Zeversolar Zeverlution 1500S, Zeverlution 1000S, Zeverlution 2000S, Zeverlution 3000S Installation And Operating Insctructions

Installation and Operating Instructions V02 1
Table of Contents
1 Notes on this manual ...................................................................................... 4
1.1 Validity ............................................................................................ 4
1.2 Target group .................................................................................. 4
1.3 Symbols used in this manual ......................................................... 5
2 Safety ................................................................................................................ 6
2.1 Intended use ................................................................................... 6
2.2 Safety standards ........................................................................... 6
2.3 Important safety information ....................................................... 7
2.4 Symbols on the type label ........................................................... 10
2.5 Basic safety protection ................................................................. 11
3 Unpacking ........................................................................................................ 12
3.1 Scope of delivery .......................................................................... 12
3.2 Checking for transport damage ................................................... 12
4 Mounting .......................................................................................................... 13
4.1 Ambient conditions ....................................................................... 13
4.2 Selecting the mounting location .................................................. 15
4.3 Mounting the inverter with the wall bracket ............................... 16
5 Electrical connection .......................................................................... 18
5.1 Safety ........................................................................................... 18
5.2 System layout of units without integrated DC switch ................ 19
5.3 Overview of the connection area ................................................ 20
5.4 AC connection............................................................................... 21
2 Installation and Operating Instructions V02
5.5 DC connection .............................................................................. 28
6 Communication .................................................................................. 33
6.1 System monitoring via R485 ....................................................... 33
6.2 System monitoring via Ethernet ................................................. 37
6.3 System monitoring via WiFi ........................................................ 38
6.4 Communication with a third-party devices ................................ 39
7 Commissioning ................................................................................... 40
7.1 Electrical checks .......................................................................... 40
7.2 Mechanical checks ........................................................................ 41
7.3 Start-up ....................................................................................... 42
8 Disconnecting the inverter from voltage sources ............................ 43
9 Operation ........................................................................................... 45
9.1 Overview of the control panel ..................................................... 45
9.2 Display messages ....................................................................... 48
9.3 Language and safety regulation settings ................................... 50
Installation and Operating Instructions V02 3
10 Technical Data .................................................................................. 52
10.1 DC input data............................................................................... 52
10.2 AC output data ........................................................................... 53
10.3 General data ............................................................................... 54
10.4 Safety regulations ..................................................................... 55
10.5 Efficiency ................................................................................... 57
10.6 Power reduction ......................................................................... 61
10.7 Tools and torque ........................................................................ 63
11 Troubleshooting ................................................................................ 64
12 Maintenance ..................................................................................... 66
12.1 Cleaning the contacts of the DC switch ..................................... 66
12.2 Cleaning the heat sink ................................................................ 66
13 Recycling and disposal ..................................................................... 67
14 Warranty .......................................................................................... 67
15 Contact ............................................................................................. 68
4 Installation and Operating Instructions V02
1 Notes on this manual
General Notes
Zeverlution is a transformerless solar inverter with a single MPP tracker. It converts the direct current (DC) from PV arrays to grid-compliant alternating current (AC) and feeds it into the utility grid.
1.1 Validity
This manual describes the mounting, installation, commissioning and maintenance of the following Zeversolar inverters: Zeverlution 1000S, Zeverlution 1500S, Zeverlution 2000S, Zeverlution 3000S. Observe all documentation that accompanies the inverter. Keep them in a convenient place and available at all times.
1.2 Target group
This manual is for qualified electricians only who must perform the tasks exactly as described. All persons installing inverters must be trained and experienced in general safety which must be observed when working on electrical equipments. Installation personnel should also be familiar with local requirements, rules and regulations.
Installation and Operating Instructions V02 5
1.3 Symbols used in this manual
The following safety precautions and general information are used in this manual:
INFORMATION provides tips which are valuable for the optimal installation and operation of the inverter.
NOTICE indicates a situation which, if not avoided, can result in property damage.
CAUTION indicates a hazardous situation which, if not avoided, can result in minor or moderate injury.
WARNING indicates a hazardous situation which, if not avoided, can result in death or serious injury.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
6 Installation and Operating Instructions V02
2 Safety
2.1 Intended use
1. Zeverlution converts the direct current from PV arrays into grid-compliant alternating current.
2. Zeverlution is suitable for indoor and outdoor use.
3. Zeverlution must only be operated with PV arrays (PV modules and cabling) of protection class II, in accordance with IEC 61730, application class A. Do not connect any sources of energy other than PV modules to the inverter.
4. PV modules with a high capacitance to ground may only be used if their coupling capacity does not exceed 1.0μ F.
5. When the PV modules are exposed to sunlight, a DC voltage is supplied to this device.
6. When designing the PV power plants, ensure that the values comply with the permitted operating range of all components at all times. The free design program Zeverplan“ (http://www.zeverplan.com ) will assist you.
2.2 Safety standards
Zeverlution complies with the EU Low-Voltage Directive 2006/95/EC and the EMC Directive 2004/108/EC. Zeverlution also complies with the requirement for safety and EMC in Australia and New Zealand market. The inverters are labeled with the CE mark and RCM mark, fulfill the requirements specified in the specific standards. For more information about certificates in other countries and regions, please visit website ( http:// www.zeversolar.com ).
Installation and Operating Instructions V02 7
2.3 Important safety information
Danger to life due to high voltages of the PV array When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks. If you disconnect the DC connectors from the inverter under load, an electric arc may occur leading to electric shock and burns.
Do not touch non-insulated cable ends.
Do not touch the DC conductors.
Do not touch any live components of the inverter.
Have the inverter mounted, installed and commissioned only by
qualified persons with the appropriate skills.
If an error occurs, have it rectified by qualified persons only.
Prior to performing any work on the inverter, disconnect it from all
voltage sources as described in this documentation in chapter 8.
• All work on the inverter must only be carried out by qualified personnel who have read and fully understood all safety information contained in this manual.
• Children must be supervised to ensure that they do not play with this
device.
8 Installation and Operating Instructions V02
Grounding the PV array
• Comply with local regulations for grounding the PV array. We
suggest the frames of PV modules must be reliably grounded.
Do not ground any of the terminals of the strings.
Possible damage to health as a result of the effects of electromagnetic radiation
• Please maintain a distance of at least 20cm from the inverter when it
is in operation.
Risk of injury due to hot heat sink
• The heat sink may get hot during operation. Do not touch!
Risk of injury due to electric shock and fire caused by high leakage current
• The inverter must be reliably grounded in order to protect property
and personal safety.
Installation and Operating Instructions V02 9
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the
inverter through electrostatic discharge.
Ground yourself before touching any component.
Damage to the seal of the cover in sub-zero conditions
If you open the cover in sub-zero condition,the sealing of the cover
can be damaged. This can lead moisture entering the inverter.
Do not open the inverter at ambient temperatures lower than -5.
If a layer of ice has formed on the seal of the cover in sub-zero
conditions, remove it prior to opening the inverter(e.g. by melting the ice with warm air). Observe the applicable safety regulation.
10 Installation and Operating Instructions V02
2.4 Symbols on the type label
Icon
Explanation
Risk of danger, warning and caution
Safety information important for human safety. Failure to observe the
safety information in this manual may result in injury or death.
Danger to life due to electric shock
The product operates at high voltages. Prior to performing any work on the
product, disconnect the product from voltage sources. All work on the
product must be carried out by electrically qualified persons only.
Risk of burns due to hot surfaces
The product can get hot during operation. Avoid contact during operation.
Allow the product to cool down sufficiently before carrying out any work.
WEEE designation
Do not dispose of the product together with the household waste but in
accordance with the disposal regulations for electronic waste applicable at
the installation site.
CE marking
The product complies with the requirements of the applicable EU directives.
Certified safety
The product is TUV-tested and complies with the requirements of the EU
Equipment and Product Safety Act.
RCM
The product complies with the requirements of the applicable Australian
low voltage and electromagnetic compatibility standards.
Capacitors discharge
Danger to life due to high voltages in the inverter, observe the waiting
time of five minutes. Prior to performing any work on the inverter,
disconnect it from all voltage sources as described in chapter 8.
Observe the documentation
Observe all documentation supplied with the product.
Installation and Operating Instructions V02 11
2.5 Basic safety protection
We provide the following safety protection:
1) Overvoltage, undervoltage protection
2) Overfrequency, underfrequency protection
3) Overtemperature monitoring
4) Residual current monitoring
5) Isolation monitoring
6) Anti-islanding protection
7) DC feed-in monitoring
12 Installation and Operating Instructions V02
3 Unpacking
3.1 Scope of delivery
Object
Description
Quantity
A
Inverter
1 B Wall bracket
1
C
Mounting accessory kit: Wall anchors and hexagon bolts (2×) M5×12 pan head screw (2×) *M5×14 pan head screw (1×) *Ground washer (2×)
1
D
DC connector
1 E Documentation
1 F WiFi antenna
1 ( optional )
* One spare part for cover mounting
A B C
D E F
Please carefully check all of the components in the carton. If anything is missing, contact your dealer at once.
3.2 Checking for transport damage
Thoroughly inspect the packaging upon delivery. If you detect any damage to the packaging which indicates the inverter may have been damaged, inform the responsible shipping company immediately. We will be glad to assist you if required.
Installation and Operating Instructions V02 13
4 Mounting
4.1 Ambient conditions
1. Be sure the inverter is mounted out of the reach of children.
2. Mount the inverter in areas where it cannot be touched inadvertently.
3. Ensure good access to the inverter for installation and possible service.
4. The ambient temperature should be below 40°C to ensure optimal operation.
5. Observe the recommended clearances to walls, other inverters, or objects as
follows to ensure sufficient heat dissipation.
Clearances for multiple inverters
6. In order to avoid power reduction caused by overheating, do not mount the
inverter in a location that allows long-term exposure to direct sunlight.
Direction
Recommended clearance(mm)
above
300
below
300
sides
200
Clearances for one inverter
14 Installation and Operating Instructions V02
7. Ensure optimum operation and extend service life, avoid exposing theinverter to
direct sunlight, rain and snow.
8. The mounting method, location and surface must be suitable for the inverter's
weight and dimensions.
9. If mounted in a residential area, we recommend mounting the inverter on a
solid surface. Plasterboard and similar materials are not recommended due to audible vibrations when in use.
10. Do not put any objects on the inverter. Do not cover the inverter.
Installation and Operating Instructions V02 15
4.2 Selecting the mounting location
1. Mount the inverter vertically or tilted backward by a max of 15°.
2. Never mount the inverter tilted forward or sideways.
3. Never mount the inverter horizontally.
4. Mount the inverter at eye level to make it easy to operate and to read the
display.
5. The electrical connection area must point downwards.
Danger to life due to fire or explosion
• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where flammable materials are
stored.
• Do not mount the inverter in areas where there is a risk of explosion.
16 Installation and Operating Instructions V02
4.3 Mounting the inverter with the wall bracket
Mounting procedures:
1. Use the wall bracket as a drilling template and mark
the positions of the drill holes, then drill 2 holes (Φ 10) to a depth about 70mm. During operation, keep the drill vertical to the wall, and hold the drill steady to avoid tilted holes.
2. After cleaning the dust and other objects from the holes, place 2 wall anchors into
the holes, then attach the wall bracket to the wall using the hexagon head screw delivered with the inverter.
Risk of injury due to damaged cables There may be power cables or other supply lines (e.g. gas or water)
routed in the wall.
• Ensure that no lines are laid in the wall which could be damaged when
Risk of injury when lifting the inverter, or if it is dropped The inverter weighs approximately 8 kg. There is risk of injury if the inverter is lifted incorrectly or dropped while being transported or when attaching it to or removing it from the wall bracket.
• Transport and lift the inverter carefully
Installation and Operating Instructions V02 17
3. Holding the inverter using the housing side edges and attach it onto the wall bracket
tilted slightly downwards.
4. Check both sides of the heatsink to ensure that it is securely in place.
5. Push the inverter as far as possible and attach it to both sides of the wall bracket
using the M5 screws.(screw driver type: T25,torque: 2.5Nm)
If a second protective conductor is required in installation site, ground the inverter and secure it so that it cannot be lifted off the wall bracket (see section 5.4.3 ‛Second protective grounding connection“).
Dismante the inverter in reverse order.
18 Installation and Operating Instructions V02
5 Electrical connection
5.1 Safety
Danger to life due to high voltages of the PV array When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks. If you disconnect the DC connectors from the inverter under load, an electric arc may occur leading to electric shock and burns.
Do not touch non-insulated cable ends.
Do not touch the DC conductors.
Do not touch any live components of the inverter.
Have the inverter mounted, installed and commissioned only by
qualified persons with the appropriate skills.
If an error occurs, have it rectified by qualified persons only.
Prior to performing any work on the inverter, disconnect it from all
voltage sources as described in chapter 8.
Installation and Operating Instructions V02 19
5.2 System layout of units without integrated DC switch
Local standards or codes may require that PV systems are fitted with an external DC switch on the DC side. The DC switch must be able to safely disconnect the open-circuit voltage of the PV array plus a safety reserve of 20%. Install a DC switch to each PV string to isolate the DC side of the inverter. We recommend the following electrical connection:
Risk of injury due to electric shock
• The external protective grounding conductor is connected to the inverter’s protective grounding terminal through the screw terminal
block. Make sure the connection is reliable.
• When connecting, connect the AC connection first to ensure the inverter grounding reliably and then connect the DC inputs.
• When disconnecting, disconnect the DC inputs first and then
disconnect the AC connection.
• Don’t connect the DC inputs while the AC connection is disconnected under any circumstances.
• All electrical installations must be done in accordance with the National Wiring Rules Standards and Local Code.
20 Installation and Operating Instructions V02
5.3 Overview of the connection area
Object
Description
A
DC-SWITCH (optional): switch on or off for PV-load.
B
DC: plug-in connector to connect the strings.
C
COM: connect the monitoring device with network cable.
D
ANT (optional): antenna, transmit and receive Wi-Fi signal.
E
AC: connect the grid.
Installation and Operating Instructions V02 21
5.4 AC connection
5.4.1 Conditions for the AC connection
Cable Requirements The grid connection is established using three conductors (L, N, and PE). We recommend the following requirements for stranded copper cable.
Object
Description
Value
A
External diameter
5 to 13 mm
B
Conductor cross-section
2.5 to 6 mm²
C
Stripping length of the insulated conductors
approx. 12 mm
D
Stripping length of the outer sheath of AC cable
approx. 70 mm
The PE insulated conductor must be 10mm longer than the L and N conductors
Larger cross-sections should be used for longer leads.
Cable design The conductor cross-section should be dimensioned to avoid power loss in cables exceeding 1% of rated output power. The higher grid impedance of the AC cable makes the inverter easier to disconnect from the grid due to excessive voltage at the feed-in point.
Danger to life due to high voltages in the inverter
• Before performing the electrical connection, ensure that the AC
circuit breaker is switched off and cannot be reactivated.
22 Installation and Operating Instructions V02
The maximum cable lengths relative to the conductor cross-section as follows:
Conductor
cross-section
Maximum cable length
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
2.5 mm²
46m
37 m
28 m
17 m
4 mm²
74 m
59 m
44 m
27 m
6 mm²
110 m
89 m
67 m
40 m
The required conductor cross-section depends on the inverter rating, ambient temperature, routing method, cable type, cable losses, applicable installation requirements of the country of installation, etc.
5.4.2 Grid connection
Damage to the seal of the cover in sub-zero conditions
If you open the cover in sub-zero condition, the sealing of the cover
can be damaged. This can lead moisture entering the inverter.
Do not open the inverter at ambient temperatures lower than -5.
If a layer of ice has formed on the seal of the cover in sub-zero
comditions, remove it prior to opening the inverter( e.g. by melting the ice with warm air ). Observe the applicable safety regulation.
Risk of injury due to electric shock and fire caused by high leakage current
• The inverter must be reliably grounded in order to protect property
and personal safety.
Installation and Operating Instructions V02 23
Procedure:
1. Switch off the AC circuit breaker and secure it against reconnection.
2. Loosen the screws of the cover using a screwdriver (T25) and remove the cover.
3. Strip the AC cable’s outer sheath 70 mm. Shorten L and N by 10 mm each. Strip the
insulation of L, N, and PE conductor by 12 mm.
4. Route the AC cable into the inverter through the M20 cable gland.
5. If necessary, slightly loosen the swivel nut of the cable gland.
6. Insert bared conductor into the cord end terminal and crimp the contact.
loosen the screws of the cover
During loosening the screws of the cover, it is not necessary to take off the screws and conical spring washers, which can remain on the cover and will not fall off.
24 Installation and Operating Instructions V02
7. Connect the L,N,protective conductor(PE) to the screw terminal block(screw
driver type:DIN5264(blade: 1×5.5),torque: 1.2Nm).
Insert the protective conductor (green-yellow) into the screw terminal with the grounding sign and tighten the screw.
Insert the neutral conductor (blue) into the screw terminal with N sign and tighten the screw.
Insert the L conductor (brown or black) into the screw terminal with L sign and tighten the screw.
8. Make sure the insulated conductors are securely connected.
9. Tighten the swivel nut of the cable gland by using a torque of 2.5Nm and check
the tightness.
10. Secure the cover in the sequence 1 to 4 (screw driver type: T25,torque: 2.2Nm).
L N PE
Installation and Operating Instructions V02 25
5.4.3 Second protective grounding connection
If required, the grounding terminal can be used to connect a second protective conductor or as equipotential bonding.
Procedure:
1. Take out the terminal lug, insert the stripped grounding conductor into the terminal lug and crimp the contact.
2. Align the plain washer, the terminal lug with the grounding conductor, and the ground washer on the screw. The teeth of the ground washer must be facing the heat sink.
3. Insert the screw through the hole at the side of the heat sink, and tighten it firmly into the wall bracket (screw driver type: T25,torque: 2.5 Nm).
Grounding parts information:
Object
Description
1
Heatsink
2
Ground washer
3
Terminal lug(M5) with protective conductor
4
M5×12 pan head screw
1
2
3
4
26 Installation and Operating Instructions V02
5.4.4 Residual current protection
The inverter is equipped with an all-pole sensitive residual current monitoring unit (RCMU) with an integrated differential current sensor which fulfills the requirements of DIN VDE 0100-712 (IEC60364-7-712:2002). Therefore an external residual current device (RCD) is not required. If an external RCD needs to be installed because of local regulations, a RCD type A or type B can be installed as an additional safety measure. The all-pole sensitive residual current monitoring unit (RCMU) detects alternating and direct differential currents. The integrated differential current sensor detects the current difference between the neutral conductor and the line conductor. If the current difference increases suddenly, the inverter disconnects from the grid. The function of the all-pole sensitive residual current monitoring unit (RCMU) has been tested in accordance with IEC 62109-2.
Tip about the external residual current device (RCD)
Where an external residual current device (RCD) is required in a TT or
TN-S system, install a residual current device which trips at a residual current of 100mA or higher.
For each connected inverter, a rated residual current of 100mA has to
be provided. The rated residual current of the RCD must be equal to at least the sum of the rated residual currents of the connected inverter.That means that, if, for example, 2 transformerless inverters are connected, the rated residual current of the RCD must be at least 200mA.
Installation and Operating Instructions V02 27
5.4.5 Overvoltage category
The inverter can be deployed in grids of installation category III or lower, as defined under IEC 60664-1. This means that it can be permanently connected at the grid-connection point in a building. In installations involving long outdoor cable routing, additional overvoltage-reducing measures must be taken so that the overvoltage category is reduced from IV to III.
5.4.6 Rating of AC circuit breaker
No consumer load should be applied between AC circuit breaker and the inverter. Use dedicated AC circuit breakers with load switch functionality for load switching. The selection of the AC circuit breaker rating depends on the wiring design (wire cross-section area), cable type, wiring method, ambient temperature, inverter current rating etc. Derating of the circuit breaker rating may be necessary due to self-heating or if exposed to heat. The maximum output currents of the inverters and recommended AC circuit breaker can be found in the following table.
Type
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
Max. output current
5.5A
7.5 A
10 A
15 A
Recommended fuse type gL/gG or comparable circuit breaker rating
16 A
16 A
16 A
25A
Danger to life due to fire You must safeguard each inverter with an individual AC circuit breaker in order that the inverter can be disconnected safely.
28 Installation and Operating Instructions V02
5.5 DC connection
5.5.1 Requirements for the DC connection
Requirements for the PV modules of a string:
PV modules of the connected strings must be of: the same type, identical alignment
and identical tilt.
The thresholds for the input voltage and the input current of the inverter must be
adhered to (see Section 10.1 "Technical DC input data").
• On the coldest day based on statistical records, the open-circuit voltage of the PV
array must never exceed the maximum input voltage of the inverter.
The connection cables of the PV modules must be equipped with the connectors
included in the scope of delivery.
The positive connection cables of the PV modules must be equipped with the positive
DC connectors. The negative connection cables of the PV modules must be equipped with the negative DC connectors
Use of Y adapters for parallel connection of strings
The Y adapters must not be used to interrupt the DC circuit.
Do not use the Y adapters in the immediate vicinity of the inverter. The adapters must not be visible or freely accessible.
In order to interrupt the DC circuit, always disconnect the inverter as described in this document in chapter 8.
Danger to life due to high voltages in the inverter
• Before connecting the PV array, ensure that the DC switch is switched
off and that it cannot be reactivated.
• Do not disconnect the DC connectors under load.
Installation and Operating Instructions V02 29
5.5.2 Assembling the DC connectors
Assemble the DC connectors as described below. Be sure to observe the correct polarity. The DC connectors are marked with the symbols "+" and " − ".
Cable requirements: The cable must be of type PV1-F, UL-ZKLA or USE2 and comply with the following properties:
External diameter: 5 mm to 8 mm Conductor cross-section: 2.5 mm² to 6 mm² Qty single wires: minimum 7 Nominal voltage: minimum 600V
Proceed as follows to assemble each DC connector:
1. Strip 12 mm off the cable insulation.
Danger to life due to high voltages on DC conductors When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC conductors. Touching the DC conductors can lead to lethal electric shocks.
Cover the PV modules.
Do not touch the DC conductors.
30 Installation and Operating Instructions V02
2. Route the stripped cable all the way into the DC connector. Ensure that the
stripped cable and the DC connector have the same polarity.
3. Press the clamping bracket down until it audibly snaps into place.
4. Ensure that the cable is correctly positioned:
Result
Measure
If the stranded wires are visible in the chamber of the clamping bracket, the cable is correctly positioned.
Proceed to step 5.
If the stranded wires are not visible in the chamber, the cable is not correctly positioned.
Release the clamping bracket. To do so, insert a flat-blade screwdriver (blade width: 3.5 mm) into the clamping bracket and lever it open.
Remove the cable and go back to step 2.
5. Push the swivel nut up to the thread and tighten (torque: 2 Nm).
Installation and Operating Instructions V02 31
5.5.3 Disassembling the DC connectors
1. Unscrew the swivel nut.
2. To release the DC connector, insert a flat-blade screwdriver (blade width: 3.5 mm) into the side catch mechanism and lever open.
3. Carefully pull the DC connector apart.
4. Release the clamping bracket. To do so, insert a flat-blade screwdriver (blade width: 3.5 mm) into the clamping bracket and lever it open.
5. Remove the cable.
Danger to life due to high voltages on DC conductors When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC conductors. Touching the DC conductors can lead to lethal electric shocks.
Cover the PV modules.
Do not touch the DC conductors.
32 Installation and Operating Instructions V02
5.5.4 Connecting the PV array
1. Ensure that the individual AC circuit breaker is switched off and ensure it against
reconnection.
2. Ensure that the DC switch is switched off and ensure it against reconnection.
3. Ensure that there is no ground fault in the PV strings.
4. Check whether the DC connector has the correct polarity.
If the DC connector is equipped with a DC cable having the wrong polarity, the DC connector must be reassembled. The DC cable must always have the same polarity as the DC connector.
5. Ensure that the open-circuit voltage of the PV strings does not exceed the
maximum DC input voltage of the inverter.
6. Connect the assembled DC connectors to the inverter until they audibly snap into
place. Ensure that all DC connectors are securely in place.
Damage to the inverter due to overvoltage If the voltage of the strings exceeds the maximum DC input voltage of the inverter, it can be destroyed due to overvoltage. All warranty claims become void.
• Do not connect strings with an open-circuit voltage greater than the maximum DC input voltage of the inverter.
• Check the design of the PV system.
Installation and Operating Instructions V02 33
6 Communication
6.1 System monitoring via R485
This inverter is equipped with RJ45 interfaces for multipoint communication. One ZeverCom/ZeverManager connects inverters via an RS485 bus. The overall length of the network cable should not exceed 1,000 m. The monitoring system layout for inverters is as follows.
The ZeverManager connects to the inverter via the RJ45 interface, and it connects to the router via Ethernet. Then you will be able to connect the inverter to the remote monitoring platform ‛Solarcloud“. You can monitor the operating status or power generation data via a smart phone or PC. The website address of the ‛Solarcloud“ is http://solarcloud.zeversolar.com
34 Installation and Operating Instructions V02
Pinout detail of the RJ45 interface on the inverter as follows:
Pin1------- TX_RS485A
Pin2-------TX_RS485B
Pin3-------RX_RS485A
Pin4-------GND
Pin5-------GND
Pin6-------RX_RS485B
Pin7-------+7V
Pin8-------+7V
For detailed information, please refer to ZeverManager user manual.
CAT-5 with shield or higher level cable is required as the RS485 communication cable between inverter and ZeverManager. Pinout detail on both ends of the cable should comply with IA/TIA568A or 568B standard.
The cable shall be UV resistant if used outdoors.
Connect the network cable:
Damage to the inverter due to moisture and dust penetration
If the cable gland are not mounted properly, the inverter can be destroyed due to moisture and dust penetration. All the warranty claim will be invalid.
Make sure the cable gland has been tightened firmly.
Installation and Operating Instructions V02 35
1. Loosen the screws of the cover using a screwdriver (T25) and remove the cover.
(see Section 5.4.2).
2. Unscrew the swivel nut of the M25 cable gland, remove one filler-plug from the
cable gland and keep it well. If there is only one network cable, please keep another filler-plug in the remaining hole of the sealing ring against water ingress.
3. The current pinout assignment for network cable complies with the EIA/TIA 568
standard. Please refer and apply it for physical implementation as needed.
4. Route the network cable into the inverter through the M25 cable gland, and
connect it to the RJ45 socket located on the lower circuit board.
M25 cable gland for network cable
36 Installation and Operating Instructions V02
If the inverter has integrated ComBox (with Ethernet module), you need to insert the network cable into the RJ45 socket on the upper circuit board(ComBox).
5. Connect the inverter to ZeverCom/ZeverManager via the above mentioned
network cable.
6. Press the sealing ring with the network cable into the cable gland, and then tighten
the swivel nut firmly. Make sure the cable gland is mounted properly. The cable gland must be adequately locked to prevent any movement of the cable.
7.Secure the cover (screw driver type: T25,torque: 2.5Nm).
Disassemble the network cable in reverse order.
Installation and Operating Instructions V02 37
6.2 System monitoring via Ethernet
User can monitor the inverter through the integrated ComBox with Ethernet module (optional), The connection diagram between the inverter and internet with network cable is shown as follows.
Internet
LAN
Inverter_1
Inverter_n
Router
Internet
Solarcloud
LAN LAN
Inverter_2
For connecting the network cable between the router and the Ethernet port on the ComBox, please refer to the relative instruction at section 6.1.
The inverter obtains an IP address from the router via DHCP automatically and shows it on the display. It takes time to connect to the network depending on the network communication conditions.
Possible reason of communication failure due to DHCP
The router needs to support DHCP services if the ComBox use the DHCP function.
Possible reason of communication failure due to closed port
The ComBox uses port #6655 and #80 to communicates with the Solarcloud. Both of these two ports must be opened, or else the ComBox cannot communicate with the Solarcloud and upload data.
38 Installation and Operating Instructions V02
6.3 System monitoring via WiFi
User can monitor the inverter through the integrated ComBox with WiFi module (optional). The connection diagram between the inverter and internet with a WiFi connection is shown as follows.
WiFi
Solarcloud
Wireless Router
Internet Internet
Inverter
Mounting the antenna:
1. Take the antenna included in the scope of delivery.
2. Remove the sealing plug on the WIFI connection port.
3. Tighten the antenna to the WIFI connection port by hand.
4. Make sure the antenna is securely connected.
More detailed information for ComBox and Solarcloud: In order to achieve remote monitoring reliably, please visit website ( http:// www.zeversolar.com ) and download the ComBox’s manual for detailed information, you can also find how to use Solarcloud in it.
Installation and Operating Instructions V02 39
6.4 Communication with a third-party devices
This interver supports communication with a third party monitoring device such as Metecontrol, Solar-Log etc. For detailed wiring method please refer to operating manual of corresponding third party monitoring device.
40 Installation and Operating Instructions V02
7 Commissioning
7.1 Electrical checks
Carry out the main electrical checks as follows: Check the PE connection with a multimeter: check that the inverter’s exposed metal
surface has a ground connection.
Check the DC voltage values: check that the DC voltage of the strings does not
exceed the permitted limits.
Check the polarity of the DC voltage: make sure the DC voltage has the correct
polarity.
Check the PV array’s insulation to ground with a multimeter: make sure that the
insulation resistance to ground is greater than 1 MOhm.
Danger to life due to the presence of DC voltage
• Only touch the insulation of the PV array cables.
• Do not touch parts of the sub-structure and frame of PV array which
are not grouned.
• Wear personal protective equipment such as insulating gloves.
Risk of injury due to incorrect installation We strongly recommend carrying out preliminary checks before commissioning to avoid possible damage to the device caused by faulty installation.
Installation and Operating Instructions V02 41
Check the grid voltage: check that the grid voltage at the point of connection of
the inverter complies within the permitted value.
7.2 Mechanical checks
Carry out the main mechanical checks to ensure the inverter is waterproof:
Make sure the inverter and wall bracket have been correctly mounted. Make sure the cover has been correctly mounted. Make sure the communication and AC cable glands have been correctly mounted
and tightened.
Danger to life due to the presence of AC voltage
• Only touch the insulation of the AC cables.
• Wear personal protective equipment such as insulating gloves.
42 Installation and Operating Instructions V02
7.3 Start-up
After finishing the electrical and mechanical checks, switch on the AC circuit breaker and DC switch in turn. Once the DC input voltage and power are sufficiently high and the grid-connection conditions are met, the inverter will start operation automatically. Usually, there are three states during operation:
Waiting: When the initial voltage of the strings is greater than the minimum DC input voltage but lower than the start-up DC input voltage, the inverter is waiting for sufficient DC input voltage and cannot feed power into the grid.
Checking: When the initial voltage of the strings exceeds the start-up DC input voltage, the inverter will check feeding conditions at once. If there is anything wrong during checking, the inverter will switch to the ‛Fault“ mode.
Normal: After checking, the inverter will switch to ‛Normal“ state and feed power into the grid.
During periods of low radiation, the inverter may continuously start up and shut down. This is due to insufficient power generated by the PV generator. If this fault occurs often, please call service.
Quick Troubleshooting
If the inverter is in "Fault" mode, refer to Section 11 "Troubleshooting".
Installation and Operating Instructions V02 43
8 Disconnecting the inverter from voltage sources
Prior to performing any work on the inverter, disconnect it from all voltage sources as described in this section. Always adhere strictly to the prescribed sequence.
Procedure:
1. Disconnect the AC circuit breaker and secure it against reconnection.
2. Disconnect the DC switch and secure it against reconnection.
3. Use a current clamp to ensure that no current is present in the DC cables.
4. Release and remove all DC connectors. Insert a flat-blade screwdriver or an
angled screwdriver (blade width: 3.5 mm) into one of the slide slots and pull the DC connectors out downwards. Do not pull on the cable.
5. Ensure that no voltage is present at the DC input of the inverter using a suitable
measuring device.
6. Loosen the screws of the cover using a screwdriver (T25) and remove the
cover.
Danger to life due to high voltages The capacitors in the inverter take 5 minutes to discharge.
• Wait 5 minutes before opening the cover.
Destruction of the measuring device due to overvoltage
Only use measuring devices with a DC input voltage range of 1000 V or
higher.
44 Installation and Operating Instructions V02
7. Use a suitable measuring device to check that no voltage is present at the AC
screw terminal blocks between L and N and L and PE.
8. Unscrew the screws of the screw terminal blocks and the swivel nut of the
M20 cable gland, remove the AC cable .
9. Secure the cover (screw driver type: T25,torque: 2.5Nm).
Damage to the inverter due to electrostatic discharge
•Touching electronic components can cause damage to or destroy the
inverter through electrostatic discharge.
Installation and Operating Instructions V02 45
9 Operation
The information provided here covers the LED indicators, control button, display messages, and the language and safety regulation settings.
9.1 Overview of the control panel
The inverter is equipped with a text display, three LEDs indicators and one control button.
Object
Description
A
Normal (Green LED)
B
Fault (Red LED)
C
Communication (Yellow LED)
D
Control button
E
Display
ABCED
46 Installation and Operating Instructions V02
9.1.1 Display
The display consist of 16 characters×2 lines. The bottom line always shows the current output (Pac = xxxx.xW). The top line shows the current state by default, it will switch to different running information by pressing the control button, as follows. For the ‛IP Addr“ item, the top line display ComBox IP addr(it will show
0.0.0.0 without integrated Combox ), and bottom line display state whether or not the inverter has connected to Solarcloud.
(1) If the inverter is connected with external communication devices (e.g. ZeverCom, ZeverManager,
or other 3rd party devices), please read the IP address on these devices. The inverter will always show the IP address and state of the integrated communication module only, i.e. if no ComBox integrated inside the inverter ‚0.0.0.0 Disconnected‘ accordingly.
Line 1
Running
information
E-today
Daily energy
E-total
Energy generated since the inverter has been installed
Vpv
DC input voltage
Ipv
DC input current
Vac
Grid voltage
Iac
Present output current
Frequency
Grid frequency
Model
Type name
Set Language
Selected language
Version
Firmware version
Serial No.
Serial number
IP Addr
ComBox IP addr
(1)
Line 2
Pac = xxxx.xW
Current output power
connect state
Connect solarcould or not
Installation and Operating Instructions V02 47
9.1.2 Control button
The inverter has a control button which is necessary to switch between the various displays for measured values and data, enter next entry and lock the expected information.
The display menus wrap around, which means that when you arrive at the last entry, the first entry is displayed when you press the button again.
You can freeze the display as follows: Press the button for 5s when it shows the information you desire, and do not release the button until you see ‛LOCK“. The display will show the selected information until you press the button again or the operating state of the inverter changes.
To save power, the backlight of the display turns off automatically after 10s. Press the button again to activate it.
9.1.3 LEDs
The inverter is equipped with three LED indicators ‛green“, ‛red“ and ‛yellow“ which provide information about the various operating states.
Green LED: The green LED is lit when the inverter is operating normally.
Yellow LED: The yellow LED flashes during communication with other devices e.g.
ZeverCom/ZeverManager, Solarlog etc. Also, the yellow LED flashes during updating firmware through RS485.
Red LED: The red LED is lit when the inverter has stopped feeding power into the grid due to a
fault. The corresponding error code will be shown on the display.
48 Installation and Operating Instructions V02
9.2 Display messages
Along with the various operating states, various messages may be shown on the display, as follows.
State
Error code
Description
Causes
Initializat­ion
Waiting
Initial PV voltage is between minimum DC input voltage and the start-up DC input voltage of the inverter.
Checking
The inverter is checking the feed-in conditions after the start-up PV voltage exceeds the initial DC input voltage of the inverter and that both the grid voltage and frequency are normal .
Reconnect
The inverter is checking feed-in conditions after the last fault has been solved.
Normal
Normal
The inverter is feeding energy into grid normally.
fault
1
SCI Fault
Communication between the master and slave CPU has failed.
2
EEPROM R/W
Fault
Reading or writing of EEPROM has failed.
3
Rly-Check Fault
Output relay has failed.
4
DC INJ. High
Output DC feed-in exceeds the permitted upper limit.
6
High DC Bus
The voltage of DC bus exceeds the permitted upper limit.
8
AC HCT Fault
Output current is abnormal
9
GFCI Fault
Ground fault detection circuit is abnormal
10
Device Fault
Unknown Error
33
Fac Fault
The grid frequency is outside the permitted range.
Installation and Operating Instructions V02 49
34
Vac Fault
The grid voltage is outside the permitted range.
fault
35
No Utility Grid
Available
The utility cannot be detected, which may be caused by no utility, grid disconnected, AC cables damaged, fuse broken or island mode.
36
Residual
current fault
The residual current exceeds the permitted upper limit.
37
PV
Overvoltage
The voltage of the strings exceeds the permitted upper limit.
38
ISO Fault
The PV array’s insulation resistance to
ground is below the permitted value, or the electrical insulation inside the inverter has failed.
40
Over Temp.
The internal temperature exceeds the permitted value.
41
Vac differs for
M-S
A different value of grid voltage has been detected by the master and slave MCU.
42
Fac differs for
M-S
A different value of grid frequency has been detected by the master and slave MCU.
43
Residual
current differs
for M-S
A different value of residual current has been detected by the master and slave MCU.
44
DC Inj. differs
for M-S
A different value of DC feed-in has been detected by the master and slave MCU.
45
Fac,Vac
differs for M-S
A different value of grid frequency and voltage has been detected by the master and slave MCU.
The last five failure reports on the network and system protection device can be read.
An interruption in the supply voltage of ≤ 3s does not result in any loss of failure
reports (according to VDE-AR-N 4105).
50 Installation and Operating Instructions V02
9.3 Language and safety regulation settings
Before setting, switch on the DC switch, and ensure that the AC circuit breaker is switched off and cannot be reactivated, while the inverter should be reliably grounded.
9.3.1 Language setting
The inverter provides two languages: English and German.
Press the button for approx. 5s at the entry of ‛Set Language“ to enter the language
menu and select the language. The display will switch to current state information automatically and the language setting will be saved at the same time unless you press the button again within approximately 10s.
9.3.2 Safety regulation setting
There is a safety regulation setting function in the inverter. You can choose different safety regulations according to the local requirements. If the inverters are installed in Germany or Australia, you don’t need to set the safety regulation again because the default setting is correct for these two countries. Set the safety regulation as described below: Step 1: Connect the inverter to the PV generator, switch on the DC switch; the LCD displays the following:
Step 2: Press the control key (see section 9.1.1) approx. once per second until the LCD display shows:
ZL ××××S Pac= 0.0W
Error Code: 35 Pac= 0.0W
Installation and Operating Instructions V02 51
Then press the control key for 10 seconds. The LCD will show the safety regulation as illustrated below: DE VDE-AR-N 4105 means the German safety regulation (VDE4105)
Step 3: Before the display goes out from above mentioned step 2, press the control key again once a second to scroll to the safety regulations you want. For example, if you want to choose the safety regulation for the Netherlands, press the control key until the display shows ‛NL NEN50438“ as below:
Wait about 10 seconds. When the display goes out, the safety regulation setting has completed.
Comment: 1 If the display shows ‛DEFAULT“, keep on pressing the control button until the
display shows the desired safety regulation.
2 To set other safety regulations, please refer to the example of setting the
Netherlands
NL NEN50438 Pac= 0.0 W
DE VDE-AR-N 4105
Pac= 0.0W
52 Installation and Operating Instructions V02
10 Technical Data
10.1 DC input data
Type
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
Max DC convertible power (@cosφ=1)
1150W
1750W
2350W
3150W
Max. input voltage
500V
600V
MPP voltage range
70-450V
70-520V
Rated input voltage
360V
Min. start voltage
80V
Min. feed-in power
6W
Max. input current
11A
Number of independent MPP inputs
1
Strings per MPP tracker
1
Installation and Operating Instructions V02 53
10.2 AC output data
Type
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
Rated active power
1000W
1500W
2000W
3000W
Max. apparent AC power
1100VA
1650VA
2200VA
3000 VA
Nominal AC voltage / range
220V,230V,240V / 180V-280V
AC power frequency / range
50,60 / ±5Hz
Max. output current
5.5A
7.5A
10A
15A
Power factor (@rated power)
1
Adjustable displacement power factor(only for VDE4105)
0.95
inductive
...1... 0.95
capacitive
Adjustable displacement power factor
0.8
inductive
...1... 0.8
capacitive
Feed-in phases / connection phases
1 / 1
Harmonic distortion (THD) at rated output
< 3%
54 Installation and Operating Instructions V02
10.3 General data
Type
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
communication1): RS485 / Ethernet / WiFi
/ /
Display
16 x 2 characters
Dimensions (W x H x D)
346 x 346 x 132mm
346 x 346
x 146mm
Weight
7Kg
7.5Kg
Cooling concept
convection
Noise emission (typical)
< 15 dB(A)@1m
Installation
indoor & outdoor
Mounting information
wall mounting bracket
DC connection technology
SUNCLIX
AC connection technology
screw clamp terminal
Operating temperature range
-25…+60 / -13…+140
Relative humidity (non-condensing)
0% ... 100%
Max. operating altitude
4000m(>3000m derating)
Degree of protection (according to IEC 60529)
IP65
Climatic category (according to IEC 60721-3-4)
4K4H
Topology
H5
Self-consumption (night)
<1W
Standby power
<6W
—Standard —Optional -N/A
1) ComBox (Ethernet or Ethernet & WIFI communication configuration ) is optional and retrofit in the inverter,once ComBox is activated, it will replace RS485 communication functionality.
Installation and Operating Instructions V02 55
10.4 Safety regulations
Type
Zeverlution
1000S
Zeverlution
1500S
Zeverlution
2000S
Zeverlution
3000S
DC switch
PV iso / Grid monitoring
/
DC reverse polarity protection / AC short- circuit current capability
/
Residual current monitoring(GFCI) function
Protection class (according to IEC 62103) / overvoltage category (according to IEC 60664-1)
I / II(DC), III(AC)
Internal overvoltage protection
Integrated
DC feed-in monitoring
Integrated
Islanding protection
Integrated
EMC immunity
EN61000-6-1, EN61000-6-2
EMC emission
EN61000-6-3, EN61000-6-4
Utility interference
EN61000-3-2, EN61000-3-3
—Standard —Optional -N/A
1) Detailed approvals and certificates are available from the ‘Certificate Overview’ of
download area at www.zeversolar.com.
56 Installation and Operating Instructions V02
Information for choosing the safety standard VDE-AR-N 4105
If a central network and system protection device is used for power
generation systems, the value of the rise-in-voltage protection U > of
1.1Un presented in the integrated network and system protection can be changed, but a password is required. It is not necessary to adjust the value of the displacement power factor cos(phi) if the power generation system is ΣSAmax Amax generation s set to 1 as default in the embedded inverter software. However, if the power generation system is 3.68KVA <ΣSAmaxded inverter software. cos(phi) characteristic curve defined in VDE-AR-N 4105 shall be applied through the ZeverCom/ZeverManager.
Installation and Operating Instructions V02 57
10.5 Efficiency
The operating efficiency is shown for the three input voltages (V
mppmax
, V
dc,r
and
V
mppmin
) graphically. In all cases the efficiency refers to the standardized power
output (Pac/P
ac,r
). (According to EN 50524 (VDE 0126-13): 2008-10, cl. 4.5.3). Notes: Values are based on rated grid voltage, cos(phi) = 1 and an ambient temperature of 25.
10.5.1 Efficiency curve Zeverlution 1000S
Max. efficiency, η
max
95.8%
European weighted efficiency, ηEU
94.4%
MPPT efficiency
99.50%
58 Installation and Operating Instructions V02
10.5.2 Efficiency curve Zeverlution 1500S
Max. efficiency, η
max
97.1%
European weighted efficiency, ηEU
96.4%
MPPT efficiency
99.50%
Installation and Operating Instructions V02 59
10.5.3 Efficiency curve Zeverlution 2000S
Max. efficiency, η
max
97.2%
European weighted efficiency, ηEU
96.6%
MPPT efficiency
99.50%
60 Installation and Operating Instructions V02
10.5.4 Efficiency curve Zeverlution 3000S
Max. efficiency, η
max
97.4%
European weighted efficiency, ηEU
97%
MPPT efficiency
99.50%
Installation and Operating Instructions V02 61
10.6 Power reduction
In order to ensure inverter operation under safe conditions ,the device may automatically decrease power output. Power reduction depends on many operating parameters including ambient temperature and input voltage, grid voltage, grid frequency and power available from the PV modules. This device can decrease power output during certain periods of the day according to these parameters. Notes: Values are based on rated grid voltage and cos (phi) = 1.
Power reduction with increased ambient temperature (Zeverlution 1000S)
Power reduction with increased ambient temperature (Zeverlution 1500S)
62 Installation and Operating Instructions V02
Power reduction with increased ambient temperature (Zeverlution 2000S)
Power reduction with increased ambient temperature (Zeverlution 3000S)
Installation and Operating Instructions V02 63
10.7 Tools and torque
Tools and torque required for installation and electrical connections.
Tools, model
Object
Torque
Torque screwdriver,
T25
Screws for the cover
2.2Nm Screw for second protective grounding connection
Screws for tightening the inverter and wall bracket
Flat-head screwdriver,
blade with 1×5.5mm
Screw terminal block for AC cable
1.2Nm
Flat-head screwdriver,
blade with 3.5mm
Sunclix DC connector Antenna
Hand-tight
Socket
wrench
Open end of 30
Swivel nut of M25 cable gland
Hand-tight
Open end of 24
Swivel nut of M20 cable gland
Hand-tight
Open end of 15
Swivel nut of sunclix connector
2.0Nm
Open end of 10
Hex bolts for wall bracket
Wire stripper
Peel cable jackets
Crimping tools
Crimp power cables
Hammer drill,
drill bit of Ø10
Drill holes on the wall
Rubber mallet
Hammer wall plugs into holes
Cable cutter
Cut power cables
Multimeter
Check electrical connection
Current clamp
Marker
Mark the positions of drill holes
ESD glove
Wear ESD glove when opening the inverter
Safety goggle
Wear safety goggle during drilling holes.
Anti-dust respirator
Wear anti-dust respirator during drilling holes.
64 Installation and Operating Instructions V02
11 Troubleshooting
When the PV power plant does not operate normally, fault information will be shown up on the display of the inverter and the red LED will be lit at the same time. We recommend the following actions for quick troubleshooting. The corresponding causes are described in section 9.2 ‛Display messages“.
Object
Error code
Corrective measures
Presumable Fault
6
Check the open-circuit voltages of the strings and make sure it is below the maximum DC input voltage of the inverter.
If the input voltage is within the permitted range and the fault still occurs, it might be that the internal circuit has broken. Contact the service.
33
• Check the grid frequency and observe how often
major fluctuations occur. If this fault is caused by frequent fluctuations, try to modify the operating parameters after informing the grid operator first.
34
•Check the grid voltage and grid connection on inverter.
• Check the grid voltage at the point of connection of
inverter. If the grid voltage is outside the permissible range due to local grid conditions, try to modify the values of the monitored operational limits after informing the electric utility company first. If the grid voltage lies within the permitted range and this fault still occurs, please call service.
35
• Check the fuse and the triggering of the circuit breaker
in the distribution box.
• Check the grid voltage, grid usability.
• Check the AC cable, grid connection on the inverter.
If this fault is still being shown, contact the service.
Installation and Operating Instructions V02 65
Presumable Fault
36
• Make sure the grounding connection of the inverter is
reliable.
•Make a visual inspection of all PV cables and modules. If this fault is still shown, contact the service.
37
• Check the open-circuit voltages of the strings and make sure it is below the maximum DC input voltage of the inverter. If the input voltage lies within the permitted range and the fault still occurs, please call service.
38
•Check the PV array’s insulation to ground and make
sure that the insulation resistance to ground is greater than 1 MOhm. Otherwise, make a visual inspection of all PV cables and modules.
• Make sure the grounding connection of the inverter is
reliable. If this fault occurs often, contact the service.
40
•Check whether the airflow to the heat sink is
obstructed.
•Check whether the ambient temperature around the inverter is too high.
41, 42
43, 44
45
• Disconnect the inverter from the grid and the PV
arrays, reconnect them after 3 minutes. If this fault is still being shown, contact the service.
Permanent Fault
1, 2,3, 4,5,6, 8,9
Disconnect the inverter from the utility grid and the PV arrays, reconnect them after display and LED turn off. If this fault is still being displayed, contact the service.
Contact the Zeversolar service if you meet other problems not in the above table.
66 Installation and Operating Instructions V02
12 Maintenance
Normally, the inverter needs no maintenance or calibration. Regularly inspect the inverter and the cables for visible damage. Disconnect the inverter from all power sources before cleaning. Clean the housing, cover and display with a soft cloth. Ensure the heat sink at the rear of the inverter is not covered.
12.1 Cleaning the contacts of the DC switch
Clean the contacts of the DC switch annually. Perform cleaning by cycling the switch to “ and “ positions 5 times. The DC switch is located at the lower left of the housing.
12.2 Cleaning the heat sink
Clean the heat sink with compressed air or a soft brush. Do not use aggressive chemicals, cleaning solvents or strong detergents.
For proper function and long service life, ensure free air circulation around the heat sink.
Risk of injury due to hot heat sink
• The heat sink may exceed 70℃ during operation. Do not touch the
heat sink during operation.
• Wait approx. 30 minutes before cleaning until the heat sink has
cooled down.
• Ground yourself before touching any component.
Installation and Operating Instructions V02 67
13 Recycling and disposal
Dispose of the packaging and replaced parts according to the rules applicable in the country where the device is installed. Do not dispose the inverter with normal domestic waste.
14 Warranty
The factory warranty card is enclosed with the package, please keep well the factory warranty card. Warranty terms and conditions can be downloaded at www.zeversolar.com/service/warranty/ if required. When the customer needs warranty service during the warranty period, the customer must provide a copy of the invoice, factory warranty card, and ensure the type label of the inverter is legible. If these conditions are not met, Zeversolar has the right to refuse to provide with the relevant warranty service.
WEEE designation
Do not dispose of the product together with the household waste but in accordance with the disposal regulations for electronic waste applicable at the installation site.
68 Installation and Operating Instructions V02
15 Contact
If you have any technical problems concerning our products, please contact zeversolar service. We require the following information in order to provide you with the necessary assistance:
Inverter device type
• Inverter serial number
• Type and number of connected PV modules
• Error code
• Mounting location
• Warranty card
Zeversolar Factory Warranty Warranty card will be shipped with inverter. The warranty terms are available for download on www.zeversolar.com.
Zeversolar Service Contact Our regional service contact information can be found at : https://www.zeversolar.com/service/customer-interaction-center/
Jiangsu Zeversolar New Energy Co., Ltd.
Tel.: +86 512 6937 0998 Fax: +86 512 6937 3159 Web: www.zeversolar.com Factory add.: No.588 Gangxing Road, Yangzhong Jiangsu, China Headquarters add.: Building 9, No.198 Xiangyang Road, Suzhou 215011, China
Loading...