FOR YOUR SAFETY: This product must be installed and serviced by a contractor who is gas safe registered and
HWB1 certified. Before installing this product, read and follow all warning notices and instructions that accompany
this product. Failure to follow warning notices and instructions may result in property damage, personal injury, or
death. Improper installation and/or operation can create carbon monoxide gas and flue gases which can cause
serious injury, property damage, or death. For indoor installations, as an additional measure of safety, Zodiac
Pool Systems, Inc. strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this
appliance and in any adjacent occupied spaces. Improper installation and/or operation will void the warranty.
WARNING
The GAS SAFETY (INSTALLATION AND USE) REGULATIONS 1998 as amended, place statutory requirements
on gas users.
This heater is certified to European requirements for use only as a swimming pool or spa heater. The heater must
not be used for any other purpose and must be installed and serviced by a qualified professional. The heater must
be operated strictly in accordance with the user's instructions and applicable laws.
If the heater is installed in a room, it must be separated from a living space, and adequate air supply and
ventilation must be provided and maintained.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
If these instructions are not followed exactly, a fire or explosion may result,
causing property damage, personal injury, or death.
Read this manual in its entirety. If these instructions are not followed exactly,
a fire or explosion may result, causing property damage, personal injury, or death.
H0316500 Rev F
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Table of Contents
ENGLISH
Page 3
Section 1. General Information .................... 5
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 5
Section 1. General Information
1.1 Introduction
This manual provides installation and operation
instructions for the Legacy Model LRZ millivolt pool
and spa heaters. Read these installation and operation
instructions completely before proceeding with the
installation. The installation must be conducted by a
qualied professional. While the entire manual should
be read by both the qualied professional installer
and the user, Sections 2 through 7 of this manual are
intended for the qualied professional installer. The
Operating instructions for the user begin in Section 8.
Consult the Zodiac factory, or local factory representative, with any questions regarding this equipment. The
instructions cover two (2) types of heaters as follows:
1. Type A (ueless) for outdoor installations only.
2. Type B11 ue for outdoor and indoor installations,
but must not be installed in a living space.
The Legacy model LRZ millivolt heater is a self
contained standing pilot unit and requires no external
power.
The Legacy Model LRZ millivolt heater
is specically designed for heating fresh water
swimming pools and spas, and with proper installation
and care, will provide years of reliable service. Do not
use the heater to maintain pool or spa water temperature below 21°C (70°F). Do not use it as a heating
boiler or general service water heater. Consult your
dealer for the appropriate Zodiac products for these
applications.
NOTE “Fresh water swimming pools and spas”
include systems that utilize saltwater chlorine
generator units, such as the Jandy AquaPure®
Electronic Chlorine Generator. Please ensure
that the salt content of the pool/spa does not
exceed4000ppmandwaterowrateiswithin
110-470 lpm.
1.2 Consumer Information and Safety
The Legacy Model LRZ millivolt heater is
designed and manufactured to provide many years of
safe and reliable service when installed, operated and
maintained according to the information in this manual
and the installation codes referred to in later sections.
Throughout the manual safety warnings and cautions
are identied by the "
comply with all of the warnings and cautions.
1.2.1 Spa/Hot Tub Safety Rules
Elevated water temperature can be hazardous.
Consult heater operation and installation instructions for water temperature guidelines before setting
temperature.
" symbol. Be sure to read and
WARNING
1. Spa or hot tub water temperature should never
exceed 40°C (104°F). Thirty-eight degrees
Celsius (38°C [100°F]) is considered safe for a
healthy adult. Special caution is recommended
for young children.
2. The drinking of alcoholic beverages before or
during spa or hot tub use can cause drowsiness
which could lead to unconsciousness, and subsequently result in drowning.
3. Pregnant women take note! Soaking in water
above 38.5°C (102°F) can cause fetal damage
during the rst three (3) months of pregnancy
(which could result in the birth of a braindamaged or deformed child). If pregnant women
are going to use a spa or hot tub, they should
make sure the water temperature is below 38°C
(100°F) maximum.
4. The water temperature should always be checked
with an accurate thermometer before entering a
spa or hot tub. Temperature controls may vary by
as much as 1°C (1°F).
5. Persons with a medical history of heart disease,
diabetes, circulatory or blood pressure problems
should consult their physician before using a hot
tub or spa.
6. Persons taking any medication which induces
drowsiness (e.g., tranquilizers, antihistamines, or
anticoagulants) should not use spas or hot tubs.
7. This appliance is not intended for use by persons
(including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of
appliance by a person responsible for their safety.
Children should be supervised to ensure that they
do not play with the appliance.
8. Prolonged immersion in hot water can induce
hyperthermia.
Hyperthermia occurs when the internal body
temperature reaches a level several degrees above the
normal body temperature of 37°C (98.6°F). Symptoms
include dizziness, fainting, drowsiness, lethargy, and
an increase in the internal body temperature. The
effects of hyperthermia include:
• Lack of awareness of impending hazard
• Failure to perceive heat
• Failure to recognize need to leave spa
• Physical inability to leave spa
• Fetal damage in pregnant women
• Unconsciousness resulting in a danger of
drowning
Page 6ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
1.2.2 Swimming Pool Energy Saving
Tips
Zodiac Pool Systems, Inc., ("Zodiac") offers the
following recommendations to help conserve fuel
and minimize the cost of operating your pool heater
without sacricing comfort.
1. The American Red Cross recommends a
maximum water temperature of 25°C (78°F).
Use an accurate pool thermometer. A difference
of 2°C (4°F), between 26°C and 28°C (78°F and
82°F), will use as much as 40% more gas.
2. Carefully monitor the water temperature of your
pool in the summertime. You can reduce heater
usage due to warmer air temperatures.
3. Find the proper setting on the pool heater temperature control and use the Set Point Lockout
feature to discourage further adjustments.
4. Set the pump time clock to start the pump no
earlier than 6:00 AM during the pool heating
season. This is the time when nightly heat loss
balances.
5. If the pool is only going to be used on weekends,
reduce the heater temperature control setting by
8 or 10 degrees during the week. Reset it to the
25°C (78°F) level a day or so before you plan to
use the pool.
6. During the winter or when on vacation for longer
than a week, shut down the heater by following
the shutdown instructions found on the inside of
the heater.
7. Where possible, shelter the pool from prevailing winds with well-trimmed hedges or other
landscaping, cabanas, or fencing.
8. Always use a pool cover when practical. Besides
providing a valuable safety feature, a pool cover
will reduce heat loss, conserve chemicals, and
reduce the load on lter systems.
1.3 Warranty
The Legacy Model LRZ millivolt heater is sold
with a limited factory warranty. Details are specied
on the back cover of this manual.
Make all warranty claims to an authorized Zodiac
representative or directly to the factory. Claims must
include the heater serial number and model (this information can be found on the rating plate), installation
date, and name of the installer. Shipping costs are not
included in the warranty coverage.
The warranty does NOT cover damage caused
by improper assembly, installation, operation or eld
modication. Also, damage to the heat exchanger by
corrosive water is NOT covered by the warranty. See
Section 9.1 for maintaining proper pool water
chemistry.
NOTE Keep this manual in a safe place for future
reference when inspecting or servicing the heater.
1.4 Codes and Standards
The Legacy Model LRZ millivolt heater has
been tested and certied by GL Industrial Services for
compliance with the Gas Appliance Directive (GAD;
2009/142/EC) and the latest version of European
Standard, BSEN 656. In addition, the product has
also been found to be in compliance with the essen-
tial requirements of the Low Voltage Directive (LVD;
2006/95/EC), and the Electromagnetic Compatibility
Directive (EMC Directive; 2004/108/EC).
All Zodiac heaters must be installed in accordance with the local building and installation codes as
per the utility or authorities having jurisdiction.
Any changes to the heater, gas controls, gas
orices, wiring, draft hood, vent cap, or improper
installation may void the warranty. If change is
required to any of the above, consult the factory.
1.5 Technical Assistance
Consult your local Zodiac distributor with any
questions or problems involving the specications,
installation, and operation of your Zodiac equipment.
1.6 Materials Installer Must Provide
1.6.1 Materials for All Applications
The following items are needed and are to be
supplied by the installer for all Legacy Model LRZ
millivolt heater installations:
1. The correct size gas pipe to supply gas from the
meter to the heater (see Section 4.1).
2. A manually operated gas cock to be installed in
the gas line outside of the heater jacket.
3. Plumbing items needed to provide a sediment
trap (drip leg) in the gas line between the manual
gas cock and the heater (see Section 4.1).
1.6.2 Materials for Special
Applications
In addition to the items listed above, the follow-
ing items are needed for special applications:
1. A factory authorized draft hood and any vent
pipe needed for indoor installations. See Section
3.3.2. Draft hoods are available from any Zodiac
distributor.
2. Primer and cement suitable for cementing PVC
pipe to the CPVC Zodiac unions supplied with
the heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 7
3. A noncombustible platform for installation
Section 2. Installation Instructions
on combustible surfaces (see Section 2.5.3).
Noncombustible bases are available from your
2.1 Introduction
Zodiac distributor.
4. A factory approved vent cap for all outdoor
installations where wind conditions may cause
downdrafting. Approved vent caps are available
from your Zodiac distributor. See Section 12.2,
"Parts List", of this manual for the correct part
number.
1.7Specications
1.7.1GeneralSpecications
1. Installation Location:
Certied for use:
Natural Gas: Indoor and Outdoor
LPG: Outdoor Only
Refer to Table 1.
2. Minimum Clearance From Combustible Material
See Table 4.
1.7.2PerformanceSpecications
The Legacy Model LRZ millivolt heater perfor-
mance specications are shown in Table 2.
1.7.3 Dimensions
This product must be installed and serviced by a
contractorwhoislicensedandqualiedinpool
equipment. Improper installation or maintenance
can cause nausea or asphyxiation from carbon
injury, or death. For indoor installations, as an additional measure of safety, Zodiac strongly recommends installation of suitable Carbon Monoxide
detectors in the vicinity of this appliance and in any
adjacent occupied spaces. The heater may only be
installed in a room which complies with the appropriate ventilation requirements and which is separate from living areas.
Install the Legacy Model LRZ millivolt heater,
vent caps and draft hoods in accordance with the
procedures in this manual, local codes and ordinances,
and in accordance with the latest edition of the appro-
priate national code (see Section 1.4 "Codes and
Standards").
All gas-red products require correct installation
to assure safe operation. The requirements for pool
heaters include the following:
1. Field assembly (if required)
WARNING
2. Appropriate site location (clearances) and ooring
See Figure 1 for a diagram showing the heater's
exterior dimensions and dimensions to critical connec-
3. Sufcient combustion and ventilation air
4. Properly sized gas meter and piping
tions on the heater.
Table1.GeneralSpecications
LRZ
125175250325400
Water Capacity (L)0,810,951,161,351,57
Minimum Water Flow (l/min)75,775,794,6113,6113,6
Maximum Static Head (bar)5,15,15,15,15,1
Maximum Outlet Temp (C)4040404040
Dry Weight (kg)60677888100
Gas Connection3/4 in Bsp
Water Inlet Connection2" unthreaded PVC
Water Outlet Connection2" unthreaded PVC
Electrical Supply
IP RatingIPX4
Flue TypesFlue Type A (Flueless) for Outdoor Installations Only
Note: The LPG heat inputs apply up to an altitude of 600 m. Above this altitude, de-rate the heat input by 4% for every 300 m.
(Rc 3/4)
or CPVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
Flue Type B11 (with Vent Cap for High Wind Areas) For Outdoor Installation Only
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
Flue Type B11 (with Draft Hood) for Indoor Installation Only
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
3/4 in Bsp
(Rc 3/4)
2" unthreaded PVC
or CPVC
2" unthreaded PVC
or CPVC
220-240VAC, 50 Hz,
5 Amps Max
Page 8ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
1041 mm
1000 mm
A
Outdoor Flueless Heater ConfigurationIndoor Open Flue Configuration with Draft Hood
Heater Width
Model
125384150441413
175460150457613
250578175464641
325683200479673
400822230546699
Dim "A"
mmmmmmmm
Vent Diameter
194 mm
333 mm
95 mm
Venting Dimensions
Dimension "H"
406 mm
127 mm203 mm
Outdoor Flue Configuration with Vent Cap
Outdoor
264 mm
Indoor
Dimension "H"
H
724 mm
Figure1. GeneralConguration
5. Proper electrical wiring (if required)
6. Adequate water ow
This manual provides the information needed to
meet these requirements. Review all application and
installation procedures completely before continuing
the installation.
2.2. Statutory Information
It is the law that all gas appliances are to be
installed only by competent persons (e.g., registered
members of Gas Safe) in accordance with the Gas
Safety (Installation and Use) Regulations, latest
published version of BS6798, BS5440 Pt. 1 and
Pt. 2, BS6891, and BS5482 Pt. 2. Failure to install
appliances correctly could lead to prosecution.
The Legacy heater, as supplied, has been tested
and certied by Gas Appliance Directive (GAD;
2009/142/EC) and the latest version of European
Standard, BSEN 656 for use with natural and LPG
gases. Legacy heaters are only permitted to be installed
in the open air or in a room which is separated from
living rooms and provided with appropriate ventilation
directly to the outside.
WARNING
TheLegacyheateriscertiedtoEuropeanrequirements for use only as a swimming pool or spa
heater. The Legacy heater must not be used for any
other purpose and must be installed and serviced
be operated strictly in accordance with the manufacturer's instructions. If the Legacy heater is installed
in a room, adequate air supply and ventilation
must be provided and maintained. Never store any
materials within the area of the heater or ventilation
openings.
It is important that no external control devices
(e.g., ue dampers, economizers, etc.) be directly
connected to the Legacy heater unless covered by
these installation and servicing instructions or other-
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
wise recommended in writing by Zodiac, if in doubt
please ask. Any direct connection of a control device
not approved by Zodiac, could invalidate the Gas
Appliance Directive (GAD) certication, the normal
Legacy heater warranty, and could also violate applicable gas safety regulations.
2.3 General Installation Requirements
The Legacy heater must be installed by compe-
tent persons (e.g., registered member of Safe Gas).
The Legacy heater must be installed in accordance
with the relevant requirements of the Gas Safety
Regulations, current I.E.E. Regulations, Model Water
Bylaws, local Water Authority Bylaws, and any
relevant requirements of local gas region, local authority, and relevant British Standard Codes of Practice
and Building Regulations.
2.4 Field Assembly
The Legacy Model LRZ millivolt heater is
shipped from the factory with the top assembly in
the low-prole ueless Type A conguration for
outdoor installation. The Legacy Model LRZ millivolt
heater is design certied for indoor installation when
equipped with a draft hood and Type B11 ue, which
must be installed without modication.
Check the rating plate on the heater or the Parts
List (Section 12) of this manual for the correct Zodiac
draft hood or vent cap part number. See instructions
supplied with the draft hood or vent cap for instal-
lation and attachment. When the draft hood is used,
locate the heater so as to be in the same atmospheric
pressure zone as the combustion air inlet to the heater.
2.5 Location Requirements
2.5.1 Introduction
CAUTION
When pool equipment is located below the pool
surface, a leak from any component can cause
The Legacy Model LRZ millivolt heater may
be installed indoors or outdoors as outlined in later
sections. Location of the heater below or above the
pool water level affects operation of its water pressure
switch. See sections on water piping and heater startup for more information about this.
Avoid placing the heater in locations where it can
cause damage by water or condensate leakage. If this
is not possible, provide a suitable drain pan to catch
and divert any leakage. The pan must not restrict the
air ow around the heater.
All criteria given in the following sections
reect minimum clearances as stated in the national
standards. However, each installation must also be
evaluated, taking into account the prevailing local
conditions such as wind speed and direction, proximity and height of walls that may block ventilation, and
proximity to public access areas.
2.5.2 Clearances
The heater must be placed to provide clearances
on all sides for maintenance and inspection. There
must also be minimum distances maintained from
combustible surfaces (see Table 3).
Page 10ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
At least 457 mm access must be available in
front of the heater for burner removal and access to the
igniter.
If the heater is to be installed in a garage, or
similar structure, all burners and burner ignition
devices must have a minimum 457 mm clearance
above the oor.
This heater must be installed at least 1.52 m from
the inside wall of a pool unless the heater is separated
from the pool by a solid fence, wall or other permanent
solid barrier.
2.5.3 Flooring
The heater must be installed on a level surface
of noncombustible construction or on re-resistant
slabs or arches. Noncombustible ooring is dened
as ooring material and surface nish not capable of
being ignited and burning and with no combustible
materials against the underside. Acceptable materials
are those consisting entirely of a combination of steel,
iron, brick, tile, concrete, slate, glass or plaster. Do not
install the heater directly on a combustible wood or
carpet oor without placing a noncombustible platform
between the oor and the heater.
The heater can be installed on a combustible oor
if a noncombustible base assembly, available from
Zodiac, is used. See the heater rating plate or the Parts
List (Section 12) of this manual for the appropriate
base part number. Heaters must never be installed
directly on carpeting.
As an alternative to the Zodiac noncombustible
base plate, the heater may be placed on a combustible
surface when there is a platform under the heater made
of hollow masonry no less than 102 mm thick, covered
with sheet metal at least 24 gauge thick and extending beyond the full width and depth of the heater by at
least 153 mm in all directions. The masonry must be
laid with ends unsealed, and joints matched to provide
free circulation of air from side to side through the
masonry (see Figure 2). If the heater is installed in a
carpeted alcove, the entire oor of the alcove must be
covered by a noncombustible panel.
2.5.4 Outdoor Installation
The Legacy Model LRZ millivolt heater can be
installed in the low-prole Type A ueless conguration as received from the factory. Alternately, the
heater may be installed outdoors using a Type B11
vent cap. This vent cap is used in high wind installations. No draft hood is required for this type of outdoor
installation.
Locate the heater in an open, unroofed area. Do
not install the heater under a deck. Do not locate the
heater below or adjacent to any doors, glass openings,
louvers, grills, etc., which connect in any way with an
inhabited area of a building, even though the access
might be through another structure (e.g., a garage
or utility room). There must be a minimum of 2 m
horizontally or 2 m vertically between the heater and
any door, glass opening, or gravity inlet into a building. See Figure 3.
The top surface of the heater must be at least
0.91 m above any forced air inlet, or intake ducts
located within 3.0 m horizontally.
If the heater is installed under an overhang, there
must be a minimum clearance of 1.5 m above the top
of the heater and the structure should not overhang the
heater more than 0.30 m. The area under the overhang
must be open on three (3) sides. This prevents combustion gases from being diverted into living areas
through doors, windows, or gravity inlets.
Sheet Metal Min.
Thickness 24 Ga
Table 3. Minimum Heater Clearances
From Combustible Surfaces
SIDE OF HEATERMINIMUM CLEARANCE
Millimeters
BLANK203
REAR 150
PIPING355
TOP1120
FRONT457
Note: Clearances listed in Table 4 are manufacturer's tested
values. These are given as minimum values. Where local
codes apply, and values are different than those listed in
Table 4, use the greater value to ensure safe operation.
Hollow Concrete
Block Platform
153mm
Notes:
1. Blocks must provide a solid base and be braced so they
cannot slip out of place.
2. Air openings in blocks must be arranged to provide unrestricted opening through entire width or length of base.
3. Sheet metal must be at least 24 ga. and extend 153 mm
beyond the heater jacket on all sides.
Figure 2. Noncombustible Platform
153mm
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
2m
2m
2m
ENGLISH
Page 11
If the heater is installed close to a structure,
protect it from rain water runoff with rain gutters on
the roof or other measures. Do not locate the heater
near irrigation sprinkler systems that could spray water
on it. Water from sprinklers may cause damage to
controls and electronic components.
Avoid locations where wind deection off nearby
structures might cause downdraft conditions. Where
downdraft conditions exist, locate the heater at least
0.91 m from vertical surfaces (e.g., nearby buildings
and walls).
2.5.5 Indoor for Natural Gas
Installation Only
The Legacy heater can be installed indoors using
the draft diverter available from Zodiac, and a Type
B11 ue system complying with the national and
local applicable standards in addition to the Building
Regulations (see Section 2).
Section 3. Venting
The applicable codes, standards and Zodiac,
require that the heater be properly vented as outlined
in this manual. Proper ventilation of exhaust and
combustion air are essential for the safe and efcient
operation of the heater.
3.1 Combustion Air Supply
The heater location must provide sufcient air
supply for proper combustion and ventilation of the
surrounding area.
In general, the room in which a heater is installed
should be provided with two (2) permanent air supply
openings; one within 305 mm of the ceiling, the other
within 305 mm of the oor. All indoor installations
must have uninterrupted openings to outside air for
combustion, ventilation, and dilution of ue gases
from inside the building (see Figure 4 and Table 4).
Zodiac, does not recommend indoor installations that
do not provide combustion air from outside the building.
Figure 3. Outdoor Heater Installation
Table 4. Ventilation Requirements
Positions of Air VentsAir Vent Areas
(Air Direct From Outside)
2
High Level270 cm
excess of 60 kW total rated input
Low Level540 cm
excess of 60 kW total rated input
plus 2.25 cm2 per kW in
2
plus 4.5 cm2 per kW in
Exhaust Fans or Vents: Any equipment
which exhausts air from the room where the heater
is installed can deplete the combustion air supply or
reverse the natural draft action of the venting system.
This could cause ue products to accumulate in the
room. Additional air must be supplied to compensate
for such exhaust.
The information in Table 3 is not applicable in
installations where exhaust fans or blowers of any type
are used. Such installations must be designed by quali-
ed engineers.
The heater must be completely isolated and
protected from any source of corrosive chemical fumes
such as those emitted by trichlorethylene, perchloroethylene, chlorine, etc.
WARNING
Do not store any chemicals, cleaners, or other corrosive material near combustion air openings or in
the room. Avoid locating appliance vents in the vicinity of combustion air openings. Failure to prevent
corrosive materials from mixing with combustion air
can result in reduced heater life and unsafe heater
operation.
3.2 Flue System Type B11 (Indoor)
Connect the draft diverter to a Type B11 ue
system of at least the same diameter, and end at least
0.6 meters above the highest point of the roof or other
object that is within 3.05 m of the vent. Install a certi-
ed terminal which allows a full equivalent opening
for ue products (see Figure 4). There must be at least
600 mm of vertical ue above the drafthood. Bends in
the ue should not exceed 45° to the vertical.
To make sure the heater operates safely and satis-
factorily, the ue system must be able to completely
remove combustion products at all times. The number
of bends and lengths of horizontal ue pipe used
should be kept to a minimum in order to reduce gas
ow resistance.
Compliance with all national and local applicable
installation codes and regulations should be strictly
observed.
The ue design should avoid the formation of
excessive quantities of condensate. For this reason, it
is recommended that all ues be insulated and lined.
For brick or similar structures, a stainless steel rigid
or exible ue liner (Grade 304/316) may be used in
conjunction with a 50 mm (minimum) thick layer or
Page 12ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
vermiculite or perlite granules between the liner and
the inner skin of the chimney body.
Liners should be sealed at both top and bottom.
Drainage points should be provided at the bottom of
all vertical ue sections. Drain pipes should be:
1. No less than 25 mm inside diameter.
2. Made from acid condensate resistant material
(e.g., stainless steel).
3. Positioned so that pipe runs and discharge points
are not subject to the effects of frost and ue
gases cannot leak into the boiler room.
3.3 Vent Pipe Sizing and General
Installation
3.3.1 Outdoor Installations
For outdoor installations, exhaust venting consid-
erations will determine the placement of the heater
(See Section 2.5.4). If the heater cannot be placed so
as to meet the requirements stated in Section 2.5.4,
a Type B11 vent pipe and cap may be added to the
heater to move the exhaust vent opening to a position
that complies with the requirements. When the heater
is installed in areas of high wind or when unavoidably
installed near a vertical obstruction where downdrafting may occur, it may be desirable to add a vent cap
directly to the top of the heater. In all cases, vent pipes
and caps must be of the same diameter as the exhaust
outlet of the heater. Approved vent caps may be
obtained through your Zodiac distributor.
VENT TERMINATED
AT LEAST 600 mm
ABOVE ANY OBJECT
WITHIN 3.1 m
3.1 m
LISTED FLUE TERMINAL
3.3.2 Indoor Installations (Natural
Gas ONLY)
WARNING
Vent pipe diameter must be as required by applicable local gas appliance installation codes such as
BS 5440. Undersized pipe can result in inadequate
venting and oversize pipe can result in vent condensation. In either case the result can be release of
combustion products to the indoors. This can cause
serious injury or death by carbon monoxide poisoning or asphyxiation.
All indoor installations and outdoor shelter
installations require a factory approved draft hood and
Type B11 venting. The draft hood must be installed
without modication. All vent installations must be
made in accordance with all local, state or provincial
codes and with:
Avoid long horizontal runs of the vent pipe, and
90° elbows, reductions and restrictions. Horizontal
runs should have at least a 20 mm rise per meter in the
direction of ow.
Avoid terminating heater vents near air conditioning or air supply fans. The fans can pick up
exhaust ue products from the heater and return them
inside the building, creating a possible health hazard.
Do not locate the vent terminal where ue
products could strike against building materials and
cause degradation.
Vent opening should be well away from trees
or other obstructions that would prevent free air ow
to and from vent terminal. Do not terminate the vent
under decks, stairways, or car ports.
Be sure to support all venting so that connections will not separate and so that the weight of the
vent pipe does not rest on the heater draft hood. All
connections should be made with rustproof sheet metal
screws. Do not weld or fasten the vent pipe to the
heater draft hood. The draft hood and heater top must
be easily removable for normal heater service and
inspection.
6.35 mm
minimum pitch
per meter
of horizontal
pipe
NOTE
Use approved
roof jack.
Figure 4. Indoor Installation Venting or Outdoor Shelter Venting
AT LEAST
600 mm OF
VERTICAL
FLUE ABOVE
THE DRAFT
HOOD
NON-COMBUSTIBLE
BASE
BENDS
SHOULD NOT
EXCEED 45°
DRAFT HOOD
4)
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 13
The draft hood outlet is to be connected to an
unobstructed vent pipe of the same diameter, terminating outside the building. The vent must terminate at
least 0.6 m above the highest point of the roof or other
object that is within 3.05 m of the vent termination.
The vent pipe must have a listed vent cap which allows
a full equivalent opening for ue products (see Figure
4). The top of the vent cap must be at least ve (5) feet
in vertical height above the draft hood outlet.
Double wall or equivalent vent pipe is recommended.
IMPORTANT NOTE: Do not use sheet metal screws at
the snap lock joints of gas vents.
When venting multiple appliances through one
common duct, each appliance must have its own vent
temperature limit switch. All vent limit switches must
be wired in series so as to prevent any appliance from
ring in the event of a blocked vent. Refer to national
and local installation codes for more information on
multiple venting.
3.3.3 Inspection and Replacement of
Existing Vent System with New
Components
If the Legacy heater is being installed to replace
an existing pool heater, it is recommended that a new
appropriate venting system be installed with the new
heater. However, if an existing venting system must be
used, be sure to carefully inspect the venting system to
ensure that it is in good condition and continues to be
appropriate for the Legacy heater. Replace any parts
that are not in good and serviceable condition with
new parts before completing the pool heater installation.
Section 4. Gas Connections
such as "The Gas Safety (Installation and Use)
Regulations" (Statutory Instrument 1998 No.
2451).
2. Check the gas supply to be sure that it is the same
as the gas indicated on the heater's rating plate.
3. If there is any doubt regarding the capacity of
any existing service pipes or the size required
for new service pipes then the advice of the
gas supplier should be requested. Installation
pipework should be tted and tested for gas
soundness. Zodiac recommends the gas inlet pipe
sizes listed in Table 5.
4. Use the gures in Table 5 to size the gas inlet
piping from the gas meter to the heater. Check all
local codes for compliance before installing the
heater.
Table 5. Pipe Size Requirements*
Distance from Gas Meter
Heater
Size
125202525
175252532
250253232
325323240
400324040
0-15 m15-30 m30-60 m
mmmmmm
5. Before operating the heater, test for gas sound-
ness. Do not use a naked ame.
6. If the gas supply pressure is less than required,
check for undersized pipe between the meter and
the heater, a restrictive tting, or an undersized
gas meter. Gas supply pressures to the heater are
listed in Table 2.
4.1 Gas Supply and Piping
Review the following general instructions before
continuing the installation.
WARNING
The Legacy Model LRZ pool and spa heaters are
designed for use with either natural gas or LPG.
Check the rating plate on the inner panel to be sure
that the heater is designed to use the type of gas
being supplied. DO NOT ATTEMPT TO CONVERT
THIS HEATER FOR USE WITH ANY OTHER
TYPE OF FUEL.
CAUTION
Permanent damage to the gas valve will occur if the
following procedures are not followed.
1. Gas piping installation must be in accordance
with all applicable local rules and regulations
Inlet Gas Pressure
Test Port
Gas Cock
Burner Pressure
Point
Figure 5. Fitting a Gas Service Cock
Page 14ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
4.2 Burner Pressure
Conrm that gas supply pressure is correct. If
the gas supply pressure is less than required, check for
undersized pipe between the meter and the heater, a
restrictive tting, or an undersized gas meter. Gas inlet
pressures to the heater, when it is operating, are listed
in Table 2.
CAUTION
Burner gas pressure for the Legacy Model LRZ
natural gas heaters should be set to the values
listed in Table 2.
The burner pressure may be checked by connecting a manometer to the pressure port on the burner.
Refer to Figure 5. The pressure will be zero when the
heater is not running. When the heater is operating the
burner gas pressure should be the values listed in
Table 2.
If the burner pressure indicated above is not
correct, check the gas train for possible problems.
Check the meter, gas line, gas ttings, and gas shut off
for under sizing. Check the gas valve inlet for excess
pipe dope, if all is correct, then it may be necessary to
adjust the gas valve regulator. To adjust the burner gas
pressure, rst remove the slotted cap next to the inlet
pressure port on the inlet side of the gas valve. Under
the slotted cap is a slotted plastic screw which increases the burner pressure when turned clockwise and
decreases the burner pressure when turned counterclockwise. After measurements, and adjustments if
necessary, have been made, make sure to replace the
test point plugs on the inlet and burner pressure ports,
and the cap on the burner pressure adjustment screw.
It is extremely important to replace these parts before
leaving the installation. Failure to do so can result in
damage to property or injury or death. With the heater ring, the pressure must be within the range shown in
Table 2. Also check the pressure with the heater off.
4.3 Special Precautions for LPG
LPG is heavier than air and can therefore more
readily collect or “pool” in enclosed areas if provision
for proper ventilation is not made. Installation of pool
heaters in enclosed areas such as pits is not recommended.
Consult any local code and re protection authorities about specic installation restrictions in your area.
Section 5. Water Connections
5.1 Water Piping
Figure 6 illustrates typical piping for pool equip-
ment in pool/spa combination pools.
For normal installations, do not install a shutoff
valve or any kind of variable restriction in the water
piping between the heater outlet and the pool/spa. In
special installations where a shut-off valve, diverter
valve or other variable restriction is required in the
plumbing between the heater outlet and the pool,
Zodiac recommends the installation of a pressure relief
valve on the heater (see Section 5.7).
Arrangement of pool system components other
than as illustrated in these diagrams can affect the
operation of the heater’s water pressure switch.
Location of the heater above or below the pool water
surface can also affect operation of the switch. In
general, the pressure switch can be adjusted to accommodate this effect if the heater water connections
are no more than 1.8 m below the pool water surface
and no more than 4.5 m above it. See instructions for
pressure switch adjustment (Section 5.7) in the heater
start-up section of this manual for more information
about this.
Note that when pool equipment is located below
the pool surface a leak can result in large scale water
loss or ooding. Zodiac cannot be responsible for such
water loss or ooding or the damage caused by either
occurrence.
For special installations such as water connections below the water level of the pool, or for other
questions consult your local Zodiac dealer.
5.2 Hydraulic Head Loss
To verify that the minimum ows required
for the heater are met, a hydraulic head loss curve
is shown in Figure 7. This should be checked when
installing this heater into a new or existing piping
system. This should also be consulted when installing
a new pump.
5.3 Check Valve Installation
WARNING
A check valve can interfere with the proper
operation of certain Suction Vacuum Release
System (SVRS) products. To avoid possible entrapment hazard, serious injury, or death, make
sure to review the operation/owners manual of
your particular SVRS product before installing
the check valve.
The heater must be protected from back-siphoning of water, which can result in dry starts. If there is
any chance of back-siphoning, provide a check valve
between the pool and the lter pump inlet.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Figure 6. Typical Piping Installation
AQUAPURE
ENGLISH
MANUAL BY-PASS DETAIL
MANUAL BY-PASS IS USED
WHEN FILTRATION RATE
EXCEEDS 125 GPM
Page 15
5
4.5
4
3.5
3
2.5
2
Pressure Drop (m H2O)
1.5
1
0.5
0
01002 003004 00500
Figure 7. Hydraulic Head Loss Curve
LRZ400
LRZ325
LRZ175
LRZ250
LRZ125
When an automatic chemical feeder is installed
in the plumbing, it must be installed downstream of
the heater (see Section 5.7). A check valve must be
installed between the heater and the chemical feeder to
prevent back-siphoning of chemically saturated water
into the heater where it will damage the components.
5.4 Automatic Flow Control Valve
The inlet/outlet header of the Legacy Model LRZ
millivolt heater comes equipped with an automatic
ow control valve. The automatic ow control valve
maintains the proper ow through the heater at rates
up to approximately 475 lpm. If the lter system ow
rate is higher than approximately 475 lpm, install a
manual bypass valve (see Figure 6), then perform a
temperature rise test (see Section 11.6) and adjust the
ow using the bypass valve until the proper temperature rise is obtained.
LRZ Pressure Drop vs Flow
Water Flow (L PM)
5.5 Reversible Water Connections
The Legacy Model LRZ millivolt heater is
shipped with water connections on the right side,
but can be modied in the eld to provide left-side
water connections. This procedure involves removing the heat exchanger headers and reinstalling them
on opposite ends of the tube assembly. Some of the
heater wiring must be disconnected and re-routed, so
this procedure must be done only by a trained service
technician. Heat exchanger reversals are generally
done before the installation of power and water to the
heater. If you need to reverse the heat exchanger on
a previously installed heater be sure that all electrical power, the gas supply and water supply have been
turned off before starting the procedure. These instructions have been written to include the steps needed
when reversing the water connections on an existing
installation. If you are reversing the headers on a new
installation, some steps will be ignored.
Page 16ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Water connection reversal is illustrated in Figures
8 and 9. Proceed as follows:
1. For an existing installation, drain the heater by
removing the two (2) drain plugs on the inlet/
outlet header and the drain plug on the return
header.
2. Remove the heater front panel (door).
3. Remove the I/O header side cover plates, top and
bottom. See Figure 10.
4. Remove the return header side cover plates, top
and bottom. See Figure 10.
5. Tag and disconnect the black high limit wire
leading to the pressure switch (PS) and the black
wire on the Fireman's switch terminal which
leads to the high limit switch.
6. Remove the water temperature sensor nut from
the inlet/outlet header and remove the sensor.
7. Tag and disconnect the black and white wires
from the water pressure switch.
CAUTION
In order to prevent property damage or injury, ensure that the wiring is handled and routed carefully
so as not to cause any damage to it. Additionally, be
careful not to create any kinks in the water pressure
switch copper tubing when handling the header.
8. For an existing installation, remove the coupling
nuts from the header and disconnect the water
supply from the heater.
9. Remove the 10 bolts and washers from the inlet/
outlet header and remove the header from the
tube assembly.
10. Remove the 10 bolts and washers from the return
header and remove the header from the tube
assembly.
11. For an existing installation, remove the tube
gaskets and clean the header's mating surface of
any corrosion or debris. Replace the tube gaskets
with new ones. Do not use any metal tools on the
header surface. Scratches may compromise the
seal integrity.
WARNING
To avoid product failure which can cause property
damage, serious personal injury or death, install the
inlet/outlet header with the high limit devices on the
bottom.
Figure 8. Water Connections as Shipped
DO NOT
INTALL THE
INLET/OUTLET
HEADER
UPSIDE-DOWN
THE HIGH LIMIT
DEVICES MUST
BE ON THE
BOTTOM
NOTE: When reversal
is complete the water
temperature sensor
wires and the syphon
loop tube will exit the
inlet/outlet header at
the back of the heater
and the drain plugs are
facing down.
Bypass
Assembly
Figure 9. Water Connections Reversed
VENT TOP
RETURN HEADER SIDE
COVER PLATES
TOP AND BOTTOM
LEFT SIDE PANEL
®
CONTROL PANEL
FRONT PANEL
(DOOR)
BASE
TOP PANEL
REAR PANEL
IN/OUT HEADER
SIDE COVER PLATES
TOP AND BOTTOM
RIGHT SIDE PANEL
Figure10. LegacyPanelIdentication
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 17
12. Place the inlet/outlet header over the bolts and
gasketed tubes on the left side of the tube assembly. Make sure the high limit devices are on the
bottom. Refer to Figure 9. Align the bolt and tube
holes in the header with the bolts and tubes in the
header bar and slide the assembly together.
13. Thread on the 10 bolts and washers and hand
tighten.
14. Place the return header over the bolts and gasketed tubes on the right side of the tube assembly.
Align the bolt and tube holes in the header with
the bolts and tubes in the header bar and slide the
assembly together.
15. Thread on the 10 bolts and washers and hand
tighten.
16. Use a torque wrench to tighten the bolts on each
header to 4 ft-lbs. The bolts must be tightened in
the sequence indicated in Figure 11.
CAUTION
Failure to tighten the header as indicated in step 16
may cause the header to leak or become permanently damaged from warping.
17. Remove the 3/4 inch button plug located in the
left side panel below the inlet/outlet header and
replace with the 3/4 inch wire grommet from
the right side panel below the return header.
The high limit leads were routed through this
grommet prior to removal in step 5. Install the
3/4 inch plug in the opening where the 3/4 inch
wire grommet was removed.
18. Reconnect the white wire on the pressure switch
(PS) and the white wire on the Fireman's switch
terminal.
19. Reinstall the temperature sensor in the inlet/
outlet header and tighten the nut.
20. Reconnect the black and white wires to the water
pressure switch.
21. Use plastic wire ties to refasten the temperature
sensor, high limit switch and water pressure
switch wires to each other. Bundle the wires near
the control panel and fasten them with a wire tie.
CAUTION
In order to prevent property damage or injury, be
sure that none of the wires are in contact with a
sharp edge or a hot surface.
22. Install the return header side cover plate on the
right side of the unit.
23. Install the I/O header side cover plates, top and
bottom on the left side of the unit.
24. Replace the front panel (door).
5.6 Connections at Heater
The Legacy Model LRZ millivolt heater has a
standard 2 inch water header and coupling design.
With this feature, only nominal 2 inch PVC or CPVC
may be connected to the heater. However, by installing
the appropriate pipe adapters and two (2) short pieces
of 2 inch plastic pipe (supplied by the installer), any
size existing pipe may be tted to the heater.
To connect a section of 2 inch PVC or CPVC
pipe to the heater, rst slip a coupling nut onto the
pipe. Then prepare the end of the pipe with the proper
PVC/CPVC primer and glue. Follow the manufacturer’s instructions provided with the primer and glue
for preparation procedures and curing times. Apply
the slip-t side of the coupling to the end of the pipe.
Allow the glue to cure completely. Set the o-ring
into the groove on the face of the coupling. Slide the
coupling nut up to the coupling and tighten it to the
threaded connection on the header (see Figure 12).
5.7 Pressure Relief Valve
A pressure relief valve (PRV) is recommended in
all installations, and is mandatory in any installation
in which the water ow can be shut off between the
heater outlet and the pool/spa.
A pressure relief valve is not supplied with the
Legacy Model LRZ millivolt heater. However, it is
recommended that a pressure relief valve be installed
and may even be required by local codes.
7
3
2
8
6
4
1
9
5
10
Figure 11. Header Bolt Tightening Sequence
O-RING
COUPLING
COUPLING
Figure 12. Piping to Heater
PVC OR CPVC PIPE
NUT
Page 18ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Be sure to check any applicable installation codes
in your area to determine whether a pressure relief
valve is required. See Section 12.2 (Parts List) of this
manual for the appropriate kit part number.
The pressure rating of the valve should be at or
below the lowest working pressure of any component
in the system. The maximum working pressure of this
heater is 5.1 bar.
Follow these steps to install a pressure relief valve:
1. To protect the threads while drilling, screw the
brass adapter (included with the Zodiac PRV
kit) into the blind threaded hole on the top of the
inlet/outlet header.
2. Using the countersink in the center of the blind
hole as a guide, drill a 6.4 mm (1/4 inch) hole
through the plastic (see Figure 13).
3. Open the hole by reaming it with a 9.5 mm (3/8
inch) drill bit.
4. Open the hole again by reaming it with a 12.7
mm (1/2 inch) drill bit.
CAUTION
Initially drilling a 12.7 mm (1/2 inch) hole without
reaming may cause the bit to "grab" on the plastic. This may cause personal injury or damage the
plastic header.
TEMPORARILY INSTALL
START WITH A 1/4" BIT
THEN OPEN HOLE WITH
A 3/8" BIT THEN OPEN
HOLE WITH A 1/2" BIT
Figure 13. Drill Hole for Pressure Relief Valve
PRESSURE RELIEF
VALVE HAND
TIGHTEN ONLY
RUBBER WASHER
BRASS ADAPTER TO
PROTECT PLASTIC
THREADS
BRASS ADAPTER
5. Remove the brass adapter and clean the cuttings
out of the hole.
6. Install the rubber washer at the bottom of the
hole (see Figure 14).
7. Thread the adapter into the hole and tighten so
that it seals against the rubber washer.
8. With a permanent marker, place a mark on the
adapter so that the mark faces the same direction
as the water connections on the header.
9. Remove the adapter from the hole.
10. Coat the threads of the pressure relief valve
(PRV) with an appropriate metal to metal thread
sealant.
11. Install the adapter on the PRV and tighten using
two (2) wrenches. Use the mark made earlier on
the adapter to orient the PRV to the desired direc-
tion in relation to the water connections on the
header.
12. Reinstall the adapter, with the PRV, into the
plastic threaded hole and tighten it until the mark
on the adapter is once again facing the same
direction as the water connections on the header.
Figure 14. Pressure Relief Valve Installation
CAUTION
Do not use any pipe compound or pipe dope on
the threads of the adapter or any part that comes in
contact with the plastic headers. These compounds
may damage the header over a period of time.
CAUTION
In order to prevent property damage, do not overtighten. Overtightening may crack the header.
DO NOT TIGHTEN WITH A WRENCH.
Overtightening may crack the header. Route the
discharge piping so that discharge from the pipe does
not endanger anyone near the heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 19
Refer to your local installation codes for more
detailed information. The valve setting should be
at or below the maximum working pressure of any
component in the lter system. The maximum working
pressure of the Legacy Model LRZ millivolt heater is
5.1 bar.
5.8 Auxiliary Components,
Chlorinators, Ozone Generators,
and Sanitizing Chemicals
The Legacy Model LRZ millivolt heater is
manufactured with materials that are not compatible
with high concentrations of ozone, chlorine, bromine,
or other sanitizing chemicals. Heater damage caused
by excessive chemicals or improper ozonization is not
covered by the Zodiac warranty. Be sure to adhere to
the following:
• When ozone is injected upstream of the heater,
install an offgas mixing chamber, or an ozone
bypass system between the heater and the ozone
injector to prevent ozone and air from entering
the heater.
• When chemical feeders are used, plumb the
feeder downstream of the heater and install
an in-line check valve between the heater and
the feeder (a minimum of 450 mm is required
between the heater and the check valve).
• Wire any electrical chemical feeder so that it
cannot operate unless the lter pump is running.
If the feeder has an independent clock control,
synchronize it with the lter clock.
• Never deposit chemicals directly in the pool
skimmer.
Section 6. Electrical
WARNING
This product must be installed and serviced by a
contractorwhoislicensedandqualiedinpool
equipment by the jurisdiction in which the product
will be installed where such state or local requirements exists. In the event no such state or local
requirement exists, the installer or maintainer must
equipment installation and maintenance so that all
of the instructions in this manual can be followed
exactly. Before installing this product, read and follow all warning notices and instructions that accompany this product. Failure to follow warning notices
and instructions may result in property damage,
personal injury, or death.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
6.1 Main Power
The Legacy heater does not require an external
source of electrical power to operate. The power for
the gas valve and safety circuit are generated by a
thermopile. The thermopile generates a millivolt signal
when heated by the pilot ame. Figure 15 shows the
internal electrical wiring diagram and schematic of the
heater.
6.2 Earth Bonding
CAUTION
To prevent premature failure of the appliance resulting from stray voltages and voltage differentials, the
heater must be bonded to other equipment which is
part of the pool plumbing system with a solid copper
wire not smaller in diameter than 8 AWG (10mm2).
Zodiac requires that the appliance be connected
to an "earth bonding loop" that includes all electrical
equipment in the system and on the equipment pad.
Earth bonding lugs must be connected with a solid
copper wire not smaller than 8 AWG (10mm
2
). Failure
to do so will void warranty.
Additionally, all metallic components of a pool
structure, including reinforcing steel, metal ttings
and above ground components be bonded together
(forming an “earth bonding grid”) with a solid copper
conductor not smaller than a 8 AWG (10mm
2
).
Page 20ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
TH
BK
TP
R
W
TP/TH
GAS VALVE
EARTH
BONDING
LUG
W
GENERATOR
PILOT
PILOT
WR
Figure 15. Legacy Wiring Diagram
W
ROLL-OUT SWITCH
(FUSIBLE LINK)
W
R
W
240°C (464°F)
TEMPERATURE
IGNITER
VENT
LIMIT
TEMPERATURE
CONTROL
BK
BK
HIGH
LIMIT
W
W
FIREMAN
SWITCH
BK
W
52°C
(126°F)
®
HIGH
LIMIT
42°C
(108°F)
PRESSURE
SWITCH
BKBK
BK - BLACK
R - RED
W - WHITE
H0321000 Rev E
BK
The equipment and/or appliances associated
with the pool water circulating system, including, but
not limited to, pump motors and heaters must also be
bonded together as part of the equipotential bonding
grid. Zodiac provides a special labeled earth bonding
lug on the right side of the heater to accommodate this
requirement. Consult your local applicable installation
codes/regulations for additional requirements that may
apply.
6.3 Auxiliary Time Clock Wiring
If you install a time clock to control the lter
pump operation, it is recommended that the time clock
have its own low voltage (Fireman’s) switch to turn
off the heater before turning off the pump. The switch
should shut off the heater about 15 minutes before
the lter pump shuts off. This will allow for a more
efcient operation by removing any residual heat
contained in the heat exchanger back to the pool.
To install a time clock auxiliary switch into the
heater wires (see Figure 16):
1. Remove heater door.
2. Remove the factory installed wire between termi-
nals 1 and 2 on the terminal strip (see Figure 16).
3. Connect the wires from the time clock auxiliary
switch to the two (2) terminals. Use 14 AWG (2,5
2
) stranded copper wire with a temperature
mm
rating of 105°C (221°F) or greater.
The length of the wire between the heater and
the time clock should not exceed 4.57 m. The contact
points of the time clock switch should be silver, or a
low resistance alloy.
BLACKBLACK
OR CONTROL
ROLL-OUT SWITCH
(VENT FUSIBLE LINK)
Figure 16. Time Clock Wiring or Control Connection
VENT TEMPERATURE LIMIT
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 21
Section 7. Commissioning
7.1 Heater Start-Up
1. When the heater has lit, remove the service door
and check all gas connections for soundness with
leak detection uid.
2. Check the manifold (burner) pressure setting and
adjust as necessary (see Table 1).
3. Start the adjustment procedure with the heater
cold, on full load, and with the temperature
control set at maximum. This will ensure, as far
as possible, that thermostatic shutdown does not
interfere while the pressure is being checked and
adjusted.
4. Remove the blanking screw in the manifold
(burner) setting pressure test nipple (see Figure
17) and securely connect a suitable gas pressure
gauge.
5. Light the heater and allow it to operate for about
15 minutes to stabilize the burners.
6. Check the pressure and adjust it for the appropriate heater size. Refer to Table 2. The burner
pressure setting adjuster is found on the gas
control (valve).
7. Remove the dust cover over the adjuster and,
using a screwdriver, turn the screw beneath
clockwise to increase or anti-clockwise to
decrease the pressure. Replace the dust cover
when nished.
8. Turn off the burner, disconnect the gas pressure
gauge, and replace the blanking screw in the
burner setting pressure test nipple.
9 Relight and check for gas soundness.
10. For heaters installed with a draft hood, perform
a spillage test in accordance with BS.5440:1 to
check for spillage of combustion products from
the heater draft diverter.
11. Check that the main burner responds correctly to
manual ON/OFF operations of any controls tted
in the gas control circuit.
12. Check the operation of the ame failure safety
device using the following steps:
a. Extinguish the main burner and pilot burner
by turning off the main gas inlet cock.
b. Check that the ame failure device is heard
to close within one (1) minute.
c. Wait three (3) minutes, then turn on the gas
and re-light the pilot.
13. With the pump running, check for water leaks in
the heat exchanger or water piping.
14 Adjust the water pressure switch according to the
procedure in Section 11.5.
15. Perform a temperature rise test acording to the
procedure in Section 11.6.
16. Ret the service door and return all controls to
the required settings.
Pressure Test Nipple
with Blanking Screw
Figure 17. Lighting the Pilot
Inlet Gas Pressure
Test Point
Burner Pressure
Adjustment
Section 8. Operating Instructions
8.1 Normal Operation
WARNING
Improper installation or maintenance can cause
nausea or asphyxiation from carbon monoxide in
death. For indoor installations, as an additional
measure of safety, Zodiac strongly recommends
installation of suitable Carbon Monoxide detectors
in the vicinity of this appliance and in any adjacent
occupied spaces.
The Legacy model LRZ millivolt heaters are
capable of automatic operation based on a call for
heat at a preset temperature. The heater has an internal safety system which allows operation in a variety
of conditions and prevents operation when certain
adverse conditions are encountered.
When the heater's pilot is lit and the pilot
generator is providing a millivolt signal to the safety
circuit, water is owing through the heater, and the
temperature of the water entering the heater is below
Page 22ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
the temperature control setting, an operating cycle is
initiated by the automatic control. The temperature
control circuit is closed, activating the gas valve and
the gas valve is opened. Gas ows through the burners,
is mixed with air in the combustion chamber, and is
ignited by the pilot. Operation will continue until the
temperature of the water entering the heater reaches
the temperature control setting.
If ignition is unsuccessful, or if the ame fails
during normal operation, the temperature control
circuit opens and shuts off the gas valve.
8.2 Start-Up
CAUTION
Do not use this heater if any part has been under
water.Immediatelycallaqualiedservicetechnician to inspect the heater and replace any part of
the control system and any gas control which has
been under water.
CAUTION
Should overheating occur or the gas supply fail to
shut off, turn off the manual gas control valve to the
heater.
CAUTION
Do not attempt repairs on the gas controls or appliance. Tampering is dangerous and voids all warranties.
CAUTION
Keep all objects off the top of the heater. Blocking
Vent pipes, draft hoods, and heater tops get hot!
These surfaces can cause serious burns. Do not
touch these surfaces while the heater is in operation. Adding a vent cap reduces the temperature on
the top.
WARNING
For your safety, when starting the heater, keep your
headandfacewellawayfromthelowerrebox
opening to prevent any risk of personal injury.
Be sure that there is water in the pool and that the
surface level is above the skimmer or other inlet of the
pool’s lter system.
Conrm that pool water is owing normally
through the pool system and equipment. With any
new pool or spa installation, operate the lter pump
with the heater off long enough to completely clean
the water. This will remove any installation residue
from the water. Clean the lter at the end of this
operation before starting the heater. Start the heater
in accordance with the Operating Instructions section
of this manual, with particular attention to the lighting and shutdown instructions and temperature control
operation.
The heater may not start on the rst try. Air in
the gas line or other start-up situations may cause it to
cycle.
When raising the temperature of a cold pool,
remove all time clock settings. This lets the lter
system and heater operate continuously until the water
reaches the temperature setting on the temperature
control. When that happens, the heater will automatically shut off, but the lter pump will keep running.
When the heater starts, immediately feel the
outlet header of the heater to conrm that there is
adequate water ow. The header should not be hot.
Normally, water temperature will rise only a few
degrees as it passes through the heater, and a “hot”
header or pipe indicates low water ow.
WARNING
Whentheheaterisredforthersttime,thecombustion chamber refractory binder material is driven
outbytheheatoftheame.Whitesmokeand/or
sharp odors may be emitted from the vent during
this period. Do not inhale combustion product fumes
at any time, and especially when these fumes are
being emitted. This "burn-in" period will last only a
few minutes.
8.3 Lighting and Shutdown Procedures
Before starting your heater, be sure that you are
familiar with the setting and operation of the heater
controls. Once the controls are set to your preferences,
follow the instructions outlined on the following page.
Read and follow all safety instructions rst.
A more detailed set of instructions of the operation of the controller follows in the next section.
heater must be relit following the instructions
found on the inside of the heater. A copy of
these instructions appears on the following
page.
WARNING
DO NOT attempt repairs on the gas control or
heater. Tampering can cause severe bodily injury or
death and voids all warranties.
WARNING
Do not attempt to operate the heater with the door
off. Doing so may cause severe bodily injury.
8.3.1 Lighting the Heater
Full lighting and shutdown instructions can
also be found attached to the wall inside the control
compartment door. See Figure 18.
1. Remove the service door on the front of the
heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 23
WARNING
LP Gas Models: Toavoidpossibleinjury,reand
explosion, read and follow these precautions and
all instructions on this appliance before starting the
heater. LP (propane) gas is heavier than air and
will remain at ground level if there is a leak. Before
lighting, sniff at ground level. If you smell gas, follow
these rules:
1. DO NOT light matches. DO NOT turn electric
lights or switches on or off in area. DO NOT use
an electric fan to remove the gas from area.
2. Shut off gas at LP tank.
3. Telephonegascompanyandredepartment
for instructions. Give your name, address and
phone number.
If your LP tank runs out of fuel, turn off gas at the
2. Turn gas control knob clockwise until it stops at
“ ” (OFF) position.
3. Wait five (5) minutes before lighting pilot.
4. Turn knob on gas valve counterclockwise to
“ ” (PILOT) then push control knob all the way and
hold down. Push the button of the sparker, repeating
until confirming that pilot lights, by observing reflection
on burner tray mirror. Continue to hold the control knob
in for about one (1) minute after the pilot is lit. If it goes
out, repeat steps 3 and 4.
5. Turn gas control knob counterclockwise to “ ”
(ON).
6. After replacing door, set thermostat to desired setting
and turn appliance ON/OFF switch to “ON”. Valve has
built-in delay before coming on.
RELIGHTING
If pilot goes out, repeat steps 1 through 6.
TO SHUT OFF HEATER
To shut off main burners turn gas control knob
clockwise until it stops at “ ” (PILOT). For
complete shut-off press down slightly on knob while
turning clockwise to “ ” (OFF). Do not force.
Position ON/OFF switch to “OFF”.
Control Knob
with OFF, Pilot
and ON Position
Pilot Adjustment
Regulator
IMPORTANT INFORMATION
1. CAUTION: Do not store pool chemicals or flammable
materials near this appliance.
2. PH LEVEL: Pool Water must be maintained between 7.4
and 7.6 when operating unit (See section entitled "Water
Chemistry" in operating manual).
3. BACKWASHING: Turn heater off 20 minutes before
backwashing or shutting down filter to prevent damage
to unit.
4. WINTERIZE: All gas to unit must be shut off and all water
drained from unit to protect it from freezing damage.
NOTE: THIS DOOR MUST BE FITTED TO UNIT DURING
NORMAL OPERATIONS.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS
OR ANY OTHER APPLIANCE.
NOTE: SOME EXPOSED PARTS OF THIS HEATER MAY BE
HOT WHEN OPERATING.
®
H0320600 Rev B
Figure 18. Legacy Lighting and Shutdown Procedures
Page 24ENGLISH
Control Knob
with OFF, Pilot
and ON Position
Regulator
Figure 19. Natural Gas/Propane Control Valve
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Pilot Adjustment
2. Turn the gas control knob clockwise until it stops
at the OFF position (see Figure 19).
3. Wait ve (5) minutes before lighting the pilot.
4. Turn the knob on the gas valve counterclockwise
to PILOT, then push the control knob all the way
and hold down. Push the button of the sparker,
repeating until conrming that the pilot lights by
observing the reection on the burner tray mirror.
Continue to hold the control knob in for about
one (1) minute after the pilot is lit. If it goes out,
repeat Steps 3 and 4.
5. Release the control knob and verify that the pilot
is lit.
6. If the pilot burner does not remain lit when the
button is released, press and release the red
button. Wait at least three (3) minutes and then
repeat the lighting procedure from step 4.
7. If the pilot cannot be established, check that the
pilot burner ame correctly envelops the thermocouple tip by 10 to 13 mm. If not, check that the
pilot adjustment screw on the gas control (see
Figure 19) is fully unscrewed, then turn it one (1)
turn back in. Check that the thermocouple lead
connections at the gas control and at the overheat
thermostat are clean and secure. Repeat from
Step 4.
8. Turn gas valve knob to ON. Replace the service
door.
9. Turn the rocker switch to ON.
8.3.2 Relighting the Heater
If the pilot goes out, repeat steps 5 through 7 in
Section 8.3.1.
8.3.3 Shut-Down Procedure
1. To turn the main burner off, turn the rocker
switch to OFF.
2. To turn the heater off (including the pilot), turn
the gas valve knob to the OFF position.
8.4 Turning the Heater On/Off and
Setting the Temperature Control
The temperature control (see Figure 20) is
calibrated at the factory and covers a range from
approximately 21°C to 40°C (70°F to 104°F). Use an
accurate pool thermometer to determine the best water
temperature for your use.
The Legacy temperature control panel has a
rocker switch to turn the heater on and off. It also has
a rotary dial to set the desired thermostat setting (see
Figure 20).
Once the heater has been lit by following the
safety and lighting procedures in Section 8.3, set the
toggle switch on the control panel to "ON" to start the
heater operation. If the heater senses that the pump
is on and the thermostat setting is higher than the
temperature of the pool/spa water, the pilot will ignite
the main burners.
CAUTION
In order to prevent property damage, the heater is
designedtorunonlywhenthelterpumpisrunning. If the heater does not immediately turn off
when the pump turns off, turn the heater off at the
control panel. The heater's pressure switch may
need adjusting (see Section 11.5)
10. Set temperature control to against the Temp-Lok
tab. The main burner should light. Until the water
reaches a temperature of about 21°C (70°F), it is
normal to have some water accumulating in the
base of the heater.
11. Set the time clock, if one is installed.
H0286600
Figure 20. Temperature Control
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 25
Once the pool/spa water temperature reaches the
thermostat setting, the heater will automatically stop
ring. As the pool/spa water temperature falls below
the thermostat setting the heater will once again start
the heating cycle.
Rotate the thermostat dial clockwise to increase
the temperature setting and counterclockwise to
decrease the setting. It may take several attempts to
set the thermostat dial to the desired temperature. Be
sure to use an accurate thermometer to measure water
temperature. Once the desired temperature setting is
found, loosen the screw on the Temp-Lok ring and
rotate the ring until the stop rests against the knob.
Tighten the screw to hold the knob in position. This
will prevent accidental moving of the dial and possible
overheating of the water.
IMPORTANT: The temperature controls cannot
be calibrated in the eld. If the control is faulty,
shut down the heater by following the procedures in
Section 8.3 and have a qualied service technician
replace the control. DO NOT use the thermostat switch
to completely shut down the heater.
Section 9. Maintenance
Table 7. Optimal Water Chemistry Ranges*
TestRecommended Level
Free Chlorine1.0 to 3.0 ppm
Bromine2.0 to 4.0 ppm
pH7.4 to 7.6
Total Alkalinity (TA)80 to 120 ppm
Calcium Hardness (CH)175 to 400 ppm
Cyanuric Acid10 to 50 ppm
Total Dissolved Solids
(TDS)
Copper0 ppm
* Concentration levels taken from "Basic Pool and Spa
Technology" published by APSP (Association of Pool and Spa
Professionals).
1000 to 2000 ppm (Excluding dissolved NaCl from a Salt Chlorine
Generator)
9.2 Seasonal Care
CAUTION
Do not operate this heater outdoors at temperatures below 20 degrees Fahrenheit (°F) (-7 degrees
Celsius [°C]).
9.1 Water Chemistry
The mineral content of swimming pool water
increases daily due to natural evaporation and the
addition of sanitizing chemicals. If the mineral concentration in the pool gets too high, the excess miner-
als will deposit on the walls of the pool, in the lter
system, and in the heater tubes.
The proper chemical balance in spa water is
more critical than in a swimming pool heater operation. Due to the spa's size, high water temperature and
heavy usage, chemical values in a spa can vary greatly.
This chemical imbalance can result in unsanitary water
conditions, and affect the life of the heater.
Proper chemical balances are necessary for
sanitary bathing conditions as well as ensuring your
heater's long life. Kits are available from your local
pool supply dealer for making the various tests for
mineral content. One of these kits will detect copper
in the system. This is usually a warning that corrosion is taking place, possibly due to a low pH value
combined with other chemistry problems. The condition can be corrected by changing the spa water and
closely monitoring the pH factor and chemical properties of the water. Be sure to keep your chemical levels
within the values indicated in Table 7. Zodiac does
not warrant heat exchangers damaged by corrosive
chemical levels or excess dissolved solids in pool or
spa water.
For spas, it is also necessary to perform water
changes in addition to chemical treatment. It is recommended to change the spa water every 60 days for light
usage and every 30 days if usage is heavy.
9.2.1 Spring and Fall Operation
During periods when the pool is only going to be
used occasionally, turn the temperature control down
to the MIN setting. This prevents the pool water from
becoming chilled, and minimizes the time required to
raise the pool water back up to the desired temperature.
In areas subject to only short freeze periods, turn
off the heater and run the pump continuously for the
length of the freeze period.
If the heater is not going to be used for a long
period of time, shut it down completely. Refer to
Figure 19 and follow the instructions found on the
inside of the heater:
9.2.2 Winterizing
In areas where freezing temperatures occur in
winter, and the pool or spa will not be used, have your
service technician perform the following steps:
1. Turn off the main gas supply valve to the heater,
outside the heater jacket.
2. Remove heater door.
3. Shut down the heater following the shutdown
instructions found on the inside of the heater or
Figure 19.
4. Remove the drain plug from the inlet/outlet
header, and completely drain the heater before
the rst frost. See Figure 21.
Page 26ENGLISH
O-RING
DRAIN PLUG
Figure 21. Draining the Heater
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
9.3 Inspection and Service
The Legacy heater is designed and constructed
to provide long performance life when installed and
operated properly under normal conditions. Periodic
inspections, especially at spring start-up, are impor-
tant to keep your heater running safely and efciently
through the years.
WARNING
Improper installation or maintenance can cause
nausea or asphyxiation from carbon monoxide in
5. After all water has drained from the heater, check
for mineral buildup in the openings.
6. Use compressed air to blow out any standing
water remaining in the heat exchanger.
7. Inspect the gaskets on the drain plugs and
reinstall the plugs, but do not tighten.
8. Disconnect the pressure switch from the copper
tubing. See Figure 22.
9.2.3 Spring Start-up
To restart the heater in the spring, have a profes-
sional service technician reassemble the heater as
follows:
1. Attach the copper tubing to the pressure switch
(see Figure 22).
2. Tighten the drain plugs.
3. Turn on the lter pump and circulate water
through the heater for ve (5) minutes. Check for
leaks while circulating.
9.3.1 Owner Inspection
Zodiac recommends that you inspect the heater
on a continual basis and especially after abnormal
weather conditions. The following basic guidelines are
suggested for your inspection:
1. Keep the top and surrounding area of the heater
clear of all debris.
2. Keep the area around and beneath the heater
clean and free of all combustible materials such
as paper, leaves, etc.
CAUTION
Donotstoreorusegasolineorotherammable
vapors, liquids or chemicals in the vicinity of this or
any other appliance.
WARNING
Do not use this heater if any part has been under
water.Immediatelycallaqualiedservicetechnician to inspect the heater and replace any part of
the control system and any gas control which has
been under water.
4. Turn on the main gas supply valve to the heater,
outside the heater jacket.
5. Turn on the heater following the lighting instructions found on the inside of the heater, or Figure
19 of this manual.
Pressure Switch
Disconnect here
(Winterizing)
Figure 22. Pressure Switch Copper Tubing
Copper
Tubbing
3. If the heater is equipped with a pressure relief
valve, check for corrosion in and around the
valve. Twice a year, with the lter pump on, lift
the release lever on the top of the valve to make
sure that water runs freely through it. If corrosion
is found, replace the pressure relief valve. When
replacing the valve, be sure that the pump is off.
Install the valve so that the discharge is directed
away from any area that may be damaged by
water.
4. Be sure all combustion air and ventilation
openings are not blocked. Check for spider webs
and other debris inside the heater, in the vents on
all sides of the heater jacket and in the exhaust
outlet– especially after a long period of nonuse.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
9.3.2 Professional Inspection
Inspections performed at least once a year by
a qualied technician are required to maintain your
heater's safe and efcient operation. The following
basic safety checks must be performed.
1. Inspect the venting system for blockage, leakage,
and corrosion.
2. Inspect burners and verify that they are clean.
Clean with a wire brush if necessary to remove
debris.
3. Check for spider webs and other debris in the
pilot and main burner orices - especially at
spring start-up.
4. Check for loose or broken wires and terminal
connections.
5. Make sure that the pressure switch operates
properly by shutting the lter pump off and on
a few times. The burner should go off immediately after the pump stops. An ignition sequence
should start shortly after the pump is turned back
on.
ENGLISH
Pilot, Thermopile and Thermocouple Position
ThermocoupleThermopile
Main Burner Flame Pattern
Page 27
6. Make a visual check of the main burner and pilot
ame patterns. The ame can be seen in a mirror
arrangement held beneath the burners. The ame
should be:
a. Blue in color.
b. 25 mm to 102 mm above burner surface (see
Figure 23).
7. Inspect the gas and electronic controls, including
the following:
a. High temperature limit switch
b. Water pressure switch
c. Automatic gas valve
d. Roll-out switch (fusible link)
e. Temperature control
F. Vent temperature limit
8. Perform a temperature rise test in accordance
with Section 11.6.
9. If the heater is equipped with a pressure relief
valve, check for corrosion in and around the
valve. With the lter pump on, lift the release
lever on the top of the valve to make sure that
water runs freely through it. If corrosion is found,
replace the pressure relief valve. When replacing
the valve, be sure that the pump is off. Install the
valve so that the discharge is directed away from
any area that may be damaged by water.
Figure 23. Pilot, Thermopile and Thermocouple
Positions, and Main Burner Flame Patterns
10. Inspect the external surfaces of the heat exchanger tubes for black carbon soot buildup by placing
a mirror between and under the burners when the
heater is ring. Remove any soot that has collected on the tubes, and correct the cause.
heat exchanger for black carbon soot buildup
after the following periods of operation: 24
hours, 7 days, 30 days, 90 days, and once
every 6 months thereafter.
11. Conduct a normal operating cycle and observe
that the sequence proceeds as intended.
CAUTION
For your safety, when starting the heater, keep your
head and face away from the burner area opening
to prevent any risk of personal injury.
NOTE Keep this manual in a safe place for future
reference by you and your professional
technician when inspecting and servicing the
heater.
Page 28ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
Section 10. Troubleshooting
10.1 General Heater Troubleshooting
Table 8 lists some of the more common
problems, causes and solutions encountered when
running the heater. Most problems occur when the
heater is being started for the rst time after installation or at spring start-up. Careful installation and
maintenance will help ensure years of trouble free use
from your Legacy heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Table 8. Legacy Troubleshooting Guide
#
SymptomCauseRemedy
1.Pump not operating
A. No power.
B. Pump defective.
C. Incorrectly wired.
A. Check circuit breakers and power source.
B. Replace pump.*
C. Recheck wiring.*
ENGLISH
Page 29
2.Pilot outageA. Inlet gas pressure too low.
B. Inlet gas pressure too high causing
an unstable blowing pilot.
C. Weak or defective thermocouple or thermopile.
D. Damaged pilot, thermocouple or thermopile.
E. Dirty pilot.
A. Blockedue.
B. Pilot out of position (delayed ignition).
C. Blocked heat exchanger.
D. Refractory blanket out of place.
E. Altered vent cap.
F. Low gas pressure.
A. Cold chimney.
B. Vent pipe pitches down to chimney.
C. Blocked chimney.
D. Altered draft hood.
E. Prefabricated chimney with incorrect cap.
A. Low primary air.
B. Incorrect burner pressure.
B. Low burner gas pressure.
C. Heater size inadequate.
D. Low temperature rise.
A. Inadequatewaterowthroughheater.A. Check temperature rise between inlet and outlet heater
A. Low water temperature.A. Flue product moisture will condense at the start-up until the
A. Restrictioninwaterowsystematordownstream of heater.
A. Consult gas utility company. Inlet gas pressure to
heater should be 13.7 to 24.9 mbar on natural
gas. 24.9 to 34.8 mbar on propane gas.*
B. Pressure should be regulated within limits shown above.*
C. Replace thermocouple or thermopile.*
D. Replace.*
E. Blow dust or lint out of pilot.*
A. Remove blockage.*
B. Correct pilot position.*
C. Clean and correct as necessary.*
D. Clean and correct blanket as necessary.*
E. Install an unaltered factory approved vent cap.*
F. Check and correct gas pressure.*
A. Allowheatertooperateve(5)minutestocreatedraftaction.
B. Reinstall vent pipe to pitch up from the heater to chimney.*
C. Remove blockage.*
D. Install factory-provided draft hood.*
E. Install U.L. listed vent cap.*
A. Check for internal burner obstructions.*
B. Adjust burner pressure according to rating plate.*
Clean burner ports if dirty.*
A. Gas meter too small. Gas line from meter to heater too small.*
B. Gas pressure on heater burner should be adjusted to the
values list in Table 2.*
C. Replace with heater of higher input.*
D. Checkandcorrectwaterow.*
piping. See section 11.6 for recommended range of
temperature rise. If temperature rise is above the maximum
recommended, check for closed valve in system.*
heater water temperature reaches the normal operating
conditions.*
A. Check for proper operation of all valves, bypass valve and
any equipment between pool and heater outlet.*
A. Turn knob to “on” position.
B. Investigate reason for overheating and replace hi-limit switch
as necessary.*
C. Adjust pressure switch (see Section 11.5) or replace as
F. Check continuity through thermostat circuit with wires
disconnected.*
G. Check heater wiring against wiring diagram in Section 6,
correct as necessary.*
H. Thoroughly investigate the causes for vent temp limit failure,
correct the problem and replace the vent temp limit.
A. Increase size of pump or increase piping size.*
B. Check hi-limit switches and replace as necessary.*
Page 30ENGLISH
Section 11. Professional
Maintenance and Service
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
EXHAUST
VENT TOP
WARNING
SERVICING SAFETY
Some of the servicing procedures for the Legacy
heater are hazardous because they involve fuel
gas, electricity, moving parts and procedures which
require testing or temporary bypass of safety controls. For this reason, the heater must be serviced
The Legacy heater incorporates unique design features. Incorrect service of this heater can result in
property damage, personal injury or death. To avoid
such hazards, the heater must be serviced only by
aqualiedprofessionalservicetechnician.
11.1 General Information
A qualied professional technician must
service the Legacy model LRZ millivolt pool heater
using Zodiac service procedures. Before calling for
service, however, the owner should check for obvious
problems. The other components in the pool system,
including pump, lters and strainers, water valves, gas
supply and time clocks have an effect on heater operation.
Conrm that the Legacy heater control switch is
set to 'ON' and that the temperature control knob is set
high enough to make the heater operate. Make sure the
pump is operating, that the lter and strainers are not
clogged, that there are no mis-positioned water valves,
that the gas is not shut off and that time clocks are
properly adjusted. Also be sure that there is no blockage of the vent or louvers which supply combustion air
to the burners.
11.2 Natural-Draft Combustion System
The Legacy model LRZ millivolt pool heater
has an atmospheric combustion system. This system is
illustrated in Figure 24.
As the heated exhaust gases rise out of the
combustion chamber, ow is created through the
system and fresh combustion air is drawn into the
heater through the louvers cut into the front and sides
of the heater. Gas is forced through an orice into
the open end of a burner. When the gas ows into the
burner, a “negative” pressure is created at the opening
of the burner. This negative pressure pulls air into the
burner with the gas and mixes the two together. As
the gas/air mixture ow through the burner ports it
is ignited in the combustion chamber. Hot combus-
tion products then rise through a highly efcient heat
exchanger. Combustion products then enter a ue
collector and are directed to the outdoors through the
grate top of the heater or a vent pipe and cap.
FLUE COLLECTOR
HEAT EXCHANGER
AIR FLOW
Figure 24. Atmospheric Combustion System
COMBUSTION CHAMBER
BURNER
BURNER TRAY SHELF
11.3 Heater Components and Their
Operation
1. Gas Valve / Regulator - The gas valve controls
gas ow into the burner. It provides ow only
when the temperature controls require heat and
only if all safety controls enable operation. It is
also a positive pressure regulator. It regulates
the gas pressure in the burner to specications
addressed earlier in this manual. This is necessary for proper operation of the burner system.
2. Temperature Control - The Zodiac Legacy
pool/spa heater is controlled by a mechanical
thermostat which controls heater operation to
bring the water to the desired temperature. The
desired temperature is set by rotating a knob on
the face of the control panel. To achieve accurate
water temperatures, the pool/spa water must be
monitored with an accurate pool thermometer.
3. Pilot/Pilot Ignition - The Legacy heater relies
on a standing pilot to ignite the burners when the
temperature control calls for heat. When lit, the
pilot receives a constant ow of gas from the gas
valve. If the pilot extinguishes, the gas valve is
automatically signalled to stop the ow of gas to
the pilot and the burners to prevent a gas build
up in the heater. Igniting the pilot is achieved by
means of a piezo spark igniter mounted on the
inner front panel of the controls compartment of
the heater.
4. Pilot Generator (Thermopile) - The pilot gener-
ator is a device, that when heated by the ame
of the pilot, generates a small electrical voltage
of approximately 750 millivolts. The voltage
is placed across the temperature controller and
safety circuit of the heater. If this current is
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 31
broken at any time, the gas valve is immediately
shut off and the heater stops ring. This voltage
is also used to activate the gas valve's pilot coil
which allows gas to ow to the pilot after the gas
valve knob is released.
4. Thermocouple - The thermocouple is a device
that senses if the pilot ame is hot enough to
ignite the gas fuel from the burner. If hot enough,
the main gas valve is allowed to open. If the
thermocouple does not sense enough heat from
the pilot ame (such as when the pilot is out),
then the thermocouple shuts off the gas valve to
the burners.
5. Limit Switches - Two (2) limit switches prevent
excessive water temperature - one (1) within the
heat exchanger and one (1) for water leaving the
heater. If either senses excessive temperature,
burner operation is interrupted.
6. Water Pressure Switch - This control senses
whether or not water is available to the heater
by measuring back pressure inside of the heat
exchanger. If the pool water pump fails or the
water lter is blocked, the pressure switch
prevents operation of the burner.
7. Roll-Out Switch (Fusible Link) - This is
a single-use switch which detects abnormal
temperature in the component vestibule. It is a
roll-out switch (fusible link) which is held to
the inner panel just above the burner tray by a
sheet metal bracket. Excessive temperature in
the component compartment, possibly due to a
blocked ue or ame roll-out, will cause the link
to fail. This opens the safety circuit which shuts
off the gas valve and shuts the heater down.
8. Vent Temperature Limit - This is a single-use
switch which detects abnormal temperature in the
vent system. It is mounted to the ue collector
assembly. Excessive temperatures will cause the
switch to open. Excessive temperatures can be
caused by inadequate water ow or a damaged
heat exchanger. The vent temperature limit will
open the safety circuit which shuts off the gas
valve and shuts down the heater.
11.4 Electrical Troubleshooting
This section describes procedures for check-
ing the pilot generator and control components of the
heater one at a time and in the order they appear in the
control circuit.
NOTE Pump must be running during the
troubleshooting procedure.
These procedures require a voltmeter with a
minimum 0-1000 mVDC range. Figure 25 shows the
pilot generator and control circuits, and where to take
measurements. Location numbers and letters in circles
have been added, and will be referenced in the follow-
ing sections.
As stated at the beginning of this manual, some
of these procedures are hazardous. Only a qualied
service technician should service the heater.
During the trouble shooting procedure, the lter
pump must be on, the pilot on the heater must be lit,
the ON/OFF switch on the heater must be in the ON
position and the control knob must be turned to the
maximum setting so that there is a call for heat. We
recommend turning the gas valve control knob to the
"PILOT" position to prevent the main burners from
ring throughout the procedure. Before starting the
procedure, be sure that the pilot has been lit for at least
two (2) minutes and that the pilot generator (thermo-
pile) is positioned correctly within the ame of the
pilot.
The pilot generator also operates the pilot coil of
the gas valve, allowing gas to ow to the pilot when
the gas valve knob is released from the pilot light-
ing position (see Section 8.3 "Lighting and Shutdown
Procedures"). If the pilot will not stay lit when the gas
valve knob is released, check the pilot generator output
as described in Section 11.4.2 and replace if necessary.
If the pilot generator output is sufcient, then check
the gas valve as outlined in Section 11.4.1.
11.4.1 Gas Valve
The gas valve consists of two (2) separate
internal operating valves. The main valve supplies
gas to the main burners for heater operation. The pilot
valve supplies gas to the pilot when the pilot generator
activates the pilot coil.
If the pilot will not stay lit after following the
lighting instructions in Section 8.3, check for the
following:
• Pilot generator output
• Correct type of gas supplied
• Correct gas supply pressure
• Air in the gas line
• Pilot coil wire connections clean and tight
• Faulty thermocouple
If the pilot will not stay lit after checking the
items listed above, the pilot coil may be causing the
fault. Replace the gas valve.
If the main burners will not light after following the lighting instructions in Section 11.4.2, check
the voltage reading between the PP terminal on the
gas valve (test point 1) and the TH terminal on the
gas valve (test point 17). If the meter shows less than
220mVDC then there is a problem with the pilot
generator, the sensors in the safety loop or the control
panel. Follow the trouble shooting procedure as
outlined in sections 11.4.2 through 11.4.7.
If the meter shows more than 220mVDC at test
point 17, then check for the following:
Page 32ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
GAS VALVE
EARTH
BONDING
LUG
TP/TH
2
17
TH
TP
R
W
GENERATOR
W
PILOT
TEMPERATURE
BK
BK
1
HIGH
LIMIT
W
3
ROLL-OUT SWITCH
(FUSIBLE LINK)
PILOT
WR
R
W
4
W
5
240°C (464°F)
TEMPERATURE
IGNITER
VENT
LIMIT
W
6
7
W
FIREMAN
SWITCH
BK
9
8
W
52°C
(126°F)
1112
10
®
16
HIGH
LIMIT
42°C
(108°F)
CONTROL
BKBK
13
BK - BLACK
R - RED
W - WHITE
15
PRESSURE
SWITCH
BK
BK
14
H0321000 Rev E
Figure25. TestPointIdenticationDiagram
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
ENGLISH
Page 33
• Correct type of gas supplied
• Correct gas supply pressure
• Correct gas burner pressure
• Correct orice size
• Air in the gas line
If the main burners will not stay lit after checking
the items listed above, the gas valve may be causing
the fault. Replace the gas valve.
11.4.2 Pilot Generator
The pilot generator generates a 700-750mVDC
signal when heated by the pilot ame. When the pilot
generator is connected to the heater's control components, there will be some voltage drop in the circuit so
that the measured voltage will be less than 750mVDC.
But the measured voltage should never be below
500mVDC when the ON/OFF switch is in the "OFF"
position or 220mVDC when the ON/OFF switch is in
the "ON" position.
With the pilot generator connected to the gas
valve and the ON/OFF switch in the OFF position,
place the red lead of the voltmeter on the TPP terminal (test point 1) of the gas valve. Place the black lead
of the meter on the TPP/TH terminal (test point 2) of
the gas valve. The meter should show a minimum of
500mVDC. If the meter show less than 500mV, check
for partial shorts, loose or corroded connections or
partially broken wires between the pilot generator and
the gas valve.
If the wires and connections are sound, check the
pilot generator output. You will need alligator clips
to do this. Disconnect the pilot generator from the
gas valve. The pilot will go out. Light the pilot while
pressing down on the gas valve control knob. Continue
holding the knob for at least one (1) minute. Immediately measure the voltage between the two (2) wires of
the pilot generator. If the meter does not show at least
700mV, replace the pilot generator.
11.4.3 Roll-Out Switch (Fusible Link)
Check the voltage going to the safety circuit. Be
sure that the pilot generator is correctly wired to the
gas valve, the pilot is lit and the control knob on the
gas valve is in the "PILOT" position. Leave the red
voltmeter lead in place at test point 1. Touch the black
lead of the meter to the terminal of the roll-out switch
(fusible link) where the white wire from the gas valve
is connected (test point 3).
If no voltage is detected at test point 3, the wire
between the gas valve and the roll-out switch (fusible
link) is broken. Replace the wire.
If there is a minimum of 220mV at test point 3,
move the black meter lead to the other terminal of the
roll-out switch (fusible link) (test point 4).
If no voltage is detected at test point 4, the
roll-out switch (fusible link) has failed. This indicates
higher than normal temperatures in the component
compartment (vestibule). Normal component compart-
o
ment temperature is well below 148.9°C (300
F).
The roll-out switch (fusible link) is designed to fail
at temperatures above 151.7°C (305°F). Excessive
temperature might be due to a blocked ue or heat
exchanger. Clean the heat exchanger and clear the
ue and vent of any restrictions. Sometimes the rollout switch (fusible link) fails due to ame roll-out.
Flame roll-out may be caused by delayed ignition or
downdrafting in windy areas. Thoroughly investigate
the causes for ame roll-out and correct the problem
when replacing the roll-out switch (fusible link).
Check the voltage going to the vent temperature
limit. Leave the red voltmeter lead in place at test
point 1. Touch the black lead of the meter to the terminal of the vent temperature limit where the white wire
from the roll-out switch (fusible link) is connected
(test point 5).
If no voltage is detected at test point 5, the wire
between the roll-out switch (fusible link) and the vent
temperature limit is broken. Replace the wire.
If there is a minimum of 220mV at test point 5,
move the black meter lead to the other terminal of the
vent temperature limit (test point 6).
If no voltage is detected at test point 6, the vent
temperature limit has failed. The vent temperature
limit will fail due to abnormal temperatures in the vent
system. Excessive temperatures will cause the switch
to open.
The vent temperature limit is designed to fail
at temperatures above 464°F (240°C). Excessive
temperatures can be cause by inadequate water ow
or a damaged heat exchanger. Thoroughly investigate
the causes for vent temperature limit switch failure and
correct the problem when replacing the vent temperature limit.
11.4.4 Fireman Switch and External
Interlocks
Check the voltage going to the external device.
Touch the black lead of the meter to the reman switch
terminal strip where the white wire from the roll-out
switch (fusible link) is connected (test point 7). The
meter should read at least 220mV. If the voltage is
less than 220mV, there may be a bad connection or
wire between the roll-out switch (fusible link) and the
terminal strip. The wire may need to be replaced. If
voltage of 220mV or more is detected at test point 7,
move the black lead of the meter to the reman switch
terminal strip connection where the white wire from
the high limit is connected (test point 8). The meter
should read at least 220mV. If there is no voltage, the
time clock switch or other external interlock may be
mis-adjusted, mis-connected or defective. Correct this
external problem.
Page 34ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
11.4.5 Limit Switches
Since the limit switches are not easily accessible,
you can check the voltage going into the component
after the limit switches in the circuit. If voltage is
detected there, then the limit switches are closed and
are operational.
Check the voltage going to the water pressure
switch. Leave the red voltmeter lead in place at test
point 1. Touch the black lead of the meter to the terminal of the water pressure switch where the black wire
is connected (test point 13).
If the voltage is less than 220mV, there may be
a bad connection, a partial short or a faulty sensor. If
there is no voltage, one of the limit switches is open.
This is normally due to excessive water temperature, which should be thoroughly investigated before
replacement of limit switches. Excessive water temper-
ature may be caused by low water ow. Water ow
deciency may be due to obvious problems such as a
defective pump or blocked water lter. Alternatively,
excessive water temperature may be due to over-ring,
or to a problem with the water piping or the heater's
internal bypass control. Over-ring might be a result
of an incorrect gas orice or supply of propane gas to a
heater intended for natural gas.
If there are no such fundamental problems,
identify which of the switches is open. Limit switch
access is through the limit switch plugs on the inlet/
outlet header. Remove the limit switch plugs from
the bottom of the header and gently remove the limit
switches from the wells. Move the black lead of the
meter to the terminal on the 42°C (108°F) limit switch
(test point 9) that is connected to the reman switch
terminal block. Less than 220mV at this point means
that the wire between the terminal block and the limit
switch has a poor or broken connection or a partial
short. Replace the wire assembly. If at least 220mV is
detected at test point 9, then move the black lead of the
meter to the other terminal of the 42°C (108°F) limit
switch (test point 10). Low or no voltage here means
that the limit is open and must be replaced.
If 220mV or more is detected at test point 10,
move the black lead of the meter to the terminal on
the 52°C (126°F) limit switch (test point 11) that is
connected to the 42°C (108°F) limit switch. Less than
220mV at this point means that the wire between the
two limit switches has a poor or broken connection
or a partial short. Replace the wire assembly. If at
least 220mV is detected at test point 11, then move
the black lead of the meter to the other terminal of the
52°C (126°F) limit switch (test point 12). Low or no
voltage here means that the limit switch is open and
must be replaced. If voltage is detected at test point 12,
move the black lead of the meter to the terminal of the
water pressure switch where the black wire from the
high limits is connected (test point 13).
Less than 220mV at this point indicates that the
wire connecting the high limits to the water pressure
switch is faulty or poorly connected. Correct the
problem or replace the wire.
NOTE The limit switches have different trip points,
and it is important that replacements are
correct. The 42°C (108°F) switch has a red
dot on the top of the switch, and must be
installed in the inlet side of the header. The
52°C (126°F) switch has no dot and must be
installed in the outlet side of the header in the
well farthest from the heater jacket.
11.4.6 Water Pressure Switch
If the meter shows at least a 220mV signal at test
point 11, move the black lead of the meter to the other
terminal on the water pressure switch (test point 14).
If there is no voltage, the pressure switch contacts
are open. This is almost always due to a water ow
deciency, the most common one being a blocked water
lter or defective pump. However, sometimes it is due
to blockage of the copper tube or mis-adjustment of
the switch. Investigate thoroughly, referring to Section
11.5 “Adjusting the Water Pressure Switch”. If there
is no problem with the pool system or pressure switch
adjustment, replace the pressure switch.
11.4.7 Temperature Control Circuit
The temperature control circuit consists of two
(2) major components which must all be working
correctly for the signal to be transmitted to the gas
valve. The components are the ON/OFF toggle switch
and the mechanical thermostat. Use the following
procedure to check each component for functionality.
Check the temperature control as a complete
circuit before checking each component individually.
With the red lead of the meter still at test point 1, place
the black lead of the meter on the back of the mechanical thermostat (test point 16). If the meter shows more
than 220mV at the pressure switch (test point 14) but
not at test point 16, then one of the components of the
temperature control circuit is faulty. Proceed with the
following sections to test the components.
11.4.7.1 ON/OFF Toggle Switch
Remove the temperature control panel from the
bezel on the front of the heater to gain access to the
switch. Be sure that the toggle switch is in the "ON"
position. Place the black lead of the meter on the
toggle switch terminal (test point 15) that is connected
to the pressure switch. Less than 220mV at this point
indicates that there is a problem with the black wire
that connects the pressure switch to the toggle switch.
If at least 220mV is detected at test point 15, move the
black meter lead to the other terminal on the toggle
switch (test point 16).
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater
Slowly turn adjustment
sprocket clockwise
until heater goes off.
Figure 26. Pressure Switch Adjustment
A reading of less than 220mV here indicates a
faulty switch. If the reading is more than 500mV, turn
the switch "OFF" and then "ON" again to be sure that
the internal contacts are working correctly. The volt
meter reading should drop to zero when the switch is
"OFF" and return to at least 220mV when the switch is
placed back in the "ON" position.
11.5 Adjusting the Water Pressure
Switch
CAUTION
The water pressure switch should be adjusted to
turn the heater off when the pump is off. Setting the
appliance. Adjust the switch to turn the heater off,
not on.
The pressure switch is preset at the factory for
activation at 14 kPa. Do not adjust the pressure switch
if the heater is installed more than 4.57 m below the
pool surface. Consult your local Zodiac representative
for recommendations.
On some installations, the piping from the heater
to the pool is very short. The back pressure could be
too low to trigger the pressure switch. If this happens,
it may be necessary to install a directional tting or
elbows where the return line enters the pool. This will
increase back pressure enough for the heater to operate
properly.
Make sure the pool lter is clean before making
any pressure switch adjustment. A dirty lter will
restrict the water ow and the pressure switch cannot
be adjusted properly.
To adjust the pressure switch, refer to Figure 26
and proceed as follows:
1. Turn the heater control to OFF. See Figure 20.
2. Remove the side panel above the front header to
access the water pressure switch.
ENGLISH
Page 35
3. Start the lter pump and conrm by means of a
voltmeter that the pressure switch closes (if the
switch fails to close, replace it with a switch that
has a lower minimum setting).
4. Set the temperature control to the max position.
Heater should start.
5. With your ngers, turn the adjustment sprocket
very slowly clockwise until the heater goes off.
6. Slowly turn the pressure switch adjustment
sprocket counterclockwise one-quarter turn. The
heater should come back on.
7. Check the adjustment by turning the lter pump
OFF. The burners should shut off immediately.
If they do not, restart the lter pump and repeat
Steps 5 and 6. Check the adjustment again.
8. Return the pool temperature control to the
desired temperature.
It may be necessary to repeat these steps to get
a proper setting. The switch must be set so that the
heater will not re unless the pump is running. If a
proper setting cannot be reached, contact the factory
service department.
11.6 Temperature Rise
The Legacy pool and spa heaters have an inter-
nal bypass which accommodates a wide range of
water ow. The bypass is easily adjustable to change
the temperature rise for optimum performance and
length of heater life. The bypass assures constant heat
exchanger ow even though ow through the lter
system will vary depending on how dirty the lter is.
BYPASS
ADJUSTMENT
SCREW
THERMOMETER WITH
PETE'S PLUG
Figure 27. Temperature Rise Measurement
Page 36ENGLISH
Legacy™ Model LRZM Pool/Spa Heater | Installation and Operation Manual
For most installations, an external bypass valve
is not needed in the heater water piping. This is due
to the large size of the heater's internal bypass valve.
If the pump ow rate is known to exceed 470 lpm, an
external bypass may be needed to assure proper heater
operation.
Water ow should be conrmed upon start-up of
the heater and in most servicing situations. If the ow
is not normal, corrections must be made to the pool
system. Flow is evaluated by determining the water
temperature rise through the heat exchanger.
Before checking the temperature rise, make
sure that the pool lter is clean and that gas supply
and burner pressures are correct. If necessary, clean
all components of the lter system. Temperature rise
is measured in the return header of the Legacy. To
measure the temperature rise, turn off the lter pump
and remove the plastic plug protruding through the
cabinet on the return header side of the heater. See
Figure 27. With the plug removed, install the special
®
thread adapter and Pete’s Plug
tting and insert a
pocket thermometer. A temperature rise measurement
kit is available through your Zodiac distributor. See
Section 12 of this manual for the correct kit number.
The internal bypass can be adjusted by means of
a screw on the right-hand side of the header. To adjust
the temperature rise to within the ranges specied in
Table 7, proceed as follows:
1. If the piping system has an external bypass valve,
close it.
2. Turn the heater control panel to OFF.
3. Start the lter pump.
7. If the temperature rise is too low and cannot be
raised by means of the adjustment screw, the
ow is in excess of 470 lpm. An external bypass
will need to be installed, or if one already exists,
open the external bypass valve gradually until the
temperature range in Table 6 is achieved.
8. If it was necessary to adjust the external bypass
as outlined in step 7, scribe a line on the bypass
shaft and case to mark the correct adjustment
position. Wire or remove the valve handle to
prevent tampering.
Table 6. Water Temperature Rise and Flow Rates
(Measured at Return Header)
ModelMinimum
Temp Rise,
°C (°F)
1254 (7)5 (10)1.9 (30)
1756 (10)7 (13)1.9 (30)
2509 (16)11 (20)1.9 (30)
32511 (20)14 (26)1.9 (30)
40013 (23)16 (29)1.9 (30)
Maximum
Temp Rise,
°C (°F)
Minimum
System Flow
lps (GPM)
In a system without external bypass, it may be
necessary to make changes. If temperature rise is too
low, a manual bypass must be installed. If tempera-
ture rise is too high, there is inadequate ow, possibly
requiring a change to the piping system or a larger
pump. Before proceeding with either remedy, verify
proper heater operation. Low gas input results in low
temperature rise and vice-versa. A problem with the
heater internal bypass assembly also affects measured
temperature rise.
4. After three (3) minutes, note and record the
thermometer reading. This is the pool water
temperature.
5. Start the heater by turning the controller to ON.
Allow the heater to operate for ve (5) minutes
or more. Note and record the thermometer
reading. Subtract pool water temperature from
this reading. This difference is the temperature
rise. Refer to Table 6. If your measured temperature rise is within the range designated for your
heater, skip steps 6 through 8.
6. Locate the bypass adjustment screw on the righthand side of the header (see Figure 22). Loosen
the nut so that the screw can be adjusted. A slight
water leak past the nut may be expected. Turn the
screw counterclockwise to decrease the temperature rise, and clockwise to increase the temperature rise as needed to achieve the ranges in Table
6. After the adjustment, tighten the nut so that no
leaks occur.
Section 12. Replacement Parts
12.1 Ordering Information
To order or purchase parts for the Legacy pool
and spa heater, contact your nearest Zodiac dealer or
distributor. See the Zodiac web site at www.Zodiac.
com for the nearest service center. If they cannot
supply you with what you need, contact Technical
Support at Zodiac, telephone (800) 822-7933.
NOTE To supply the correct part it is important that
you state the model number, serial number
and type of gas when applicable. This
information is on the rating plate inside the
heater.
The following pages contain a parts list, general
exploded view, and detailed exploded views to aid in
parts identication. Pleas refer to these pages when
ordering parts for your Legacy pool/spa heater.
Installation and Operation Manual | Legacy™ Model LRZM Pool/Spa Heater