1600W Power Supplies and Battery Chargers
ZAT1600 SERIES
TASHEET
/ OPERATING INSTRUCTIONS
Wide output adjustment range 0…72VDC
Analog control by external 0-5VDC voltage
Temp.comp charging, sense as on option
Power fail relay alarm
Master-Slave connection
Analog control
modular connector
Microprocessor controlled charging curves for all kind of
batteries
Master-Slave
connection

©We reserve the right to change the specification without
zentro-elektrik
GmbH KG | Tel.: +49
(0)
72 32 / 3131 0 | Fax: +49
(0)
72 32 / 3131 399 | E-mail: info@zentro-elektrik.de
DATASHEET
/ OPERATING INSTRUCTIONS
POWER SUPPLIES AND BATTERY CHARGERS, TRIMMER ADJUSTABLE
Installation / dimensions
(Width x Height x Depth, mm)
ANALOG CONTROLLABLE MODELS BY EXTERNAL 0-5VDC VOLTAGE
Installation /
dimensions
(Width x Height x Depth, mm)
BATTERY CHARGERS WITH TEMPERATURE COMPENSATION
Output
voltage
factory setting
Programmed
output voltages
(see table)
Output
current
(see table)
Installation /
dimensions
(Width x Height x Depth, mm)
*) Cable sets with modular connectors are included in packing: 1.5m cable set for analog control and 2.5m for or temp.comp models
**) Reduced power 55…200VAC or 78…200VDC, see curves at next page
MODELS WITH POWER FAIL RELAY ALARM (24V models as a type number example)
Trimmer adjustable model with power fail relay alarm
Analog controllable model with power fail relay alarm
Analog 1.5m + relay cables 1.5m
Temp.comp model with Power fail relay alarm
Temp.comp 2.5m + relay cables 1.5m
MASTER-SLAVE CONNECTION (24V models as a type number example)
ZAT1600/24/60 or ZAT1600/24/60 AI or ZAT1600/27,4/60 T
Control to slave via RS-232 bus
ZAT1600/24/60 S RS-232 control bus in and out
ZAT1600/24/60 SH slave unit with relay, RS-232 bus in only
Cable set for master slave connection is included in slave unit type number, length 0.6m modular connectors in both ends
***) Master unit or slave with RS-232 bus output can not include the relay alarm
CUSTOMISED VERSIONS ON
•
Cyclic battery chargers or customzed charging curves for all kind of batteries
•
Sense models
•
Customised mechanics

©We reserve the right to change the specification without
zentro-elektrik
GmbH KG | Tel.: +49
(0)
72 32 / 3131 0 | Fax: +49
(0)
72 32 / 3131 399 | E-mail: info@zentro-elektrik.de
Three color LED, red-yellow-green
EN55022B, EN50081-1, EN50082-2
267 x 135 x 85 mm with rubber ends
1,9kg without output cables
Temperature controlled fan
Operating temperature range
+40…+ 70ºC, see curve below
DATASHEET
/ OPERATING INSTRUCTIONS
TECHNICAL DATA
Input voltage 50…260 VAC (50…200VAC reduced power, see curve below)
50…340 VDC (50…200VDC reduced power)
Input current 9 A
Power factor >0.99
Efficiency (230VAC, 10…100% load) > 88%
Inrush current <30A, cold start
Line regulation 0.01%
Load regulation 0.2V
Output setting accuracy ± 0.1%
Output ripple (f > 50Hz) <30mVrms
Hold up time > 5ms
Nominal output voltage / current characteristics 1600W models
Output power / input voltage derating curve