing and shutdown instructions and temperature control operation.
The heater may not start on the rst try. Air in
the gas line or other start-up situations may cause it to cycle.
When raising the temperature of a cold pool,
remove all time clock settings. This lets the lter
system and heater operate continuously until the water reaches the temperature setting on the temperature
control. When that happens, the heater will automati­cally shut off, but the lter pump will keep running.
When the heater starts, immediately feel the outlet header of the heater to conrm that there is adequate water ow. The header should not be hot.
Normally, water temperature will rise only a few degrees as it passes through the heater, and a “hot”
header or pipe indicates low water ow.
WARNING
Whentheheaterisredforthersttime,thecom­bustion chamber refractory binder material is driven
outbytheheatoftheame.Whitesmokeand/or
sharp odors may be emitted from the vent during this period. Do not inhale combustion product fumes at any time, and especially when these fumes are being emitted. This "burn-in" period will last only a few minutes.
8.3 Lighting and Shutdown Procedures
Before starting your heater, be sure that you are familiar with the setting and operation of the heater controls. Once the controls are set to your preferences, follow the instructions outlined on the following page.
Read and follow all safety instructions rst.
A more detailed set of instructions of the opera­tion of the controller follows in the next section.
NOTE IfyourheaterisconguredtooperateonLPG
and the LPG tank runs out of fuel, turn off
gasattheheater.Afterthetankisrelled,the
heater must be relit following the instructions found on the inside of the heater. A copy of these instructions appears on the following page.
WARNING DO NOT attempt repairs on the gas control or heater. Tampering can cause severe bodily injury or death and voids all warranties.
WARNING Do not attempt to operate the heater with the door off. Doing so may cause severe bodily injury.
8.3.1 Lighting the Heater
Full lighting and shutdown instructions can also be found attached to the wall inside the control compartment door. See Figure 18.
1. Remove the service door on the front of the
heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 23
WARNING
LP Gas Models: Toavoidpossibleinjury,reand
explosion, read and follow these precautions and all instructions on this appliance before starting the heater. LP (propane) gas is heavier than air and will remain at ground level if there is a leak. Before lighting, sniff at ground level. If you smell gas, follow these rules:
1. DO NOT light matches. DO NOT turn electric lights or switches on or off in area. DO NOT use an electric fan to remove the gas from area.
2. Shut off gas at LP tank.
3. Telephonegascompanyandredepartment
for instructions. Give your name, address and phone number.
If your LP tank runs out of fuel, turn off gas at the
appliance.Afterthetankisrelled,theappliance
must be re-started according to the instructions located on the inside of the door.
WARNING
Natural Gas Models: Toavoidpossibleinjury,re
and explosion, read and follow these precautions and all instructions on this heater before lighting the pilot. If you smell gas, follow these rules:
1. DO NOT light matches. DO NOT turn electric lights or switches on or off in area. DO NOT use an electric fan to remove the gas from area.
2. Shut off gas at gas service cock.
3. Telephonegascompanyandredepartment
for instructions. Give your name, address and phone number.
DO NOT attempt repairs on the gas control or heater. Tampering is dangerous and voids all war­ranties.
FOR YOUR SAFETY READ
BEFORE OPERATING
WARNING: If you do not follow these instructions
exactly,areorexplosionmayresult,causingprop-
erty damage, personal injury or loss of life.
LIGHTING INSTRUCTIONS
INSTRUCTIONS TO LIGHT HEATER
1. Position ON/OFF switch to “OFF”.
2. Turn gas control knob clockwise until it stops at “ ” (OFF) position.
3. Wait five (5) minutes before lighting pilot.
4. Turn knob on gas valve counterclockwise to “ ” (PILOT) then push control knob all the way and hold down. Push the button of the sparker, repeating until confirming that pilot lights, by observing reflection on burner tray mirror. Continue to hold the control knob in for about one (1) minute after the pilot is lit. If it goes out, repeat steps 3 and 4.
5. Turn gas control knob counterclockwise to “ ” (ON).
6. After replacing door, set thermostat to desired setting and turn appliance ON/OFF switch to “ON”. Valve has built-in delay before coming on.
RELIGHTING If pilot goes out, repeat steps 1 through 6. TO SHUT OFF HEATER To shut off main burners turn gas control knob
clockwise until it stops at “ ” (PILOT). For complete shut-off press down slightly on knob while turning clockwise to “ ” (OFF). Do not force. Position ON/OFF switch to “OFF”.
Control Knob with OFF, Pilot and ON Position
Pilot Adjustment
Regulator
IMPORTANT INFORMATION
1. CAUTION: Do not store pool chemicals or flammable materials near this appliance.
2. PH LEVEL: Pool Water must be maintained between 7.4 and 7.6 when operating unit (See section entitled "Water Chemistry" in operating manual).
3. BACKWASHING: Turn heater off 20 minutes before backwashing or shutting down filter to prevent damage to unit.
4. WINTERIZE: All gas to unit must be shut off and all water drained from unit to protect it from freezing damage.
NOTE: THIS DOOR MUST BE FITTED TO UNIT DURING NORMAL OPERATIONS.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE. NOTE: SOME EXPOSED PARTS OF THIS HEATER MAY BE HOT WHEN OPERATING.
®
H0320600 Rev B
Figure 18. Legacy Lighting and Shutdown Procedures
Page 24 ENGLISH
Control Knob with OFF, Pilot and ON Position
Regulator
Figure 19. Natural Gas/Propane Control Valve
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Pilot Adjustment
2. Turn the gas control knob clockwise until it stops at the OFF position (see Figure 19).
3. Wait ve (5) minutes before lighting the pilot.
4. Turn the knob on the gas valve counterclockwise to PILOT, then push the control knob all the way and hold down. Push the button of the sparker,
repeating until conrming that the pilot lights by observing the reection on the burner tray mirror.
Continue to hold the control knob in for about one (1) minute after the pilot is lit. If it goes out, repeat Steps 3 and 4.
5. Release the control knob and verify that the pilot is lit.
6. If the pilot burner does not remain lit when the button is released, press and release the red
button. Wait at least three (3) minutes and then
repeat the lighting procedure from step 4.
7. If the pilot cannot be established, check that the pilot burner ame correctly envelops the thermo­couple tip by 10 to 13 mm. If not, check that the pilot adjustment screw on the gas control (see Figure 19) is fully unscrewed, then turn it one (1) turn back in. Check that the thermocouple lead connections at the gas control and at the overheat thermostat are clean and secure. Repeat from Step 4.
8. Turn gas valve knob to ON. Replace the service door.
9. Turn the rocker switch to ON.
8.3.2 Relighting the Heater
If the pilot goes out, repeat steps 5 through 7 in
Section 8.3.1.
8.3.3 Shut-Down Procedure
1. To turn the main burner off, turn the rocker switch to OFF.
2. To turn the heater off (including the pilot), turn the gas valve knob to the OFF position.
8.4 Turning the Heater On/Off and
Setting the Temperature Control
The temperature control (see Figure 20) is
calibrated at the factory and covers a range from
approximately 21°C to 40°C (70°F to 104°F). Use an
accurate pool thermometer to determine the best water temperature for your use.
The Legacy temperature control panel has a
rocker switch to turn the heater on and off. It also has a rotary dial to set the desired thermostat setting (see Figure 20).
Once the heater has been lit by following the
safety and lighting procedures in Section 8.3, set the
toggle switch on the control panel to "ON" to start the
heater operation. If the heater senses that the pump is on and the thermostat setting is higher than the temperature of the pool/spa water, the pilot will ignite the main burners.
CAUTION
In order to prevent property damage, the heater is designedtorunonlywhenthelterpumpisrun­ning. If the heater does not immediately turn off when the pump turns off, turn the heater off at the control panel. The heater's pressure switch may need adjusting (see Section 11.5)
10. Set temperature control to against the Temp-Lok
tab. The main burner should light. Until the water
reaches a temperature of about 21°C (70°F), it is normal to have some water accumulating in the base of the heater.
11. Set the time clock, if one is installed.
H0286600
Figure 20. Temperature Control
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 25
Once the pool/spa water temperature reaches the
thermostat setting, the heater will automatically stop
ring. As the pool/spa water temperature falls below
the thermostat setting the heater will once again start the heating cycle.
Rotate the thermostat dial clockwise to increase the temperature setting and counterclockwise to decrease the setting. It may take several attempts to set the thermostat dial to the desired temperature. Be sure to use an accurate thermometer to measure water temperature. Once the desired temperature setting is found, loosen the screw on the Temp-Lok ring and rotate the ring until the stop rests against the knob. Tighten the screw to hold the knob in position. This will prevent accidental moving of the dial and possible overheating of the water.
IMPORTANT: The temperature controls cannot
be calibrated in the eld. If the control is faulty,
shut down the heater by following the procedures in
Section 8.3 and have a qualied service technician
replace the control. DO NOT use the thermostat switch to completely shut down the heater.
Section 9. Maintenance
Table 7. Optimal Water Chemistry Ranges*
Test Recommended Level
Free Chlorine 1.0 to 3.0 ppm
Bromine 2.0 to 4.0 ppm
pH 7.4 to 7.6
Total Alkalinity (TA) 80 to 120 ppm
Calcium Hardness (CH) 175 to 400 ppm
Cyanuric Acid 10 to 50 ppm
Total Dissolved Solids (TDS)
Copper 0 ppm
* Concentration levels taken from "Basic Pool and Spa Technology" published by APSP (Association of Pool and Spa Professionals).
1000 to 2000 ppm (Excluding dis­solved NaCl from a Salt Chlorine Generator)
9.2 Seasonal Care
CAUTION
Do not operate this heater outdoors at tempera­tures below 20 degrees Fahrenheit (°F) (-7 degrees Celsius [°C]).
9.1 Water Chemistry
The mineral content of swimming pool water increases daily due to natural evaporation and the addition of sanitizing chemicals. If the mineral concen­tration in the pool gets too high, the excess miner-
als will deposit on the walls of the pool, in the lter
system, and in the heater tubes.
The proper chemical balance in spa water is more critical than in a swimming pool heater opera­tion. Due to the spa's size, high water temperature and heavy usage, chemical values in a spa can vary greatly. This chemical imbalance can result in unsanitary water conditions, and affect the life of the heater.
Proper chemical balances are necessary for sanitary bathing conditions as well as ensuring your heater's long life. Kits are available from your local pool supply dealer for making the various tests for mineral content. One of these kits will detect copper in the system. This is usually a warning that corro­sion is taking place, possibly due to a low pH value combined with other chemistry problems. The condi­tion can be corrected by changing the spa water and closely monitoring the pH factor and chemical proper­ties of the water. Be sure to keep your chemical levels within the values indicated in Table 7. Zodiac does
not warrant heat exchangers damaged by corrosive chemical levels or excess dissolved solids in pool or spa water.
For spas, it is also necessary to perform water changes in addition to chemical treatment. It is recom­mended to change the spa water every 60 days for light usage and every 30 days if usage is heavy.
9.2.1 Spring and Fall Operation
During periods when the pool is only going to be used occasionally, turn the temperature control down to the MIN setting. This prevents the pool water from becoming chilled, and minimizes the time required to raise the pool water back up to the desired tempera­ture.
In areas subject to only short freeze periods, turn off the heater and run the pump continuously for the length of the freeze period.
If the heater is not going to be used for a long period of time, shut it down completely. Refer to Figure 19 and follow the instructions found on the inside of the heater:
9.2.2 Winterizing
In areas where freezing temperatures occur in winter, and the pool or spa will not be used, have your service technician perform the following steps:
1. Turn off the main gas supply valve to the heater,
outside the heater jacket.
2. Remove heater door.
3. Shut down the heater following the shutdown
instructions found on the inside of the heater or
Figure 19.
4. Remove the drain plug from the inlet/outlet
header, and completely drain the heater before
the rst frost. See Figure 21.
Page 26 ENGLISH
O-RING
DRAIN PLUG
Figure 21. Draining the Heater
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
9.3 Inspection and Service
The Legacy heater is designed and constructed to provide long performance life when installed and operated properly under normal conditions. Periodic inspections, especially at spring start-up, are impor-
tant to keep your heater running safely and efciently
through the years.
WARNING Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in
uegaseswhichcouldresultinsevereinjury,or
death.
5. After all water has drained from the heater, check for mineral buildup in the openings.
6. Use compressed air to blow out any standing
water remaining in the heat exchanger.
7. Inspect the gaskets on the drain plugs and reinstall the plugs, but do not tighten.
8. Disconnect the pressure switch from the copper tubing. See Figure 22.
9.2.3 Spring Start-up
To restart the heater in the spring, have a profes-
sional service technician reassemble the heater as follows:
1. Attach the copper tubing to the pressure switch (see Figure 22).
2. Tighten the drain plugs.
3. Turn on the lter pump and circulate water through the heater for ve (5) minutes. Check for
leaks while circulating.
9.3.1 Owner Inspection
Zodiac recommends that you inspect the heater on a continual basis and especially after abnormal weather conditions. The following basic guidelines are suggested for your inspection:
1. Keep the top and surrounding area of the heater
clear of all debris.
2. Keep the area around and beneath the heater
clean and free of all combustible materials such
as paper, leaves, etc.
CAUTION
Donotstoreorusegasolineorotherammable
vapors, liquids or chemicals in the vicinity of this or any other appliance.
WARNING Do not use this heater if any part has been under water.Immediatelycallaqualiedservicetechni­cian to inspect the heater and replace any part of the control system and any gas control which has been under water.
4. Turn on the main gas supply valve to the heater, outside the heater jacket.
5. Turn on the heater following the lighting instruc­tions found on the inside of the heater, or Figure 19 of this manual.
Pressure Switch
Disconnect here (Winterizing)
Figure 22. Pressure Switch Copper Tubing
Copper Tubbing
3. If the heater is equipped with a pressure relief valve, check for corrosion in and around the
valve. Twice a year, with the lter pump on, lift
the release lever on the top of the valve to make sure that water runs freely through it. If corrosion
is found, replace the pressure relief valve. When
replacing the valve, be sure that the pump is off. Install the valve so that the discharge is directed away from any area that may be damaged by water.
4. Be sure all combustion air and ventilation openings are not blocked. Check for spider webs and other debris inside the heater, in the vents on all sides of the heater jacket and in the exhaust outlet– especially after a long period of nonuse.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
9.3.2 Professional Inspection
Inspections performed at least once a year by
a qualied technician are required to maintain your heater's safe and efcient operation. The following
basic safety checks must be performed.
1. Inspect the venting system for blockage, leakage, and corrosion.
2. Inspect burners and verify that they are clean. Clean with a wire brush if necessary to remove debris.
3. Check for spider webs and other debris in the
pilot and main burner orices - especially at
spring start-up.
4. Check for loose or broken wires and terminal connections.
5. Make sure that the pressure switch operates
properly by shutting the lter pump off and on
a few times. The burner should go off immedi­ately after the pump stops. An ignition sequence should start shortly after the pump is turned back on.
ENGLISH
Pilot, Thermopile and Thermocouple Position
Thermocouple Thermopile
Main Burner Flame Pattern
Page 27
6. Make a visual check of the main burner and pilot
ame patterns. The ame can be seen in a mirror arrangement held beneath the burners. The ame
should be:
a. Blue in color.
b. 25 mm to 102 mm above burner surface (see
Figure 23).
7. Inspect the gas and electronic controls, including the following:
a. High temperature limit switch
b. Water pressure switch
c. Automatic gas valve
d. Roll-out switch (fusible link)
e. Temperature control
F. Vent temperature limit
8. Perform a temperature rise test in accordance with Section 11.6.
9. If the heater is equipped with a pressure relief valve, check for corrosion in and around the
valve. With the lter pump on, lift the release
lever on the top of the valve to make sure that water runs freely through it. If corrosion is found,
replace the pressure relief valve. When replacing
the valve, be sure that the pump is off. Install the valve so that the discharge is directed away from any area that may be damaged by water.
Figure 23. Pilot, Thermopile and Thermocouple
Positions, and Main Burner Flame Patterns
10. Inspect the external surfaces of the heat exchang­er tubes for black carbon soot buildup by placing a mirror between and under the burners when the heater is ring. Remove any soot that has collect­ed on the tubes, and correct the cause.
NOTE Afterinstallationandrststart-up,checkthe
heat exchanger for black carbon soot buildup after the following periods of operation: 24 hours, 7 days, 30 days, 90 days, and once every 6 months thereafter.
11. Conduct a normal operating cycle and observe that the sequence proceeds as intended.
CAUTION
For your safety, when starting the heater, keep your head and face away from the burner area opening to prevent any risk of personal injury.
NOTE Keep this manual in a safe place for future
reference by you and your professional technician when inspecting and servicing the heater.
Page 28 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Section 10. Troubleshooting
10.1 General Heater Troubleshooting
Table 8 lists some of the more common problems, causes and solutions encountered when running the heater. Most problems occur when the heater is being started for the rst time after instal­lation or at spring start-up. Careful installation and maintenance will help ensure years of trouble free use from your Legacy heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Table 8. Legacy Troubleshooting Guide
#
Symptom Cause Remedy
1. Pump not oper­ating
A. No power. B. Pump defective. C. Incorrectly wired.
A. Check circuit breakers and power source. B. Replace pump.* C. Recheck wiring.*
ENGLISH
Page 29
2. Pilot outage A. Inlet gas pressure too low.
B. Inlet gas pressure too high causing an unstable blowing pilot. C. Weak or defective thermocouple or thermopile. D. Damaged pilot, thermocouple or thermopile. E. Dirty pilot.
F. Pluggedorundersizedpilotorice. G. Pluggedburnerorice(s).
3. Flame roll-out at start-up
4. Spillage at draft hood
5. Lazyamewith yellow tip
6. Not enough heat A. Inadequate gas supply.
7. Heater pounding or knocking
8. Heater condens­ing
9. Pressure relief valve opens
10. Pilot is lit but main burners will not come on
11. Heater short cycles
A. Blockedue. B. Pilot out of position (delayed ignition). C. Blocked heat exchanger. D. Refractory blanket out of place. E. Altered vent cap. F. Low gas pressure.
A. Cold chimney. B. Vent pipe pitches down to chimney. C. Blocked chimney. D. Altered draft hood. E. Prefabricated chimney with incorrect cap.
A. Low primary air.
B. Incorrect burner pressure.
B. Low burner gas pressure.
C. Heater size inadequate. D. Low temperature rise.
A. Inadequatewaterowthroughheater. A. Check temperature rise between inlet and outlet heater
A. Low water temperature. A. Flue product moisture will condense at the start-up until the
A. Restrictioninwaterowsystemator downstream of heater.
A. Gas valve not at “on” position.
B. Hi-limit switches failed.
C. Pressure switch failed or out of adjustment.
D. Roll-out switch (fusible link) failed.
E. Gas valve failed.
F. Broken wire in thermostat circuit or
defective thermostat.
G. Heater wired incorrectly.
H. Vent temperature limit failed.
A. Lowwaterowthroughheater.
B. Failing hi-limit switch.
* Mustbeperformedbyaqualiedprofessionalpooltechnician.
A. Consult gas utility company. Inlet gas pressure to heater should be 13.7 to 24.9 mbar on natural gas. 24.9 to 34.8 mbar on propane gas.* B. Pressure should be regulated within limits shown above.*
C. Replace thermocouple or thermopile.* D. Replace.* E. Blow dust or lint out of pilot.*
F. Cleanorreplacepilotorice.* G. Removeandcleanallorices.*
A. Remove blockage.* B. Correct pilot position.* C. Clean and correct as necessary.* D. Clean and correct blanket as necessary.* E. Install an unaltered factory approved vent cap.* F. Check and correct gas pressure.*
A. Allowheatertooperateve(5)minutestocreatedraftaction. B. Reinstall vent pipe to pitch up from the heater to chimney.* C. Remove blockage.* D. Install factory-provided draft hood.* E. Install U.L. listed vent cap.*
A. Check for internal burner obstructions.*
B. Adjust burner pressure according to rating plate.*
Clean burner ports if dirty.*
A. Gas meter too small. Gas line from meter to heater too small.* B. Gas pressure on heater burner should be adjusted to the values list in Table 2.* C. Replace with heater of higher input.*
D. Checkandcorrectwaterow.*
piping. See section 11.6 for recommended range of temperature rise. If temperature rise is above the maximum recommended, check for closed valve in system.*
heater water temperature reaches the normal operating conditions.*
A. Check for proper operation of all valves, bypass valve and any equipment between pool and heater outlet.*
A. Turn knob to “on” position.
B. Investigate reason for overheating and replace hi-limit switch
as necessary.*
C. Adjust pressure switch (see Section 11.5) or replace as
necessary.*
D. Investigatereasonforamerolloutandreplaceroll-out
switch as necessary.*
E. Check and replace gas valve as necessary.*
F. Check continuity through thermostat circuit with wires
disconnected.*
G. Check heater wiring against wiring diagram in Section 6,
correct as necessary.*
H. Thoroughly investigate the causes for vent temp limit failure,
correct the problem and replace the vent temp limit.
A. Increase size of pump or increase piping size.*
B. Check hi-limit switches and replace as necessary.*
Page 30 ENGLISH
Section 11. Professional Maintenance and Service
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
EXHAUST
VENT TOP
WARNING
SERVICING SAFETY
Some of the servicing procedures for the Legacy heater are hazardous because they involve fuel gas, electricity, moving parts and procedures which require testing or temporary bypass of safety con­trols. For this reason, the heater must be serviced
onlybyaqualiedprofessionalservicetechnician.
IMPROPER SERVICE HAZARD
The Legacy heater incorporates unique design fea­tures. Incorrect service of this heater can result in property damage, personal injury or death. To avoid such hazards, the heater must be serviced only by
aqualiedprofessionalservicetechnician.
11.1 General Information
A qualied professional technician must
service the Legacy model LRZ millivolt pool heater using Zodiac service procedures. Before calling for service, however, the owner should check for obvious problems. The other components in the pool system,
including pump, lters and strainers, water valves, gas
supply and time clocks have an effect on heater opera­tion.
Conrm that the Legacy heater control switch is
set to 'ON' and that the temperature control knob is set high enough to make the heater operate. Make sure the
pump is operating, that the lter and strainers are not
clogged, that there are no mis-positioned water valves, that the gas is not shut off and that time clocks are properly adjusted. Also be sure that there is no block­age of the vent or louvers which supply combustion air to the burners.
11.2 Natural-Draft Combustion System
The Legacy model LRZ millivolt pool heater has an atmospheric combustion system. This system is illustrated in Figure 24.
As the heated exhaust gases rise out of the
combustion chamber, ow is created through the
system and fresh combustion air is drawn into the heater through the louvers cut into the front and sides
of the heater. Gas is forced through an orice into the open end of a burner. When the gas ows into the
burner, a “negative” pressure is created at the opening of the burner. This negative pressure pulls air into the burner with the gas and mixes the two together. As
the gas/air mixture ow through the burner ports it
is ignited in the combustion chamber. Hot combus-
tion products then rise through a highly efcient heat exchanger. Combustion products then enter a ue
collector and are directed to the outdoors through the grate top of the heater or a vent pipe and cap.
FLUE COLLECTOR
HEAT EXCHANGER
AIR FLOW
Figure 24. Atmospheric Combustion System
COMBUSTION CHAMBER
BURNER
BURNER TRAY SHELF
11.3 Heater Components and Their Operation
1. Gas Valve / Regulator - The gas valve controls
gas ow into the burner. It provides ow only
when the temperature controls require heat and only if all safety controls enable operation. It is also a positive pressure regulator. It regulates
the gas pressure in the burner to specications
addressed earlier in this manual. This is neces­sary for proper operation of the burner system.
2. Temperature Control - The Zodiac Legacy
pool/spa heater is controlled by a mechanical thermostat which controls heater operation to bring the water to the desired temperature. The desired temperature is set by rotating a knob on the face of the control panel. To achieve accurate water temperatures, the pool/spa water must be monitored with an accurate pool thermometer.
3. Pilot/Pilot Ignition - The Legacy heater relies
on a standing pilot to ignite the burners when the
temperature control calls for heat. When lit, the pilot receives a constant ow of gas from the gas
valve. If the pilot extinguishes, the gas valve is
automatically signalled to stop the ow of gas to
the pilot and the burners to prevent a gas build up in the heater. Igniting the pilot is achieved by means of a piezo spark igniter mounted on the inner front panel of the controls compartment of the heater.
4. Pilot Generator (Thermopile) - The pilot gener-
ator is a device, that when heated by the ame
of the pilot, generates a small electrical voltage of approximately 750 millivolts. The voltage is placed across the temperature controller and safety circuit of the heater. If this current is
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 31
broken at any time, the gas valve is immediately
shut off and the heater stops ring. This voltage
is also used to activate the gas valve's pilot coil
which allows gas to ow to the pilot after the gas
valve knob is released.
4. Thermocouple - The thermocouple is a device
that senses if the pilot ame is hot enough to
ignite the gas fuel from the burner. If hot enough, the main gas valve is allowed to open. If the thermocouple does not sense enough heat from
the pilot ame (such as when the pilot is out),
then the thermocouple shuts off the gas valve to the burners.
5. Limit Switches - Two (2) limit switches prevent excessive water temperature - one (1) within the heat exchanger and one (1) for water leaving the heater. If either senses excessive temperature, burner operation is interrupted.
6. Water Pressure Switch - This control senses whether or not water is available to the heater by measuring back pressure inside of the heat exchanger. If the pool water pump fails or the
water lter is blocked, the pressure switch
prevents operation of the burner.
7. Roll-Out Switch (Fusible Link) - This is a single-use switch which detects abnormal temperature in the component vestibule. It is a roll-out switch (fusible link) which is held to the inner panel just above the burner tray by a sheet metal bracket. Excessive temperature in the component compartment, possibly due to a
blocked ue or ame roll-out, will cause the link
to fail. This opens the safety circuit which shuts off the gas valve and shuts the heater down.
8. Vent Temperature Limit - This is a single-use switch which detects abnormal temperature in the
vent system. It is mounted to the ue collector
assembly. Excessive temperatures will cause the switch to open. Excessive temperatures can be
caused by inadequate water ow or a damaged
heat exchanger. The vent temperature limit will open the safety circuit which shuts off the gas valve and shuts down the heater.
11.4 Electrical Troubleshooting
This section describes procedures for check-
ing the pilot generator and control components of the heater one at a time and in the order they appear in the control circuit.
NOTE Pump must be running during the
troubleshooting procedure.
These procedures require a voltmeter with a
minimum 0-1000 mVDC range. Figure 25 shows the pilot generator and control circuits, and where to take measurements. Location numbers and letters in circles have been added, and will be referenced in the follow-
ing sections.
As stated at the beginning of this manual, some
of these procedures are hazardous. Only a qualied
service technician should service the heater.
During the trouble shooting procedure, the lter
pump must be on, the pilot on the heater must be lit, the ON/OFF switch on the heater must be in the ON position and the control knob must be turned to the
maximum setting so that there is a call for heat. We
recommend turning the gas valve control knob to the
"PILOT" position to prevent the main burners from ring throughout the procedure. Before starting the
procedure, be sure that the pilot has been lit for at least two (2) minutes and that the pilot generator (thermo-
pile) is positioned correctly within the ame of the
pilot.
The pilot generator also operates the pilot coil of
the gas valve, allowing gas to ow to the pilot when
the gas valve knob is released from the pilot light-
ing position (see Section 8.3 "Lighting and Shutdown Procedures"). If the pilot will not stay lit when the gas
valve knob is released, check the pilot generator output as described in Section 11.4.2 and replace if necessary.
If the pilot generator output is sufcient, then check
the gas valve as outlined in Section 11.4.1.
11.4.1 Gas Valve
The gas valve consists of two (2) separate internal operating valves. The main valve supplies gas to the main burners for heater operation. The pilot valve supplies gas to the pilot when the pilot generator activates the pilot coil.
If the pilot will not stay lit after following the lighting instructions in Section 8.3, check for the following:
• Pilot generator output
• Correct type of gas supplied
• Correct gas supply pressure
• Air in the gas line
• Pilot coil wire connections clean and tight
• Faulty thermocouple
If the pilot will not stay lit after checking the items listed above, the pilot coil may be causing the fault. Replace the gas valve.
If the main burners will not light after follow­ing the lighting instructions in Section 11.4.2, check the voltage reading between the PP terminal on the gas valve (test point 1) and the TH terminal on the gas valve (test point 17). If the meter shows less than 220mVDC then there is a problem with the pilot generator, the sensors in the safety loop or the control panel. Follow the trouble shooting procedure as outlined in sections 11.4.2 through 11.4.7.
If the meter shows more than 220mVDC at test point 17, then check for the following:
Page 32 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
GAS VALVE
EARTH BONDING LUG
TP/TH
2
17
TH
TP
R
W
GENERATOR
W
PILOT
TEMPERATURE
BK
BK
1
HIGH LIMIT
W
3
ROLL-OUT SWITCH
(FUSIBLE LINK)
PILOT
WR
R
W
4
W
5
240°C (464°F)
TEMPERATURE
IGNITER
VENT
LIMIT
W
6
7
W
FIREMAN SWITCH
BK
9
8
W
52°C
(126°F)
11 12
10
®
16
HIGH LIMIT
42°C
(108°F)
CONTROL
BKBK
13
BK - BLACK R - RED W - WHITE
15
PRESSURE SWITCH
BK
BK
14
H0321000 Rev E
Figure25. TestPointIdenticationDiagram
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 33
• Correct type of gas supplied
• Correct gas supply pressure
• Correct gas burner pressure
• Correct orice size
• Air in the gas line
If the main burners will not stay lit after checking the items listed above, the gas valve may be causing the fault. Replace the gas valve.
11.4.2 Pilot Generator
The pilot generator generates a 700-750mVDC
signal when heated by the pilot ame. When the pilot
generator is connected to the heater's control compo­nents, there will be some voltage drop in the circuit so that the measured voltage will be less than 750mVDC. But the measured voltage should never be below
500mVDC when the ON/OFF switch is in the "OFF"
position or 220mVDC when the ON/OFF switch is in
the "ON" position.
With the pilot generator connected to the gas
valve and the ON/OFF switch in the OFF position, place the red lead of the voltmeter on the TPP termi­nal (test point 1) of the gas valve. Place the black lead of the meter on the TPP/TH terminal (test point 2) of the gas valve. The meter should show a minimum of 500mVDC. If the meter show less than 500mV, check for partial shorts, loose or corroded connections or partially broken wires between the pilot generator and the gas valve.
If the wires and connections are sound, check the pilot generator output. You will need alligator clips to do this. Disconnect the pilot generator from the gas valve. The pilot will go out. Light the pilot while pressing down on the gas valve control knob. Continue holding the knob for at least one (1) minute. Immedi­ately measure the voltage between the two (2) wires of the pilot generator. If the meter does not show at least 700mV, replace the pilot generator.
11.4.3 Roll-Out Switch (Fusible Link)
Check the voltage going to the safety circuit. Be sure that the pilot generator is correctly wired to the gas valve, the pilot is lit and the control knob on the
gas valve is in the "PILOT" position. Leave the red
voltmeter lead in place at test point 1. Touch the black lead of the meter to the terminal of the roll-out switch (fusible link) where the white wire from the gas valve is connected (test point 3).
If no voltage is detected at test point 3, the wire between the gas valve and the roll-out switch (fusible link) is broken. Replace the wire.
If there is a minimum of 220mV at test point 3, move the black meter lead to the other terminal of the roll-out switch (fusible link) (test point 4).
If no voltage is detected at test point 4, the
roll-out switch (fusible link) has failed. This indicates higher than normal temperatures in the component compartment (vestibule). Normal component compart-
o
ment temperature is well below 148.9°C (300
F). The roll-out switch (fusible link) is designed to fail at temperatures above 151.7°C (305°F). Excessive
temperature might be due to a blocked ue or heat
exchanger. Clean the heat exchanger and clear the
ue and vent of any restrictions. Sometimes the roll­out switch (fusible link) fails due to ame roll-out.
Flame roll-out may be caused by delayed ignition or downdrafting in windy areas. Thoroughly investigate
the causes for ame roll-out and correct the problem
when replacing the roll-out switch (fusible link).
Check the voltage going to the vent temperature limit. Leave the red voltmeter lead in place at test point 1. Touch the black lead of the meter to the termi­nal of the vent temperature limit where the white wire from the roll-out switch (fusible link) is connected (test point 5).
If no voltage is detected at test point 5, the wire between the roll-out switch (fusible link) and the vent temperature limit is broken. Replace the wire.
If there is a minimum of 220mV at test point 5, move the black meter lead to the other terminal of the vent temperature limit (test point 6).
If no voltage is detected at test point 6, the vent temperature limit has failed. The vent temperature limit will fail due to abnormal temperatures in the vent system. Excessive temperatures will cause the switch to open.
The vent temperature limit is designed to fail at temperatures above 464°F (240°C). Excessive
temperatures can be cause by inadequate water ow
or a damaged heat exchanger. Thoroughly investigate the causes for vent temperature limit switch failure and correct the problem when replacing the vent tempera­ture limit.
11.4.4 Fireman Switch and External Interlocks
Check the voltage going to the external device.
Touch the black lead of the meter to the reman switch
terminal strip where the white wire from the roll-out switch (fusible link) is connected (test point 7). The meter should read at least 220mV. If the voltage is less than 220mV, there may be a bad connection or wire between the roll-out switch (fusible link) and the terminal strip. The wire may need to be replaced. If voltage of 220mV or more is detected at test point 7,
move the black lead of the meter to the reman switch
terminal strip connection where the white wire from the high limit is connected (test point 8). The meter should read at least 220mV. If there is no voltage, the time clock switch or other external interlock may be mis-adjusted, mis-connected or defective. Correct this external problem.
Page 34 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
11.4.5 Limit Switches
Since the limit switches are not easily accessible, you can check the voltage going into the component after the limit switches in the circuit. If voltage is detected there, then the limit switches are closed and are operational.
Check the voltage going to the water pressure switch. Leave the red voltmeter lead in place at test point 1. Touch the black lead of the meter to the termi­nal of the water pressure switch where the black wire is connected (test point 13).
If the voltage is less than 220mV, there may be a bad connection, a partial short or a faulty sensor. If there is no voltage, one of the limit switches is open. This is normally due to excessive water tempera­ture, which should be thoroughly investigated before replacement of limit switches. Excessive water temper-
ature may be caused by low water ow. Water ow deciency may be due to obvious problems such as a defective pump or blocked water lter. Alternatively, excessive water temperature may be due to over-ring,
or to a problem with the water piping or the heater's
internal bypass control. Over-ring might be a result of an incorrect gas orice or supply of propane gas to a
heater intended for natural gas.
If there are no such fundamental problems, identify which of the switches is open. Limit switch access is through the limit switch plugs on the inlet/ outlet header. Remove the limit switch plugs from the bottom of the header and gently remove the limit switches from the wells. Move the black lead of the meter to the terminal on the 42°C (108°F) limit switch
(test point 9) that is connected to the reman switch
terminal block. Less than 220mV at this point means that the wire between the terminal block and the limit switch has a poor or broken connection or a partial short. Replace the wire assembly. If at least 220mV is detected at test point 9, then move the black lead of the meter to the other terminal of the 42°C (108°F) limit switch (test point 10). Low or no voltage here means that the limit is open and must be replaced.
If 220mV or more is detected at test point 10, move the black lead of the meter to the terminal on the 52°C (126°F) limit switch (test point 11) that is connected to the 42°C (108°F) limit switch. Less than 220mV at this point means that the wire between the two limit switches has a poor or broken connection or a partial short. Replace the wire assembly. If at least 220mV is detected at test point 11, then move the black lead of the meter to the other terminal of the 52°C (126°F) limit switch (test point 12). Low or no voltage here means that the limit switch is open and must be replaced. If voltage is detected at test point 12, move the black lead of the meter to the terminal of the water pressure switch where the black wire from the high limits is connected (test point 13).
Less than 220mV at this point indicates that the wire connecting the high limits to the water pressure switch is faulty or poorly connected. Correct the problem or replace the wire.
NOTE The limit switches have different trip points,
and it is important that replacements are correct. The 42°C (108°F) switch has a red dot on the top of the switch, and must be installed in the inlet side of the header. The 52°C (126°F) switch has no dot and must be installed in the outlet side of the header in the well farthest from the heater jacket.
11.4.6 Water Pressure Switch
If the meter shows at least a 220mV signal at test point 11, move the black lead of the meter to the other terminal on the water pressure switch (test point 14).
If there is no voltage, the pressure switch contacts
are open. This is almost always due to a water ow deciency, the most common one being a blocked water lter or defective pump. However, sometimes it is due
to blockage of the copper tube or mis-adjustment of the switch. Investigate thoroughly, referring to Section
11.5 “Adjusting the Water Pressure Switch”. If there
is no problem with the pool system or pressure switch adjustment, replace the pressure switch.
11.4.7 Temperature Control Circuit
The temperature control circuit consists of two (2) major components which must all be working correctly for the signal to be transmitted to the gas valve. The components are the ON/OFF toggle switch
and the mechanical thermostat. Use the following
procedure to check each component for functionality.
Check the temperature control as a complete circuit before checking each component individually.
With the red lead of the meter still at test point 1, place
the black lead of the meter on the back of the mechani­cal thermostat (test point 16). If the meter shows more than 220mV at the pressure switch (test point 14) but not at test point 16, then one of the components of the temperature control circuit is faulty. Proceed with the following sections to test the components.
11.4.7.1 ON/OFF Toggle Switch
Remove the temperature control panel from the bezel on the front of the heater to gain access to the
switch. Be sure that the toggle switch is in the "ON"
position. Place the black lead of the meter on the toggle switch terminal (test point 15) that is connected to the pressure switch. Less than 220mV at this point indicates that there is a problem with the black wire that connects the pressure switch to the toggle switch. If at least 220mV is detected at test point 15, move the black meter lead to the other terminal on the toggle switch (test point 16).
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Slowly turn adjustment sprocket clockwise until heater goes off.
Figure 26. Pressure Switch Adjustment
A reading of less than 220mV here indicates a
faulty switch. If the reading is more than 500mV, turn
the switch "OFF" and then "ON" again to be sure that
the internal contacts are working correctly. The volt meter reading should drop to zero when the switch is
"OFF" and return to at least 220mV when the switch is placed back in the "ON" position.
11.5 Adjusting the Water Pressure Switch
CAUTION The water pressure switch should be adjusted to turn the heater off when the pump is off. Setting the
switchtocloseattoolowofaowcandamagethe
appliance. Adjust the switch to turn the heater off, not on.
The pressure switch is preset at the factory for activation at 14 kPa. Do not adjust the pressure switch if the heater is installed more than 4.57 m below the pool surface. Consult your local Zodiac representative for recommendations.
On some installations, the piping from the heater to the pool is very short. The back pressure could be too low to trigger the pressure switch. If this happens,
it may be necessary to install a directional tting or
elbows where the return line enters the pool. This will increase back pressure enough for the heater to operate properly.
Make sure the pool lter is clean before making any pressure switch adjustment. A dirty lter will restrict the water ow and the pressure switch cannot
be adjusted properly.
To adjust the pressure switch, refer to Figure 26 and proceed as follows:
1. Turn the heater control to OFF. See Figure 20.
2. Remove the side panel above the front header to
access the water pressure switch.
ENGLISH
Page 35
3. Start the lter pump and conrm by means of a
voltmeter that the pressure switch closes (if the switch fails to close, replace it with a switch that has a lower minimum setting).
4. Set the temperature control to the max position. Heater should start.
5. With your ngers, turn the adjustment sprocket
very slowly clockwise until the heater goes off.
6. Slowly turn the pressure switch adjustment sprocket counterclockwise one-quarter turn. The heater should come back on.
7. Check the adjustment by turning the lter pump
OFF. The burners should shut off immediately.
If they do not, restart the lter pump and repeat
Steps 5 and 6. Check the adjustment again.
8. Return the pool temperature control to the desired temperature.
It may be necessary to repeat these steps to get
a proper setting. The switch must be set so that the
heater will not re unless the pump is running. If a
proper setting cannot be reached, contact the factory service department.
11.6 Temperature Rise
The Legacy pool and spa heaters have an inter-
nal bypass which accommodates a wide range of
water ow. The bypass is easily adjustable to change
the temperature rise for optimum performance and length of heater life. The bypass assures constant heat
exchanger ow even though ow through the lter system will vary depending on how dirty the lter is.
BYPASS
ADJUSTMENT
SCREW
THERMOMETER WITH
PETE'S PLUG
Figure 27. Temperature Rise Measurement
Page 36 ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
For most installations, an external bypass valve is not needed in the heater water piping. This is due to the large size of the heater's internal bypass valve.
If the pump ow rate is known to exceed 470 lpm, an
external bypass may be needed to assure proper heater operation.
Water ow should be conrmed upon start-up of the heater and in most servicing situations. If the ow
is not normal, corrections must be made to the pool system. Flow is evaluated by determining the water temperature rise through the heat exchanger.
Before checking the temperature rise, make
sure that the pool lter is clean and that gas supply
and burner pressures are correct. If necessary, clean
all components of the lter system. Temperature rise
is measured in the return header of the Legacy. To
measure the temperature rise, turn off the lter pump
and remove the plastic plug protruding through the cabinet on the return header side of the heater. See
Figure 27. With the plug removed, install the special
®
thread adapter and Pete’s Plug
tting and insert a
pocket thermometer. A temperature rise measurement kit is available through your Zodiac distributor. See Section 12 of this manual for the correct kit number.
The internal bypass can be adjusted by means of a screw on the right-hand side of the header. To adjust
the temperature rise to within the ranges specied in
Table 7, proceed as follows:
1. If the piping system has an external bypass valve,
close it.
2. Turn the heater control panel to OFF.
3. Start the lter pump.
7. If the temperature rise is too low and cannot be raised by means of the adjustment screw, the
ow is in excess of 470 lpm. An external bypass
will need to be installed, or if one already exists, open the external bypass valve gradually until the temperature range in Table 6 is achieved.
8. If it was necessary to adjust the external bypass as outlined in step 7, scribe a line on the bypass shaft and case to mark the correct adjustment
position. Wire or remove the valve handle to
prevent tampering.
Table 6. Water Temperature Rise and Flow Rates
(Measured at Return Header)
Model Minimum
Temp Rise,
°C (°F)
125 4 (7) 5 (10) 1.9 (30)
175 6 (10) 7 (13) 1.9 (30)
250 9 (16) 11 (20) 1.9 (30)
325 11 (20) 14 (26) 1.9 (30)
400 13 (23) 16 (29) 1.9 (30)
Maximum
Temp Rise,
°C (°F)
Minimum
System Flow
lps (GPM)
In a system without external bypass, it may be
necessary to make changes. If temperature rise is too low, a manual bypass must be installed. If tempera-
ture rise is too high, there is inadequate ow, possibly
requiring a change to the piping system or a larger pump. Before proceeding with either remedy, verify proper heater operation. Low gas input results in low temperature rise and vice-versa. A problem with the heater internal bypass assembly also affects measured temperature rise.
4. After three (3) minutes, note and record the thermometer reading. This is the pool water temperature.
5. Start the heater by turning the controller to ON.
Allow the heater to operate for ve (5) minutes
or more. Note and record the thermometer reading. Subtract pool water temperature from this reading. This difference is the temperature rise. Refer to Table 6. If your measured tempera­ture rise is within the range designated for your heater, skip steps 6 through 8.
6. Locate the bypass adjustment screw on the right­hand side of the header (see Figure 22). Loosen the nut so that the screw can be adjusted. A slight water leak past the nut may be expected. Turn the screw counterclockwise to decrease the tempera­ture rise, and clockwise to increase the tempera­ture rise as needed to achieve the ranges in Table
6. After the adjustment, tighten the nut so that no leaks occur.
Section 12. Replacement Parts
12.1 Ordering Information
To order or purchase parts for the Legacy pool and spa heater, contact your nearest Zodiac dealer or distributor. See the Zodiac web site at www.Zodiac. com for the nearest service center. If they cannot supply you with what you need, contact Technical Support at Zodiac, telephone (800) 822-7933.
NOTE To supply the correct part it is important that
you state the model number, serial number and type of gas when applicable. This information is on the rating plate inside the heater.
The following pages contain a parts list, general exploded view, and detailed exploded views to aid in
parts identication. Pleas refer to these pages when
ordering parts for your Legacy pool/spa heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
12.2 Parts List
Key No. Description
Pilot/Igniter System
1 Pilot, Main Burner Assembly, Natural All R0522101
1 Pilot, Main Burner Assembly, LPG All R0522102
2 Pilot Burner, Natural All R0522201
2 Pilot Burner, LPG All R0522202
3 Burner, Main w/ Pilot Bracket All R0522300
4 * High Voltage Lead Assembly All R0493400
5 Piezo Lighter Assembly All R0355900
Main Gas Assembly
6 Burner Tray Assy, Natural Gas 125-400 R0484701-05
6 Burner Tray Assy, LPG 125-400 R0484801-05
7 Burner Tray, Shelf Only 125-400 R0469101-05
8 Gas Valve, Natural 125-400 R0486600
8 Gas Valve, LPG 125-400 R0546500
9 Manifold Assy, Natural Gas 125-400 R0485901-05
9 Manifold Assy, LPG 125-400 R0486001-05
10 Anti-Rotation Bracket All R0485200
11 Burner, Main All R0469800
12 Burner Manifold 125-400 R0485101-05
13 GasOrice,Natural All R0469200
13 GasOrice,LPG All R0469500
14 Gas Valve Fitting All R0485300
Electrical System
15 Temp Control/User Interface All R0471902
16 Temp Control/User Interface w/Housing All R0491701
17 * Wire Harness Set All R0490400
18 On-Off Switch All R0099800
19 Temperature Control Label All R0490500
20 Temperature Control with Sensor All R0318800
21 Temperature Control Bulb Gasket All R0456600
22 Thermostat Knob, Black All R0010700
23 Stop Plate, "Temp-Lok" All R0472200
24 Temperature Control Plate Assembly All R0472002
25 Stop Plate Screw All R0474600
26 Temperature Sensor Plug All R0456800
27 Water Pressure Switch Tubing All R0483600
28 Pressure Switch, 2 PSI All R0013200
29 Cap, Sensor and Pressure Switch w/
O-ring
30 * Pressure Switch, 1-10 PSI All R0015500
31 High-Limit Switch Assembly All R0514002
32 High-Limit Switch, 42°C (108°F) All R0514200
33 High-Limit Switch, 52°C (126°F) All R0514300
34 Roll-Out (Fusible Link) Assembly All R0012200
35 Roll-Out (Fusible Link) Bracket All R0337200
36 Terminal Block All R0097800
37 Nut, Sensor Retainer All R0523900
Vent System
38 Top Enclosure 125-400 R0470301-05
39 Vent Cover 125-400 R0470401-05
40 Rainshield (Partition) 125-400 R0478201-05
41 Flue Collector Assembly 125-400 R0470501-05
42 Outdoor Vent Cap 125-175 R0491606
42 Outdoor Vent Cap 250-400 R0491603-05
43 Indoor Draft Hood 125-175 R0499606
43 Indoor Draft Hood 250-400 R0499603-05
Model No. Order
Part No.
All R0455400
ENGLISH
Key No. Description
44 Adapter Plate 125-400 R0478301-05
45 * Clip All R0500200
46 Vent Temp Limit Switch Assembly All R0543101
47 Vent Temp Limit, 240°C (464°F) All R0524300
Water System
48 Inlet/Outlet Header Assy, Polymer All R0470800
49 Return Header Assy, Polymer All R0454201
50 * Header Hardware Set, Polymer All R0454500
51 Heat Exchanger Assembly, Complete 125-400 R0485706-10
52 Heat Exchanger Drain Plugs (2),
Polymer
53 3" Coupling Nut Kit w/ O-ring All R0454000
54 Bypass Assembly, Polymer 125-400 R0453701
55 Bypass Spring, Adjustable, Polymer All R0453901
56 Tailpiece w/ Union Nut (Set of 2), 50mm All R0472800
57 Header Gasket Assembly (Set of 18) All R0454300
58 * Bypass Hardware, Gaskets All R0453800
59 Heat Exchanger Tube Assy, Copper 125-400 R0490101-05
60 Plug Sensor All R0456800
Firebox Components
61 Combustion Chamber Panels 125-400 R0494906-10
Jacket Components
62 Door with Latch 125-400 R0470901-05
63 Latch Assembly All R0334900
64 Grommet, Sealing, 2" All R0460300
65 Grommet, 7/8" All R0492800
66 Rear Panel Assy 125-400 R0482301-05
Side Panel, Right All R0482400
67
68 In/Out Cover Panel, Top All R0482500
69 In/Out Cover Panel, Bottom All R0482600
70 Side Panel, Left All R0482700
71 Return Side Cover, Top All R0482800
72 Return Side Cover, Bottom All R0482900
73 Heat Shield 125-400 R0483101-05
74 HeatDeectorGuard,Front 125-400 R0483201-05
75 Rear Partition 125-400 R0483401-05
76 HeatDeectorGuard,Rear 125-400 R0483501-05
77 Controller Mounting Panel 125-400 R0483901-05
78 Plug, Button, 7/8" All R0491100
79 Weather Stripping All R0491000
Optional Components
80 * Noncombustible Base 125-400 R0471001-05
81 * Press Relief Valve Kit,75 PSI, Polymer All R0336100
82 * Temp Rise Measurement Kit All R0336000
NOTES:
1. All hardware sets contain all pieces necessary for assembly, including gaskets.
2. Gaskets and hardware are included in all kits that involve the removal of a gasket as part of the procedure to replace a part.
* PARTS NOT SHOWN ON KEY VIEW
Page 37
Model No. Order
Part No.
All R0446000
Page 38 ENGLISH
12.3 General Exploded View
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
39
42
72
43
44
71
70
49
51
41
47
46
38
40
66
77
79
16
15
64
65
63
62
61
48
61
27
70
28
35
34
75
68
5
76
69
10
74
78
67
6
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
12.4 Detailed Exploded View
5
15
19
24
ENGLISH
Page 39
36
8
9
52
13
14
14
12
18
11
21
25
59
23
20
21
7
1
3
2
57
57
53
37
29
52
33
60
52
31
54
55
48
32
Zodiac Pool Systems, Inc.
2620 Commerce Way, Vista, CA 92081
1.800.822.7933 | www.ZodiacPoolSystems.com
®
is a registered trademark of Zodiac International, S.A.S.U., used under license.
ZODIAC All trademarks referenced herein are the property of their respective owners.
©2012 Zodiac Pool Systems, Inc. H0316500 Rev F 1204
Loading...