Zennio KLIC-TS User Manual

KNX – AB Gateway for
Toshiba AC Units
USER MANUAL
ZCL-TS
Application program version: [1.0]
User manual edition: [1.0]_a
www.zennio.com
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
2
CONTENTS
Contents ........................................................................................................................................ 2
1 Introduction .......................................................................................................................... 3
1.1 KLIC-TS .............................................................................................................................. 3
1.2 Installation ........................................................................................................................ 4
1.3 Start-Up and Power Loss .................................................................................................. 5
2 Configuration......................................................................................................................... 6
2.1 General ............................................................................................................................. 6
2.2 Inputs ............................................................................................................................... 8
2.2.1 Binary Input .............................................................................................................. 8
2.2.2 Temperature Probe .................................................................................................. 8
2.2.3 Motion Detector ...................................................................................................... 9
2.3 Logic Functions ............................................................................................................... 10
2.4 A/C Gateway .................................................................................................................. 11
2.4.1 Configuration ......................................................................................................... 11
2.4.2 Initial Configuration ............................................................................................... 21
2.4.3 Scenes .................................................................................................................... 22
2.4.4 Error Handling ........................................................................................................ 24
ANNEX I. Communication Objects............................................................................................... 26
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
3
1 INTRODUCTION
1.1 KLIC-TS
KLIC-TS from Zennio is a gateway that provides full-duplex communication between the KNX home automation system and Toshiba air-conditioning systems through connection wires provided by the latter.
Because of this bidirectional communication, the air conditioning system can be controlled from the home automation system in the same manner as it is through its own controls. Moreover, the actual status of the unit can be monitored and periodically sent to the KNX bus to inform other devices.
The most outstanding features of KLIC-TS are:
Bidirectional control of Toshiba A/C units through the connection wires AB
provided by Toshiba (15 VDC).
Control of the main functions of the A/C unit: On/Off, temperature, mode of
operation, fan speed, position of the flaps, etc.
Error management to handle specific error codes from the A/C unit itself as
well as any communication issues that may arise.
Up to five scenes.
Three analogue-digital inputs, for the connection of temperature probes,
motion detectors or binary pushbuttons or switches.
10 customisable, multi-operation logic functions.
Heartbeat or periodical “still-alive” notification.
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
4
1.2 INSTALLATION
Figure 1. Element scheme.
KLIC-TS connects to the KNX bus via the corresponding built-in terminal (5). Once the device is provided with power from the KNX bus, both the physical address and the KLIC­TS application program can be downloaded.
This device does not need any external power as it is entirely powered through the KNX bus.
The remaining elements are described next.
Prog./Test button (2): a short press on this button will set the device into the
programming mode, making the associated LED (1) light in red.
Note: if this button is held while plugging the device into the KNX bus, the device will enter into safe mode. The LED will blink in red every 0.5 seconds
Analogue-Digital Inputs (3): input ports for the stripped cables of external
elements such as switches, motion detectors, temperature probes, etc.
Terminal connection, AB (4): wires that will connect KLIC-TS to the A/C unit.
The other end of the cable, therefore, is intended to be connected to the corresponding connectors in the PCB board of the internal unit.
Figure 2. Connecting KLIC-TS to the A/C unit.
1. Prog./Test LED indicator
2. Prog./Test button
3. Analogue/digital inputs
4. Terminal connection RWB.
5. KNX connector
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
5
Important: if intending to control the A/C unit both through its incorporated wired remote control and through KLIC-TS, it must be taken into account that orders sent from the wired control will have a higher priority than those sent through KLIC-TS. In addition, certain parameterisations made in the device can be ignored.
For detailed information about the technical features of KLIC-TS, as well as on security and installation procedures, please refer to the device Datasheet, bundled in the device packaging and also available at http://www.zennio.com.
1.3 START-UP AND POWER LOSS
Depending on the configuration, some specific actions will be performed during the device start-up. The integrator may set up an initial status to be sent to the A/C unit after the bus power recovery, and whether certain objects should be sent to the bus after the power recovery, as described in later sections.
On the other hand, when a bus power failure takes place, the device will interrupt any pending actions, and will save its state so it can be recovered once the power supply is restored.
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
6
2 CONFIGURATION
2.1 GENERAL
The general configuration of the device consists in enabling the specific functionalities that will be required during normal operation:
Heartbeat or periodical “still-alive” notification.
Inputs: see section 2.2.
Logic functions: see section 2.3
A/C gateway: see section 2.4.
The latter entails all functions specific to KLIC-TS, i.e., all the functions related to interfacing with the A/C unit and to the management of the climate control system.
ETS PARAMETERISATION
After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by right-clicking into the device and selecting Edit parameters
The General screen is shown in the first place, containing the following parameters:
Enabling Inputs, Logic Functions and A/C Gateway brings additional tabs
into the menu on the left. These functions and their parameters will be explained in later sections of this document. Please note that A/C Gateway is permanently enabled.
Figure 3. General.
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
7
Heartbeat (Periodical Alive Notification): this parameter lets the integrator
incorporate a 1-Bit object to the project (“[Heartbeat] Object to Send ‘1’”) that will be sent periodically with value “1” to notify that the device is still working (still alive).
Note: The first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings match the period set.
Regardless of the above parameters, the following objects are available by default:
[AC] On/Off” and “[AC] On/Off (Status)”: allow switching on (value “1”) and
off (value “0”) the A/C unit or reading the current status, respectively.
[AC] Temperature Setpoint” and “[AC] Temperature Setpoint (Status)”:
allow setting the desired temperature setpoint or reading the current value, respectively. See section 2.4.1 for further options.
[AC] Reference Temperature (Status): allows receiving values of
temperature that the A/C unit are taken in account in order to execute the control of temperature. See section 2.4.1 for further options.
[AC] Mode” and “[AC] Mode (Status)”: allow setting the desired operation
mode (either Automatic, Heating, Cooling, Fan or Dry) or reading the current mode, respectively. See section 2.4.1 for further options.
[AC] Speed: Percentage Control” and “[AC] Speed: Percentage Control
(Status)”: allow establishing desired fan speed. See section 2.4.1 for further options.
Several error objects. See section 2.4.4.
[AC] Operating Time”: allow reading operating hours of the A/C unit. See
section 2.4.1 for further options.
Figure 4 Heartbeat.
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
8
2.2 INPUTS
KLIC-TS incorporates three analogue/digital inputs, each configurable as a:
Binary Input, for the connection of a pushbutton or a switch/sensor.
Temperature Probe, for the connection of a temperature from Zennio.
Motion Detector, for the connection of a motion detector (models ZN1IO-
DETEC-P and ZN1IO-DETEC-X from Zennio).
Important: older models of the Zennio motion detector (e.g., ZN1IO-DETEC and ZN1IO-DETEC-N) will not work properly with KLIC-TS.
ETS PARAMETERISATION
When Inputs has been activated in the General parameters screen, the following drop­down lists will be available for the selection of the specific functions required.
All inputs are disabled by default. Depending on the function selected for each input, additional tabs will be included in the menu on the left.
2.2.1 BINARY INPUT
Please refer to the “Binary Inputs user manual, available in the KLIC-TS product section, at the Zennio website (www.zennio.com).
2.2.2 TEMPERATURE PROBE
Please refer to the “Temperature Probe” user manual, available in the KLIC-TS product section, at the Zennio website (www.zennio.com).
Figure 5. Inputs. Configuration.
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
9
2.2.3 MOTION DETECTOR
It is possible to connect motion detectors (models ZN1IO-DETEC-P and ZN1IO-DETEC- X from Zennio) to the input ports of KLIC-TS.
Please refer to the “Motion Detector user manual, available in the KLIC-TS product section, at the Zennio website (www.zennio.com).
Notes:
The ZN1IO-DETEC-P motion detector is compatible with a variety of Zennio
devices. However, depending on the device it is actually being connected to, the functionality may differ slightly. Therefore, please refer specifically to the corresponding product section to obtain the aforementioned document.
Motion detectors with references ZN1IO-DETEC and ZN1IO-DETEC-N are not
compatible with KLIC-TS (may report inaccurate measurements if connected
to this device).
When connected to KLIC-TS, the rear micro-switch of model ZN1IO-DETEC-P
should be set to position Type B”.
KLIC-TS
http://www.zennio.com Technical Support: http://support.zennio.com
10
2.3 LOGIC FUNCTIONS
This module makes it possible to perform numeric and binary operations with incoming values received from the KNX bus, and to send the results through other communication objects specifically enabled for this purpose.
KLIC-TS can implement up to 10 different and independent functions, each of them entirely customisable and consisting in up to 4 consecutive operations each.
The execution of each function can depend on a configurable condition, which will be evaluated every time the function is triggered through specific, parameterisable communication objects. The result after executing the operations of the function can also be evaluated according to certain conditions and afterwards sent (or not) to the KNX bus, which can be done every time the function is executed, periodically or only when the result differs from the last one.
Please refer to the Logic Functions user manual (available in the KLIC-TS product section at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
Loading...
+ 23 hidden pages