ZIEHL-ABEGG Dcontrol PKDM25, Dcontrol PKDM10, Dcontrol PKDM35, Dcontrol PKDM20, Dcontrol PKDM25E Operating Instructions Manual

...
Dcontrol
PKDM6..80
P-controller and speed controller for variable voltage 3 ~ fans
Operating Instructions
Software version: D2498A from Version 02.00
L-BAL-E143-GB 1914 Index 009 Part.-No.
english
1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Explanations of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Requirements placed on the personnel / due diligence . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Start-up and during operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6 Work on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7 Modications / interventions in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.8 Operators obligation of diligence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.9 Employment of external personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Operational area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Name plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2 Minimum space requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.3 Fastening the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.4 Outdoor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.5 Installation location for agriculture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.6 Temperature inuences during commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 EMC-compatible installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2.1 Motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2.2 Control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2.3 Harmonics current for devices 16 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.4 Harmonics current and line impedance for devices > 16 A and 75 A . . . . . . . . . 12
5.3 Mains connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.1 Line voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2 Required quality attributes for the mains voltage . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.3 Operating in IT-System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.4 Residual-current-operated protective device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.5 Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.5.1 Running noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.6 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.7 Signal connection or sensor connection to analog inputs (Analog In 1, Analog In 2) . . 14
5.7.1 Setting signal for operation speed controller
1.01 . . . . . . . . . . . . . . . . . . . . . . . . 14
5.7.2 Sensor connection for operation as P-Controller
2.01 ... 3.02 . . . . . . . . . . . . . . . . . 15
5.8 Output voltage 0 - 10 V (A1 = Analog Out 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.9 Voltage supply for external devices (+24V, GND) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.10 Digital inputs (D1, D2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Operating Instructions Dcontrol – model series PKDM6..80
L-BAL-E143-GB 1914 Index 009 Part.-No.
2/40
5.10.1 D1 = Enable (Device ON / OFF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.10.2 D2 = Reverse action of the control function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.11 Relay outputs (K1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.12 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.12.1 Networking via MODBUS-RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.12.2 RS-485 - network design and interface parameter . . . . . . . . . . . . . . . . . . . . . . . . 17
5.12.3 USB-interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.13 Potential at control voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6 Operating and display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7 Base setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.1 Programming of the desired function (Speed controller / P-Controller) . . . . . . . . . . . . . 20
7.2 Select operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.3 Dipswitch for operation as Speed controller:
1.00 , 1.01 . . . . . . . . . . . . . . . . . . . . . . . 21
7.4 Dipswitch for operation as P-controller:
2.01 , 2.02 , 3.01 , 3.02 . . . . . . . . . . . . . . . . . 22
7.5 Minimum speed cut off DIP 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.5.1 For mode Speed controller
1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.5.2 For operation as P-Controller(from
2.01 ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.6 Hardstart function DIP 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.7 Adjusting of CosPhi for motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.8 Adapting to specic mains conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.8.1 Fix 60 Hz allocation DIP 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.8.2 Deactivate phase monitoring DIP 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.1 Prerequisites for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9 Setting for operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9.1 Speed controller
1.00 and 1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9.1.1 Setting for operation as Speed controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9.1.2 Operation with two variable output voltages (two steps) . . . . . . . . . . . . . . . . . . . . . 25
9.2 Temperature control
2.01 and 2.02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.2.1 Setting for operation as Temperature controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.2.2 Example Temperature control Cooling function (factory setting) . . . . . . . . . . . . . . 27
9.2.3 Example Temperature control Heating function . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.3 Pressure control condensers
3.01 and 3.02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.3.1 Setting for operation as Pressure controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.3.2 Example Pressure control condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.3.3 Setting with refrigerant medium table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10 Diagnostics / Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.1 If controller doesn´t work correctly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.1.1 Max. load depending on ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
11.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
11.3 Dimensions [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.4 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
11.5 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
11.6 Service information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Operating Instructions Dcontrol – model series PKDM6..80
L-BAL-E143-GB 1914 Index 009 Part.-No.
3/40

1 General notes

Compliance with the following instructions is mandatory to ensure the functionality and safety of the product. If the following instructions given especially but not limited for general safety, transport, storage, mounting, operating conditions, start-up, maintenance, repair, cleaning and disposal / recy­cling are not observed, the product may not operate safely and may cause a hazard to the life and limb of users and third parties. Deviations from the following requirements may therefore lead both to the loss of the statutory material defect liability rights and to the liability of the buyer for the product that has become unsafe due to the deviation from the specications.

1.1 Structure of the operating instructions

Before installation and start-up, read this manual carefully to ensure correct use! We emphasize that these operating instructions apply to specic units only, and are in no way valid for the complete system! Use these operating instructions to work safely with and on the device. They contain safety instruc­tions that must be complied with as well as information that is required for failure-free operation of the device. Keep these operating instructions together with the device. It must be ensured that all persons that are to work on the device can refer to the operating instructions at any time. Keep the operating instructions for continued use. They must be passed-on to all successive owners, users and nal customers.

1.2 Target group

The operating instructions address persons entrusted with planning, installation, start-up, mainte­nance and servicing, who have the corresponding qualications and skills for their job.

1.3 Exclusion of liability

Concurrence between the contents of these operating instructions and the described hardware and software in the device has been examined. It is still possible that non-compliances exist; no guarantee is assumed for complete conformity. To allow for future developments, construction methods and technical data given are subject to alteration. We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. ZIEHL-ABEGG SE is not liable for damage due to misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modications.

1.4 Copyright

These operating instructions contain copyright protected information. The operating instructions may be neither completely nor partially photocopied, reproduced, translated or put on data medium without previous explicit consent from ZIEHL-ABEGG SE. Infringements are liable for damages. All rights reserved, including those that arise through patent issue or registration on a utility model.

2 Safety instructions

This chapter contains instructions to prevent personal injury and property damage. These instructions do not lay claim to completeness. In case of questions and problems, please consult our company technicians.

2.1 Intended use

The equipment is to be used solely for the purposes specied and conrmed in the order. Any other use above and beyond this is considered not for the intended purpose unless agreed otherwise by contract. The manufacturer will not be liable for any damage resulting from this. The individual or company using it bears the sole risk. Reading these operating instructions and complying with all contained instructions - especially the safety notications contained therein - are considered part of intended use. To consider is also the manual of attached components. Not the manufacturer, rather the operator of the device is liable for any personal harm or material damage arising from non-intended use!
Operating Instructions Dcontrol – model series PKDM6..80 General notes
L-BAL-E143-GB 1914 Index 009 Part.-No.
4/40

2.2 Explanations of symbols

Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows.
Attention!
General hazardous area. Death or severe injury or signicant property damage can occur if the corresponding precautions are not taken!
Danger due to electric current
Danger by dangerous, electric voltage! Death or severe injury can occur if the corresponding precautions are not taken!
Information
Important additional information and advice for user.

2.3 Product safety

The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable. The device and its accessories must only be used in a flawless condition and installed and operated in compliance with the assembly instructions and/or operating instructions. Operating out­side the device's technical specications (see name plate and attachment / technical data) can lead to a defect in the device and additional damage!
Information
In the case of a malfunction or a failure of the equipment check all functions with alarms in order to prevent injury to persons or property. Note possibility of back-up operation. If used in intensive animal environments, any malfunctions in the air supply must be detected as soon as possible to prevent the development of a life-threatening situation for the animals. The design and installation of the system must comply with local regulations and directives. In Germany these include DIN VDE 0100, the animal protection and the keeping of working animals ordinance and the pig-keeping ordinance etc. Also note the instructions of AEL, DLG, VdS.

2.4 Requirements placed on the personnel / due diligence

Persons entrusted with the planning, installation, commissioning and maintenance and servicing in connection with the frequency inverter must have the corresponding qualications and skills for these jobs. In addition, they must be knowledgeable about the safety regulations, EU/EC directives, rules for the prevention of accidents and the corresponding national as well as regional and in-house regulations. Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supervision of an experienced person. This also applies to personnel undergoing general training. Comply with the legal minimum age.
2.5 Start-up and during operation
Attention!
During commissioning, unexpected and hazardous conditions can arise in the entire installation due to defective adjustments, defective components or incorrect electrical connections. Remove all persons and objects from the hazardous area.
During operation, the device must be closed or installed in a control cabinet. Fuses may only be replaced by new ones and must not be repaired or bypassed. The data for the maximum line fuse are to be considered absolutely (see Technical data). Use only fuses specied in schematic diagrams.
Any faults detected in the electric system/modules/operating equipment must be corrected immediately. If these faults are not corrected, the device/system is potentially very dangerous. The device/system must therefore not be operated when it is faulty.
Pay attention to smooth, low vibration running of the motor/fan, the appropriate instructions in the drive documentation must be observed!
Operating Instructions Dcontrol – model series PKDM6..80 Safety instructions
L-BAL-E143-GB 1914 Index 009 Part.-No.
5/40

2.6 Work on the device

Information
Mounting, electrical connection, and start-up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)!
Danger due to electric current
It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP00! It is possible to touch hazardous voltages directly. The safe isolation from the supply must be checked using a two-pole voltage detector.
Attention!
Even after switching off, dangerous temperatures can still occur in and on the device.
Attention!
Automatically restart after a power failure or mains disconnection!
2.7 Modications / interventions in the device
Attention!
For reasons of safety, no unauthorized interventions or modications may be made on the device. All planned modications must be authorized by the manufacturer in writing.
Use only genuine spare parts / genuine wearing parts / genuine accessories from ZIEHL-ABEGG.Th­ese parts were specically designed for the device. There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements. Parts and optional equipment not supplied by ZIEHL-ABEGG are not approved by ZIEHL-ABEGG for use.

2.8 Operators obligation of diligence

The contractor or owner must also ensure that the electric systems and equipment are operated and maintained in accordance with electro-technical regulations.
The owner is obliged to ensure that the device is operated in perfect working order only.
The device may only be used as intended.
You must periodically examine the safety equipment for their properly functioning condition.
The assembly instructions and/or operating instructions are always readily available at the location where the device is being used, are complete and are in legible condition.
These persons are regularly instructed in all applicable questions regarding occupational safety and environmental protection and are knowledgeable regarding the assembly instructions and/or operating instructions and, especially, are familiar with the safety instructions contained therein.
All safety and warning notices attached to the device are never removed and remain legible.

2.9 Employment of external personnel

Maintenance and service work are frequently carried out by external employees who often do not recognize the specic situations and the thus resulting dangers.These persons must be comprehen­sively informed about the hazards in their area of activity. You must monitor their working methods in order to intervene in good time if necessary.
Operating Instructions Dcontrol – model series PKDM6..80 Safety instructions
L-BAL-E143-GB 1914 Index 009 Part.-No.
6/40

3 Product overview

3.1 Operational area

The controller described is used for continuous speed adjustment on variable voltage 3~ motors used to drive ventilators or pumps.

3.2 Name plate

The name plate carries the technical data valid for the delivered product.
Example for name plate
no. Designation no. Designation
1 Type designation 4 Part no.
2 ZIEHL-ABEGG brand name 5 Serial number
3 Type of voltage
Line voltage Mains frequency Rated current (output) Protection rating
6 Production code
7 DATA MATRIX code serial number
8 European mark of conformity
9 Eurasian mark of conformity

3.3 Maintenance

The device must be checked for soiling and, if necessary, cleaned in periodic intervals.

3.4 Transport

The device is packed ex factory to suit the transport method previously agreed.
Always use the original packaging materials when transporting the device.
Avoid shocks and impacts to the device during the transport.
During manual handling the human lifting and carrying restrictions must be observed and adhered to.

3.5 Storage

The device must be stored in its original packaging in a dry and weather-proof room.
Avoid exposure to extreme heat and cold.
Avoid over-long storage periods (we recommend a maximum of one year).

3.6 Disposal / recycling

Disposal must be carried out professionally and in an environmentally friendly way in accordance with the respective national legal stipulations.
" Separate the materials by type and in an environmentally friendly way. " If necessary, commission a specialist company with the waste disposal.
Operating Instructions Dcontrol – model series PKDM6..80 Product overview
L-BAL-E143-GB 1914 Index 009 Part.-No.
7/40

4 Mounting

4.1 General notes

Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental inuences:
Before installation remove the device from the packing and check for any possible shipping damage! Start-up is not allowed in the case of transport damage!
At a weight greater than 25 kg for men / 10 kg for women, the device should be lifted out by two persons (according to REFA). The values may differ from country to country.
Wear safety shoes and gloves for handling!
Assemble the device on a clean and stable base. Do not distort during assembly! Use the appropriate mounting devices for proper installation of the unit!
Do not mount equipment on vibrating base!
When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock loads. Any banging shut of doors that are integrated into these lightweight walls, can result in extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
The device should be installed in a location where it will not be disturbed, but at the same time can be easily accessed!
Depending on the housing model use supplied stoppers for cable inlets, cut off necessary cable inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands. Any cable ducts openings not used must be sealed!
Care must be taken to avoid direct radiation from the sun!
The device is designed for vertical installation (bottom cable inlet). A horizontal or reclined installa­tion is only permissible after technical release of the manufacturer!
Be sure to observe proper heat dissipation (see Technical data, heat dissipation).

4.2 Minimum space requirement

In order to ensure sufcient ventilation of the device, clearance on all sides of at least 50 mm has to be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance applies to the installation of several devices next to each other. When installing several devices on top of each other, the danger of reciprocal heating exists. This layout is only then permissible when the air suctioned from the upper unit does not become warmer than the permissible ambient temperature (see Technical data). I.e., a correspondingly larger clear­ance or thermal shielding is required.
Operating Instructions Dcontrol – model series PKDM6..80 Mounting
L-BAL-E143-GB 1914 Index 009 Part.-No.
8/40

4.3 Fastening the device

The type of fastening and the number of fastening points are dependent on the housing design. All the fastening points available must be used for safe fastening.
Proceed as follows:
Type PKDM6/10 (PKDM12/15)
Fastening at 3 points
3
2
1
GM00012A_M
12.07.2017
" Drill fastening point 1. " Screw in at-head screw up to a distance of approx. 2 mm and mount the device. " Remove the terminal compartment cover. " Align the device and mark the position of both lower fastening points 2 + 3. " Remove the device and drill the fastening points 2 + 3”. " Remount the device and tighten the fastening point screws 2 + 3.
Type PKDM20 (PKDM25/35)
Fastening at 4 points
GM00005A_M
15.12.2015
1
2
4
3
" Drill fastening points 1 - 4”. " Fasten device with screws.
Operating Instructions Dcontrol – model series PKDM6..80 Mounting
L-BAL-E143-GB 1914 Index 009 Part.-No.
9/40
Type PKDM25/35E (PKDM50/80E)
Fastening at 4 points
SR031X17_M
12.07.2017
1 2
34
" Drill 4 fastening points. " Screw in screws 1 - 4 up to a distance of approx. 5 mm and mount the device. " Tighten fastening point screws 1 - 4”.
Type PKDM50/80
Fastening at 8 points
GM00002A_M
15.12.2015
1
7
2
34
5
6
8
" Drill 8 fastening points. " Screw in fastening point screws 1 - 4 up to a distance of approx. 5 mm and mount the device. " Tighten fastening point screws 1 - 4”. " Screw in fastening point screws 5 - 8 and tighten.
Operating Instructions Dcontrol – model series PKDM6..80 Mounting
L-BAL-E143-GB 1914 Index 009 Part.-No.
10/40

4.4 Outdoor installation

Outdoor installation is possible up to -20 °C when the controller supply is not switched off. Installation must be protected from the effects of weather as much as possible, including protection from direct sunlight!

4.5 Installation location for agriculture

When using for animal keeping, do not install the device directly in the stable but in a separate room with a lower pollutant load. This helps to avoid damages caused by pollutant gases (e.g. ammonia fumes, hydrogen sulphide fumes).
4.6 Temperature inuences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by storing the controller at room temperature!

5 Electrical installation

5.1 Safety precautions

Danger due to electric current
Work on electric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accordance with electrical engineering regulations.
The 5 electrical safety rules must be observed!
It is forbidden to carry out work on electrically live parts.
Cover neighbouring electrical equipment during installation work.
Other measures may be necessary to achieve safe electrical isolation.
A second person must always be present when working on energized parts or lines who disconnects in case of emergency.
Electrical equipment must be checked regularly: Loose connections are to be re-tightened and damaged lines or cables must be replaced immediately.
Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for authorized persons using a key or special tool.
Operating the device with the housing cover removed is prohibited because energized, exposed parts are present inside the device. Disregarding this regulation can lead to severe personal injury.
The required protective earth connection is established using screws between the housing parts in metal terminal space covers and housing casings. Commissioning is only permissible after these screws have been properly attached!
The device owner is responsible for the EMC of the entire plant according to the locally applicable standards.
Metal screwed-connections are not permitted in plastic housing parts because there is no potential equalization.
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this Operating Instructions (see connection diagram)!
5.2 EMC-compatible installation

5.2.1 Motor cable

The applicable standard for interference emissions is EN 61000-6-3. Compliance with this standard is achieved through the use of an unscreened motor feed cable.

5.2.2 Control cables

Pay attention to sufcient distance from powerlines and motor wires to prevent interferences. The control cable may not be longer than 30 m. Screened control cables must be used when the cable length is longer than 20 m. When using a shielded cable connect the shielding to one side only, i.e. only to the control unit with the protective ground (keep cable short and with as little inductance as possible!).
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
11/40

5.2.3 Harmonics current for devices ≤ 16 A

According to EN 61000-3-2 these devices are to be classied as professional devices. Connection to a low voltage supply (public networks) is allowed insofar as this has been claried with the respective energy supply company responsible. Note: up to a maximum current of approx. 4 A, the limits are adhered to with no restrictions. Exception for Germany: An energy provider follows the technical connection conditions of the TAB2007, in which case the use of phase angle controlled devices up to a rating of 3.4 kVA per phase is allowed.
5.2.4 Harmonics current and line impedance for devices > 16 A and 75 A
Extract from EN 61000-3-12, valid for equipments with rated current > 16 A and 75 A, connected to public low-voltage systems.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power S
SC
is greater than or equal
to R
SCE
x S
equ
at the interface point between the user's supply and the public system.
It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S
SC
greater than or equal to R
SCE
x S
equ
.
S
SC
Short-circuit power from line at the interface point between the user's supply and the public system
S
equ
Rated - apparent power for three phase devices: S
equ
= 3 x UI x I
equ
(UI = phase to phase voltage se Technical data Line voltage) (I
equ
= rated current of the device se Technical data Rated current input)
R
SCE
Short-circuit ratio For this devices: R
SCE
120

5.3 Mains connection

5.3.1 Line voltage

Power from the mains is connected to terminals: PE, L1, L2, L3 and N. Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specications (
Technical data
and nameplate afxed to the side). The neutral conductor connection N is only for the leakage currents`s reduction. It is of no signicance for the fuction of the device. The connection is not applicable for power supply networks without a neutral conductor.

5.3.2 Required quality attributes for the mains voltage

Danger due to electric current
The mains voltage must comply with the EN 50160 quality characteristics and the dened standard voltages in IEC 60038!
5.3.3 Operating in IT-System
In the IT-System the neutral point of voltage supply is not grounded; in the case of a short-circuit between a phase (e.g. L1) and protective earth “PE becomes the protective earth potential = L1.
In order to ensure a trouble free operation in this case:
1. the GND potential of the control ports have to be connected with the protective grounding
potential.
2. the N lead must not be connected.
As consequence of the connection between GND potential of the control ports with protec­tive earth potential, the following must be considered (exception oating relay contacts):
1. connection only with wires, suitable for mains voltage and surrounding area.
2. connection with suitable isolated ampliers only.
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
12/40
5.4 Residual-current-operated protective device
Danger due to electric current
Owing to possible leakage currents occurring when the device is switched on, it is advisable to use short-time-delayed current-operated circuit-breakers. This prevents any triggering by mistake. Plants without neutral conductor connection Mains connection.

5.5 Motor connection

The motor leads are connected to the terminals: PE, U, V, W. Several fans can be connected to the controller-the maximum total current of all motors (maximum rated current for electronic control of the voltage) must not exceed the current rating for the controller. If the maximum control current for electronic voltage regulation is not known, a supplementary of the rated motor current must be made. Typical is this for 2- and 4-pole motors at approx. 25 %, for 6-pole motors at approx. 20 %, for 8- and 10-pole motors at approx. 15 % and higher pole motors at approx. 5 %. When controlling motors from other manufacturers, the controllability and the maximum current for electronic voltage regulation should be requested from the manufacturer.
Information
It is recommended that a separate motor protection unit be foreseen for each fan.
For motors with thermistors TP (PTC thermistor) e.g. type U-EK230E
For motors with thermostats TB (thermal contacts) e. g. type STDT16 or AWE-SK (
Enclosure:
Connection suggestion for several motors with motor protection unit type STDT.)

5.5.1 Running noise

When controlling ventilators using electronic voltage regulators, motor noise can occur (due to the system), which can be troublesome (Phase cutting = series P...). On fast running ventilators with a high level of air noise, this noise is relatively low. On slow running ventilators with a low level of air noise, this noise may be dominant in the lower speed range due to the occurrence of resonance. For systems where noise is critical, we recommend using our Fcontrol series frequency converters with integrated sinusoidal lter.

5.6 Motor protection

Motor protectionis possible by connecting thermostats TB (thermal contacts) or thermistors TP (PTC).
When several motors are connected ensure that the thermostats TB or thermistors TP are always connected in series. A maximum of six individual thermistors TP (DIN 44081 or DIN 44082) may be connected in series to a single device. Depending on the motor type, at least two or three individual sensors are built in.
Monitoring of motors in Ex zones is not permissible. For systems of this type, an additional posistor tripping unit is required, with disconnection via a separate motor protection circuit.
When a connected thermostat or thermistor responds (interruption between the two terminals TB/TP the device switches off and does not switch back on. Relais K1 is de-energized, terminals 11 - 12 bridged. The signal lamp flashes in code
|2|
(
Diagnostics / faults).
Possibilities for re-starting after the drive has cooled down (terminals TB bridged) by:
By switching the mains voltage off and then on again.
Via a digital input for remote control (ON / OFF enable).
Attention!
An outside voltage may never be connected to the terminals TB/TP and/or!
If a bypass circuit is installed, or in the 100 % position on devices with a main switch, the motor protection inside the controller has no function. In this case, additional motor monitoring may be required.
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
13/40

5.7 Signal connection or sensor connection to analog inputs (Analog In 1, Analog In 2)

The unit has two analog inputs: Analog In 1
|E1|
and Analog In 2 |E2|. The connection is independent of the programmed operating mode and from the sensor signal employed.
Danger due to electric current
Never apply line voltage to analog inputs! Make sure the setting signal or the active sensor signal has the correct polarity!

5.7.1 Setting signal for operation speed controller

1.01
Factory setting for Analog In 1 |E1| for operation as speed controller with input 0 - 10 V. By the internal dipswitches further settings are possible (
basic settings).
Signal type at E1 (E2)
DIP 3 =
|
OFF| * Control via external setting signal 0...10 V at the terminals E1 and GND.
Speed setting by 10 kΩ potentiometer at terminals +10 V and GND pick-off at terminals E1”.
By external wiring with a resistor (499 Ω / 0,25 W) between the terminals E1 and GND parallel to the input signal, activation with a 0...20 mA signal is possible.
DIP 3 =
|ON|
Setting signal 4...20 mA at the terminals E1 and GND.
Inverting signal input E1 (E2)
DIP 4 =
|
OFF| * Inverting OFF: 0 - 10 V, 0 - 20 mA, 4 - 20 mA
DIP 4 =
|ON|
Inverting ON: 10 - 0 V, 20 - 0 mA, 20 - 4 mA
Input E2
DIP 7= |OFF| * Input E2 not active
DIP 7 =
|ON|
Input E2 active (function DIP 3 and DIP 4 ) The device works automatically at the input with the higher setting value (E1 or E2). At inverting OFF (DIP 4 =
|
OFF|) to the higher of both signals.
At inverting ON (DIP 4 =
|ON|
) to the lower of both signals.
* factory setting
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
14/40
Diagram: setting signal and output voltage (ohmic load)
U
Out
50 %
100 %
0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0
0 2 4 6 8 10 12 14 16 18 20
20 18 16 14 12 10 8 6 4 2 0
4 5,6 7,2 8,8 10,4 12 13,6 15,2 16,8 18,4 20
20 18,4 16,8 15,2 13,6 12 10,4 8,8 7,2 5,6 4
0 – 10 V
10 – 0 V 0 – 20 mA 20 – 0 mA 4 – 20 mA 20 – 4 mA
n-min 0 % Uinn-max. = 100 % U
in
24.10.2011
v_ua_pkdm_101.vsd
Si
n-min 30 % Uinn-max. = 100 % U
in
n-min 0 % Uinn-max. = 90 % U
in
n-min 20 % Uinn-max. = 80 % U
in
n-min OFF
Uout Output voltage (Motor) Si Setting signal n-min Setting minimal output voltage n-max Setting maximal output voltage Uin Line voltage input n-min OFF Operation with minimum air switch-off (DIP 5 = ON)
5.7.2 Sensor connection for operation as P-Controller
2.01 ... 3.02
For operation as P-Controller (DIP 1 = |ON|) Analog In 1 |E1| preset for operation as Pressure controller for condensers (DIP 2 =
|
OFF|) with 4 - 20 mA input. By the internal dipswitches further
settings are possible (
basic settings).
Signal type at E1 (E2)
DIP 3 =
|
OFF| * for Pressure control (DIP 2 = |OFF|): 4 - 20 mA (e.g. for pressure sensor type MBG..)
for Temperature control (DIP 2 = |ON|): type TF..(KTY81-210)
DIP 3 =
|ON|
for Pressure control (DIP 2 = |OFF|): 0 - 10 V for Temperature control (DIP 2 =
|ON|
): PT1000
Input E2
DIP 7 =
|
OFF| * Input E2 not active
DIP 7 =
|ON|
Input E2 active (function DIP 3) The controller works automatically at the input with the higher sensor value (E1 or E2). E.g. for dual circuit condensers in refrigeration technology with two sensors. Automatic control
to sensor which is measuring the higher pressure.
* factory setting
When connecting passive temperature sensors type TF.. (KTY81-210) or PT1000 at terminals E1 / T and/or E2 / T must be paid attention to no polarity. For a high interference immunity a capacitor must be connected directly to the sensor (1 nF parallel). With temperature sensors type TF.. (KTY81-210) a capacitor is integrated.
When connecting aktive sensors at the terminals E1 / GND and/or E2 / GND attention must be paid to correct polarity, a 24 V DC power supply is integrated.
For sensors in two-wire-technology (4 - 20 mA signal), the connection is made on the E1 / 24 V and/or E2 / 24 V, “GND” terminal is omitted.
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
15/40
5.8 Output voltage 0 - 10 V (A1 = Analog Out 1)
Connection to terminals A1 - GND = “Analog Out 1” (I
max
10 mA).
It is not permissible to connect outputs of several devices to each other!
The function of the signal output A1 (Analog Out 1) can be determined by DIP 8 (
basic settings / dipswitches).
DIP 8 =
|
OFF|Constant voltage + 10 V for external potentiometer (factory setting)
DIP 8 =
|ON|
0 - 10 V modulation 0 - 100 %
Proportional the internal control of modulation with consideration “n-min” and minimum air switch-off. The setting for “n-max” is not considered.
For enable “OFF” it goes not back to0 V.
For motor fault the output signal remains for a slave controller (“Master-Slave” combina­tion).
5.9 Voltage supply for external devices (+24V, GND)
A voltage supply is integrated for external devices e.g. a sensor (max. current load see technical data). In case of overload or short circuit (24 V – GND), the external power supply is shut down (multi-fuse). The device performs a Reset and continues operation.
It is not permissible to connect voltage outputs of several devices to each other!
It is not permissible to connect voltage outputs in the device to each other!

5.10 Digital inputs (D1, D2)

Activation via oating contacts, a low voltage of approx. 24 V DC is connected.
Attention!
No disconnection (isolation) when turned off, in accordance with VBG4 §6)! Never apply line voltage to the digital input! It is not permissible to connect inputs of several devices to each other!

5.10.1 D1 = Enable (Device ON / OFF)

Electronic disconnection and Reset after motor fault via floating contact at terminals “D1” - D1
Device ON for closed contact.
Controller OFF with opened contact.
Relais K1 remains energized, terminals 11 - 14 bridged. The signal lamp ashes in code
|1|
(
Diagnostics / faults).

5.10.2 D2 = Reverse action of the control function

For operation as P-Controller
2.01 .. 3.02 , the digital input D2 can used for reverse of control
function.
For the effect of the regulation there are two functions:
Val > Set = n+”
increasing modulation for increasing actual value over setpoint.
Val < Set = n+”
increasing modulation for decreasing actual value below setpoint.
When terminals D2 - D2 bridged, the device works with the opposite function than the one set with DIP 4!
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
16/40
5.11 Relay outputs (K1)
An external fault indicator is available over the potential-free contacts of the built-in relay (max. contact rating
Technical data and connection diagram).
For operation the relay is energized, terminals 11 and 14 are bridged. For fault the relay is de­energized, terminals 11 and 12 are bridged (
Diagnostics / faults).
Fault indicated for: line fault, blown internal semiconductor fuse, broken controller-internal voltage supply, motor over temperature (thermostatsTB, thermistors TP connected).
By sensor failure (only in P-Control operation
2.01 .. 3.02 ) message only via ash code of signal
lamp (code
|3|
), the relay remains energized.
When switching off via enable (D1 = Digital In 1), the relay remains energized.

5.12 Communication

5.12.1 Networking via MODBUS-RTU
The device comes equipped with a RS-485 interface for networking via MODBUS. Conntection at: A (D+), B (D-) and GND. Addressing is performed by an external terminal or a PC with the appropriate software. Alternatively the USB interface can be used for networking over MODBUS. A maximum of 64 participants can be directly connected to one another, and another 64 participants via a repeater.
5.12.2 RS-485 - network design and interface parameter
Please ensure the correct connection; i.e. "A (D+)" must always be connected to "A (D+)" of the next devices. The same applies to "B (D-)" . In addition, a "GND" connection must be established, as dissimilar potential (over 10 V!) will lead to the destruction of the RS-485 interface (e.g. lightning).
general example for MODBUS device connection
The data line must be connected from one device to the next. No other type of wiring is allowed! Always use only two wires of one lead (twisted pair) for the connection.
MODBUS
26.02.2007
v_modbus_verbindung.vsd
Example for MODBUS connection
Recommended wire types
1. CAT5 / CAT7 cables
2. J-Y (St) 2x2x0.6 (telephone cable)
3. AWG22 (2x2 twisted pair)
When using telephone cable with four cable cores, we recommend the following allocation: A (D+) = red, “B (D-) = black, GND = white
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
17/40
Information
Pay attention to sufcient distance from powerlines and motor wires (min. 20 cm).
Except the data link "A (D+)", "B (D-)" and "GND"- connection may no further cable cores of the data line be used.
Max allowed wire length 1000 m (CAT5/7 500 m).
Shielding
The use of shielded cables is normally not needed but offers high protection against electromagnetic interferences, especially high frequencies. However, the effectiveness of the shield depends on care­ful installation of the line. If shielded cables are used, the shield should be placed at PE on at least one side (preferably on the master connection). The occurrence of compensating currents may have to be considered if the shield is contacted on both sides.
Shield connection correct Shield connection incorrect
Default interface parameter
Baudrate = 19200 Bits = 8 Parity = Even (None, exception of devices agriculture) Stop bits = 1 Handshake = none
Information
If any matters are unclear, please contact our V-STE support department for control systems ­ventilation technology. The information sheet "Network structure of MODBUS" R-TIL08_01 contains detailed information about "MODBUS".
5.12.3 USB-interface
Over the USB interface if necessary a software update can be made. For this a consultation with our V-STE support department for control systems-ventilation technology is necessary. For communication with a PC (Virtual COM Port) we make the necessary programs available on request.
Danger due to electric current Plug the jumper J1 to both PINs only for a software update via USB interface. The device will not
switch on if this jumper is plugged to both PINs! Do not replug the jumper under voltage, observe the safety instructions!

5.13 Potential at control voltage connections

The connections for the control voltage (< 30 V) relate to the common GND potential (exception: relay contacts are potential-free). There is a potential isolation between the connections for the control voltage and the PE conductor. It must be ensured that the maximum external voltage at the con­nections for the control voltage cannot exceed 30 V (between the GND and “PE conductor terminals). A connection to the PE conductor potential can be made if required; t a bridge between the GND terminal and the PE connection (terminal for shield).
Operating Instructions Dcontrol – model series PKDM6..80 Electrical installation
L-BAL-E143-GB 1914 Index 009 Part.-No.
18/40

6 Operating and display elements

15.09.2011
v_pkdm_bedien_anzeige.VSD
%
n-max
0 100
%
set
0 100
%
n-min
0 100
ON
OFF
10987654321
S1
%
Pband
5
30
V
Potentiometer
set
Function dependently on selected mode of operation
For Speed controller
1.00 adjusting via built-in potentiometer: output voltage 0 -
100 %.
For Speed controller
1.01 control via external signal: without function.
For Temperature control
2.01 , 2.02 with passive sensors type TF.. (KTY) /
PT1000: Set point 0 - 100 %
-25...75 °C.
For control with active sensors
3.01 , 3.02 (4 - 20 mA, 0 - 10 V): setpoint 0 -
100 %
measuring range of sensor.
Potentiometer
Pband
Function dependently on selected mode of operation
For Speed controller
1.00 , 1.01 : without function
For Temperature control
2.01 , 2.02 with passive sensors type TF.. (KTY) /
PT1000: control range 5 - 30 %
5 - 30 K.
For control with active sensors
3.01 , 3.02 (4 - 20 mA, 0 - 10 V): control
range 5 - 30 %
5 - 30 % measuring range of sensor.
Potentiometer
n-min
Minimal output voltage (basic speed)
Setting range: 0 - “n-max”
Potentiometer
n-max
Maximal output voltage (speed limiter)
Setting range: 100 % - 0 (takes priority over n-min )
Dipswitch
S1
Basic setting for device function
Status LED
V
Indicate the operating conditions over ashing code
Operating Instructions Dcontrol – model series PKDM6..80 Operating and display elements
L-BAL-E143-GB 1914 Index 009 Part.-No.
19/40

7 Base setup

7.1 Programming of the desired function (Speed controller / P-Controller)
It is possible to use the device as a Speed controller or as a P-controller. Selection of the function must rst be made by setting the internal dipswitch S1.
Factory setting of all dipswitches is
|
OFF| position for operation as Speed controller 1.01
with external setting signa 0 - 10 V. In the following the fundamental dipswitch positions for further
modes of operation are represented. Depending upon desired function further adjustments are necessary (
function dipswitches).
Factory setting for all dipswitches is position
|
OFF| = operation as Speed controller 1.01
24.07.2012
v_dip_s1_dcontrol_mode.vsd
ON
OFF
10987654321
S1
1.00
%
set
0 100
ON
OFF
10987654321
S1
24V
GND
E1
GND
31
BN GN
MBG..
(4 - 20 mA)
3.02
MBG..-I
24V
GND
E2
GND
31
BN GN
MBG..
(4 - 20 mA)
0 - 10 V
1.01
ON
OFF
10987654321
S1
0 - 10 V
10 k
A1
GND
E1
GND
ON
OFF
10987654321
S1
24V
GND
E1
GND
31
BN GN
MBG..
(4 - 20 mA)
3.01
MBG..-I
ON
OFF
10987654321
S1
2.01
E1
GND
T
T
KTY81-210
TF.. (KTY81-210)
ON
OFF
10987654321
S1
2.02
TF.. (KTY81-210)
KTY81-210
E1
GND
T
T
E2
GND
T
T
KTY81-210
Attention!
Setting of switches not under voltage! Observe the safety notices! Changed functions become active partly only after renewed switching on the mains voltage!
Operating Instructions Dcontrol – model series PKDM6..80 Base setup
L-BAL-E143-GB 1914 Index 009 Part.-No.
20/40

7.2 Select operation mode

Simple installation is possible through the use of modes of operation.
Mode
Signal or Sensor
(input)
Function
1.00 -
Speed controller, setting the output voltage by internal potentiometer set.
1.01 Signal 0 - 10 V (E1)
Speed controller, setting the output voltage by external signal (factory setting).
2.01
Sensor KTY81-210 / PT1000 (E1) (for PT1000 dipswitch
|3|
to ON)
Temperature control airconditioning and refrigeration.
2.02
1x Sensor KTY81-210 (E1) 1x Sensor KTY81-210 (E1) (for PT1000 dipswitch
|3|
to ON)
Temperature control with 2 sensors. Automatic control to the temperature sensor with higher value.
3.01 Sensor type MBG.. (E1) Pressure control condensers (refrigeration)
3.02
1x sensor type MBG.. (E1) 1x sensor type MBG.. (E2)
Pressure control condensers (refrigerant technology) with 2 sensors. Automatic control to the pressure sensor with higher value (for two
circuit condensers).

7.3 Dipswitch for operation as Speed controller:

1.00 , 1.01
For operation as a Speed controller (DIP |1| = |OFF|) the output voltage is set manually by adjusting the built-in potentiometer, by an external potentiometer or external signal. The desired function is determined with dipswitch S1. Position factory setting for all dipswitches =
|
OFF|.
DIP Function DIP =
|
OFF
|
DIP = |ON
|
1
Selection: Speed controller / P-Controller
RPM controller P-Controller
2 Signal source of control
Setting of output voltage by external signal to E1
(Internal potentiometer set without func­tion)
Setting the output voltage by internal po­tentiometer set
3 Signal type at E1 (E2) 0 - 10 V, 0 - 20 mA* 4 - 20 mA
4 Inverting signal input E1 (E2)
Inverting not active: 0 - 10 V, 0 - 20 mA*, 4 - 20 mA
Inverting active: 10 - 0 V, 20 - 0 mA* 20 - 4 mA
5 Minimum speed cut off not active active
6 Hardstart function not active active
7 Input E2 Input E2 not active Input E2 active
8
Function signal output Analog Out 1
Constant voltage + 10 V for external potentiometer
0 - 10 V
modulation 0 - 100 %
9 60 Hz allocation automatic detection 60 Hz x
10 Phase failure detection Detection active Detection not active
* By external wiring with a resistor (499 Ω / 0,25 W) between the terminals “E1 and GND parallel to the input signal,
activation with a 0...20 mA signal is possible.
Operating Instructions Dcontrol – model series PKDM6..80 Base setup
L-BAL-E143-GB 1914 Index 009 Part.-No.
21/40
7.4 Dipswitch for operation as P-controller: 2.01 , 2.02 , 3.01 , 3.02
For operation as a P-controller (DIP |1| = |ON|) the actual value measured by the sensor is compared with the nominal value that has been set. The output voltage and hence the rotational speed of the connected motor automatically change as a function of the parameter settings. The desired function is determined with dipswitch S1. Position factory setting for all dipswitches =
|
OFF|.
DIP Function DIP =
|
OFF
|
DIP = |ON
|
1
Selection: Speed controller / P-Controller
RPM controller P-Controller
2
Pressure control / Temperature control
Pressure control Temperature control
3 Signal type at E1 (E2)
for Pressure control: 4 - 20 mA for Temperature control: TF..(KTY81-210)
for Pressure control: 0 - 10 V for Temperature control: PT1000
4
Control function (e.g. Cooling / Heating
increasing modulation for increasing actual value (cooling)
increasing modulation for decreasing ac­tual value (heating)
5 Minimum speed cut off not active active
6 Hardstart function not active active
7 Input E2 Input E2 not active Input E2 active
8
Function signal output Analog Out 1
Constant voltage + 10 V for external potentiometer
0 - 10 V
modulation 0 - 100 %
9 60 Hz allocation automatic detection 60 Hz x
10 Phase failure detection Detection active Detection not active

7.5 Minimum speed cut off DIP 5

7.5.1 For mode Speed controller

1.01
If no n-min is adjusted,output voltage goes continuously with reduction of the regulating variable down to 0 (cutoff below approx. 2 % regulating variable).
Without minimum speed cut OFF (DIP 5 =
|
OFF| = factory setting)
If minimal speed n-min is adjusted (e.g. 20%), then no disconnection of the fan takes place. I.e. always a minimum ventilation is ensured (fan does not go under setting “n-min).
With minimum speed cut off (DIP 5 =
|ON|
)
Cutoff below approx. 2 % regulating variable from sestting n-min to 0”.
Switch on again for a regulating variable above 5 % (to setting n-min).
Functional diagram
setting for operation as Speed controller
7.5.2 For operation as P-Controller(from
2.01 )
Without minimum speed cut OFF (DIP 5 =
|
OFF
|
=
factory setting)
If no “n-min” is adjusted, the fan stops with reaching the desired value.
If “n-min” is adjusted (e.g. 20 %), then no disconnection of the fan takes place. I.e. always a minimum ventilation is ensured (fan does not go under setting “n-min”).
With minimum speed cut off (DIP 5 =
|ON|
)
When the setpoint is reached, the modulation is reduced to “0 %”, or to the set value if “n-min” is specied.
For actual value = setpoint disconnection takes place from “n-min” to “0”. Hysteresis (ON / OFF) approx. 2.5 % of 100 % set value.
nM
50 %
100 %
I
Min.
Min. 35 % Max. = 100 %
20 °C
S
7 K
R
27 °C
-2.0 K
10.05.2007
v_min_luft_abschalt.vsd
Minimum speed cut off (idealized principle diagram)
nM Motor speed S Setpoint R Pband I Actual value
Operating Instructions Dcontrol – model series PKDM6..80 Base setup
L-BAL-E143-GB 1914 Index 009 Part.-No.
22/40

7.6 Hardstart function DIP 6

Special function for motorstart with maximum output voltage.
DIP 6 =
|
OFF
|
Hardstart function = OFF (factory setting).
After switching the mains voltage on the output voltage rises during the rmly programmed run-up time to the given value.
DIP 6 =
|ON|
Hardstart function = ON.
For a safe starting of the connected fans the function Hard start can be activated. After switching on (line voltage or enable via digital input D1) the controller generates for
approx. 10 seconds max. voltage 100 % ignoring any control or sensor signal. Afterwards the output voltage adjusts itself to the given or over the control amplier calculated
value. For operation as controller(from mode 2.01 ) the “Hard start function works also by switching
over the control function (“Heating / Cooling).

7.7 Adjusting of CosPhi for motor

The output voltage of the unit depends on the inductance of the motor (CosPhi).
In operation as speed controller the maximum output voltage can therefore reached below the maximum input signal (<10 V).
For mode as P-controler the maximum output voltage can reached at a control deviation which is too low.
For CosPhi adjustment of output voltage turn potentiometer n-max counterclockwise such that the maximum output voltage will just be measured (with TRUE-RMS multimeter). This adjustment must be made for maximum output from the fans. All aps must be opened when using centrifugal fans.
7.8 Adapting to specic mains conditions

7.8.1 Fix 60 Hz allocation DIP 9

Upon switch-on, the mains frequency (50 or 60 Hz) is automatically detected and used to trigger ignition of the thyristors. If, in exceptional cases, a 60 Hz mains frequency can not be clearly identied, xed allocation can be necessary (mains failure, as device operates at 50 Hz if 60 Hz is not detected). If a x allocation is made at 50 Hz the device indicates lline fault (
Diagnostic / Faults).
DIP 9 =
|
OFF
|
OFF (down) = automatic detection
DIP 9 =
|ON|
ON (up) = 60 Hz x

7.8.2 Deactivate phase monitoring DIP 10

The device is provided with a built-in phase-monitoring function (
Diagnostics / faults: line fault).
For special applications (e.g. unstable mains supply, phase position other than 120° on a soft generator or for transformer operation) this can be disconnected after consultation with ZIEHL-ABEGG. The motor is thus no longer protected by TWO PHASE OPERATION (observe Motor protection chapter).
DIP 10 =
|
OFF|OFF (down) = phase monitoring active
DIP 10 =
|ON|
ON (down) = phase monitoring deactivated
Operating Instructions Dcontrol – model series PKDM6..80 Base setup
L-BAL-E143-GB 1914 Index 009 Part.-No.
23/40
8 Start-up

8.1 Prerequisites for commissioning

Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the hazardous area.

9 Setting for operation

9.1 Speed controller

1.00 and 1.01

9.1.1 Setting for operation as Speed controller

1.00 Ansteuerung über internes Potenziometer
1.01 Setting via external signal or external potentiometer (factory setting)
%
set
0 100
18.07.2011 v_set_pxet.VSD
1.00 Potenziometer set (DIP 2 = |ON|)
Setting range: Output voltage from approx. 0 - 100 % of connected line voltage or in range of settings n-min up to n-max.
Signal to:
E1
E1
GND
14.02.2008
v_signal_e1.vsd
1.01 signal E1 (factory setting: DIP 2 = |OFF|)
Control via external setting signal 0...10 V
By external wiring with a resistor (499 Ω / 0,25 W) between the terminals “E1” and “GND” parallel to the input signal, activation with a 0...20 mA signal is possible.
Setting range: Output voltage from approx. 0 - 100 % of connected line voltage or in range of settings n-min up to n-max.
(Potentiometer set without function)
18.07.2011 v_nmin_pxet.VSD
%
n-min
0 100
Minimum output voltage (basic speed)
Setting range: 0 - “n-max”
18.07.2011 v_nmax_pxet.VSD
%
n-max
0 100
Maximal output voltage (speed limiter)
Setting range: 100 % - 0 (takes priority over n-min) Output voltage depending on load
Adjusting of CosPhi for motor”.
Operating Instructions Dcontrol – model series PKDM6..80 Start-up
L-BAL-E143-GB 1914 Index 009 Part.-No.
24/40
9.1.2 Operation with two variable output voltages (two steps)
DIP2 =
|
OFF| for setting via external signall.
Switchover between two steps via external potential-free contact possible.
Step 1 (low speed). When there is no input signal connected to the input terminal E1, then the unit supplies the output voltage set by n-min.
Step 2 (high speed). When the terminal “A1 (+10 V) is connected with the input terminal E1 then the units supplies the output voltage set by n-max.
n-min
nM
100 %
1
t
n-max
12
05.02.2008
v_diagr_2stufen.VSD
"A1" (+10 V)
"E1"
nMotor
= "n-max"
nMotor
= "n-min"
1
2
05.02.2008
v_schalter_2stufen.VSD
Operating Instructions Dcontrol – model series PKDM6..80 Setting for operation
L-BAL-E143-GB 1914 Index 009 Part.-No.
25/40

9.2 Temperature control 2.01 and 2.02

2.01 Temperature control with one sensor
2.02 Temperature control with 2 sensors.
Automatic control to the temperature sensor with higher value.

9.2.1 Setting for operation as Temperature controller

%
set
0 100
18.07.2011 v_set_pxet.VSD
Setpoint
For Temperature control with passive sensors type TF.. (KTY), PT1000 Setting range: 0 - 100 %
-26...75 °C (measuring range of controller: -50...+150 °C)
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 0 - 100 %
measuring range of sensor
Scale 0 - 100 %
-25...75 °C for Temperature control with passive sensors
set
[%]
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
[° C] -25 -20 -15 -10 -5 -0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
19.07.2011 v_pband_pxet.VSD
%
Pband
5
30
Pband
Narrow control range = Short control times Wide control range = Longer control times and more stable control
For Temperature control with passive sensors type TF.. (KTY), PT1000 Setting range: 5 - 30 %
5 - 30 K
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 5 - 30 %
5 - 30 % measuring range of sensor
18.07.2011 v_nmin_pxet.VSD
%
n-min
0 100
Minimum output voltage (basic speed)
Setting range: 0 - “n-max”
18.07.2011 v_nmax_pxet.VSD
%
n-max
0 100
Maximal output voltage (speed limiter)
Setting range: 100 % - 0 (takes priority over n-min) Output voltage depending on load
Adjusting of CosPhi for motor”.
Operating Instructions Dcontrol – model series PKDM6..80 Setting for operation
L-BAL-E143-GB 1914 Index 009 Part.-No.
26/40

9.2.2 Example Temperature control Cooling function (factory setting)

Val > Set = n+” (DIP4 =
|
OFF|)
Temperature sensor type TF.. (KTY), PT1000
Settings
set = 50 %
25 °C
Pband = 10 %
10 K
U
Motor
50 %
100 %
[°C]
n-min. 0 %, n-max. = 100 %
50 % ^ 25 °C
Set
Pband 10 % ^ 10.2 K
11.03.2008
v_temp_cool_umotor.vsd
35.2 °C
n-min. 35 %, n-max. = 85 %
Idealized principle diagram

9.2.3 Example Temperature control Heating function

Val < Set = n+” (DIP4 =
|ON|
)
Temperature sensor type TF.. (KTY), PT1000
Settings
set = 50 %
25 °C
Pband = 10 %
10 K
U
Motor
50 %
100 %
[°C]
n-max. = 100 %, n-min. 0 %
50 % ^ 25 °C
Set
Pband 10 % ^ 10.2 K
11.03.2008
v_temp_heat_umotor.vsd
14.8 °C
n-max. = 85 %, n-min. 35 %
Idealized principle diagram
Operating Instructions Dcontrol – model series PKDM6..80 Setting for operation
L-BAL-E143-GB 1914 Index 009 Part.-No.
27/40

9.3 Pressure control condensers 3.01 and 3.02

3.01 Pressure control condensers (refrigeration)
3.03 Pressure control condensers (refrigerant technology) with 2 sensors.
Automatic control to the pressure sensor with higher value (for two circuit condensers).

9.3.1 Setting for operation as Pressure controller

%
set
0 100
18.07.2011 v_set_pxet.VSD
Setpoint
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 0 - 100 %
measuring range of sensor
19.07.2011 v_pband_pxet.VSD
%
Pband
5
30
Pband
Narrow control range = Short control times Wide control range = Longer control times and more stable control
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 5 - 30 %
5 - 30 % measuring range of sensor
18.07.2011 v_nmin_pxet.VSD
%
n-min
0 100
Minimum output voltage (basic speed)
Setting range: 0 - “n-max”
18.07.2011 v_nmax_pxet.VSD
%
n-max
0 100
Maximal output voltage (speed limiter)
Setting range: 100 % - 0 (takes priority over n-min) Output voltage depending on load
Adjusting of CosPhi for motor”.

9.3.2 Example Pressure control condensers

Pressure sensor
Type MBG-30I
Measuring range 0 - 30 bar
Output signal 4...20 mA
Settings
set = 50 %
15.0 bar, in use of refrigerant medium table for R507
Pband = 10 %
3.0 bar
U
Motor
50 %
100 %
[bar] / [°C]
50 %
15 bar ^ 34.28 °C @
507
Set
Pband 10 %
12.03.2008
v_diagramm_bar_c.vsd
18 bar ^ 41.53 °C @ 507
n-min. 0 %, n-max. = 100 %
n-min. 35 %, n-max. = 85 %
Idealized principle diagram
Operating Instructions Dcontrol – model series PKDM6..80 Setting for operation
L-BAL-E143-GB 1914 Index 009 Part.-No.
28/40
9.3.3 Setting with refrigerant medium table
Information
Calculation for relative pressure (differential measurement of pressure relative to ambient pressure).
Set
0 %5 %10%15%20%25%30%35%40%45%50%55%60%65%70%75%80%85%90%95%100
%
MBG-30I
[bar]
0.00 1.50 3.00 4.50 6.00 7.50 9.00 10.50 12.00 13.50
15.00
16.50
18.00
19.50 21.00 22.50 24.00 25.50 27.00 28.50 30.00
I
[mA]
4.0 4.8 5.6 6.4 7.2 8.0 8.8 9.6 10.4 11.2 12.0 12.8 13.6 14.4 15.2 16.0 16.8 17.6 18.4 19.2 20.0
R12 [°C]
-30.09 -6.28 8.11 18.90 27.70 35.22 41.84 47.80 53.23 58.23 62.90 67.27 71.39 75.30 79.01 82.57 85.97 89.24 92.39 95.43 98.37
R13 [°C]
-81.99 -62.83 -51.33 -42.75 -35.77 -29.82 -24.60 -19.91 -15.65 -11.72 -8.07 -4.65 -1.43 1.61 4.51 7.27 9.91 12.45 14.89 17.25 19.52
R13b1
[°C]
-58.14 -36.81 -23.92 -14.26 -6.38 0.36 6.29 11.63 16.49 20.97 25.15 29.06 32.75 36.25 39.58 42.76 45.81 48.74 51.56 54.28 56.92
R22 [°C]
-41,11 -19.52 -6.57 3.09 10.95 17.65 23.53 28.80 33.60 38.02 42.13 45.97 49.59 53.02 56.27 59.38 62.35 65.20 67.95 70.59 73.15
R23 [°C]
-82.44 -64.82 -54.36 -46.61 -40.34 -35.02 -30.36 -26.20 -22.43 -18.96 -15.75 -12.75 -9.94 -7.27 -4.75 -2.35 -0.05 2.15 4.26 6.30 8.26
R32
[°C]
-52.53 -32.24 -20.30 -11.51 -4.44 1.54 6.76 11.41 15.62 19.47 23.03 26.35 29.47 32.40 35.18 37.83 40.35 42.76 45.07 47.30 49.44
R114
[°C]
3.45 30.02 46.05 58.04 67.82 76.17 83.53 90.13 96.15 101.70 106.87 111.71 116.27 120.59 124.71 128.63 132.40
136.0­11
139.49 142.85 146.10
R134a
[°C]
-26.43 -4.29 8.93 18.75 26.72 33.49 39.43 44.75 49.58 54.02 58.14 61.99 65.62 69.04 72.30 75.40 78.36 81.20 83.93 86.57 89.11
R142B
[°C]
-10.07 15.44 30.54 41.71 50.72 58.37 65.05 71.01 76.42 81.38 85.98 90.27 94.29 98.09 101.70 105.13 108.40 111.54 114.55 117.44 120.24
R227
[°C]
-17.58 5.82 20.05 30.76 39.52 47.03 53.66 59.63 65.09 70.13 74.83 79.24 83.41 87.37 91.13 94.74 98.20 101.52 104.73 107.83 110.83
R401
[°C]
-27.05 -4.65 8.71 18.63 26.68 33.52 39.52 44.89 49.77 54.25 58.41 62.30 65.96 69.41 72.70 75.82 78.81 81.68 84.44 87.09 89.66
R401A
[°C]
-29.21 -6.93 6.40 16.33 24.39 31.26 37.28 42.68 47.59 52.10 56.29 60.22 63.91 67.40 70.72 73.88 76.91 79.81 82.60 85.29 87.99
R401B
[°C]
-28.97 -6.74 6.52 16.37 24.35 31.14 37.08 42.41 47.24 51.69 55.81 59.67 63.29 66.72 69.97 73.07 76.03 78.87 81.60 84.23 86.77
R402
[°C]
-47.59 -26.34 -13.71 -4.36 3.21 9.64 15.26 20.29 24.85 29.04 32.92 36.55 39.95 43.17 46.23 49.13 51.91 54.57 57.13 59.59 61.97
R402A
[°C]
-47.59 -26.34 -13.71 -4.36 3.21 9.64 15.26 20.29 24.85 29.04 32.92 36.55 39.95 43.17 46.23 49.13 51.91 54.57 57.13 59.59 61.97
R402B
[°C]
-45.46 -24.06 -11.33 -1.89 5.75 12.23 17.92 22.99 27.61 31.84 35.77 39.44 42.89 46.14 49.23 52.18 54.99 57.69 60.28 62.77 65.18
R404A
[°C]
-46.36 -24.92 -12.18 -2.74 4.89 11.37 17.04 22.11 26.72 30.94 34.86 38.52 41.95 45.20 48.28 51.21 54.01 56.70 59.28 61.67 64.16
R407A
[°C]
-39.47 -18.64 -6.32 2.78 10.13 16.36 21.80 26.66 31.06 35.10 38.84 42.33 45.60 48.69 51.62 54.41 57.07 59.62 62.06 64.42 66.69
R407B
[°C]
-43.49 -22.74 -10.44 -1.34 6.01 12.24 17.69 22.55 26.97 31.02 34.77 38.27 41.56 44.66 47.61 50.41 53.09 55.65 58.11 60.48 62.76
R407C
[°C]
-37.31 -16.35 -3.95 5.22 12.62 18.89 24.37 29.27 33.70 37.77 41.54 45.06 48.36 51.47 54.43 57.24 59.92 62.49 64.96 67.34 69.63
R500
[°C]
-33.80 -10.77 3.02 13.28 21.62 28.72 34.96 40.54 45.62 50.29 54.63 58.69 65.51 66.13 66.56 72.83 75.97 78.97 81.86 84.65 87.34
R502
[°C]
-45.54 -23.63 -10.53 -0.77 7.15 13.89 19.81 25.10 29.92 34.35 38.47 42.32 45.94 49.37 52.62 55.72 58.69 61.54 64.28 66.91 69.46
R503
[°C]
-88.64 -70.55 -59.77 -51.77 -45.29 -39.79 -34.96 -30.65 -26.73 -23.12 -19.78 -16.66 -13.72 -10.95 -8.32 -5.81 -3.41 -1.11 1.10 3.22 5.28
R507
[°C]
-46.51 -25.59 -13.02 -3.64 3.98 10.49 16.20 21.32 25.99 30.28
34.28
38.01
41.53
44.86 48.03 51.05 53.94 56.72 59.39 61.97 64.46
R717
[°C]
-33.59 -13.65 -1.88 6.80 13.80 19.73 24.91 29.52 33.71 37.54 41.09 44.40 47.50 50.43 53.21 55.84 58.36 60.78 63.09 65.32 67.46
Operating Instructions Dcontrol – model series PKDM6..80 Setting for operation
L-BAL-E143-GB 1914 Index 009 Part.-No.
29/40

10 Diagnostics / Faults

Operating conditions are indicated by the status LED with ashing code.
30.01.2012
v_flash_explain1_7.VSD
3 x
2 x
ON
OFF
5 x
1 x
6 x
7 x
Code LED
Relay
K1
Explanation
Reaction of Controller
Adjustment
OFF
de-energized terminals 11 - 12 bridged
No line voltage
In the event of a mains interruption the unit switches OFF and automatically ON when the voltage has been re­stored.
Check line and internal controller fuse.
ON
energized terminals 11 - 14 bridged
Normal operation without fault
1
energized terminals 11 - 14 bridged
no enable
Terminals “D1” - “D1” (Digital In 1) not bridged.
Switch OFF by external contact (
digi-
tal input).
2
de-energized terminals 11 - 12 bridged
Motor fault
A connected thermostat or thermistor has tripped the circuit / interruption between both terminals TB.
The unit cuts out and does not switch on again.
Check motor and connection then reset (
Motor protection).
3
de-energized terminals 11 - 12 bridged
Overload
Power semiconductor (heat sink) too hot.
Switch OFF at 95 °C, switch ON when cooled down to 65 °C.
Check for any overloading of the device. I.e. whether the maximum control current occurring is above the rated current for the device.
Check temperature in controller, Check cooling of the controller.
4
energized terminals 11 - 14 bridged
Sensor heat sink
Line interruption to the heat-sink sensor (NTC).
The temperature monitoring of the power semiconductor is not active any longer!
Check sensor line, if no adjustment possi­ble replace the device!
5
de-energized terminals 11 - 12 bridged
Line fault
Failure by a line phase unstable mains supply.
Unit switches OFF and automatically ON again during intact voltage supply.
check line supply and internal controller fuse (so far available)
Operating Instructions Dcontrol – model series PKDM6..80 Diagnostics / Faults
L-BAL-E143-GB 1914 Index 009 Part.-No.
30/40
6
7
energized terminals 11 - 14 bridged
Signal fault
Code 6 for input “E1” Code 7 for input “E2”
Function only in controller mode (from
2.01 )!
Interruption or short circuit in the sensor leads or sensor values measured are out­side measuring range:
- For temperature sensors type TF.. (KTY), PT1000 below approx. -25 °C and above approx. 75 °C
- For active sensors with reaching mini­mum or maximum signal values (depend­ing on selected signal type).
The device works with minimal or maxi­mum modulation depending on whether there is a short-circuit or an interruption, and on the programmed mode of opera­tion.
The controller functions automatically again with the value measured at the temperature sensor after the fault has been rectied.
Check sensor.

10.1 If controller doesn´t work correctly

Information
Setting of dip switches in principle only when device is not under voltage.
If the device is on mains supply modications will partly not be identied and realized.
Plug the jumper J1 to both PINs only for a software update via USB interface. The device will not switch on if this jumper is plugged to both PINs!
Attention!
It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly.
Operating Instructions Dcontrol – model series PKDM6..80 Diagnostics / Faults
L-BAL-E143-GB 1914 Index 009 Part.-No.
31/40

11 Enclosure

11.1 Technical data

Version: housing IP54, internal semiconductor fuses
Type Part-No.
Rated cur­rent
{1}
Rated tem­perature
max. line fuse
{2}
Integrated semi­conductor fuse
{3}
max. heat dissipation
{4}
Weight
[A] [°C] [A]
[W] [kg]
PKDM6 304587 6 40 10
FF20 A 6x32 mm (00089798)
30 2.2
PKDM10 304588 10 45 16 50 2.7
PKDM12 304589 12 40 16
FF30 A 10x38 mm (00155987)
75 3.6
PKDM15 304590 15 40 20 100 4.9
PKDM20 304591 20 45 25
FF30 A 10 x 38 mm gRL
(00155984)
200 5.45
PKDM25 304592 25 45 35
FF50 A D02 (00091006)
270 11.05
PKDM35 304593 35 50 50
FF63 A D02 (00089795)
440 11.1
PKDM50 304631 50 40 63
FF100 A NH00 (00150320)
170 19.5
PKDM80 304632 80 40 100
FF160 A NH00 (00089793)
270 20.5
{1} Rated current
current specication rating plate @ rated voltage, @ rated temperature {2} Max. supply side line fuse according to DIN EN 60204-1 classication VDE0113 chapter 1 {3} Integrated semiconductor fuse in device (no line safety switch) {4} At rated voltage, values for different specications on request
Version: housing IP54, without internal semiconductor fuses (Z version)
Type Part-No.
Rated cur­rent
{1}
Rated tem­perature
max. line fuse
{2}
Semiconductor fuse on site
{3}
max. heat dissipation
{4}
Weight
[A] [°C] [A]
[W] [kg]
PKDM10Z 304601 10 50 16
FF20 A 6x32 mm (00089798)
45 2.7
PKDM12Z 304602 12 50 16
FF30 A 10x38 mm (00155987)
70 3.6
PKDM15Z 304603 15 50 20 95 4.9
PKDM20Z 304604 20 50 25
FF30 A 10 x 38 mm gRL
(00155984)
190 5.45
PKDM25Z 304605 25 50 35
FF50 A D02 (e.g. fuse kits
349030)
260 11.05
PKDM35Z 304606 35 55 50
FF63 A D02 (e.g. fuse kits
349031)
430 11.1
{1} Rated current
current specication rating plate @ rated voltage, @ rated temperature {2} Max. supply side line fuse according to DIN EN 60204-1 classication VDE0113 chapter 1 {3} Semiconductor fuse not in the scope of supply, as accessories available. For protection of damages in the case of short-
circuits installation on site recommended
{4} At rated voltage, values for different specications on request
Operating Instructions Dcontrol – model series PKDM6..80 Enclosure
L-BAL-E143-GB 1914 Index 009 Part.-No.
32/40
Version: housing IP20, for switch cabinet mounting without internal semiconductor fuses
Type Part-No.
Rated cur­rent
{1}
Rated tem­perature
max. line fuse
{2}
Semiconductor fuse on site
{3}
max. heat dissipation
{4}
Weight
[A] [°C] [A]
[W] [kg]
PKDM25E 304622 25 50 35 FF50 A D02
(e.g. fuse kits
349030)
260 7.4
PKDM35E 304623 35 50 50 FF63 A D02
(e.g. fuse kits
349031)
430 7.5
PKDM50E 304635 50 50 63 FF100 A NH00
(e.g. fuse kits
349032)
160 13.8
PKDM80E 304636 80 50 100 FF160 A NH00
(00089793)
255 15.4
{1} Rated current
current specication rating plate @ rated voltage, @ rated temperature {2} Max. supply side line fuse according to DIN EN 60204-1 classication VDE0113 chapter 1 {3} Semiconductor fuse not in the scope of supply, as accessories available. For protection of damages in the case of short-
circuits installation on site recommended
{4} At rated voltage, values for different specications on request
Line voltage 3 ~ 208...415 V (-15 up to +10 %), 50/60 Hz
Rated voltage 400 V
Stepless controlled output volt­age
approx. 20...100 % of connected line voltage
Min. motor current for PKDM6: 0.2 A, for PKDM10...80: 0.5 A
Input resistance for sensor or signal set for the rotational speed
for 0 - 10 V input: R
i
>100 k
for input 4 - 20 mA: R
i
= 250
Voltage supply e.g. for sen­sors
+24 V ± 20 %, I
max
120 mA (for connection to an external AXG terminal minus approx. 50 mA)
Output (0 - 10 V) I
max
10 mA (short-circuit-proof)
Contact rating of the internal relay
max. AC 250 V 2 A
Max. permissible ambient tem­perature for operation
55 °C
Min. permissible ambient tem­perature
0 °C (if mains voltage is not switched off up to -20 °C)
Max. permissible installation height
0...4000 m amsl 1000 m: no limitation > 1000 m: max. permissible output current = current indication name plate minus 5 % / 1000 m > 2000 m: max. permissible line voltage = max. voltage indication name plate minus 1.29 % /
100 m
Permissible rel. humidity 85 % no condensation
Electromagnetic compatibility for the standard voltage 230 / 400 V according to IEC 60038
Interference emission EN 61000-6-3 (domestic household applications) Interference immunity EN 61000-6-2 (industrial applications)
Max. leakage current accord­ing to the dened networks of EN 60990
< 3.5 mA
Harmonics current For devices 16A
According EN 61000-3-2 (for a “professional device)
Electrical installation / harmonics current
For devices > 16 A and ≤ 75 A according EN 61000-3-12 (
Electrical installation / harmonics current and line impedance)
Operating Instructions Dcontrol – model series PKDM6..80 Enclosure
L-BAL-E143-GB 1914 Index 009 Part.-No.
33/40
Maximum cross section for line and motor connection
PKDM6...20: 2,5 mm
2
PKDM25/35: 10 mm
2
PKDM25/35E: 10 mm
2
PKDM50/80E: 35 mm
2

11.1.1 Max. load depending on ambient temperature

The maximum permissible temperature for the rated current at rated voltage is specied as rated temperature. Since the dissipation of the power loss (heat development) in the device is decisively dependent on the ambient temperature, the max. load must be reduced at an ambient temperature above the rated temperature (see following table)! The average value measured during a 24 h period must be 5 K under the max. ambient temperature. For installation in a switch cabinet, the devices dissipation and its possible affect on the ambient temperature must be taken into consideration!
Maximal motor current depending on ambient temperature for versions with internal fuses
Type Part-No.
40 °C 45 °C 50 °C 55 °C
[A] [A] [A] [A]
PKDM6 304587 6 5.5 5.0 4.5
PKDM10 304588 10 10.0 9.0 8.0
PKDM12 304589 12 11.0 10.0 9.0
PKDM15 304590 15 13.5 12.0 10.0
PKDM20 304591 20 20.0 18.0 16.0
PKDM25 304592 25 25.0 22.5 22.5
PKDM35 304593 35 35.0 35.0 31.5
PKDM50 304631 50 44.5 39.0 33.5
PKDM80 304632 80 71.2 62.4 53.6
Maximal motor current depending on ambient temperature for versions without internal fuses
Type Part-No.
50 °C 55 °C
[A] [A]
PKDM10Z 304601 10 9.0
PKDM12Z 304602 12 10.0
PKDM15Z 304603 15 12.0
PKDM20Z 304604 20 18.0
PKDM25Z 304605 25 22.5
PKDM35Z 304606 35 35.0
PKDM25E 304622 25 22.5
PKDM35E 304623 35 31.5
PKDM50E 304635 50 44.5
PKDM80E 304636 80 71.2
Operating Instructions Dcontrol – model series PKDM6..80 Enclosure
L-BAL-E143-GB 1914 Index 009 Part.-No.
34/40

11.2 Connection diagram

PDUN20K1
13.07.2017
11 14 12
GND
D1
D1 A1
GND 24V
24V E1
GND GND
E2
D2
D2
U
V W
Netz
Line
3 ~ 208...415 V 50/60 Hz
1
K1
Dcontrol PKDM
Kontaktbelastung
Contact rating
max. AC 250 V 2 A
8
Eingang
Input
0...10 V
0...20 mA
+
5
1
Eingang
Input
0...10 V
0...20 mA
+
6
2
Ausgang
Output
0...10 V
(I
max
= 10 mA)
+
4
Digital
In 1
Analog
Out 1
Digital
In 2
Analog
In 1
Analog
In 2
24 V DC
Out
M
3 ~
U
V
W
PE TB
Y/Δ
q
3 ~ Motor
mit eingebauten Thermostatschaltern
with internal thermostats
3
TB
L3N L2L1PE
N L1 L2 L3 TB
TB
T
T
TF
In 1/2
TF..
TF..
J1
USB
7
1
24V GND
MODBUS
(RS-485)
GND24 V
A
(D+)
B
(D-)
TB/TP
In
01
Aus / Ein
Off / On
°C/bar > set → U
A
+
°C/bar < set →
U
A
+
1 3
BN GN
MBG..
1 3
BN GN
MBG..
4...20 mA
KTY 81-210
PT 1000
4...20 mA
01
24 Vdc
6 mA max.
(3 ~ 208...500 V 50/60 Hz)
Sonderausführung
Special version
2
1 Line 3 ~ 208...415 V, 50/60 Hz 2 Special version for line 3 ~ 208...500 V, 50/60 Hz 3 3 ~ Motor with internal thermostats 4 Output 0...10 V (I
max
= 10 mA) 5 Input 1: 0...10 V, 4...20 mA, TF...(KTY81-210), PT1000 6 Input 1: 0...10 V, 4...20 mA, TF...(KTY81-210), PT1000 7 USB-interface 8 Contact rating max. AC 250 V 5 A
Attention! Plug the jumper J1 to both PINs only for a software update via USB interface. The device will not switch on if this jumper is
plugged to both PINs!
Operating Instructions Dcontrol – model series PKDM6..80 Enclosure
L-BAL-E143-GB 1914 Index 009 Part.-No.
35/40

11.2.1 Connection suggestion for several motors with motor protection units type STDT

Full motor protection by switch-off when activating the attached thermostat switches “TB”. Reset after malfunction by key press.
Line protection: A thermal over current sensor and a magnetic short circuit releasing elements are the parts of the integral line protection. Adjustment to the thermal overcurrent sensor to the max. permissible current of the connected cable (max. line fuse 80 A).
No cut-off if the mains supply is interrupted
3~ Controller
UPE V W
NL1 L2 L3
L3 NL2L1
PE
3~ 208 .. 415 V
4 mm²
KT00005H
27.09.2007
1 3
2 4 6
I>
5
STDT16
TB TB
I> I >
3~ Motor
M 3~
PE
V WU
TB TB
4 mm²
1,5 mm²
1 3
2 4 6
I>
5
STDT16
TB TB
I> I >
3~ Motor
M 3~
PE
V WU
TB TB
4 mm²
1,5 mm²
1 3
2 4 6
I>
5
STDT16
TB TB
I> I >
3~ Motor
M 3~
PE
V WU
TB TB
4 mm²
1,5 mm²
Y/
Y/ Y/
Consider max. terminal load Operating Instructions! (General example, data for the connection of the controller dependent on the used type of device)
Operating Instructions Dcontrol – model series PKDM6..80 Enclosure
L-BAL-E143-GB 1914 Index 009 Part.-No.
36/40
11.3 Dimensions [mm]
PKDM6/10 (PKDM12/15)
PKDM20 (PKDM25/35)
Operating Instructions Dcontrol – model series PKDM6..80 Enclosure
L-BAL-E143-GB 1914 Index 009 Part.-No.
37/40
PKDM25/35E (PKDM50/80E)
PKDM50/80
Operating Instructions Dcontrol – model series PKDM6..80 Enclosure
L-BAL-E143-GB 1914 Index 009 Part.-No.
38/40
Operating Instructions Dcontrol – model series PKDM6..80
L-BAL-E143-GB 1914 Index 009 Part.-No.
39/40
11.4 Index
B
basic speed 18 bypass circuit 13
C
control cable 11 control function 16 CosPhi adjustment 21 current-operated circuit-
breakers 13
E
Ex zones 13 external potentiometer 22 external signal 22
H
heat dissipation 29-30
I
Input resistance 30
L
leakage current 30 line fuse 29-30 line impedance 12
M
mains 12 maximum control current 13 MBG-30I 25 Minimum space requirement 8 Minimum speed cut off 21 MODBUS 16 Mode 19 motor feed cable 11 motor leads 13 Motor protection 13 motor protection unit 13
O
Outdoor installation 11
P
P-controller 18 PT1000 15 PTC 13
R
refrigerant medium table 26 relative pressure 26 relay 16 Relay outputs 16 Reset 15
S
Speed controller 18 speed limiter 18
T
Technical data 3, 29 two steps 23 two-wire-technology 15
U
USB 17
V
voltage regulation 13

11.5 Manufacturer reference

Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact:
ZIEHL-ABEGG SE Heinz-Ziehl-Straße 74653 Künzelsau Telephone: +49 (0) 7940 16-0 Telefax: +49 (0) 7940 16-504 info@ziehl-abegg.de http://www.ziehl-abegg.de

11.6 Service information

If you have any technical questions while commissioning or regarding malfunctions, please contact our technical support for control systems - ventilation technology.
phone: +49 (0) 7940 16-800 Email: fan-controls-service@ziehl-abegg.de
Our worldwide contacts are available in our subsidiaries for deliveries outside of Germany, see www.ziehl-abegg.com.
Operating Instructions Dcontrol – model series PKDM6..80 Index
L-BAL-E143-GB 1914 Index 009 Part.-No.
40/40
Loading...