ZIEHL-ABEGG ZA dynpro Original Operating Instructions

R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
-Installation
-Start-up
ZA dynpro
Frequency inverter
Original operating instructions
Store for future use!
Content
1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Explanation of symbols and designators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Pictographs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Requirements placed on the personnel / due diligence . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7 Working on device / Hazards through residual voltage . . . . . . . . . . . . . . . . . . . . . . . . 6
2.8 Modications / interventions in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.9 Operators obligation of diligence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.10 Employment of external personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Name plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Service & maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4.1 Storage duration: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.5 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Mechanical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2 Dimensional drawings / Minimum distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 EMC-compatible installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.1 Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.2 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.2.3 EMC-compatible assembly of the control cabinet . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.2.4 Motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Terminal positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.3.1 011-032 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4 Protective ground connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.5 Mains connection (X1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.6 Residual current operated device (RCCB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.7 Brake resistor (X 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.8 Motor connection (X 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.9 Digital inputs (X-IN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.10 Digital outputs (X-OUT1, X-OUT2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.11 CAN interface (X-CAN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.12 STO interface (X-STO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.13 Connection of asynchronous motor rotary encoder (X-ENC15) . . . . . . . . . . . . . . . . . . 26
5.13.1 X-ENC15 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.14 Rotary encoder connection for synchronous motors (X-ENC15) . . . . . . . . . . . . . . . . . . 27
5.14.1 Pin assignment for EnDat 01, SSI, SIN/COS interface . . . . . . . . . . . . . . . . . . . . . 27
Original operating instructions
ZAdynpro – Part 1
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
/64
5.15 Rotary encoder simulation (X-ENCO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.16 External 24 V voltage supply (X-ENCO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.16.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.16.2 Connection X-EXT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.17 Standby input (X-SBY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.18 Motor contactors (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.18.1 Monitoring of the motor contactors (X-BR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.19 Brakes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.19.1 Brake release monitoring (X-BR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.20 ZAdynpro circuit suggestion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6 Operation and parameterising . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.1 Options for control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.1.1 ZApadpro control terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.1.1.1 Mounting / Fastening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.1.1.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.2 Menu navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.2.1 ZApadpro and ZAmon control interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.2.2 Control key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.2.3 Menu and parameter navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.2.4 The different operating levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.2.5 Meaning of the arrows appearing in the display: . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3 Entering numerical values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3.1 Continuous change of a parameter value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3.2 Changing individual digits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.2 Conguring the . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3 Testing the Safe Torque Off function (STO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.4 Setting the switch-off points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.4.1 Interrupt points for the travel speeds V_3 and V_2 . . . . . . . . . . . . . . . . . . . . . . . . 42
7.4.2 Cut-off points for travel speed V_1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.5 Carrying out the rst test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.6 Optimisation of the startup and drive behaviour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
8 "Safe Torque Off (STO)" function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8.2 Safety concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8.3 Principle circuit diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
8.4 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
8.5 Notes for operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
8.6 Notes on use of motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
8.7 Deactivation of the STO function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.8 Testing the "Safe Torque Off (STO)" safety function . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.9 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
9.1 Technical data for ZAdynpro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
9.2 EC/EU declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
9.3 Adjustment card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.4 Type designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.5 Certicates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9.6 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Original operating instructions
ZAdynpro – Part 1
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
/64
1 General
Compliance with the following instructions is mandatory to ensure the functionality and safety of the product. If the following instructions given especially but not limited for general safety, transport, storage, mounting, operating conditions, start-up, maintenance, repair, cleaning and disposal / recy­cling are not observed, the product may not operate safely and may cause a hazard to the life and limb of users and third parties. Deviations from the following requirements may therefore lead both to the loss of the statutory material defect liability rights and to the liability of the buyer for the product that has become unsafe due to the deviation from the specications.
The ZAdynpro may be operated in the area of application of standards EN 12015 and EN 12016 (compare chapter 5.2 "EMC compatible installation") only with the expert use of a line reactor. ZIEHL-ABEGG recommends the use of the line reactor of type NDxx which is optimally geared to the ZAdynpro (compare also chapter 5.5. Mains connection). Also outside the area of application of standards EN 12015 and EN 12016, the use of a line reactor is the precondition for the validity of the type examination of the STO function (Safe Torque Off according to DIN EN 61800-5-2).
1.1 Validity
This instruction manual applies to: Frequency inverter from the series:ZAdynpro from software version 4.53
1.2 Structure of the operating instructions
These operating instructions help you to work safely on and with the frequency inverter ZAdynpro. They contain safety instructions that must be complied with as well as information that is required for failure-free operation of the frequency inverter. The operating instructions are to be stored together with the frequency inverter. It must be ensured that all persons who have to perform activities on the frequency inverter can consult the operating instructions at any time. Instructions for use in accordance with the German Occupational Safety and Health Act and the German Work Equipment Ordinance must be provided in addition to the operating instructions. Keep the operating instructions for continued use. They must be passed-on to all successive owners, users and nal customers.
1.3 Target group
The operating instructions address persons entrusted with planning, installation, commissioning and maintenance and servicing and who have the corresponding qualications and skills for their job.
1.4 Exclusion of liability
It has been established that the content of these operating instructions is concurrent with the frequency inverter hardware and software described. It is still possible that non-compliances exist; no guarantee is assumed for complete conformity. The contents of this manual are put through periodic reviews. Necessary modications are incorporated into the next version. ZIEHL-ABEGG SEis not liable for damage due to misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modications.
Symbols description
Asynchronous motors
The contents in the operating instructions refer specically to the operation of asynchronous motors.
Synchronous motors. The contents in the operating instructions refer specically to the operation of synchronous motors.
Original operating instructions ZAdynpro Part 1 General
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
/64
1.5 Copyright
These operating instructions contain information protected by copyright. The operating instructions may be neither completely nor partially photocopied, reproduced, translated or put on a data medium without prior explicit consent from ZIEHL-ABEGG SE. Infringements are liable for damages. All rights reserved, including those that arise through patent issue or registration on a utility model.
1.6 Explanation of symbols and designators
Symbol Meaning
"
Instruction. Follow the instructions in sequence in the order described.
Result of an action (result). Here, the result of an action is described.
2 Safety instructions
2.1 General
This chapter contains instructions to prevent personal injury and property damage. These instructions do not lay claim to completeness. In case of questions and problems, please consult our company technicians.
2.2 Intended use
The ZAdynpro is a field-orientated Frequency inverter for RPM control of asynchronous motors and synchronous motors. The Frequency inverter is designed for lift systems used to convey people and cargo. The device is not designed for any other use than those listed here – this is considered improper use. Reading these operating instructions and complying with all contained instructions – especially the safety instructions contained therein – are considered part of intended use. Furthermore, carrying out all inspection work in the prescribed scheduled intervals is part of intended use The operator of the ZAdynpro is liable for any personal harm or material damage arising from non­intended use! The manufacturer shall bear no liability for such damage!
2.3 Pictographs
Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows.
Danger!
General hazardous area. Death or severe injury or signicant property damage can occur if the corresponding precautions are not taken!
Caution!
Risk of moderate or minor injury if the corresponding precautions are not taken!
CAUTION!
Caution!
Material damage is possible if the corresponding precautions are not taken!
Danger!
Danger by dangerous, electric voltage! Death or severe injury can occur if the corresponding precautions are not taken!
Original operating instructions ZAdynpro Part 1 Safety instructions
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
/64
2
Safety instructions
Information
Important information and advice for user
2.4 Product safety
The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable. The device and its accessories must only be used in a flawless condition and installed and operated with compliance to the operating instructions. Exceeding the limits stated in the Enclosure / technical data chapter can lead to a defect in the device.
2.5 Requirements placed on the personnel / due diligence
Persons entrusted with the planning, installation, commissioning and maintenance and servicing in connection with the device must have the corresponding qualications and skills for these jobs. Based on their training, knowledge and experience as well as knowledge of the relevant standards, they must be able to judge the work transferred to them and be able to recognize possible hazards. In addition, they must be knowledgeable about the safety regulations, EU directives, rules for the prevention of accidents and the corresponding national as well as regional and in-house regulations. Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supervision of an experienced person. This also applies to personnel undergoing general training. Comply with the legal minimum age
2.6 Commissioning
Danger!
During commissioning, unexpected and hazardous conditions can arise in the entire system due to incorrect settings, defective components or incorrect electrical connections
During the commissioning following has to be observed:
Remove all persons and objects from the hazardous area
The EMERGENCY-STOP function must be in working order
The mechanical safety brakes must be installed and in working order
Commissioning is only permitted with compliance to the EMC directive 39/336/EEC
2.7 Working on device / Hazards through residual voltage
Before working on previously installed devices, separate them from the mains and secure them against reconnection.
Danger!
Through use of capacitors, danger of death exists even after switching off the device through directly touching the energized parts or due to parts that have become energized due to faults. Wait at least 3 minutes before working on the device. The safe isolation from the supply must be checked using a two-pole voltage detector.
Danger!
It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly.
2.8 Modications / interventions in the device
For reasons of safety, no unauthorized interventions or modications may be made on the device . All planned modications must be authorized by the manufacturer in writing. Use only genuine spare parts / genuine wearing parts / genuine accessories from the ZIEHL-ABEGG SE.These parts were specically designed for the device. There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements.
Parts and special equipment not supplied by the ZIEHL-ABEGG SE are not approved for use.
The warranty shall be void if the device is tampered with or modied without authorisation.
Original operating instructions ZAdynpro Part 1 Safety instructions
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
6
/64
2.9 Operators obligation of diligence
The device has been designed and constructed with consideration of a hazard analysis and after carefully selecting the harmonized standards to be complied with as well as additional technical specications. It thus complies with the state-of-the art and ensures the highest degree of safety. However, this safety can only be implemented in operational practice if all measures necessary for this purpose are taken. The operator of the installation has the obligation of due diligence to plan these measures and monitor their implementation.
In particular, the operator must ensure that
The device is only used as intended (cmp. chapter "Product overview" concerning this)
The installation is operated solely in a awless, functional condition and that especially the safety devices are periodically checked for their properly functioning condition
The required personal safety gear is available to and used by the operating, maintenance and repair personnel
The operating instructions are always readily available at the location where the frequency inverter is being used, are complete and are in legible condition
Only sufciently qualied and authorized personnel operate, maintain and repair the device
these staff receive regular instruction in all relevant occupational safety and environmental protec­tion issues, are knowledgeable about the operating instructions and, especially, are familiar with the safety instructions contained therein.
all safety and warning notices attached to the device are never removed and remain legible.
2.10 Employment of external personnel
Maintenance and service work are frequently carried out by external employees who often do not recognize the specic situations and the thus resulting dangers. These persons must be comprehensively informed about the hazards in their area of activity. You must monitor their working methods in order to intervene in good time if necessary.
Original operating instructions ZAdynpro Part 1 Safety instructions
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
7
/64
2
Safety instructions
3 Product overview
3.1 System overview
The drive system for ZIEHL-ABEGG SE elevators consists of several individual components.
1) ZAdynpro
Frequency inverter for RPM control of asynchronous motors and synchronous motors.
2) Power choke
System component to reduce current harmonics and to attenuate commutation notches and line feedback.
3) Elevator drive
Synchronous or asynchronous motor, with and without gearbox.
4) ZArec4c (optional)
Power feedback unit for elevator systems with frequency inverter.
5) Brake resistor
System component to convert energy generated during the regenerative run into heat.
6) ZAsbc4B (optional)
System component for contactorless actuation of electromechanical brakes.
7) EVAC3C (optional)
Evacuation module for automatic evacuation run in case of mains failure.
Original operating instructions ZAdynpro Part 1 Product overview
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
8
/64
3.2 Name plate
2 1
3
4
5
6
9
8
7
10
no. Designation
1 Part no. 2 Serial number 3 Mains connection voltage 4 Type designation 5 Mains frequency 6 Rated current for 40% on time 7 Protection rating 8 Touch current in protective earth line exceeds an
alternating current of 3.5 mA, or a direct current of 10 mA
9
CE mark
10
Internal DATA MATRIX code of ZIEHL-ABEGG SE
3.3 Service & maintenance
These jobs must be completed during the recurrent maintenance work:
Check the device for dirt and clean if necessary
Check the connections and tighten if necessary
3.4 Transport
The device is packed ex factory to suit the transport method previously agreed.
Always use the original packaging materials when transporting the device
Avoid shocks and impacts to the device during the transport
3.4.1 Storage duration:
The storage duration depends particularly on the electrolytic capacitors because the oxide coating in the capacitor deteriorates.
Storage duration:
12 months at -20 ... +50 °C
24 months at -20 .. +45 °C
36 months at -20 .. +40 °C If storage exceeds the stated maximum storage times, you must carry out a reformation of the capacitors before applying the entire mains voltage to the frequency inverter.
New formation:
To reform, the ZAdynpro needs to be connected to reduced voltage (230 VAC at L1 / L2) for approx. 1 hour.
Original operating instructions ZAdynpro Part 1 Product overview
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
9
/64
3
Product overview
3.5 Disposal / recycling
Disposal must be carried out professionally and environmentally friendly in accordance with the legal stipulations.
4 Mechanical installation
4.1 General notes
The frequency inverter ZAdynpro is designed for mounting on the wall in the switch cabinet.
Mounting outside of the switch cabinet is not permitted.
Ensure that there is sufcient cooling in the switch cabinet. When doing so, observe the power loss
of the ZAdynpro.
The following points must be complied with during the mechanical installation to avoid causing a
defect in the frequency inverter due to assembly errors or environmental inuences.
Ambient conditions
It is not permitted to mount the frequency inverter on vibrating components
The frequency inverter must not be exposed to any shock
Prevent humidity
Avoid aggressive and conductive materials in the environment
Mounting
Check frequency inverter for any transport damage
Mounting is performed on a metallic mounting plate
Mount the device in a torsion free conditions
Mounting position: Vertical, connection terminals X3, X-STO, X-SBY and X1, bottom
Permissible installation positions:
Mounted with the rear on the mounting plate (see Fig.)
Mounted with the side area on the mounting plate (see Fig.). An additional mounting bracket is
required for this.
Mounted with the rear on the mounting plate Mounted with the side area on the mounting plate
Mount the frequency inverter so that it is isolated
Prevent drilling chips, screws and other foreign bodies from reaching the interior of the frequency
inverter
Maintain the stated minimum clearances to ensure unobstructed cooling- air feed as well as
unobstructed outgoing air discharge (see g. "Minimum clearances")
Ensure sufcient cooling when mounting in the switch cabinet. When doing so, observe the power
loss of the ZAdynpro.
Original operating instructions ZAdynpro Part 1 Mechanical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
0/64
4.2 Dimensional drawings / Minimum distances
ZAdynpro 011-017
ZAdynpro 023-032
Original operating instructions ZAdynpro Part 1 Mechanical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
1/64
4
Mechanical instal-
lation
5 Electrical installation
5.1 General
Danger!
It is forbidden to carry out work on the frequency inverter when it is live. Even after disconnection, the DC-link ( terminals X2: +DC / X2:-DC ) are still live. Wait at least 3 minutes before working on the device
Danger!
It is not permitted to operate the ZAdynpro with the housing covers removed, as exposed live parts are present inside the frequency inverter. Failure to observe this provision can lead to serious injury.
Caution!
Parts can be destroyed by electrostatic discharge. Discharge yourself by suitable action before working on electrical components (connectors, etc.). You can do this, for example, by touching earthed metal parts.
Work on electric components may only be carried out by trained electricians or by persons
instructed in electricity under the supervision of an electrician in accordance with electrical engi-
neering regulations.
A second person must always be present when working on energized parts or lines who discon-
nects in case of emergency.
Electrical equipment must be checked regularly: Loose connections are to be re-tightened and
damaged lines or cables must be replaced immediately.
Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for
authorized persons using a key or special tool.
Never clean electrical equipment with water or similar liquids.
Incorrectly wired connections can destroy the electrical/electronic components.
5.2 EMC-compatible installation
5.2.1 Standards
When correctly installed, the frequency inverter corresponds to the following standards:
EN 12015:2014 Electromagnetic compatibility – Product family standard for lifts, escalators and
moving walks – Emission
EN 12016:2013 Electromagnetic compatibility – Product family standard for lifts, escalators and
moving walks – Interference immunity
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
2/64
5.2.2 Electrical connection
Lead Cable length Shielding ZAdynpro shield coating
version
Power line - - -
Motor cable Max. 25 m Earthed at both ends Clip on mounting plate Brake chopper/brake resistor line Maximum 5 m Earthed at both ends Pigtail Connecting line for standby input Max. 25 m - -
Connecting line for the digital inputs Max. 25 m - -
Connecting lines for the digital out-
puts
Max. 25 m - -
Rotary encoder line Max. 25 m Earthed at both ends Via connector
Temperature monitoring of brake re-
sistor
Maximum 5 m Earthed at the inverter
end
Pigtail
STO line Max. 50 m Earthed at both ends Pigtail
Connecting line for ZApadpro Max. 50 m Earthed at both ends Via connector
Connecting line of rotary encoder
simulation
Max. 25 m Earthed at the customer
system end
-
Connecting line for CAN interface
Main line: Max. 200 m
Stub lines: Max. 6 m
- -
Connecting line for brake release
monitoring
Max. 25 m - -
Do not twist shielding for connections; use a suitable shield connection system
Run the control cables and the encoder cables separate from the power cables
Provide connected inductances (brakes, contactors) with suppressors
In order to use the ZAdynpro safely and in compliance with standards, a power choke of type ND... from ZIEHL-ABEGG must be integrated into the power line. For assignment of the frame sizes of the ZAdynpro to the respective power chokes, refer to chapter "Electrical installation/Mains con­nection".
Operating the ZAdynpro without the ND.. type power choke voids all warranty entitlements.
In the case of a supply line of > 25 m (motor line) or > 5 m (brake resistor line), adherence to standard EN 12015 (Electromagnetic compatibility – Emission) and EN 12016 (Electromagnetic compatibility – Interference immunity) can no longer be guaranteed.
If you must interrupt the shielding on a particular line (e.g. to install motor contactors), the shielding must be subsequently continued with the lowest possible HF impedance.
Use shielded lines in the switching cabinet also
Feed the voltage supply of the motor contactors through the mains lter of the elevator control
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
3/64
5
Electrical instal-
lation
5.2.3 EMC-compatible assembly of the control cabinet
1 ZAdynpro mains connection terminal 2 Power line 3 Motor cable (shielded) 4 Clip for xing the shielding 5 Route electrical lines with the maximum possible spacing 6 Line reactor 7 Mains connection 8 Brake resistor cable (shielded) 9 Shielding (brake resistor cable)
The following points must be observed if the stand­ards outlined in chapter "EMC-compatible installa­tion/Standards" are to be adhered to:
Refer to chapter "EMC-compatible installation/Stan­dards"
Cable length between power choke and ZAdynpro maximum 200 mm
Route the power line (including the mains connection terminal and power choke) separately from the brake resistor line and the motor line
5.2.4 Motor cable
The shielding of the motor line must be extensively connected to the earth potential in the immediate vicinity of the ZAdynpro. The shielding must be continued right up to the connection terminal.
We recommend xing the shielding on the mounting plate by means of a clip (see Fig.).
1
Fixing the shielding on the mounting plate
1
Clip
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
4/64
5.3 Terminal positions
5.3.1 ZAdynpro 011-032
1 2 3 4 5
6 7 8 9
Front terminal positions
1 X-MMC memory card 2 X-OUT2 digital outputs 3 X-IN digital inputs 4 X-BC temperature monitoring for brake resistor/brake chopper 5 X-BR inputs for function monitoring of the motor brakes 6 J4 terminating resistance CAN line 7 X-CAN CAN 8 X-ENC15 rotary encoder SUB-D 9 X-ENCO rotary encoder simulation
1
2
3
4
Position of connection terminals on bottom
1 X3 motor 2 X-STO Safe Torque Off 3 X-SBY standby input 4 X1 line
2 3
1
Terminal positions top
1 X-OUT1 digital outputs 2 X-PAD ZApad 3 X2 brake chopper/brake resistor
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
5/64
5
Electrical instal-
lation
5.4 Protective ground connection
The ZAdynpro has a leakage current of > 3.5 mA according to the dened networks in DIN EN 60990 and must therefore be permanently connected.
In accordance with EN 50178, item 5.2.11 and 5.3.2.1, the PE conductor connection must have a cross-section of at least 10 mm².
In the case of PE conductors < 10 mm², an additional PE conductor must be connected. The cross­section must correspond at least to the cross-section of the PE conductor on the connecting line.
An M6 threaded bolt is available on the ZAdynpro to connect the PE conductor (see Fig.).
PE conductor connection ZAdynpro
5.5 Mains connection (X1)
Danger!
Before connecting the ZAdynpro to the mains supply, it must be checked that the technical specications on the rating plate and in the operating instructions of the ZAdynpro match the characteristics of the mains supply.
Designation of the con­nection terminal:
X1
Network congurations:
The line lter and ZAdynpro are designed for use in an earthed power supply system.
Permissible network congurations are:TN networkTT network
The line lter and ZAdynpro are unsuitable for use in the IT network!
Line cross-section:
The line cross-section must be specied dependent on the nominal motor current and the ambient conditions (e.g. temperature, wiring method) in accordance with DIN VDE 0100.
Type of cable:
Rigid or exible lines
In the case of exible lines: Wire end ferrules recommended
Not shielded
Connection type: Spring-type terminals Mains fuse The size of the mains fuse must reect the cable cross-section used and the
ambient conditions. Use the following maximum fuse sizes, depending on the frame size of the
ZAdynpro:
ZAdynpro frame size Max. fuse for operating
class gG
011/013 16 A
017 20 A 023 25 A 032 35 A
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
6/64
Line reactor: In order to use the ZAdynpro safely and in compliance with standards, a
power choke of type ND... from ZIEHL-ABEGG SE must be integrated into the power line.
Use the following power chokes, depending on the frame size of the ZAdyn­pro:
ZAdynpro frame size Line reactor Article number for
power choke
011 ND011 357180 013 ND013 357181 017 ND017 357182 023 ND023 357183 032 ND032 357184
Connection: Mains connection
X1
L1 L2 L3
L3
L2
L
1
PE
max. 200 mm
1U1
1V1
1W1 1W2
1V2
1U2
1
3
2
ND
ZAdynpro
ZAdynpro mains connection
1 Mains 3~ 400V/PE/50Hz 2 Line reactor ND 3 Central ground point
5.6 Residual current operated device (RCCB)
Frequency inverters of the ZAdynpro type do not require an FI circuit breaker for operation. The circuit at the ZAdynpro output is monitored by an electronic short-circuit protection. On detecting a short-circuit current at the output of the ZAdynpro (and thus negligible impedance between the phase conductor and a body or the protective conductor of the circuit or the protective conductor of the operating equipment in the case of an error) the output current is switched off within a time of <20 μs. On condition that the potential equalisation for the ZAdynpro and the motor was performed according to the valid standards (VDE0100-Part 540:2012-06 and DIN EN 50178:1997), this behav­iour is sufcient for the automatic switch-off in the case of an error demanded by VDE 0100-4100. If an FI circuit breaker is required for special reasons (e.g. re prevention), an all-current-sensitive FI circuit breaker type B must be used. For maximum operational reliability, ZIEHL-ABEGG recommends the use of an FI circuit breaker with a reference fault current of 300 mA for re prevention according to regulation VdS 3501.
Information
Please note that even when using a correct FI circuit breaker of type B, false tripping due to high protective earth currents (leakage currents) can still occur.
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
7/64
5
Electrical instal-
lation
5.7 Brake resistor (X 2)
Designation of the con­nection terminal:
X2
Line cross-section: Max. 6 mm
2
Type of cable: Shielded
Cable lengths:
Maximum 5 m
If the pre-assembled line is not long enough in the brake resistor of the BR11-A type, this can be extended up to a length of 5 m. A shielded, self­extinguishing line is required for this.
Connection type: Spring-type terminals Parametrisation: The brake resistor or brake chopper used must be congured in the menu
Encoder & BC/BC_TYP.
Enc od er & BC
|
-
" BC_T YP BR 25
|
-
" BR2 5
BR/ BC - Typ
Connection: Brake-Resistor connection
The brake resistor of the BR11-A type has no temperature monitor.
BR
+24 1
3
2
V
I09/ BC
X-BC
ZAdynpro
+DC
-DC
X2
R
PE
+DC
R
PE
BR11-A/BR 14-A
BR
TB1
TB2
+DC
PE
R
+DC
-DC
X2
R
ZAdynpro
1
PE
+24 1
3
2
V
I09/ BC
X-BC
BR17/BR25/BR50/BR100
CAUTION!
Caution!
It is imperative for an existing temperature monitor to be connected to the ZAdynpro! The brake resistor or the brake chopper may be burnt out in the event of a fault!
CAUTION!
Caution!
If the connection of a brake resistor (type BRxx) to the +DC and -DC terminals is faulty, it will emit a continuous power output and the device will become overheated. If a temperature monitor is not connected, the device will burn out!
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
8/64
Type BR11-A
Brake resistor BR11-A possesses connected connecting wires. These must be wound twice around the toroidal core provided. It is important to wind both wires with the same direction of winding (see gure).
Toroidal core BR11-A
5.8 Motor connection (X 3)
Designation of the con­nection terminal:
X3
Line cross-section: The line cross-section must be specied dependent on the motor´s current and
the ambient conditions (e.g. temperature, wiring method) in accordance with DIN VDE 0298-4.
Type of cable:
Shielded line
Rigid or exible lines
Rated voltage U0 / U: 450 / 750 VAC
Cable lengths:
Max. 25 m
Connection type: Spring-type terminals
Connection:
X3
V
W
M
3~
V W
U
P1 P2
U
Connection asynchronous motor / synchronous motor
Danger!
Always switch off the mains voltage when connecting the motor line. The contactorless operation mode ("safe torque off" function (STO)) does not galvanically isolate the output stage of the frequency inverter from the motor line connection terminal!
Danger!
When operating the motor with a rotary encoder, the line to the motor must be connected on the motor and inverter side phase-correct: U -> U / V -> V / W -> W. Never swap the connection; not even if the rotary direction of the motor is false!! If the motor phases are swapped, motor control is generally not possible. This can lead to jerky movements or uncontrolled acceleration of the motor.
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
1
9/64
5
Electrical instal-
lation
5.9 Digital inputs (X-IN)
Designation of the con­nection terminal:
X-IN
Number of the digital in­puts:
8, freely congurable
Technical data: The digital inputs comply with the IEC61131-2 TYPE 2 industry standard.
Voltage range: +22 ... 26 VDC Switching level low/high: <5 VDC / >11 VDC Current consumption at 24 V:10 mA (-20%)
Line cross-section: max. 1,5 mm²
Type of cable:
Individual conductors
Not shielded
Cable lengths:
Max. 25 m
Connection type: Screw terminals
Connection: Connection with external power supply
X-IN
+24V
+24V
_IN
I01 I02 I03 I04 I05 I06 I07 I08
GND
_IN
GND
+24V
0V
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13)
1
1 Modulation () terminal designation of connector
When using the external power supply the bridges between the terminals +24V / +24V_IN and GND / GND_IN the pre-assembled control cable X-I are not required. These must be removed!
Connection with internal power supply
X-IN
+24V
+24V
_IN
I01 I02 I03 I04 I05 I06 I07 I08
GND
_IN
GND
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13)
1
1 Modulation () terminal designation of connector
When using the internal power supply, a bridge must be placed between the +24V / +24V_IN terminals and between GND / GND_IN.
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
0/64
CAUTION!
Caution!
The internal 24 V power supply is provided solely for the digital inputs. Switching consumer load with this voltage is prohibited!
Terminal assignment X-IN
You can congure the inputs I1 I8 assignments. The conguration can be implemented by:Presetting the used control system (assignment corresponding to the control requirements)Free conguration
Implement conguration of the digital inputs in the Control system\CONFIG menu.
The input assignments dependent on the conguration:
Conguration
1)
Inputs
I01 I02 I03 I04 I05 I06 I07 I08
00:Free RF* V1* V2* V3* VZ* RV1 UP*
RV2
DOWN*
Free*
01:ZA_IO RF V1 V2 V3 VZ RV1 UP
RV2
DOWN
Free*
03:BP_IO RF V1 V2 V3 VZ RV1 UP
RV2
DOWN
Free*
08:KN_IO RF V1 V2 V3 VZ RV1 UP
RV2
DOWN
Free*
11:NL_IO RF V1 V2 V3 VZ RV1 UP
RV2
DOWN
Free*
13:SS_IO RF V1 V2 V3 VZ RV1 UP
RV2
DOWN
V4*
15:ZA_BIN RF DIR BIN0 BIN1 BIN2 Free* Free* Free*
16:WL_IO RF V1 V2 V3 VZ RV1 UP
RV2
DOWN
V4*
21:ST_IO RF V1 V2 V3 VZ RV1 UP
RV2
DOWN
Free*
24:CSILVA RF BIN0 BIN1 BIN2 Free*
RV2
DOWN
RV1 UP Free*
25:S+S SBIN2 SBIN1 SBIN0
RV1 UPRV2
DOWN
Free* Free* RF*
27:MAS_BIN RF DIR MBIN0 MBIN1 MBIN2 BR1 BR2 Free*
30:KS_IO RF V1 V4 V2 VZ RV1 UP
RV2
DOWN
V3*
31:KL_IO V4 V1 V2 V3 VZ RF+RV1
RF+ RV2
PA-
RA*2
32: S_SMART RF* V1* LZ* V3* V5* RV1 UP*
RV2
DOWN*
Free*
1) For the description of the congurations, see chapter "Parameter List/Control Menu" in the operating instructions - Part 2. * The function of the inputs can be changed
Information
To be able to travel, at least the following input signals need to be present:
Controller enable
Speed
Direction default
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
1/64
5
Electrical instal-
lation
Binary travelling speed default Standard (CONFIG=15:ZA_BIN)
Travel speed V_3
Binary inputs
BIN2 BIN1 BIN0
- 0 0 0 V1 0 0 1 V2 0 1 0 V3 0 1 1 V4 1 0 0 V5 1 0 1 V6 1 1 0 VZ 1 1 1
5.10 Digital outputs (X-OUT1, X-OUT2)
Designation of the con­nection terminals:
X-OUT1 X-OUT2
Number of outputs: X-OUT1: 3, freely congurable
X-OUT2: 2, freely congurable
Technical data:
X-OUT1 X-OUT2
S
hort-circuit-proof no* no*
Min. switching ca­pacity
5 mA / 12 VDC 5 mA / 12 VDC
Max. switching ca­pacity
2 A / 250 VAC 500 mA / 24 VDC
Line cross-section:
max. 1,5 mm²
Type of cable:
Not shielded
Cable lengths:
Max. 25 m
Connection type:
Screw terminals
Connection:
X-OUT1
O11 O14 O21 O24
O31 O34
(1) (2) (3) (4)
(5) (6)
1
1 Modulation () terminal designation of connector
X-OUT2
O44O41
(2)(1)
1
O54O51
(4)(3)
1 Modulation () terminal designation of connector
CAUTION!
Caution!
* In order to protect the relay contacts, switched inductivities must be provided with an external suppressor circuit (suppressor diode, RC element).
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
2/64
Terminal assignment of X-OUT1, X-OUT2
The output assignments can be congured. The conguration can be implemented by:Presetting the used control system (assignment corresponding to the control requirements)Free conguration
Implement conguration of the digital outputs in the Control system\CONFIG menu.
Please refer to the "Parameter list/Control menu" chapter for a description of the individual parameters
The output assignments dependent on the conguration:
Conguration
1)
Outputs
O11 - O14 O21 - O24 O31 - O34 O41 - O44 O51 - 54
00:Free Err* MB_Brake* MotContact* V < V_G1* STO-Info* 01:ZA_IO Fault MB_Brake MotContact V < V_G1 STO-Info 03:BP_IO Fault MB_Brake MotContact V < V_G1 STO-Info 08:KN_IO Fault MB_Brake MotContact V < V_G1 STO-Info 11:NL_IO Fault MB_Brake MotContact V < V_G1 STO-Info 13:SS_IO Fault MB_Brake MotContact V < V_G1 STO-Info 15:ZA_BIN Fault MB_Brake MotContact V < V_G1 STO-Info 16:WL_IO Fault MB_Brake MotContact V < V_G1 STO-Info 21:ST_IO Fault MB_Brake MotContact V < V_G1 STO-Info 24:CSILVA Fault MB_Brake MotContact V < V_G1 STO-Info 25:S+S MotContact MB_Brake V=O Fault STO-Info 27:MAS_BIN Fault MB_Brake MotContact Off* STO-Info 30:KS_IO Fault MB_Brake MotContact V < V_G1 STO-Info 31:KL_IO fault MB_Brake MotContact EVAC.DIR STO-Info 32: S_SMART Fault MB_Brake MotContact SD STO-Info
1) For the description of the congurations, see chapter "Parameter List/Control Menu" in the operating instructions - Part 2. * The function of the inputs can be changed
5.11 CAN interface (X-CAN)
Designation of the con­nection terminal:
X-CAN
Line cross-section:
Type of cable:
N
ot shielded
Twisted pair
Cable lengths:
Main line: Max. 200 m
Stub lines: Max. 6 m
Connection type: Screw terminals
Connection:
The wiring is in a linear structure. The individual devices are connected to the main line with short stub lines.
The bus should be terminated with a terminating resistor of 120 - 150 Ohms, at both ends of the bus.
X-CAN
CL
GND_ COM
CH
CAN High (H)
CAN Low (L)
GND (optional)
(1)
(2)
(3)
(4)
Optionaler
Schirmanschluss
() terminal designation of connector
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
3/64
5
Electrical instal-
lation
To activate the terminating resistance, the jumper at terminal J4 must be plugged into the right two pins (see Fig.).
Jumper at terminal J4
For more detailed information on CANopen lift, see chapter "Serial communication/CANopen lift" in
part 2. of the operating instructions.
5.12 STO interface (X-STO)
The following points must be observed when switching and wiring the STO signals:
Separate relays must be used for every input for switching the STO signals (two-channel activa­tion).
When wiring the STO signals, short-circuits and external shorts must be ruled out on power lines and terminal points because the internal diagnostics of the ZAdynpro does not detect any short­circuits on the power lines: – Outside the switch cabinet, the STO line must be permanently laid (xed) and protected against
external damage (e.g. cable duct, armoured tube or similar). If separate jacketed cables are used for the STO_A and STO_B signals, the cables must not be laid with protection (according to ISO 13849-2).
– Air and creep distances of at least 2 mm must be kept between the STO_A, STO_B and +24V_
STO signals according to EN81 (e.g. at terminal points).
Terminals which comply with a CENELEC or IEC standard must be used.The wiring technique must be compliant with DIN EN 60204-1.
External shorts must be ruled out in the exciter voltage of the relays that actuate the STO inputs (end of the safety chain).
Supply cables (power cable, motor cable) and STO cables must be laid separately.
The relays used to activate the STO inputs must meet the following requirements:
Rating: According to the technical data of the STO inputs: Typ. 24 V/12 mA Switching voltage: Min. 60 VDC Relay contacts: Recommended: Relays with hard-gold-plated contacts Isolation: Safe disconnection between coil and contacts according to EN 60664-1 or
equivalent standard.
Interference immunity: Sufcient interference immunity to interference voltages on the control side
(coil), such as for capacitive couplings in long control lines. If in doubt, use a relay with increased drop voltages (such as Phoenix Contact series PLC­SO46, Finder series 38.51.3 or comparable).
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
4/64
Danger!
If you use an external voltage source instead of the internally generated 24-V voltage (X-STO: +24V_STO) to actuate the STO inputs, you must use a voltage source with low voltage and safe electrical disconnection (SELV/PELV).
See the chapter "Safe Torque Off(STO) function" for further information.
Designation of the con­nection terminal:
X-STO
Technical data: Voltage range 0...30 VDC
Switching level LOW / HIGH
0 V < LOW < 3 VDC 15 V < HIGH < 30 VDC, typical: 24 VDC
Current consumption at 24 VDC
typ. 12 mA per input
Line cross-section: min. 0.25 mm²...max. 2.5 mm²
Type of cable:
Shielded lines
Apply shielding on both sides
ZAdynpro shield coating version: Connection of pigtail to terminal 1 of connection terminal X-STO
Cable lengths: Max. 50 m Connection type: Screw terminals
Connection:
X-STO
+24V_
STO
GND
STO_A
STO_B
GND_
STO
(6)
(5)
(4)
(3)
(2)
(1)
K1
K2
1
Connection with internal 24 V voltage and protected routing
1 Modulation
X-STO
+24V_
STO
GND
STO_A
STO_B
GND_
STO
(6)
(5)
(4)
(3)
(2)
(1)
K1
K2
1
Connection with internal 24 V voltage using two separate jacketed cables
1 Modulation
X-STO
+24V_
STO
GND
STO_A
STO_B
GND_
STO
(6)
(5)
(4)
(3)
(2)
(1)
K1
K2
1
+24V
0V
2
Connection with external 24 V voltage and protected routing
1 Modulation 2 External voltage source SELV/PELV
X-STO
+24V_
STO
GND
STO_A
STO_B
GND_
STO
(6)
(5)
(4)
(3)
(2)
(1)
K1
K2
1
+24V
0V
2
Connection with external 24 V voltage using two separate jacketed cables
1 Modulation 2 External voltage source SELV/PELV
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
5/64
5
Electrical instal-
lation
Terminal assignment X-STO
no. Name Function
6 +24V_STO 24VDC output voltage
(to be used only for activation of the STO inputs, do not connect
any additional loads) 5 GND Reference potential 24VDC output voltage 4 STO_A Input STO A 3 GND_STO Reference potential, inputs STO_A/B 2 STO_B Input STO_B 1
Shielding
5.13 Connection of asynchronous motor rotary encoder (X-ENC15)
Designation of the con­nection terminal:
X-ENC15
Connection type: D-Sub, 15-pin, in two rows Cable lengths: Max. 25 m Type of cable: Shielded twisted pair cable Technical data: Type: Incremental counter TTL
Signal shape: Right angle, Sin/Cos
Operating voltage: 5 VDC
Resolution: 64 ... 4096 pulse / revolution
Input resistor 120 Ω
Cut-off frequency 200 kHz
TTL differential frequency (against
GND)
Ulow <= 0.5 V Uhigh >= 2.5 V
Sine differential signal (at 2.5 V offset
against GND)
0,6 Vss ... 1,2 Vss (typ. 1Vss)
Parametrisation: Before the rotary encoder is plugged in/connected, the rotary encoder type
and resolution used must be congured in the "Encoder & BC/ENC_TYP" and
"Encoder & BC/ENC_INC " menu.
Enc od er & BC
|
-
" ENC_ Typ TTL rec t.
|
-
" TTL r ect.
Enc od er t ype
Enc od er & BC
|
-
" ENC_ INC 204 8
|
-
" 204 8
Enc od er r esolu tion
5.13.1 X-ENC15 pin assignment
1 - ­2 - ­3 - ­4 +5 V_E Voltage supply 5 DGND Ground 6 - ­7 B Track B 8 - ­9 - -
10 - -
11 - ­12 A Track A 13 /A Track A inverse 14 /B Track B inverse 15 DGND Ground
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
6/64
Housing
Shielding
5.14 Rotary encoder connection for synchronous motors (X-ENC15)
Designation of the con­nection terminal:
X-ENC15
Connection type: D-Sub, 15-pin, in two rows Cable lengths: Max. 25 m Type of cable: Shielded twisted pair cable Technical data: Type: Rotary encoder, absolute
Interfaces: EnDat 01
SSI Sin/Cos
BiSS-C Resolution: 512 ... 4096 pulse / revolution Input resistor 120 Cut-off frequency 200 kHz Sine differential signal (at 2.5 V offset
against GND)
0,6 Vss ... 1,2 Vss (typ. 1Vss)
Parametrisation: Before the rotary encoder is plugged in/connected, the encoder type and
resolution used must be congured in the "Encoder & BC/ENC_TYPE" and "Encoder & BC/ENC_INC " menus.
Enc od er & BC
|
-
" ENC_ Typ TTL rec t.
|
-
" TTL r ect.
Enc od er t ype
Enc od er & BC
|
-
" ENC_ INC 204 8
|
-
" 204 8
Enc od er r esolu tion
5.14.1 Pin assignment for EnDat 01, SSI, SIN/COS interface
1 DATA Data line 2 /DATA Data line inverse 3 /D Analog track D inverse 4 +5 V_E +5/8V voltage supply
(power supply is switched off if the rotary encoder is missing)
5 DGND Ground 6 /C Analog track C inverse 7 B Analog track B 8 C Analog track C for transmitting position 9 /CLK Clock signal invers
10 CLK Clock signal for serial transfer
11 D Analog track D for transmitting position 12 A Analog track A 13 /A Analog track A inverse 14 /B Analog track B inverse 15 DGND Ground
Housing
Shielding
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
7/64
5
Electrical instal-
lation
5.15 Rotary encoder simulation (X-ENCO)
The rotary encoder simulation transforms the signals of the rotary encoder mounted on the motor into differential signals according to ANSI standard RS422. The resolution of the rotary encoder simulation is identical to the resolution of the rotary encoder.
As a result of the connection of an external 24 V voltage source to terminal +24V_EXT, the rotary encoder simulation is active even when the ZAdynpro is switched off.
Designation of the con­nection terminal:
X-ENCO
Line cross-section: max. 1.5mm² Type of cable: Shielded twisted pair cable Connection type: Screw terminals Technical data: Output signal high min. 2,8 V / 8 mA
Output signal low max. 0,4 V / 4 mA Rload 120 Short-circuit-proof No
Connection:
X-ENCO
X
/X
Y
/Y
GND_ EXT
+24V_ EXT
(6)
(5)
(4)
(3)
(2)
(1)
1
Connection of rotary encoder simulation
1 Signals depending on the rotating direction of the motor (with view to the power take-
off side)
() terminal designation of connector
5.16 External 24 V voltage supply (X-ENCO)
By applying an external 24 V voltage supply to terminal X-ENCO, the following functions are active even when the ZAdynpro is switched off:
Rotary encoder simulation
ZETAPAD (parameter changes are possible)
USB interface of the ZApad
Information
The external 24-V power supply may only be switched on if the mains connection voltage is not applied.
5.16.1 Technical data
Voltage range 23 ... 26 V Current consumption 370 mA
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
8/64
5.16.2 Connection X-EXT
X-ENCO
X
/X
Y
/Y
GND_ EXT
+24V_ EXT
(6)
(5)
(4)
(3)
(2)
(1)
24V
0V
1
Connection external power supply
1 external power supply () terminal designation of connector
5.17 Standby input (X-SBY)
By applying a 24-V voltage, the standby mode of the ZAdynpro is activated.
In the stand-by mode, the controller units and the ZApadpro are switched off.
After the stand-by mode has been deactivated, it takes about 10 seconds for the ZAdynpro to be operational again.
Name: Standby input Symbol: X-SBY Technical data: Voltage range: +20...28 VDC
Switching level low/high <5 VDC />15 VDC Current consumption at 24 V typ. 8 mA
Line cross-section: max. 1.5 mm
2
Type of cable: Shielded lines Cable lengths: Max. 50 m Connection type: Screw terminals
Connection:
X-SBY
GND_ SBY
PE
SBY
(1)
(2)
(3)
24V
0V
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
2
9/64
5
Electrical instal-
lation
5.18 Motor contactors (optional)
The STO connection must be bridged if motor contactors are used (see g.).
X-STO
+24V_
STO
GND
STO_A
STO_B
GND_
STO
(6)
(5)
(4)
(3)
(2)
(1)
STO connection bridged
The monitor of the STO function must also be deactivated. The STO function is activated/deactivated in the Monitors/STOmenu.
Mon it ors
|
-
" STO Off
|
-
" Off
STO mon it or
The maximum cable length to the motor contactors for non-shielded lines is 200 mm. Shielded lines must be used if there is a greater distance between the contactors and the ZAdynpro.
X3
V
W
M 3~
V
W
U
P1 P2
U
R2 R1
R4 R3
K1
3 4
1 2
K2
3 4
1 2
1
Synchronous motor connection
1 Bridges can be omitted for asynchronous motors
Information
If an emergency evacuation is carried out by opening the brakes, the motor windings should be short­circuited for the evacuation to prevent an uncontrolled acceleration of the elevator. The short-circuit generates a speed-dependent braking torque, sufcient in most cases to reduce the elevator speed to a safe level.
CAUTION!
If operating with synchronous motors from other manufacturers, you have to ensure that a manually emergency evacuation is approved.
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
0/64
5.18.1 Monitoring of the motor contactors (X-BR)
Danger!
Operating lift drives is only permissible with connected and activated contactor monitoring!
Information
The switching states of the motor contactors must be monitored according to EN 81-20. The ZAdynpro contactor monitoring is no substitute for this monitoring of the motor contactors demanded in EN 81-20!
General
The ZAdynpro monitors the switching status of the motor contactors. The contactors must be retracted during travel. Opening the contactors during travel (e.g. through bar impacts) will lead to immediate interruption of the travel.
The contacts for monitoring the motor contactors are arranged in series.
The contactor monitoring is activated/deactivated in the Control system/f_XBR3 menu.
Con tr ol
|
-
" f_XB R3 44 :
|
-
" 47: C O
Fun ct ion of i npu t BR 3
Technical data for contactor monitoring
Monitoring voltage +24 VDC Contact type Normally open contact (NO) Number of inputs 1 Clamping range max. 1,5 mm² Current consumption at 24 V Typ. 10 mA -20%
Contactor monitoring connection
X-BR
+24V_ OUT
BR3
BR2
BR1
GND
K2 K1
(1)
(2)
(3)
(4)
(5)
Connection internal contactor monitoring – series circuit
() terminal designation of connector
Information
The internal 24 V power supply is only provided for the inputs of the ZAdynpro. Switching consumers with this voltage is not permitted!
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
1/64
5
Electrical instal-
lation
5.19 Brakes
5.19.1 Brake release monitoring (X-BR)
The brake release monitoring serves as monitoring for redundancy and the operation status of the brakes.
It is recommended that the brake release monitoring be connected to the ZAdynpro for optimum starting and stopping.
Information
When20the lock function is activated, the brake release monitor meets the self-monitoring requirements according to EN 81-20 Chapter 5.6.6.2 for protection devices for the cabin moving upwards against overspeeding and Chapter 5.6.7.3 as a protection device against unintended cabin movement.
Name: Brake release monitoring Symbol: X-BR Line cross-section: max. 1,5 mm² Type of cable: Not shielded Cable lengths: Max. 25 m Connection type: Screw terminals Technical data: Monitoring voltage +24 VDC
Contact type Normally open contact (NO) or nor-
mally closed contact (NC) Number of inputs 4 Clamping range max. 1.5 mm
2
Current consumption at 24 V Typ. 10 mA -20%
Parametrisation: The contactor monitoring can be activated/deactivated in the menu Monitor-
ing.
Mon it ori ng
|
-
" BR 1*NC
|
-
" 3*N C
Bra ke c on trol (BR1 .. BR4 )
The lock function of the ZAdynpro is engaged by activating the LOCKBR=On parameter in the menu Monitors.
Mon it ori ng
|
-
" LOCK BR Of f
|
-
" On
Loc k in ve rter
Activation of the parameter ensures that the ZAdynpro locks upon detection of a faulty brake circuit.
The ZAdynpro lock can only be released by setting the Monitors/UNLOCK =
On parameter.
Connection:
X-BR
+24V_ OUT
BR3
BR2
BR1
GND
(1)
(2)
(3)
(4)
(5)
1
Connection of brake release monitor with micro switches
1 Monitoring contacts () terminal designation of connector
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
2/64
ZAdynpro
+
+
-
-
X-BR
+24V_ OUT
I10
I11
I12
GND
(1)
(2)
(3)
(4)
(5)
1
Brake release monitoring connection with inductive proximity switches
1 Lift drive 0 terminal designation of connector
Information
The internal 24 V power supply is only provided for the inputs of the ZAdynpro. Switching consumers with this voltage is not permitted!
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
3/64
5
Electrical instal-
lation
5.20 ZAdynpro circuit suggestion
Original operating instructions ZAdynpro Part 1 Electrical installation
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
4/64
6 Operation and parameterising
6.1 Options for control
To operate and congure the ZAdynpro, the following control options are available:
ZApadpro control terminal
Remote control via ZAmon software
Remote control via the elevator controller display
6.1.1 ZApadpro control terminal
The ZApadpro is a control module independent of the ZAdynpro. Remote control of the ZAdynpro is possible when a longer connection line is used.
6.1.1.1 Mounting / Fastening
ZApadpro on the front
ZApadpro on the right-hand side
6.1.1.2 Connection
The RJ-45 socket of the control terminal and of the ZAdynpro (X-PAD) are used for connection.
Connection cable
Line cross-section: >= AWG26 Type of cable: CAT5 network cable, 8-core Cable lengths: Max. 50 m Connection type: both sides RJ-45 plug, 8-pole
Connection of the ZApadpro on the ZAdynpro
Original operating instructions ZAdynpro Part 1 Operation and parameterising
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
5/64
6
Operation and
parameterising
6.2 Menu navigation
6.2.1 ZApadpro and ZAmon control interface
1
24
6
3
5
ZApadpro and ZAmon control interface
1 Display 2 i key 3 Enter key 4 Arrow UP key 5 Arrow DOWN key 6 ESC key
6.2.2 Control key functions
back to menu selection
Back to parameter selection
Negation of yes-no queries
Cancel
Conrming menu selection
Conrming parameter values
Conrming parameter values
Afrmation of yes-no queries
Menu selection
Parameter selection
Increasing parameter values
Menu selection
Parameter selection
Reducing parameter values
Show / exit INFO menu
Display of current operational states
Original operating instructions ZAdynpro Part 1 Operation and parameterising
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
6/64
6.2.3 Menu and parameter navigation
Main page
ZIE HL -AB EG G SE
ZAd yn pro
SN: 0 92 295 87 /00 02
Pho ne : + 49 7 940 16 308
- Actuate with any key
Menu section
ZAd yn pro
->S ta rtu p
Sta ti stics
Mem or y car d
- Select required menu with the and keys
- Conrm menu selection with the
key
Parameter section
Sta rt up
USR _L EV Ba si c
->M OT _TY P SM 250
n 9 6 rp m
- Select required parameter with the and keys
- Conrm parameter selection with the
key
Changing parame­ter
Sta rt up
|
-
" MOT_ TYP SM2 25
|
-
" SM2 50
Mot or typ e
- Select/enter parameter value with the and keys
- Conrm value with the key
6.2.4 The different operating levels
The rmware of the ZAdynpro is divided into two control levels:
Basic Level
Three menus are available here: Startup, Statistics and Memory card.
Starting up takes place exclusively in the Startup menu.
Advanced Level
In the advanced level, all parameters are displayed. The parameters are described in the chapter "Parameter list".
Depending on the parameterisation, unneeded parameters are hidden automatically to give a better overview.
You can switch between Basic-Level and Advanced-Level by a long press of the key.
The level which is active after the controller start can be set by the parameter LCD & Passwor­d/USR_LEV.
Original operating instructions ZAdynpro Part 1 Operation and parameterising
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
7/64
6
Operation and
parameterising
6.2.5 Meaning of the arrows appearing in the display:
Mo t o r-T y p ens c h i ld
à
Encod e r & BC Anlag e -date n Steue r u n g
Selecting a menus in the menu level
Motor-Typen s c h i l d
n 128 r p m
à f 1 8 . 0 H z
I 40 . 4 A
Selecting changeable parameters in the menu
Anlag e -Date n
MOD_n* M i t D . . i 2 n* 9 4 r p m __D 0 . 2 4 0 m
Selected parameter can be modied, but is blocked at the mo­ment. The block can be implemented by assigning a password or functionally (dependent on another parameter)
Start
T_ 2 1 . 0 s T2 _real 0. 8 s T_ 3 0 . 1 s
Value / function of a parameters is only displayed for informa­tional purposes and cannot be modied.
S e r i al- N o-- - - - -- - -
01
ZAdynpro 013
SN:061282 3 8 /0001
3 .17 -1037
i
Zahl
Current position (page number) in the INFO-menue
MM C - R eco r d er
REC_ M O D On REC_ C F G 0 REC_ N U M 0
The recorder for recording measurements on the memory card is activ
Start E R R
T_2 1 . 0 s T2_real 0.8 s T_3 0 . 1 s
ERR
ZAdynpro fault The ZAdynpro must be deactivated
6.3 Entering numerical values
Entering numerical parameter values can be done in two different ways:
6.3.1 Continuous change of a parameter value
After selecting the parameter, the parameter value can be set by continuously changing the numerical value using the & key.
Short keypress: Number is incremented/decremented by 1 Long push on the key: Number automatically increases/decreases until the key is released.
Enc od er & BC
|
-
" ENC_ INC 102 4 I
|
-
" 203 6
Enc od er r eso lu tion
6.3.2 Changing individual digits
When changing a parameter by a large value, it is possible to change the individual digits separately
After selecting the parameter, use
to the select the desired digit and change from 09 with the &
key
The selected digit is marked with an arrow.
Enc od er & BC
|
-
" ENC_ INC 102 4 ^
|
-
" 203 6
I
Original operating instructions ZAdynpro Part 1 Operation and parameterising
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
8/64
7 Start-up
7.1 General
Danger!
Defective connections can cause the motor to start unexpectedly or lead to uncontrolled motor movements. Reversed connections cause the motor to rotate in the wrong direction. That can cause serious machine damage.
CAUTION!
Caution!
Incorrectly wired connections can destroy the electrical/electronic components. Electrostatic discharges can be hazardous to the electronic components and lead to errors in the software.
You must comply with the following points to prevent machine damage or life-threatening injuries when commissioning the machine:
Only suitably qualied personnel are to be entrusted with the commissioning of the device. They must comply with the safety instructions.
Before starting work, make sure all tools and external parts have been removed from the machine.
Activate all safeguards and the emergency-off switches before commissioning.
Make sure no unauthorized persons are in the machine working area and that no other persons can be endangered when the installation is started up.
inspect the electrical connections before the rst start
Pay special attention to the protective measures (e.g. grounding, ...) for the electrostatically endangered components.
Also read the chapter "General Safety Instructions".
7.2 Conguring the ZAdynpro
1.
Select Startup menu
ZAd yn pro
->S ta rtu p
Sta ti stics
Mem or y car d
2.
S
elect parameter LCD Choose language The languages German and English are integrated as
standard. A third language can be loaded with the memory card.
Sta rt -up
|
-
" LCD Deut sc h
|
-
" Eng li sh
Spr ac he - Lan guage
3.
Select parameter USR_LEV The level which is active after the controller start can be set with
the parameter USR_LEV.
Sta rt -up
|
-
" USR_ LEV Bas ic
|
-
" Adv an ced
Use r le ve l
4.
Select parameter MOT_TYP Enter the operated motor type
Sta rt -up
|
-
" MOT_ TYP SM 2 00
|
-
" SM 20 0
Mot or
5.
Select parameter n Enter the motor's rated speed
Sta rt -up
|
-
" n 72 rpm
|
-
" 72
Rat ed s pe ed
6.
Select parameter f Enter the motor's rated frequency
Sta rt up
|
-
" f 18. 0 Hz
|
-
" 18. 0
Nom in al f reque ncy
7.
Select parameter I Enter the motor's rated current
Sta rt up
|
-
" I 13. 7 A
|
-
" 13. 7
Nom in al c urren t
Original operating instructions ZAdynpro Part 1 Start-up
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
3
9/64
7
Start-up
8.
Select parameter U Enter the motor's rated voltage
Sta rt up
|
-
" U 360 V
|
-
" 360
Nom in al v oltag e
9.
Select parameter P Enter the motor's rated power
Sta rt up
|
-
" P 5.5 kW
|
-
" 5.5
Nom in al P ower
10.
Select parameter cos phi Enter power factor of the motor
Possible only for asynchronous motors
Sta rt -up
|
-
" cos p hi 0.7 5
|
-
" 0.7 5
Pow er f ac tor
11.
Select parameter TYP Choose connection type of the motor
Sta rt up
|
-
" TYP star
|
-
" tri an gle
Con ne cti on typ e
12.
Select parameter ENC_TYP Enter the type of encoder used
Sta rt -up
|
-
" ENC_ TYP EnD at /SS I
|
-
" EnD at /SS I
Enc od er t ype
13.
Select parameter ENC_INC Enter the encoder resolution
Sta rt -up
|
-
" ENC_ INC 204 8 IN C
|
-
" 204 8
Enc od er r esolu tion
14.
Select parameter BC_TYP Enter the used brake resistor or brake chopper
Sta rt -up
|
-
" BC_T YP BR 11
|
-
" BR1 1
BR/ BC t yp e
15.
Select parameter V* Enter the installation rated speed
Sta rt -up
|
-
" V* 1.00 m/ s
|
-
" 1.0 0
Nom in al s peed
16.
Select parameter __D Enter the diameter of the traction sheave
Sta rt up
|
-
" __D 0.31 5 m
|
-
" 0.4 00
Dia m. t ra c. s heave
17.
Select parameter __is Enter the installation's type of suspension
Sta rt -up
|
-
" __is 1:1
|
-
" 1:1
Sus pe nsi on
18.
Select parameter __i1 Input of i1 of the gearbox ratio i1:i2
Possible only for asynchronous motors
Sta rt -up
|
-
" __i1 23.00
|
-
" 23. 00
Gea rb ox i 1:i2
19.
Select parameter __i2 Input of i2 of the gearbox ratio i1:i2
Possible only for asynchronous motors
Sta rt -up
|
-
" __i2 1
|
-
" 1
Gea rb ox i 1:i2
20.
Select parameter Q Enter the elevator installation's rated load
Sta rt -up
|
-
" Q 600 kg
|
-
" 600
Nom in al l oad
Original operating instructions ZAdynpro Part 1 Start-up
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
0/64
21.
Select parameter CONFIG Conguration of the digital inputs according to the used control
system and type of communication
Sta rt -up
|
-
" CONF IG 01 : ZA_I O
|
-
" 01: Z A_IO
Con g ura ti on
22.
Select parameter MO_DR Changing the rotating direction of the motor It must be observed the with triggering the input RV1 the cabin
drives upwards
Sta rt -up
|
-
" MO_D R Left
|
-
" Lef t
Mot or r ot ation dir ec tio n
23.
Select parameter BR Denition of the brake monitoring
Sta rt -up
|
-
" BR Off
|
-
" 3*N O
Bra ke m on itor
24.
Select parameter P1P2 Motor temperature monitoring
Sta rt -up
|
-
" P1P2 Off
|
-
" PTC
Mot or t em p. m onito r
25.
Select parameter K_START Amplication at start (see chapter "List of parameters/menu
start-up")
Sta rt -up
|
-
" K_ST ART 1.0
|
-
" 1.0
Con tr ol v ers. at st art
26.
Select parameter SPD_KP Multiplication factor to modify the calculated basic amplication
SPD_C
Sta rt -up
|
-
" SPD_ KP 1. 00
|
-
" 1.0 0
Con tr oll er bas ic g ai n
7.3 Testing the Safe Torque Off function (STO)
In the course of start-up, the "Safe Torque Off (STO)" function must be tested as a safety function test. Proceed as follows:
Test step Result
Check the state of the two inputs STO_A and STO_B at standstill of the drive (no travel signals).
In the Info menu/Start/Stop, the STO_A and STO_B inputs must be marked as inactive by a small dot. A large dot must be visible next to the DIAG display.
Trigger application of a travel command, e.g. by briey pressing the Recover UP or DOWN button.
In the Info menu/Start/Stop, the STO_A and STO_B inputs must be marked as active by a large dot. A large dot must be visible next to the DIAG display.
Attention: As soon as the large dots are visible at STO_A and STO_B, remove the travel command.
At standstill of the drive (no travel signals), bridge the normally open contact of the relay for triggering the STO_A signal so that the STO_A input is activated.
In the Info menu/Start/Stop, the STO_A input must initially be marked as active by a large dot. A large dot must be visible next to the DIAG display. After a time of approx. 1 second, the displays for STO_A and DIAG change from a large dot to a small dot (all displays marked as inactive).
The ZAdynpro triggers the "STO diagnostic" error (error 960).
Then remove the bridge at the relay contact again. Then reset the error by switching the line voltage
off/on.
Original operating instructions ZAdynpro Part 1 Start-up
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
1/64
7
Start-up
Test step Result
At standstill of the drive (no travel signals), bridge the normally open contact of the relay for triggering the STO_B signal so that the STO_B input is activated.
In the Info menu/Start/Stop, the STO_B input must initially be marked as active by a large dot. A large dot must be visible next to the DIAG display. After a time of approx. 1 second, the displays for STO_B and DIAG change from a large dot to a small dot (all displays marked as inactive).
The ZAdynpro triggers the "STO diagnostic" error (error 960).
Then remove the bridge at the relay contact again. Then reset the error by switching the line voltage
off/on.
At standstill of the drive (no travel signals), bridge both normally open contacts of the relay for triggering the STO_A/STO_B signals so that both inputs are activated.
The ZAdynpro triggers the "STO: Travel signal miss­ing" error (error 534) after the time specied by the T_SDLY parameter.
Then remove the bridge at the relay contacts again.
The test of the STO safety function should be repeated at regular intervals (e.g. annually during routine inspections).
7.4 Setting the switch-off points
7.4.1 Interrupt points for the travel speeds V_3 and V_2
The deceleration paths after V_1 or after standstill (in DCP2 and DCP4 protocol) can be read directly in the Info menu/page 03.
Dis t. - - - - - - - - - -
03
sa: 0 .0 0 s 21 : 0 .5 2m
sr: ^0 .00 s 31 : 1 .4 5m
s1: 0 s d: 0.52 m
s31: Display of calculated deceleration path V_3
V_1 s30: Display of calculated deceleration path V_3 Standstill s21: Display of calculated deceleration path V_2 V_1 s20: Display of calculated deceleration path V_2 Standstill
7.4.2 Cut-off points for travel speed V_1
To prevent the ush alignments from being travelled over, the switch-off points of V_1 must be set depending on the deceleration A_NEG at between 2 and 5 cm before the ush alignment.
7.5 Carrying out the first test run
Caution!
Operating synchronous motors without encoder offset can cause uncontrolled motor movements
The rst trip must be carried out with the return control or as an inspection trip.
If this trip can be carried out without any problems and without any fault messages, a normal trip can be made as the next step.
If fault messages appear, an error list is available in the Diagnose chapter together with the corresponding error causes
Original operating instructions ZAdynpro Part 1 Start-up
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
2/64
7.6 Optimisation of the startup and drive behaviour
Turning away when starting up
Turning away when starting up is indicated by uncontrolled movement of the driving disc. The reason for this is insufcient amplication of the RPM controller at the time when the brake opens.
RPM controller
The SPD_KP (amplication) parameter can be used to optimise the setting of the RPM controller acting during travel.
1.
Select parameter Startup/SPD_KP Multiplication factor to modify the calculated basic amplication
SPD_C
Sta rt up
|
-
" SPD_ KP 1. 00
|
-
" 0.9 5
RPM con tr oller bas ic
gai n
2.
Increase of the parameter Startup/SPD_KP until the motor ei­ther no longer turns away or causes noises/vibrations when starting up.
Sta rt -up
|
-
" SPD_ KP 1. 00
|
-
" 1.0 0
Con tr oll er bas ic g ai n
3.
If the motor causes noises/vibrations when starting up, decrease the parameter Startup/SPD_KP until the motor no longer causes any noises/vibrations.
Sta rt -up
|
-
" SPD_ KP 1. 00
|
-
" 1.0 0
Con tr oll er bas ic g ai n
If the motor turns away when starting up despite optimum setting of the basic gain (parameter Control/SPD_KP), this can be optimised by increasing the parameter Startup/K_START.
CAUTION!
Caution! Before the parameter Start/K_START is increased, it must be ensured that the basic gain ( Controller/SPD_KP) is optimally set!
4.
Select parameter "SPD_KP" Start gain Multiplication factor for the parameter Controller/SPD_KPor
charge controller boost (depending on start-up mode)
Sta rt -up
|
-
" K_ST ART 1.0
|
-
" 3.0
Sta rt g ai n
Original operating instructions ZAdynpro Part 1 Start-up
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
3/64
7
Start-up
8 "Safe Torque Off (STO)" function
8.1 General
The "Safe torque off (STO) function in the ZAdynpro product series corresponds to the "Safe torque off (STO)" stop function in accordance with DIN EN 61800-5-2.
Activation of this function ensures that the ZAdynpro cannot supply any energy to the motor which can cause a torque.
The STO function allows the contactors that are usually installed between ZAdynpro and motor in lifts to be omitted. The requirements in accordance with EN 81-20 section 5.9.2.5.4 d) or section
5.9.3.4.2 d) are fullled.
The STO function must be taken into consideration in an application-specic risk analysis by the company responsible for the start-up. This company is also responsible for considering other valid safety regulations as well as the denition of the requirements for the component which control the STO function in compliance with standards.
Danger
There is no active braking when the STO function is activated. The drive stops gradually. This must be taken into consideration in applications in which there might be a hazard (e.g. by vertical loads). Active braking must be implemented by additional measures (e.g. by a mechanical motor brake).
8.2 Safety concept
The24devices of the ZAdynpro series have two safety-related inputs (two-channel structure). The drive can only generate a torque when a V switching signal is applied to both of these inputs. When the two 24V switching signals are switched off, the STO function is activated and the activation of the switching transistors (IGBTs) is safely prevented.
An internal diagnostic unit constantly compares the status of the two switch-off channels (STO_A and STO_B). If there is an error (unequal activation or an internal hardware defect), the internal diagnostic unit triggers switch-off of the drive.
Both inputs must be activated via two separate relays whose control voltage is supplied at the end of the electrical safety chain (see Chapter "Safe torque off (STO) function/Principle circuit dia­gram").
Information
In the version according to the principle circuit diagram, monitoring of the two relays K1/K2 by the lift control system is not necessary in order to meet the requirements of EN 81-20. The requirements are met by the internal diagnostic unit.
If the contacts are switched differently (e.g. one of the two relays does not open), this will be detected at the STO inputs by the different signals. In this case the internal diagnostic unit will turn off safely after a max. 1600 ms. In this case, a reset is only possible by switching the device off and on again.
The status of the STO function can be queried optionally (not safety-related) via the digital output "STO-Info".
Danger
The connected motor is not separated from the ZAdynpro by activation of the STO function. Therefore, you must disconnect the ZAdynpro from the supply voltage in order to perform work on the wiring or the motor. You must waitat least Allow 3 minutes for discharging the intermediate circuit capacitors. The safe isolation from the supply must be checked using a two-pole voltage detector.
Danger
If the drive is enabled again after being disabled by the STO function, the drive can restart automatically. If this is not admissible for the application, this must be implemented by external measures (restart e.g. only after conrmation).
Original operating instructions ZAdynpro Part 1 "Safe Torque Off (STO)" function
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
4/64
8.3 Principle circuit diagram
(1)
STO_B
(2)
STO_A
GND_
STO
(4)
(3)
GND
+24V_ STO
(6)
(5)
N
L
X-STO
K2
K1
1
2
4
3
O51 O54
(9) (10)
24V I1
X-OUT
STO-Info
ZAdynpro
1)
Principle circuit diagram "Safe Torque Off (STO)" function
1 Electrical safety chain 2 Modulation 3 Protected routing or design with two separate jacketed cables (see chapter "STO interface (X-STO)") 4 Digital inputs control
1) Information only, not safety-related
8.4 Electrical connection
The connection is made via the interface X-STO on the ZAdynpro (see chapter "Electrical installation / STO interface (X-STO))".
8.5 Notes for operation
The two STO inputs must be switched simultaneously by separate relays with every travel (two­channel activation). Removal of one of the two STO_A or STO_B input signals already leads to switching off of the output stage.
When switching the STO input signals STO_A / STO_B, a time offset of max. 120 ms is tolerated between the signals. With a greater offset the ZAdynpro rst triggers the error "STO: fault" (error
533). This gives the elevator control system the option of aborting travel.
If the actuation fault persists, safe switch-off is effected after a further min. 190 ms and max. 1,480 ms (typically 630 ms) by the internal diagnostics (error 960 "STO: diagnostics").
An error detected by the internal diagnostic (unequal activation or internal hardware defect) leads to a locked error state. The error can only be reset after switching the line voltage off/on.
STO_A STO_B
< 120 ms
STO_Info ST
X-STO
X-OUT
Correct activation STO
STO_A safety-related input STO_A STO_B safety-related input STO_B STO_Info inputs STO_A / STO_B active – enable output stage ST fault
Original operating instructions ZAdynpro Part 1 "Safe Torque Off (STO)" function
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
5/64
8
"Safe Torque O
(STO)" function
STO_A STO_B
1
2
STO_Info ST
X-STO
X-OUT
120 ms 190 ms < T < 1480 ms
Faulty activation STO
1 Error "STO: Fault 2 Error "STO: Diagnostic"
The following times must be kept in operation for sufcient test coverage by the diagnostics.
Activation STO (switch-off of STO_A and STO_B) at least once an hour for at least 1,600 ms.
The correct activation of the STO inputs is monitored additionally (not safety-related) by the ZAdynpro for every journey:
If the safe torque off is not cancelled (signals STO_A, STO_B remain LOW) at the beginning of travel after expiry of the time specied by the T_SDLY parameter (Monitors menu), the error "STO: Remains" (error 530) is triggered.
If no safe torque off takes place (signals STO_A, STO_B remain HIGH) at the end of travel after expiry of the time specied by the T_SDLY parameter (Monitors menu), the error "STO: Missing" (error 532) is triggered
If the safe torque off is cancelled (signals STO_A, STO_B become HIGH) at a standstill (no travel signals applied) and no travel signal is applied after the time specied by the T_SDLY parameter ( Monitors menu), the error "STO: Travel signal missing" (error 534) is triggered.
If the STO input signals are switched off during travel, the error STO: Interruption (error 531) is triggered after 200 ms.
During rst-time start-up and the recurring tests, the function "Safe torque off (STO)" must be tested (see chapter "Start-up/testing the safety function "Safe torque off (STO)"")
8.6 Notes on use of motors
Danger
A brief aligning torque is possible in the event of an error. The motor can turn in the event of an error (defect of two or more power semiconductors) by a maximum angle φ = 360°/number of poles.
If there is a random component error on two or more circuit breakers of the inverter, there may be a brief alignment movement by a few degrees with permanently excited synchronous machines even when the STO function is activated. A permanent eld of rotation cannot be generated. The effect of the aligning torque is described below.
The maximum possible cabin movements allowed by the alignment torque can be calculated with the following formula:
Cabin movement [mm] = 3.142 x
driving disk diameter [mm]
Number of poles x suspension
Examples for possible cabin movements depending on the motor, the driving disk diameter and the suspension can be found in the following table.
Original operating instructions ZAdynpro Part 1 "Safe Torque Off (STO)" function
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
6/64
Examples for max. cabin movement in mm with ZAtop (20-pole)
Ø driving disk 160 mm 210 mm 240 mm 320 mm 400 mm 450 mm 500 mm 520 mm 600 mm Suspension 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1
Cabin move­ment [mm]
26 13 7 33 17 9 38 19 10 51 26 13 63 32 16 71 36 18 79 40 20 82 41 21 95 48 24
Examples for max. cabin movement in mm with ZAsyn (30-pin)
Ø driving disk - - - 320 mm 400 mm 480 mm 520 mm 600 mm 680 mm Suspension - - - - - - - - - 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1 1:1 2:1 4:1
Cabin move­ment [mm]
- - - - - - - - - 34 17 9 42 21 11 51 26 13 55 28 14 63 32 16 72 36 18
The cabin movement must be taken into consideration in a risk analysis of the complete system.
8.7 Deactivation of the STO function
Danger
There is no safety-related switch-off of the output stage when the STO function is deactivated. Safety switch-off in accordance with EN 81 must then be implemented by other measures (e.g. by motor contactors), (refer to chapter "Electrical installation/Motor contactors (optional)".
8.8 Testing the "Safe Torque Off (STO)" safety function
In the course of start-up, the "Safe Torque Off (STO)" function must be tested as a safety function test (see chapter "Start-up/Testing the Safe Torque Off (STO) Function".
8.9 Technical data
Safety characteristics
Safety function Safe torque off (STO) according to DIN EN 61800-5-2 Protection rating SIL 3 according to DIN EN 61800-5-2
1)
Category 4, PL e according to DIN EN ISO 13849-1
1)
Meets the requirements according to DIN EN 81-20, section
5.9.2.5.4 d) or section 5.9.3.4.2 d)
1)
Probability of one dangerous failure per hour (PFH)
3.11E-10 per hour
2)
Mean time to dangerous failure of each chan­nel (MTTFd)
410 years
2)
Diagnostic coverage (DC) high Switch-off time (duration from switching off the
input signals to blocking the output stage)
< 50 ms
Minimum request rate for the STO function Once an hour for at least 1,600 ms Life cycle 20 years, then the device must be replaced by a new one max. permissible time delay between the sig-
nals STO_A / STO_B
max. 120 ms (on exceeding this, ZAdynpro outputs an error message, see
chapter "Safe Torque Off (STO) Function / Notes on Opera­tion")
1)
TÜV Rheinland conducted type examination and certication for this. Copies of the test certicates
can be requested from Ziehl-Abegg.
2)
assuming maximum device load for the entire life cycle
Original operating instructions ZAdynpro Part 1 "Safe Torque Off (STO)" function
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
7/64
9
Enclosure
9 Enclosure
9.1 Technical data for ZAdynpro
ZAdynpro
011 013 017 023 032
ZAdynpro article number
352250 352251 352252 352253 352254
Electrical data
Mains connection voltage [V] 3~ 180 ... 440 absolut M
ains frequency [Hz] 50 / 60 (±1,5 Hz) Typ. motor output (400 V) [kW] 4.6 5.5 7.5 11 14 Duty cycle at rated current and clock frequency
8 kHz
[%]
40
Nominal current for 40% duty cycle and switch­ing frequency 8 kHz xed
[A] 11 13 17 23 32
Nominal current for 40% switch-on duration and switching frequency 12 kHz x
1)
[A] 9 11 15 20 27
Nominal current for 40% duty cycle and switch­ing frequency 16 kHz x
1)
[A] 8 10 13 17 23
Max. operating current (for max. 10 s) [A] 20 24 31 42 58 Power loss at nominal current, switching fre-
quency 8 kHz and 40% duty cycle
[W] 137 150 186 230 295
Power loss at nominal current, switching fre­quency 16 kHz and 40% duty cycle
[W] 221 239 296 350 432
Power losses during standstill [W] 24 25 26 27 27 Power loss in standby [W] 3.0 W 6.0 W Switching frequency [kHz] 4 ... 16 Motor frequency [Hz] max. 200 Max. terminal cross-section line/motor/brake
chopper/brake resistor
[mm2]
16
Ambient conditions
The user must ensure that the specied ambient conditions are observed.
Protection rating (as per DIN EN 60529)
IP20
A
mbient temperature for operation [°C] 0 ... 55, from 40 °C power reduction by1.66% per 1 k temperature
increase Relative humidity [%] 90 / condensation prohibited Installation height [m über
NN]
bis 2000, ab 1000 m Leistungsreduzierung um 1% pro 100 m
Storage and shipping temperature [°C] -20 to +60 Degree of soiling (in acc. with DIN EN 61800-5-
1)
2
P
hysical data
Weight ZAdynpro [kg] 4.5 4.5 4.6 6.0 6.1 Dimensions h x w x d [mm] 290 x 150 x 195 390 x 151 x 195
1)
with a variable switching frequency (power component/M_PWM=AUTO menu), there is no reduction in power
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
8/64
9.2 EC/EU declaration of conformity - Translation -
(english)
A-KON16_06-GB
1741 Index 003
Manufacturer:ZIEHL-ABEGG SE
Heinz-Ziehl-Straße 74653 Künzelsau Germany
The manufacturer shall bear sole responsibility for issuing this EC/EU declaration of conformity.
Product description: Control devices ZAdyn/ZETADYN for elevator machines
Frequency inverters with a safe torque off (STO) function according to the Machinery directive 2006/42/EC, Annex IV, Nr. 21.
Type: ZAdyn4CA...
ZAdyn4CS... ZETADYN 4CA... ZETADYN 4CS... ZAdynpro...
(The type details contain further additions concerni
ng the version, e.g. ZAdyn4-
CA 018 HY)
Serial number from
30284129/0001
The above mentioned products of this declaration full all relevant provisions of the following Directives of the Union:
Machinery directive 2006/42/EC
EMC Directive 2014/30/EU
Because of the accordance with the Machinery directive, the protection targets of the Low voltage directive 2014/35/EU are also fullled.
The following harmonised standards have been used:
EN 61800-5-1:2007 Adjustable speed electrical power drive systems - Part 5-1:
Safety requirements ­Electrical, thermal and energy
IEC 61800-5-2:2016 Adjustable speed electrical power drive systems – Part 5-2:
Safety requirements – Functional
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
4
9/64
9
Enclosure
EN 62061:2005 + A1:2013
Safety of machinery ­Functional safety of safety-related electrical, electronic and programmable electronic control systems
EN ISO 13849-1:2008 + AC:2009
Safety of machinery ­Safety-related parts of control systems ­Part 1: General principles for design
EN ISO 13849-2:2012 Safety of machinery -
Safety-related parts of control systems ­Part 2: Validation
EN 61800-3:2004 + A1:2012
Adjustable speed electrical power drive systems ­ Part 3: EMC requirements and specic test methods
EN 12015:2014 Electromagnetic compatibility-
Productfamily standard for lifts, escalators and moving walks - Emission
EN 12016:2013 Electromagnetic compatibility-
Productfamily standard for lifts, escalators and moving walks - Immunity
The EG type-examination procedures referred to in the enclosure IX of the Machinery directive 2006/42/EC was carried out by TÜV Rheinland and certied by the type-examination certicate 01/205/5288.01/17
The identication number / address of the notied body is:
NB 0035 TÜV Rheinland Industrie Service GmbH Am Grauen Stein 51105 Köln Germany
This declaration relates exclusively to the product in the state in which it was placed on the market, and excludes components which are added and/or operations carried out subsequently by the nal user.
The authorised representative for the assembly of the technical le is: Mr. Roland Hoppenstedt (see above for address).
Kün
zelsau, 10.10.2017
(location, date of issue)
ZIEHL-ABEGG SE Werner Bundscherer Director Drive Division (name, function)
ZIEHL-ABEGG SE Roland Hoppenstedt Technical Director Drive Division (name, function)
(Signature) (signature)
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
0/64
9.3 Adjustment card
"Motor name plate" menu
Control system menu
Start menu
MOT_TYP
CONFIG
M_START
n
MO_DR
K_START
f
CTRL
T_0
p
f_I01
T_1
I
f_I02
T_2
U
f_I03
T_3
P
f_I04
V_T3
TYP
f_I05
BRK_DMP
cos phi
1)
f_I06
M_Max
f_I07
Acceleration menu
f_I08
A_POS
Encoder & BC menu
f_XBR1
R_POS1
ENC_TYP
f_XBR2
R_POS2
ENC_INC
f_XBR3
BC_TYP
f_XBR4
Travelling menu
f_O1
V_1
Installation menu
f_O2
V_2
V*
f_O3
V_3
MOD_n*
f_O4
V_Z
n*
V_G1
V_4
__D
V_G2
V_5
__iS
V_G3
V_6
__i1
SIM_V1
V_7
__i2
S_B_OFF
Q
1)
Deceleration menu
F
1)
Monitoring menu
A_NEG
G
1)
MOD_ST
R_NEG1
STO
R_NEG2
1)
The parameter is only visible if
MOT_TYP=ASM is selected.
CO
S_DI3
BR
S_DI2
LOCKBR
S_DI1
UNLOCK
S_ABH P1P2 T_ENC
Stop menu
T_SDLY
T_4 I_MAX
T_5 T_I_MAX
T_5a APC
T_5b MASK1
T_6 MASK2 MASK3
Controller
menu
MASK4
SPD_KP MASK5
SPD_TI
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
1/64
9
Enclosure
9.4 Type designation
ZAdynpro
xxx
Model range
Rated current
011 11 A 013 13 A 017 17 A
023 23 A 032 32 A
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
2/64
9.5 Certicates
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
3/64
9
Enclosure
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
4/64
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
5/64
9
Enclosure
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
6/64
9
Enclosure
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
7/64
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
8/64
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
5
9/64
9
Enclosure
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
6
0/64
9
Enclosure
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
6
1/64
Original operating instructions ZAdynpro Part 1 Enclosure
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
6
2/64
9
Enclosure
Original operating instructions
ZAdynpro – Part 1
R-TBA17_01-GB 1837 Index 004 Part.-No. 00163459-GB
6
3/64
9.6 Index
A
A
dvanced Level 37
away when starting up is 43
B
Basic Level 37 Binary travelling speed de-
fault 22 Brake release monitoring 32 Brake resistor 18 Brake-Resistor connection 18 Brakes 32
C
CAN interface 23 Certicates 3, 53 Commissioning 6, 39 Connection of asynchronous
motor rotary encoder 26 contactor monitoring 31 Copyright 5
D
Digital inputs 20 Digital outputs (X-OUT1, X-
OUT2) 22 Dimensional drawings 11 due diligence 6
E
EMC-compatible installation 12 Exclusion of liability 4 External 24 V voltage supply 28
H
Hazards 6
I
installation 10 Interrupt points 42 interventions 6
M
Mains connection 16 maintenance 9 Menu and parameter navi-
gation 37 Menu navigation 36 Minimum distances 11 Monitoring of the motor con-
tactors (X-BR) 31 Motor connection 19 Motor contactors 30-31
N
Name plate 9
O
operate and congure 35 operating levels 37
P
Pictographs 5 Product safety 6 Protective ground connection 16
R
Residual current operated
device (RCCB) 17
Rotary encoder connection
for synchronous motors 27
Rotary encoder simulation 28
S
Safety instructions 5 Service 9 Standby input (X-SBY) 29 STO 41, 44 STO interface (X-STO) 24 Symbols description 4
T
Target group 4 Technical data for ZAdynpro 48 Terminal positions 15 terminating resistor 23 Transport 9 Type designation 52
W
wiring 23
Z
ZAdynpro circuit suggestion 34
© by Ziehl-Abegg - - - 00163459-GB - 1837 Index 004 - - - Subject to technical modifications
Customer Service
phone +49 7940 16-308 fax +49 7940 16-249 drives-service@ziehl-abegg.com
Headquarters
ZIEHL-ABEGG SE Heinz-Ziehl-Strasse · 74653 Künzelsau Germany phone +49 7940 16-0 · fax +49 7940 16-249
drives@ziehl-abegg.de www.ziehl-abegg.com
Loading...