ZIEHL MSF 220 SE Operating Manual

(datum / name): 10.12.08 Su/Fz Z. Nr.: 1004 0710.2 Page 1 von 4 Type: MSF 220 SE
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: info@ziehl.de
Operating manual
MSF 220 SE
Application
The PTC-resistor trip device MSF 220 SE monitors the winding temperature of machines and equipment. Signals, that can be used as ”early warning" or ”malfunction" (switching-off), are transmitted as soon as the admissible limit temperature is exceeded. Two PTC-circuits can be connected to this unit. The integrated rise-delay time ensures a reliable mains voltage build-up.
Function
* 2 PTC resistor circuits, 1 to 6 PTC each (max. cold resistance of circuit 1500 each) * p
otential-free contact for alarm 1 * potential-free contact for alarm 2 * voltage of pin 3 is connectet to pin 1 with a time delay of 2 sec., replacing an additional
timing relay. * alarm 3 for check of relay K3 * LED´s signal state of relays K1 and K2 * relay K3 picks up time-delayed
Note
Thanks to the delayed switching-on of the error message (approx. 2 s) after the switching-on, this device is especially suitable where an auxiliary voltage is not available and the secondary voltage of the monitored transformer is being used. The MSF-200 SE can furthermore be used advantageously when combining it with operating current releases. For additional devices, the control voltage is available at terminal 1 time-delayed. In case of a breakdown of the supply voltage, the control voltage is available at terminal 7 and can be used as a message. (Attention! This message will also be given for approx. 2 s. after switching-on.)
Functional description
PTC-circuits in closed-circuit current principle. When the closed-circuit current flows, both output relays K1, K2 are picked up. Approx. 2 sec. after switching on supply power, relay K3 picks up time-delayed, closing the contact circuits at terminals 31, 14 and 31, 24. As soon as the temperature of the early warning has been reached, relay K1 releases (terminal 31, 12 closed), the alarm 1 is given. If the temperature of malfunction is reached, also relay K2 releases (terminal 31, 22 closed). This alarm 2 can be used to switch off the equipment. If the temperature drops to approx. 5 °C below the temperature of malfunction or early warning, the relays K1 and K2 resp. are switched on again.
MINIPAN
®
digital panel meters, temperature
-
and mains controlling,
special purpose instruments for customer requirements www.ziehl.com
- Archive document
www.ziehl.de
(datum / name): 10.12.08 Su/Fz Z. Nr.: 1004 0710.2 Page 2 von 4 Type: MSF 220 SE
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: info@ziehl.de
Technical Data
Supply Voltage US see type plate on the device Us: DC/AC 24 - 240 V Tolerance DC 20,4 – 297 V, AC 20 – 264 V Frequency 0, 40...500 Hz, at AC 80 V: 10...500 Hz
Us: DC/AC 90 – 240 V Tolerance DC 80 – 297 V, AC 80 – 264 V Frequency 0, 40...500 Hz, AC 10...500 Hz
Power consumption <2 VA
PTC-resistor connection 2 x 1...6 PTC in series Cut-out point 2,8...3,6 k, typ. 3,2 k Reclosing point 1,8...2,4 k, typ. 2,1 k Collective resistance of cold sensors 1,5 k Terminal voltage (sensors) 2,5 V at 250 7,5 V at 4 k max. 5 mA
Relay output contacts AgNi 015 Switching voltage max. 400 V Switching current max. 8 A Switching power max. 2000 VA Rated continious current Ith 5 A
Rated operational current Ie 2 A AC15 400 V 2A DC13 24 V 3 A AC15 250 V Prefuse for device and contacts AC: T 4 A DC: T 2 A
Mechanical contact life 3 x 107 operations Electrical contact life 1 x 105 operations (at max. switching capacity) Factor of reduction at cos = 0.4 0.5 x max. switching capacity Switching-on delay app. 2 s
Testing conditions EN 60947, EN 50178 Rated insulation voltage AC 250 V Isolation EN 60664 Rated impulse voltage 400 V Contamination level 2 Transformer EN 61558 On period 100 % max. ambient temperature -20 ... +55 °C, EN 60068-2-2 dry heat
Housing: design S-12, plug-in housing Dimensions (H x W x D) 82 x 42 x 121 mm Line connection 12-pole, max. 2 x 1.5 mm2 each Protection Housing IP 40 Protection contacts IP 20 Panel inclination any Mounting snapable on 35 mm standard rail according to EN 60715 or assembly with scrwes M 4 Weight app. 250 g
Subject to technical modifications
(datum / name): 10.12.08 Su/Fz Z. Nr.: 1004 0710.2 Page 3 von 4 Type: MSF 220 SE
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: info@ziehl.de
Installation - Putting into operation
The plug base can be mounted either with
* 35 mm mounting rail according to EN 60715 or * M4 screws
Wiring directly to plug base
* Connect wires as per wiring scheme * Plug in electronics and fix with knurled screw
Attention! Do not plug in device alive nor detach it from socket.
When installing the device into the switch-gear cabinet, please observe the max. admissible temperature. Care for both sufficient clearance to other devices or sources of heat or enough forced draught.
Before switching on make sure that the operational voltage Us of the lateral type plate and the mains voltage are the same.
* Apply mains voltage to terminals A1 and A2 * When device is ready for operation, relays K1 and K2 switch on immediately, the LED’s
are off. After approx. 2 s. relay K3 picks up, terminals 31-14, 31-24, 31-34 are
connected. * Relay K1 releases as soon as the input at terminal T11, T12 becomes high- resistive. * Relay K2 releases as soon as the input at terminal T21, T22 becomes high-resistive. * Relay K1, K2 pick up as soon as the inputs at terminals T11, T12 and T21, T22 become
low-resistive. * Relay K3 releases first, as soon as the supply voltage is switched off.
Trouble-shooting and remedies
* Relays are not switched on. Check whether supply voltage Us at terminal A1, A2 is available and corresponds to the
voltage indicated on the lateral type plate of the device.
* LED´s light up continuously. Check whether PTC’s at terminals T11, T12 and T21, T22 are connected correctly. Both
PTC’s must be connected and low-resistive.
Attention! Check PTC’s only with measuring voltages of < 2.5 V.
* In case of any other malfunctions, replace device and send it in together with a
description of the occurred malfunction.
(datum / name): 10.12.08 Su/Fz Z. Nr.: 1004 0710.2 Page 4 von 4 Type: MSF 220 SE
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: info@ziehl.de
1211871 1094 5
14
24
21
22
31
11
12
K1
34
32
K3
2
circuit 2
K2
63
circuit 1
=
PTC`s
alarm 1
alarm 2
operation 2
delayed
input-signal
of terminal 3
alarm 3
A2A1
U
s
– + DC ~ ~ AC
T11 T21
T12 T22
input-signal
operation 1
104,5
82
3623,5
5
41,5
80
34
1 2 3 4 5 6 7 8 9 10 11 12
82
41,5
17
7,5
5
11,5
17,5
5
10
1
2
3
1
1
2
6 Jackets for coding - pins
14
27,5
2
3
1 Cable bushing
Mounting bore - hole
Unlatching (only with rail - mounting)
Base
41
16
38
61
116
Wiring Scheme
Design S 12
Loading...