Zip HydroTap All-In-One BC100/125A, HydroTap All-In-One BC160/125+AV, HydroTap All-In-One BC 60/85A, HydroTap All-In-One BC160/125+A, HydroTap All-In-One BC100/125AV Installation And Operating Instructions Manual

...
HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02 Page 1 of 24
Zip HydroTap All-In-One
Filtered Boiling and Chilled water plus Hot and Cold water for kitchens and tea rooms.
Installation and Operating Instructions
This Installation Instruction covers the following HydroTap models:
®
Affix Model Number Label Here
Page 2 of 24 HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02
Installation Checklist:
A. Read the instructions.
B. Note: Not all fittings are supplied with the appliance kit. Isolation valves are not supplied.
C. Check the water pressure to determine if you require a pressure reduction valve or a flow restrictor added or removed from the kit.
D. Check the water quality to determine if extra filtration will be required.
E. Check the appliance rating plate and ensure correct power is available for the appliance.
F. Check the underbench cupboard supporting the appliance is adequate for the total weight of the appliance, when full of water.
Before Commissioning:
1. Check the unit has been secured correctly.
2. Flush the supply line before connecting.
3. Check all plumbing fittings have been tightened.
4. Ensure the outlet and vent pipes are positioned to drain correctly.
5. For undersink units ensure there is adequate ventilation.
6. Check all tubes from the undersink unit to the tap, have a constant rise and there are no ‘S’ traps or kinks in the hoses.
7. Check all electrical connections are correct and there are no loose wires.
Commission:
8. Turn on the water and check for leaks.
9. Flush the tap for 3 - 5 minutes.
10. Turn on the power.
11. Allow sufficient time for the unit to heat up, before using.
Check List
HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02 Page 3 of 24
Contents
Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Read These Warnings First . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 5
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .5 - 6
Models Covered by These Instructions. . . . . . . . . . . . . . . . . . 6
Special Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 11
Operating the Mixer Tap . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Mains version connections (diagrams) . . . . . . . . . . . . . . . . .12 - 13
Vented version connections (diagrams) . . . . . . . . . . . . . . . . .14 - 15
External Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . .16
Internal Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . 16 - 17
Operating the HydroTap . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Child Safety Lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Setting the Energy Saver Timer . . . . . . . . . . . . . . . . . . . . . . . 19 - 20
Auxiliary Fan Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Boiling Water Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Setting Boiling and Chilled dispensing Times. . . . . . . . . . . . . 21
Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
End of Life Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
NOTE:
Read all instructions and precautions before proceeding. If in doubt, or need further guidance, please call Zip on 0800 077 8302.
Please leave these instructions with the end user after installation
This unit must be installed in accordance with water supply byelaws, current IEE regulations and relevant local authority byelaws.
Page 4 of 24 HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02
Hydrotap All-In-One series are able to supply Boiling and Chilled water as well as Hot and Cold water, all from the same tap.
The ‘AV’ series have their Boiling / Chilled / Hot outlets connected to the undersink (open vented) unit, Cold outlet conneted to the mains.
The ‘A’ series have their Boiling / Chilled outlets connected to the undersink (open vented) unit and their Hot and Cold mixer outlets are connected to external (Mains) Hot water and Cold water supplies.
Product Description
The estimated temperature ranges will be:
Boiling water: 68°C - 98°C
Mixed water: From ambient up to approximately 50°C
Cold water: Ambient.
Chilled water: 5°C - 10°C
Read These Warnings First
Safety
This appliance is not intended for use by persons (Including Children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure they do not play with the appliance
Refrigerant
The HydroTap Chilling unit contains 134A refrigerant under pressure. No part of the unit should be exposed to a naked flame. Maintenance of the refrigeration unit must be carried out by an accredited service provider or qualified refrigeration mechanic.
Qualifications
If the power cable is damaged it must be repaired only by a qualified technician. To avoid hazards, all installation procedures must be carried out by a suitably qualified tradesperson. The power cable and power outlet must be in a safe visible position for connection.
Venting
Sometimes steam and / or boiling water may discharge through a vent outlet at the mouth of the tap. Ensure the tap body is located so the tap outlet safely drains into the sink bowl area.
NOTE: On startup, the controls take the system through a calibration process which causes the unit to over-boil for a period of 90 secs. Once this mode is completed the system reverts back to normal operation.
Lifting
Take care when lifting the HydroTap undersink unit. Some units may exceed safe lifting limits. If you feel this is beyond your personal capabilities, please seek assistance with the lift. The weights of the units are marked on the packaging and given in the table under the heading “Installation Requirements”. Do not lift the unit by the doors.
Airflow
The ambient temperatures this unit should operate within are 5ºC - 35ºC. Proper air circulation must be provided. The system will operate satisfactorily only if the recommended air gaps are provided, these are 65mm min rear clearance and 50mm side clearance. An air vent is provided with each unit for high usage applications, this must be installed in the top half of the cupboard door as a matter of course. An accessory exhaust fan kit is available and should be used to ensure adequate
The power point must be located within reach of its cable (length 3m). The appliance must be positioned so that the power point is accessible.
Hydrotap undersink assembly.
The appliance must be placed in a
horizontal position, as shown above.
HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02 Page 5 of 24
Read These Warnings First (continued)
ventilation. Auxiliary fan should always be fitted when supplied with large units. Make sure that the ventilation grilles of the undersink unit are not obstructed.
Included in
the installation pack are adhesive backed silicon buffers. If air vents are not installed in the cupboards housing the HydroTap, the buffers must be placed on the inside edge of the cupboard door to create a slight gap ensuring a minimum airflow. Failure to do this may cause the HydroTap to overheat and operate inefficiently.
Minimum Pressure warning:
All AV models require a minimum cold water supply pressure of 2bar (200 kPa) and a maximum of 7bar (700 kPa).
All A models requre a minimum cold and hot water supply pressure of 0.7 bar (70kpa) and a maximum working pressure of 7 bar (700 kPa).
Filter Control
The HydroTap filter control is preset to 6000 Litres to provide trouble-free flow and operation in most installations. Local water quality conditions may require an alteration to this capacity. In areas where the water has a high concentration of sediment, the preset litre capacity may be shortened to avoid poor flow, taste or odour situations. In areas where the water quality is above average, lengthening the preset capacity may be desirable, but not essential. If any of these changesis needed, follow the instructions on page 16/17 or contact your Service Provider.
Frost Protection
If this appliance is located where the ambient air temperature could fall below 5ºC when the heater is not in use, do not turn off the appliance electrically. This safeguard does not offer the same protection to the connecting pipework and fittings.
Altitude
The HydroTap is equipped with a self-calibrating program which caters for altitude adjustment.
Installation Environment Considerations
This unit is intended for indoor use only and should never be installed outdoors or exposed to the elements of nature. This unit must not be positioned in an area that may be cleaned by a water jet. This unit must not be cleaned by a water jet.
NOTE:
HydroTaps are designed to operate within 1ºC to 2ºC of boiling point and at 5ºC to 10ºC for chilled drinking water.
Before installing ensure that the following have been provided at the installation site:
• Sufficient space in the cupboard to install the undersink unit in accordance with
these Installation Instructions. A table of dimensions is given on page 6.
NOTE: Add 65mm to the Depth of the undersink unit to allow for Water and
Electrical connections and ventilation.
• A water supply connection with isolating valve inside the cupboard within reach of
the 750 mm flexible connection and positioned so that the connection point and the isolating valve will not be obstructed when the undersink unit is installed.
• Power supply of 220-240 Volt AC, for connection to the unit via a 13 amp fused
spur.
• This switch must provide all-pole disconnection with a contact separation of at
least 3mm, installed in accordance with wiring regulations.
Note:
Always ensure the tubes are shortened so that any excess is removed and their route is the most direct line between the tap assembly and the HydroTap unit.
Do not allow the tubes to sag or droop so water is trapped within the hoses. Always maintain a constant fall
Positioning of the tap assembly must be within the following parameters:
The height between the base of the Hydrotap unit and the base of the Tap assembly cannot be greater than 900mm.
Installation Requirements
Page 6 of 24 HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02
Commercial Models Covered by These Instructions
Installation Requirements (continued)
• For AV models, cold water supply with a minimum working pressure of 2 bar (200 kPa) and a maximum working pressure of 7 bar (700 kPa) connected via an isolation valve. For all A models, cold and hot water supply with a minumum working pressure of 0.7 bar (70kpa) and a maximum working pressure of 7 bar (700 kPa). If pressure is likely to exceed 7 bar, install a 5 bar (500 kPa) Pressure Limiting Valve.
• The fitting of an air flow vent, cut into the top half of the cupboard door
concealing the HydroTap requires a cut size of approximately 100mm circular, to provide adequate warm air displacement. In installations where high volume draw-off will occur, the fitting of the accessory exhaust fan is essential.
• Accessory exhaust fan must be fitted when supplied with 150/175 and 200/175+ models. Buffers must be fitted to cupboard door.
Important:
Do not proceed with the installation if these requirements are not met.
These Installation Instructions cover the A and AV HydroTap range. Use the chart on the left to identify the model you are using:
Commercial Models:
A = Boiling / Chilled and Hot / Cold. (Mains) AV = Boiling / Chilled and Hot / Cold. (Vented)
Boiling Water Capacity:
160 = 160 cups in one hour** 200 = 200 cups in one hour**
** Capacity will be reduced by the volume of water used when operating the mixer tap.
Chilled Water Capacity:
125 = 125 glasses in one hour 175 = 175 glasses in one hour
Note: The Cup measurement = 167mls, the Glass measurement = 200mls.
AV
Model
160
Cups of
Boiling Water
per Hour
125
Glasses of
Chilled Water
per Hour
Model Height
mm (inch)
Depth
mm (inch)
Width
mm (inch)
Weight empty
kg’s lbs
Weight full
kg’s lbs
BC 60/85A 340 (13.3) 430 (16.9) 430 (16.9) 28 34.5
BC100/125A, BC160/125+A
BC100/125AV, BC160/125+AV 340 (13.3) 430 (16.9) 430 (16.9) 28 (61.7) 35 (77.1)
BC150/175A, BC200/175+A
BC150/175AV, BC200/175+AV 395 (15.5) 470(18.5) 500 (19.6) 29.5 (65) 38 (83.7)
Special Tools Required
In addition to normal tools, the following will be required:
• 50mm diameter sheet metal hole punch for sink tops. (not supplied)
• 50mm diameter hole saw for timber bench tops. (not supplied)
• Nut runner tube spanner (supplied) for fixing tap assembly.
Installation Procedure
Step A - Installing the All-in-One tap (see P12-15)
1. Make sure that the tap location will allow the nozzle to drain into the sink.
NOTE 1: The tap assembly must not be positioned more than 900mm
above the HydroTap unit. Failure to do this may result in poor water delivery.
HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02 Page 7 of 24
2. Cut a 50mm hole in the bench / sink top.
3. Ensure the silicon O-Ring remains in place as this is the moisture seal against the bench / sink top. A light smearing of silicon sealant on the O-Ring will ensure a
watertight fit.
4. Pass all hoses through the 50mm hole and carefully locate the Head Assembly on the bench / sink top.
5. From the underside of the bench / sink, mount the ‘base block’ by feeding each of the tubes and electrical cable evenly in between the legs of the ‘base block’. Slide it up to meet the ‘all thread rod’, and pass the ‘all thread rod’ through the centre of the ‘base block’.
6. Hold the ‘all thread’ steady and fit the 10mm ‘fixing nut’ to the ‘all thread’ using the tube spanner supplied in the kit. Check the Tap Head position before securing it tightly against the bench / sink top.
NOTE 2: Under no circumstances should the Tap be twisted after the
installation is complete.
Step B - Installing the undersink unit
SPECIAL NOTE: The HydroTap undersink units are heavy, take note of the weights listed in the table on page 6. If you think you cannot lift the unit safely, get help and avoid possible injury.
Before positioning the heater connect the braided water inlet hose (supplied) to the cold water tee piece (see Pages 12-15). Flush the hose prior to connecting to the cold water inlet at the rear of the unit.
Position the HydroTap undersink unit as close as possible to directly beneath the All-in­One tap head.
The connection tubes supplied with the tap head assembly CANNOT be lengthened.
Leave at least a 50 mm air-gap without obstruction on each side of the unit and 65mm at the rear
Step C - Connecting the All-in-One tap outlet
Note:
Included in the installation pack are adhesive backed silicon buffers. If air vents are not installed in the cupboards housing the HydroTap, the buffers must be placed on the inside edge of the cupboard door to create a slight gap ensuring a minimum airflow. Failure to do this may cause the HydroTap to overheat and operate inefficiently.
Model: Vented
Connect the 3 braided hoses to the rear of the undersink unit as shown in pages 14 -15.
Measure and trim the blue silicon tube and connect it to the chilled water outlet located on the top front, right hand side of the undersink unit. Use spring clamps provided to secure the hose.
Measure and trim the red silicon tube and connect it to the boiling water outlet located on the top centre, right hand side of the undersink unit. Use spring clamps provided to secure the hose.
Measure and trim the clear silicon tube and connect it to the vent outlet located on the top centre, left hand side the top of the undersink unit. Use spring clamps provided to secure the hose.
Installation Procedure (continued)
O - Ring seal
Base Block
Fixing nut
Tap
All-thread rod
NOTE :
New hose sets supplied with the unit should be used. Do not use old hose sets.
Page 8 of 24 HydroTap Installation and Operating Instructions - 89650UK - August 2011 v1.02
Installation Procedure (continued)
NOTE: All tubes must have a continuous fall back to the undersink unit.
Connect the tap USB connector to the USB lead on the undersink unit. Orient the USB plug carefully and connect, do not force the plug. Once connected, fix the cable to the wall, ensure it is away from any possible water splashes and is off the floor.
NOTE: When trimming any silicon tubes trim to minimum length, do not loop any excess or allow kinking of the tubes. When connecting, slide the tube over the pipe at least 25mm. There are black plastic clamps provided on the boiling and chilled hoses to choke the flow if required. Only choke the flow if it is excessively strong.
Model: NON Vented.
Connect the two braided hoses to the Hot and Cold water supply, as shown in pages 12-13. . Measure and trim the red marked tube and connect it to the boiling water outlet on the
top of the undersink unit. Use spring clamps provided to secure the hose. Measure and trim the blue marked tube and connect it to the chilled water outlet on
the top of the undersink unit. Use spring clamps provided to secure the hose. Measure and trim the unmarked tube and connect it to the vent outlet on the top of the
undersink unit. Use spring clamps provided to secure the hose.
NOTE: All tubes must have a continuous fall back to the undersink unit.
Connect the tap USB connector to the USB lead on the undersink unit. Orient the USB plug carefully and connect, do not force the plug. Once connected, fix the cable to the wall, ensure it is away from any possible water splashes and is off the floor. Fasten the tap body to the sink using the bolt & plate system provided.
The following instruction is CRITICAL:
Adjust both cupboard door hinges and attach the supplied rubber door buffers to the doors to create a 4 mm air-gap between the doors and the cupboard. This is the minimum ventilation requirement for low usage installations.
Proper air circulation must be provided for all Boiling and Chilled models. The system will operate correctly only if the recommended air gaps are achieved during installation. A ventilation hole measuring 100mm must be cut into the top half of the cupboard door to accommodate the air vent provided. Make sure that the undersink unit ventilation grilles are not obstructed in any way.
Step D - Connecting the water supply
To prevent sediment from entering the HydroTap at connection, flush water through the supply line thoroughly before connection to the HydroTap. Open the access door and check that the filter is in place and secure. Connect the water supply to the undersink unit using the attached flexible hose .Turn on water and check for leaks. If no leaks are evident turn the power on.
Step E - Connecting an external filter.
(Not supplied as standard equipment).
To combat the build up of lime scale, a high performance external filter kit may be ordered from your Zip service provider.
NOTE: 1- The braided hose (BH2) with the BLUE ring
markings must be fitted to the Right Hand Side when the tap is oriented as shown above. Fit the WHITE marked braided hose (BH1) to the LHS. 2- The braided hose (BH3) is fitted to the copper extension joining the undersink Venturi to the tap. 3- The clear silicon tube is the vent line from the undersink unit to the tap. SEE P12 - P15
Chiller connection BLUE
From Venturi to Tap for BH3 ­Vented version only
Boiler connection RED
Blue ring on RHS mains IN for BH2 to
Venturi
White ring on LHS for
BH1 Mains in
Tap
Base block
Clear tube to Vent
Rear panel with external filter fittings
Loading...
+ 16 hidden pages