2.2 AC GATEWAY
2.2.1 CONFIGURATION
KLIC-DD v3 allows controlling and monitoring an air-conditioning unit in the same way it
would be through the wired remote control it is provided with.
Through the KNX bus, KLIC-DD v3 can be sent orders to control the following basic
functions of the air conditioning unit:
On/Off switch of the air-conditioning unit.
Operation mode: automatic, heating, cooling, fan and dry.
Temperature setpoint, which can be modified within a specific range of
values, depending on the capabilities of the specific A/C unit being controlled.
Fan speed: 5 levels and automatic mode.
Flaps swing: vertical flaps, horizontal flaps or both types depending on A/C
unit.
Moreover, KLIC-DD v3 allows configuring several advanced functions:
Temperature measured by the AC unit: allows enabling an object which
provides the value of the internal temperature probe. The automatic sending
can be configured based on: a period of time, a change in value or a
combination of both.
Setpoint limits, to restrict the range for the temperature setpoint.
External reference temperature: which allows enabling an object to use an
external reference temperature, provided by a temperature probe.
Humidity: allows enabling six objects for the humidity control function. The
availability of humidity control depends on A/C unit model.
Automatic off, which allows an automatic and temporary switch-off of the unit
(after a pre-established delay, if desired) when the communication object
associated to this function is triggered due to a certain event.