Zephyr AK7748AS Maintance Manual

Airflow Control Technology
TM
Titan Island
AK7736AS AK7742AS AK7748AS
www.zephyronline.com
Model number:
Serial Number:
SEP19.0101 © Zephyr Ventilation, LLC
Use, Care, and Installation Guide
www.zephyronline.com
SAFETY NOTICE ................................................................. 2-3
LIST OF MATERIALS ....................................................... 4
INSTALLATION
Ducting Calculation Sheet Mounting Height & Clearance Ducting Options
........................................................... 7
Hood Specications
Mounting the Hood PBD-1300A Dual Blower Ducting
FEATURES & CONTROLS
Electronic LCD Controls ................................. 13
Optional Remote Control................................ 14
MAINTENANCE
Cleaning, Filter Removal & Lights
TROUBLESHOOTING
ACT™ CONVERSION
WIRING DIAGRAMS
................................................................ 16
................................................................ 17
................................................................... 18
....................................... 5
................................ 6
................................................... 8
..................................................... 9-11
......................... 12
Table of Contents
....................... 15
LIST OF PARTS AND ACCESSORIES
WARRANTY
PRODUCT REGISTRATION
.................................................................................... 20
.................................................... 21
.............................. 19
1
READ AND SAVE THESE INSTRUCTIONS
www.zephyronline.com
WARNING
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT USE THIS FAN WITH ANY SOLID-STATE CONTROL DEVICE.
WARNING
TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a. Use this unit only in the manner intended by the manufacturer, if you have questions, contact the manufacturer.
b. Before servicing or cleaning unit, switch power o󰀨 at service panel and lock panel to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
CAUTION
For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors. Take care when using cleaning agents or detergents. Suitable for use in household cooking area.
WARNING
TO REDUCE THE RISK OF RANGE TOP GREASE FIRE:
a. Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on
low or medium settings.
b. Always turn hood ON when cooking at high heat or when aming food c. Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or lter. d. Use proper pan size. Always use cookware appropriate for the size of the surface element.
Important Safety Notice
e. Keep fan, lters and grease laden surfaces clean.
f. Use high setting on hood only when necessary.
g. Don’t leave hood unattended when cooking. h. Always use cookware and utensils appropriate for the type of and amount of food being prepared.
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE, OBSERVE THE FOLLOWING:
a. SMOTHER FLAMES with a close-tting lid, cookie sheet, or metal tray, then turn o󰀨 the burner. BE CAREFUL TO PREVENT BURNS.
If the ames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
b. NEVER PICK UP A FLAMING PAN – You may be burned. c. DO NOT USE WATER, including wet dishcloths or towels – a violent steam explosion will result. d. Use an extinguisher ONLY if:
1. You know you have a Class ABC extinguisher, and you already know how to operate it.
2. The re is small and contained in the area where it started.
3. The re department is being called.
4. You can ght the re with your back to an exit
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a. Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable codes and standards. Including
re-rated construction.
b. Su󰀩cient air is needed for power combustion and exhausting of gases through the ue (chimney) of fuel burning equipment to prevent
back-drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA) and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and the
local code authorities. c. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. d. Ducted fans must always vent to the outdoors. e. NEVER place a switch where it can be reached from a tub or shower.
f. Make sure the power is o󰀨 before installing, wiring or maintenancing.
WARNING
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
CAUTION
To reduce risk of re and to properly exhaust air outside - Do not vent exhaust air into spaces within walls, ceilings,
attics, crawl spaces or garages. Not for use over an outdoor grill.
2
OPERATION
Always leave safety grilles and lters in place. Without these components, operating blowers could catch onto hair, ngers and loose
clothing.
The manufacturer declines all responsibility in the event of failure to observe the instructions given here for installation, maintenance and suitable use of the product. The manufacturer further declines all responsibility for injury due to negligence and the warranty of the unit automatically expires due to improper maintenance.
*NOTE: Please check www.zephyronline.com for revisions before doing any custom work.
ELECTRICAL REQUIREMENTS
Important:
Observe all governing codes and ordinances.
It is the customer’s responsibility:
- To contact a qualied electrical installer.
- To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 latest edition* or CSA standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No.0-M91 - latest edition** and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrician determine that the ground path is
adequate.
Do not ground to a gas pipe.
Check with a qualied electrician if you are not sure the range hood is properly grounded.
Do not have a fuse in the neutral or ground circuit.
*National Fire Protection Association Batterymarch Park, Quincy, Massachusetts 02269 ** CSA International 8501 East Pleasant Valley Road, Cleveland, Ohio 44131-5575
This appliance requires a 120V 60Hz electrical supply and connected to an individual properly grounded branch circuit protected by
a 15 or 20 ampere circuit breaker or time delay fuse. Wiring must be 2 wire with ground. Please also refer to Electrical Diagram on
product.
A cable locking connector (not supplied) might also be required by local codes. Check with local requirements, purchase and install
appropriate connector if necessary.
AK7736AS, AK7742AS - 286 Watts, 4 Amps
AK7748AS - 299 Watts, 4.2 Amps
Power consumption shown above is the default power specs. Hoods with Zephyr’s proprietary Airow Control Technology (ACT)
enabled will consume less power. See wiring diagram at the end of this manual for more information.
FEDERAL COMMUNICATION COMMISSION INTERFACE STATEMENT
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment o󰀨 and on, the user is encouraged to try to correct the interference by one of the following measures:
. Reorient or relocate the receiving antenna.
. Increase the separation between the equipment and receiver.
. Connect the equipment into an outlet on a circuit di󰀨erent from that to which the receiver is connected.
. Consult the dealer or an experienced radio/TV technician for help
Important Safety Notice
Prop. 65 Warning for California Residents
WARNING:
Cancer and Reproductive Harm - www.P65Warnings.ca.gov
3
www.zephyronline.com
www.zephyronline.com
www.zephyronline.com
MODELS: AK7736AS, AK7742AS, AK7748AS
PARTS SUPPLIED
1 - Hood 4 - Duct covers, 2 upper & 2 lower 2 - Support frames, 1 upper & 1 lower 2- Angled support brackets 1- Middle support frame 4 - Baffle filters, AK7736AS & AK7742AS 6 - Baffle filters, AK7748AS
List of Materials
2 - LED light bulbs, AK7736AS & AK7742AS 4 - LED light bulbs, AK7748AS 1 - 8 in. round starting collar (for single blower ducting) 1 - Paper ceiling template 1 - Hardware package
6# x 1” (6) 6# x 1-1/2” (6) 6# x 2” (6)
6# x 1” (4)
6# x 1-1/2” (4) 6# x 2” (4)
M4 x 8 (6)
M4 x 8 (14)
M4 x 8 (12) 3/16*7/8 (4)
M4 x 10 (16) 3/16*7/8 (4)
5x24mm Washers (6)Wire Caps(3)
* M4 x 8 (12) screws are pre-installed into the support frame
PARTS NOT SUPPLIED
- Ducting, conduit and all installation tools
- Cable connector (if required by local codes)
- Duct cover extension accessory (Z1C-0077 - 36”, 42”)
- Duct cover extension accessory (Z1C-0177 - 48”)
- Dual blower kit (PBD-1300A)
(1) M4 x 12
safety screw
Light Bulb Removal Suction Cup (1)
3/16 x 1/4” (4)
4
4
4
Duct pieces
3- 1/4” x 10” Rect., straight
6”, 7”, 8”, 10” Round, straight
3- 1/4” x 10”
0
Rect. 90 elbow
3- 1/4” x 10”
0
Rect. 45 elbow
3- 1/4” x 10”
0
Rect. 90 flat elbow
7” to 6” or 8” to 7” Round tapered reducer
6”, 7“, 8” Round in-line damper
6”, 7”, 8”, 10” Round,
0
90
elbow
6”, 7”, 8”, 10” Round,
0
45
elbow
Equivalent number length x used =
1 Ft. x ( ) =
1 Ft. x ( ) =
15 Ft. x ( ) =
9 Ft. x ( ) =
24 Ft. x ( ) =
25 Ft. x ( ) =
15
Ft. x ( ) =
15 Ft.
x ( ) =
9 Ft. x ( ) =
Subtotal column 1 =
To tal
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Duct pieces
3- 1/4” x 10” Rect. to 6” round transition
3- 1/4” x 10” Rect. to 6” round transition
0
elbow
90
6” round to 3- 1/4” x 10” rect. transition
6” round to 3- 1/4” x 10” rect. transition
0
90
elbow
7” round to 3 1/ 4” x 10” rect. transition
7” round to 3- 1/4” x 10” rect. transition
0
elbow
90
3- 1/4” x 10” Rect. wall cap with damper
6”, 7”, 8”, 10” Round, wall cap with damper
6”, 7”, 8”, 10” Round roof cap
Equivalent number length x used =
5 Ft. x ( ) =
20 Ft. x ( ) =
1 Ft. x ( ) =
16 Ft. x ( ) =
8 Ft. x ( ) =
23 Ft. x ( ) =
30 Ft. x ( ) =
30 Ft. x ( ) =
30 Ft. x ( ) =
To tal
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Installation – Ducting Calculation Sheet
Maximum Duct Length: For satisfactory air movement,
the total duct length
should not exceed 100 equivalent feet.
Subtotal column 2 =
Subtotal column 1 =
Total ductwork =
Ft.
Ft.
Ft.
5
www.zephyronline.com
min. A max. B
Standard Extension
Hood Heights Duct Cover Duct Cover
minimum ducted (A) 33” 49“ maximum (B) 50” 78”
Ceiling Heights
minimum ducted (C) 93” (7’ 9”) 109“ (9’ 1”) maximum (D) 122” (10’ 2“) 148” (12’ 4”)
36”
24” min. 36” max.
min. C max. D
ALWAYS, when possible, reduce the number or transitions and turns. If long duct run is required, increase duct size.
If turns or transitions are required; install as far away from hood duct output and as far apart, between the two as possible.
Minimum mount height between range top to hood bottom should be no less than 24”.
Maximum mount height should be no higher than 36”.
It is important to install the hood at the proper mounting height. Hoods mounted too low could
result in heat damage and re hazard; while hoods
mounted too high will be hard to reach and will
lose its performance and e󰀩ciency.
If available, also refer range manufacturer’s height clearance requirements and recommended hood mounting height above range.
Installation – Mounting Height & Clearance
A minimum of 8” round duct must be used to
DUCTING
maintain maximum air ow e󰀩ciency for single
internal blower and 10” round duct for dual internal blower.
Always use rigid type metal ducts only. Flexible
ducts could restrict air ow by up to 50%.
Also use calculation (on page 5) to compute total
available duct run when using elbows, transitions and caps.
SHIPMENT / INSTALLATION:
• Please fully inspect unit for damage before installation.
• If the unit is damaged in shipment, return the unit to the store in which it was bought for repair or replacement.
• If the unit is damaged by the customer, repair or replacement is the responsibility of the customer.
• If the unit is damaged by the installer (if other than the customer), repair of replacement must
be made by arrangement between customer and installer.
6
WARNING FIRE HAZARD
side wall cap w/ gravity damper
Soffit or crawl space
Roof Pitch w/ Flashing & Cap
NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling, attics or garages. All exhaust must be ducted to the outside.
Use rigid metal ductwork only.
Fasten all connections with sheet metal screws and tape all joints with certied Aluminum Tape or Duct Tape.
Some Ducting Options
Installation – Ducting Options
7
www.zephyronline.com
4”
16 1/4
Standard Min. - 33” Max. - 50“
15/16(36”, 42“)
17
21
5/8” (48”)
27 15/16
3 5/16
5/16
14
Z1C-0077 (36”, 42“) Z1C-0177 (48”) Min. - 49” Max. - 78”
35 15/16” (36”)
15/16” (42”)
41 47
15/16” (48”)
FRONT
Installation – Hood Specications
18” (36”)
20
15/16” (42”)
23
15/16” (48”)
C/L
C/L
7/8
7
14 9/16
1
1/8
6
31 5/8
SIDE
13 1/4” (36”, 42“)
16
15/16” (48”)
15/16(36”, 42“)
8
3/4” (48”)
Front Side
6
5/16(36”, 42“)
8
3/16” (48”)
2 3/16
7/16
11
TOP of HOOD
TOP SUPPORT FRAME
(top view)
8
1
2
Ceiling Joists
Wood Blocking
Top Support Frame
Support Frame Arm
Bottom Support Frame
Hood Body
3
Mounting Screws (pre-installed)
4
CAUTION: At least two installers are
required hood.
!
XP022220
A
B
Cut-Out Shaded Area
due to the weight and size of the
FRONT
FIG. B
FIG. A
1. Determine mounting location on ceiling and temporarily tape paper template (included with the hood) to
the ceiling. Cut out internal shaded area of template to allow the ducting and electrical to pass through.
If necessary, add wood blocking (min. 2” x 4”) to ceiling joists located behind the drywall to reinforce the mounting location*. (FIG. A1) Secure (2) M6 x 2” wood screws with washers to points A and B of the paper template (FIG. B). Do not completely tighten screws, leave approx. 1/4” exposed.
2. Remove screws securing top and bottom support frames together. Adjust support frame to accomodate the
desired hood height and re-assemble the frame using the previously removed screws (4 screws for each support frame arm). (FIG. A3)
*Hood is intended to be mounted to a nished ceiling.
9
Installation – Mounting the Hood
Duct Cover Standard Frame
Assembly Instructions
1.
2.
1/2
bottomtop
3.
Top Support Frame
Front
www.zephyronline.com
Side
Installation – Mounting the Hood
3. Attach square support bracket inside the support frame assembly. The placement of the square support bracket should preferably be aligned in the middle where the top and bottom frame intersect (FIG. C1) Install (8) M4 x 8 screws to secure the square support bracket onto the frame. Mount diagonal support brackets onto the support frame assembly facing away from each other in a crossed formation (FIG. C2). The diagonal support brackets have a ledge on the side. During installation, mount the diagonal support brackets with the ledge facing inwards to the unit (FIG C3). Install (4) M4 x 8 screws to secure the diagonal support brackets onto the frame.
4. Lift support frame assembly up to the ceiling making sure the word “front” on the top support frame faces the front of the hood where the controls will be located (FIG. D). The key holes on the top support frame should cover the wood screws previously installed in the ceiling. Slide support frame towards narrow end of key holes to lock the frame in place. Install the last (4) M6 x 2” wood screws with washers into the four remaining holes of the top support frame to secure it to the ceiling. (2) M6 x 2” wood screws with washers are installed on the corners and the other (2) M6 x 2” wood screws are installed on the front and rear long sides of the support bracket (FIG. D). Tighten all screws.
5. Install the (4) 3/16 x 7/8 mounting screws on the top four corners of the unit body (FIG. A4). Lift hood and align the mounting screws with the (4) key holes on the Bottom of Support Frame (FIG. E). Slide hood towards the narrow end of key holes to lock into place. Hand tighten each of the (4) screws with a screwdriver to secure hood to Bottom Support Frame. Further secure bottom support frame to unit body by one M4 x 12 safety screw (FIG. F).
FIG. C
FIG. D
FIG. F
Bottom Support Frame
(secures to top of blower housing)
back
Key Holes
front - facing controls
FIG. E
10
Top Support Frame
Bottom Support Fram
Cable Lock
Front
Side
WARNING: Electrical wiring must be done by a qualified person(s) in
accordance
be
properly
.
!
1
Cable Lock
Top Duct Covers
A cable locking connector (not supplied) might be required by local codes. Check with local
requirements and codes, purchase and install appropriate connector if necessary.
Bottom Duct Covers
e
FIG. G
with all applicable codes and standards. This range hood must
grounded. Turn off electrical power at service entrance before wiring
6. Remove tape securing electronics mounting bracket to hood and reposition electronics mounting bracket with (2) M4 x 8 screws (FIG. G). Install electrical and duct work. A cable lock, not supplied, might be required by local codes (FIG. G). Seal duct work with aluminum duct tape.
7. Power up hood, verify all functions and check for leaks around duct tape.
8. Assemble Top Duct Covers (with louver holes) together over Top Support Frame, secure Top Duct Covers
together by magnetic strips.
9. Secure Top Duct Covers to Top Support Frame by using (4) 3/16 x 1/4” screws (2 screws for each Top Duct Cover). (FIG. H).
10. Assemble Bottom Duct Covers together over Top Duct Covers and secure together by magnetic strips. Bottom Duct Covers should rest on top of the Hood Body.
FIG. H
Installation – Mounting the Hood
11
www.zephyronline.com
This range hood is equipped standard with a single blower vertical duct option. To convert from single blower vertical ducting to dual blower vertical ducting please following the instructions below.
1. Disconnect blower plug and white and black
power cables.
3. Remove (4) screws attaching single blower to
single blower plate.
Installation – PBD-1300A Dual Blower Ducting
2. Remove (4) screws from interior of hood body
attaching single blower plate to top of hood body. Remove single blower and single blower plate.
4. Attach single blower to dual blower plate by (4)
previously removed screws from step 3.
5. Position dual blower inside hood body as
shown. Be sure to tuck dual blower plate into blower plate tabs. Secure dual blower by (4)
screws previously removed from step 2.
6. Attach 10” round blower collar to top of hood
body by (4) M4 x 8 screws. Connect blower
wire extension cable to new blower and connect plugs from each blower to female plugs behind
12
switch panel.
Loading...
+ 32 hidden pages