Application and short description
With its 4 digit, 14 mm high display, Digital Panel meters of MINIPAN 350 V- series allow the
accurate display of different values in the range -1999 ... +9999.
Only 3 designs cover the measuring of DC voltage and current, AC voltage and current and
temperature with Pt 100- sensors (RTD).
The display can be easily programmed by the customer (e.g. input 0-10 V --> display 0-350.0
ms or AC 0-1 A ---> 0- 400.0 A
With the built-in universal power supply AC/DC 24-240 V it is especially versatile.
Overview of functions and connection plan
Easy programming with 3 buttons:
• Display (scaling, decimal-point)
• Display of MIN- and MAX-values
• Delay for display at unstable signals
• Code-lock against manipulation of settings
• Terminals pluggable
• Face-Plate 36 x 72 mm
date / name ) : 08.10.07 WL / Fu Z. Nr.: 12180-0701-01
Page 2 of 12 Type: Minipan 350 V
May lead to electrical shock and burn.
Before beginning of work switch unit and equipment free of voltage.
Only let persons work with the equipment who are familiar with installation, start and use
and who have appropriate qualification corresponding to their function. They must observe
the contents of the instructions manual, the information which are written on the equipment
and the relevant security instructions for the setting up and the use of electrical units.
The equipments are built according to DIN / EN and checked and leave the plant according
to security in perfect condition.
If, in any case the information in the instructions manual is not sufficient, please contact
our company or the responsible representative.
Instead of the industrial norms and regulations written in this instructions manual valid for
Europe, you must observe the valid and relevant regulations of the corresponding country.
The measuring inputs is are insulated from supply-voltage but not from each
other. Connect one input only!
!
Universal power supply.
The device has got a universal power supply, that is suitable forDC- and AC-voltages.
Before connecting the device to supply-voltage make sure that the connected voltage
corresponds with the voltage on the type plate on the device.
Assembly
• Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715
• With screws M4 for installation on walls or panel. (additional latch not included in delivery)
Putting into Operation
Connect supply-voltage Us.
Connect signal to measuring input. Connect one input only!
date / name ) : 08.10.07 WL / Fu Z. Nr.: 12180-0701-01
Page 4 of 12 Type: Minipan 350 V
Decimal point behind last digit:
off = display mode (measured values)
on = menu mode, select the menu items
blinking = parameter setting mode
Display Mode
Display of actual measured value.
Function buttons Up/Down
Push short Change to menu mode, selection of menu item
Push for > 2 s Display of stored MIN- or MAX- values
Function of button Set /Reset
Push short no function Push for > 2 s Reset of MIN- or MAX-value (with Min- or Max-button pushed
simultaneously)
Push for > 10 s Display of software-version
Menu Mode (Decimal point behind last digit ON)
Selection of the menu items for changing the parameters.
Function buttons Up/Down
Push short Selection of menu item; Change into display mode
Function Taste Set/Reset
Push short Change into parameter setting mode
Parameter setting mode (Decimal point behind the last digit FLASHES)
Function buttons Up/Down
Push short/long Adjustment of parameter value (slow/fast)
Function button Set/Reset
Push short Storage of setting and choice of next parameter.
Change into menu mode after the last parameter
Parametrizing of Input / Measuring Range
Select menu item with Up/Down until display InPU and measuring range alternate.
Change into parametrizing mode with Set and select measuring range with Up/Down.
Confirm and change to next menu with Set.
When changing measuring range parameters for scaling the display are set to:
InLo = 0%, InHi = 100 % of measuring range, diLi = 0, diHi = 5000 und dp = 0000.
Scaling the Display
Select menu item with Up/Down until display ScAL and mode (Auto or USEr) alternate.
Change into parametrizing mode with Set and select mode with Up/Down.
Auto: Display = measured signal without scaling.
USEr: Range of input-signal and range of display can be set by the user. The range of the
input-signal must be within the measuring range.
date / name ) : 08.10.07 WL / Fu Z. Nr.: 12180-0701-01
Page 5 of 12 Type: Minipan 350 V
Input 0..10 V
Display 30..100 %
Input 4..20 mA
Display 0..100 %
Input 0..20 mA
Display 50.0..500.0
Input 10..90 V
Display 50.0..500.0
Input 0-60 mV
Display 0,0..30.0
Input 2..5 V
Display -50.0..100.0
InPU ScAL InLo InHi diLo diHi dP
10 USEr 0.00 10.00 30 100 0000.
4-20 USEr 4.00 20.00 0 100 0000.
0-20 USEr 0.00 20.00 500 5000 000.0
100 USEr 10.0 90.0 500 5000 000.0
300 USEr 0 60 0 300 000.0
10 USEr 2.00 5.00 -500 1000 000.0
Confirm and change to next menu with Set.
Delay of Display (recommended at unstable signals)
Select menu item with Up/Down until display ddiS and programmed value alternate.
Change into parametrizing mode with Set and set delay of display with Up/Down.
Now the measured value will be written into the display every 0,1 ... 2 s.
Confirm and change to next menu with Set.
Fixed Digits (recommended when measured signal is very unstable or changing rapidly)
Select menu item with Up/Down until F and the fixed digits blinking are displayed. When no
fixed digit is programmed, the last 2 digits are dark.
Set the fixed digits:
Fi no
Fi 0 last digit fixed (0)
Fi00 last digit fixed (00)
These digits display 0, independent from measured value.
Confirm and change to next menu with Set.
Code-lock
Select menu item with Up/Down until display Code programmed state alternate.
Here the parameters can be protected by activating the code-lock. After pushing Set, Pin is
displayed. Change to Pin 504 with buttons Up/Down (factory setting). After pushing Set the
code-lock can be activated or de-activated. After pushing Set again, an individual Pin
Can be selected (write down)
With activated code-lock, all parameters can be seen but not changed any more.
In case of problems with the code-lock (forgotten Pin), the lock can be switched off and the
Pin can be set back to 504,by pushing the button Set/Reset while connecting the device to
supply voltage until Code / ofF is displayed.
date / name ) : 08.10.07 WL / Fu Z. Nr.: 12180-0701-01
Page 6 of 12 Type: Minipan 350 V
Line-Resistance at version for Pt 100-sensors (RTD):
Select menu item with Up/Down until display L-A and programmed parameter alternate.
Change into parametrizing mode with Set and do the line-compensation with Up/Down (enter
value of line-resistance) or 3-wire (3-L).
2-wire-configuration, compensation of cable-resistance:
Short-circuit the wires nearby the sensor and measure the resistance of the cable. Set
„LA“ to this value.
Measuring Unit (°C or °F) at version for Pt 100-sensors (RTD):
Select menu item with Up/Down until display Unit and programmed unit alternate.
Change into parametrizing mode with Set and select unit (°C or °F).
Tips:
- After finishing one menu item it is switched automatically to the next one.
- When the right decimal point in the 7 segment display is on, the display mode has been left,
and the menu items can be chosen with up/down (menu mode).
- When the right decimal point blinks, you are in the parameter setting mode and can change
the setting with up/down.
- Long pushing on up/down speeds up the changes in the display.
- Pushing button up and down at the same time sets values to zero.
- With reset (press set/reset for 2s) the display mode can be reached from every position of the
parameter setting mode (the last selected value in is being stored).
- With InLo and InHi scaling is simplified when measuring-range and range of signal are
different.
Example: Display 0-500.0 at input-signal 10-90 V:
• Connect to measuring input 100 V and select InPU = 100
• Set InLo to 10.0
• Set InHi to 100.0
• Set diLo to 0
• Set diHi to 5000
• Set dP to 000.0
date / name ) : 08.10.07 WL / Fu Z. Nr.: 12180-0701-01
Page 7 of 12 Type: Minipan 350 V
Reset to factory setting: Push button Set for 10 s when applying supply voltage until “----" is
displayed.
Version
Parameter MINIPAN DC MINIPAN AC MINIPAN Pt 100 Users own Data
InpU 10 1 L-A - - 3-L
Unit - - °C
ScAL Auto Auto InLo 0.00 0.000 InHi 10.00 1.000 DiLo 0 0 DiHi 5000 5000 dp 0000. 0000. ddis 0.5 0.5 0.5
Fi Fi Fi Code off off off
Pin 504 504 504
• Unit cannot be programmed – Code lock
The code lock gives protection against unauthorized manipulation of the unit. When code
lock is activated the parameters can not be changed. The pin can be set by the user.
Pin unknown? Make code-reset: When switching in supply-voltage keep pushed button
„Set“ for 2 s.
Power Supply
Rated supply voltage Us AC/DC 24-240 V
Tolerance DC DC 20 - 297 V (0,85 x 24 V...1,35 x 220 V)
Tolerance AC AC 20 - 264 V (0,85 x 24 V...1,1 x 240 V)
Power consumption < 3 VA
Frequency 48...62 Hz
Measuring Inputs insulated from supply-voltage
(connect 1 input only)
DC-Meter ± 300 mV / 120 kΩ / max. ±2,5 V
Measuring range / resistance of input ± 10.00 V / 1 MΩ / max. ±50 V
/ overload capacity ± 500.0 V / 3 MΩ / max. ±600 V
± 100.0 V / 3 MΩ / max. ±600 V
± 20.00 mA / Shunt 15 Ω/ max. ±100
± 1.00 A / Shunt 150 mΩ / max. ±2 A
AC-Meter 150 mV / 900 Ω / max. 2,5 V
Measuring range / resistance of input 10.00 V / 100 kΩ / max. 50 V
/ overload capacity 50.0 V / 1 MΩ / max. 60 V
500.0 V / 3 MΩ / max. 600 V
1.00 A / Shunt 150 mΩ / max. 2 A
Measuring time AC/DC < 400 ms + delay of display ddisPt 100- Meter - 199,9 ... + 850,0 °C (= -328 ... +1563 °F) Sensor-connection Pt 100, 2- or 3-wire
Wire-resistance 3-wire max. 3 x 50 ΩMeasuring time temperature < 400 ms + delay of display ddis
AccuracyResolution +9999 / -1999
Accuracy (of full measuring range) DC voltage and current ± 0,1 % ± 1 Digit
AC voltage and current ± 0,5 % ± 1 Digit
Temperature factor ± 0,02 % / Kelvin
Accuracy Pt 100- Meter ± 0,3 % of value ± 0,5 K
Temperature factor ± 0,03 °C / K
Test conditionsEN 50178 / EN 61010-1
EN 61326-1 industrial applications
Measuring category CAT II 600 V DOUBLE INSULATION
CAT III 300 V DOUBLE INSULATION
Contamination level 2
On-time 100 %
Rated ambient temperature range -20 °C ... +60 °C
EN 60068-2-1 dry heat
Vibration resistance EN 60068-2-6 2…25 Hz ±1,6 mm
25 ... 150 Hz 5 g
date / name ) : 08.10.07 WL / Fu Z. Nr.: 12180-0701-01
Page 11 of 12 Type: Minipan 350 V
Housing Design V2, switchgear mounting
Mounting height 55 mm
Width 2 TE
Dimensions (width x height x depth) 35 x 90 x 58 mm
Wire connection, one wire each 1 x 0,5…1,5 mm2
Stranded wire with insulated ferrules each 1 x 0,14…1,0 mm2
Protection class housing IP 30
Protection class terminal IP 20
Installation Snap mounting on mounting rail 35 mm according to
EN 60 715 or with screws M 4
Weight approx. 120 g
Subject to technical changes
Form
45
61,8
Dimensions in mm
58
48
16,5
35
Option
5
(90)
98
116
4
6
3
1
2
3
7
1 Cover
2 Base
3 Bar for snap mounting
4 Latch for sealing
5 Front panel
6 Position downward
7 For fixing to wall with screws, Ø 4,2 mm.
date / name ) : 08.10.07 WL / Fu Z. Nr.: 12180-0701-01
Page 12 of 12 Type: Minipan 350 V