Zander Aachen ENS20 Operating Instructions

R
R
Digital Timer/Counter ENS20
Correct Use
Features
Function
ENS20 is a compact, in all usual functions and time ranges simply programmable digital timer/counter. By use of a tight-fitting keyboard the front of the equipment is protected against splash­water completely. Therefore ENS20 is suitable ideally for the employment at bakery machines, machine tools, manufacturing automats etc..
Front protection IP65 Simple programming by integrated keyboard 7 programmable time ranges 0.01 s - 999 h All usual functions programmable Only 48 x 48 mm front size
Timing begins either with the programmed time value
(preselection) and ends at zero or it begins with zero and
ends at the preselected value. Stop, resetting as well as adjusting new parameters during the timing operation are possible.
Keyboard function during timing/counting
The keyboard disabling (LOCK) is activated, if the keys "<" and "R" are pressed while connecting the supply voltage. By this the keyboard can be blocked against inadvertent adjusting in critical applications. Deactivating is effected by renewed actuation "<" and "R" while switching on the supp- ly voltage.
Reset functions
By operation of the backspace key "R" or the RESET-input (1-2) the ENS20 is set to the programmed preselected
value in each operating condition. The RESET signal (1-2) and "R" - key have priority in relation to the START signal.
ENS20 can be used in numerous modes of operation as timer or as counter. The different functions are now descri­bed in detail.
Reset on zero or to the preselected value
Announcement of the preselected value; timing continues in the back­ground with all switching functions
Programming mode; depending on function attitudes only possible if no
+
starting signal is acticvated
With power on activate the simultan-
+
eous pressing of these keys the LOCK function (keyboard disabling)
Errors and technical changes reserved
English translation
Safety Precautions
The installation and operation must be carried out by
qualified personnel only,
who is familiar with the professional handling of machine
equipment,
who is familiar with the valid rules of industrial safety
and accident prevention,
who read and understood the operating instructions. The safe function of the device during machine operation
cannot be guaranteed in case of wrong connection or improper operation. This may lead to fatal injuries.
Pay attention to country specific regulations. The electrical installation must be performed after dis-
connecting the device and the machine from the mains supply.
The wiring must be carried out according to the instruc-
Non-observance of the instructions above will cause the loss of warranty.
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
tions of this operating manual.
The person who programs the device must be protected
against electrostatic discharge (ESD protection).
Opening the device, any manipulation of the device and
the avoidance of the safety facilities are not permitted.
All relevant safety regulations and standards must be
attended to.
Non-observance of the safety regulations may cause
death, severe injuries or substantial damage to property.
Before use, please, read the operating instructions and
keep it in a safe place. Make sure that the operating instructions are always available for installation, initial operation and maintenance.
L05
E61-282-00
1
A2
1 2 3 15 18 16
A1
25 26 28
L
1
(
L
+
)
E
S
E
T
S
T
A
R
T
/
C
O
U
N
T
N
(
M
)
O
pti
o
n
+
+
0V
R R
Digital Timer/Counter ENS20
Installation
Electrical connection
ENS20 is a panel-mounting device for 45 x 45 mm cutout. The front of the device is water and dust proof.
A1-A2 are operating voltage connections for AC 230 V,
AC 115 V for DC 24 V.
If the DC 24 V version is used, a control transformer
according to EN 61558-2-6 or a power supply unit with electrical isolation from the mains must be connected.
External fusing of the contacts (6 A slow-blow or 8 A
quick-action) must be provided.
The line cross section must not exceed 2.5 mmIf the device does not function after commissioning, it
must be returned to the manufacturer unopened. Ope­ning the device will void the warranty.
2
Errors and technical changes reserved
English translation
A plastic front frame with external dimensions of 55 x 55 mm is available as an accessory.
A1: Power supply (+24 V at DC-version) A2 : Power supply (0 V at DC-version)
1: 0 V for ext. connections 2: Reset input 3: Start input 15-16-18: Contact 1 25-26-28: Contakt 2
Programming
The programming mode is activated by simultaneously pressing of "<" and ">" keys. Note: The LOCK function must be deactivated.
There are 8 functions (1..8), which are working on in se­quence. The display flashes in the programming mode.
Programming mode; depending on attitude only possible if no start-signal
+
is turned on, the display flashes, begin­ning with time preselection (function 1)
Attitude of the values, e.g. time presel­ection or time range
" R " and afterwards " > " - key: Storing
of the new value and next function
2x " R " one after the other: Leave the
programming mode and back to the normal operation
Display
last pro-
grammed
value,
e.g. 472
Function 1: Timer/counter preselection
Select the time/count-preselection with the keys "< " and " > ". Single and conti­nuous pressure are possible.
Storing and next function with "R" .
The display shows "r - >": Next function with key ">", return to the operating mode with "R" - key.
L05
E61-282-00
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
2
Digital Timer/Counter ENS20
Programming
ENS20 as timer (2-0 to 2-6, see function 2)
Timing begins with turning on the starting signal (1-3) and can be interrupted by this input as desired. The START input 1-3 can be closed by a cable link. In this case timing begins directly with switching on the mains voltage. RESET and START input have an internal noise pulse suppression. They may be activated by contacts or electronic initiators.
ENS20 as counter (2-7, see function 2)
All functions 3 to 8 also apply to the counter mode. The clock input is provided at the terminals 3 (+12..24 V) and 1
(0 V). Counting is done by closing an external counting
contact. Also 2- or 3-wire semiconductor outputs of initia­tors can be used. The falling edge is counted.
The following function settings are valid depending on the value of the function 2 for timer mode (2-0 to 2-6) or
counter mode (2-7).
Display
Function 3: Timing functions
3– 0 On-delay. Timing begins with applying of
the mains voltage and closing of the START-contact. After timing the contacts switch from 15-16 to 15-18 until the arrival of a resetting signal, at least however for
100 ms.
3 – 1 Impulse-limiting. As On-delay, however
the contacts are switched on with applicati­on of the mains voltage immediately (15-
18) and back to 15-16 after timing.
Errors and technical changes reserved
Display
2 – 0 0.01 - 9.99 s
2 – 1 0.1 - 99.9 s
2 – 2 1 - 999 s
2 – 3 0.1 - 99.9 min
2 – 4 1 - 999 min
2 – 5 0.1 - 99.9 h
2 – 6 1 - 999 h
2—7 Counter mode
Display
Function 5:
Function 2
Timing ranges
Power failure function
5 – 0 Continuation. Timing is continued after
power failure with the value reached last.
5 – 1 Restart. Timing begins after power failure
with zero or with the preselected value
(RESET after power failure).
Display
Function 6: Enable/disable programming
6 – 0 Programming enabled during timing.
Programming during timing (i.e. the START signal is turned on) is enabled. Timing is stopped and continued after the recent time preselection with the new values.
English translation
3 – 2 Flashing (T1=T2). The ENS20 works after
applying of the mains voltage and closing of the START contact as symmetrical cyc­ling timer. The cycle starts with output off
(relay switched off). On and off time are
equal.
3 – 3 Flashing (T2=100ms). In this operating
condition the output relay switches periodi­cally for 100ms. The total cycle time is de­termined by the preselected current value.
3 – 4 Signal off-delay. The control is made by
the START contact. The contacts switch on immediately and after opening the starting contact timing begins. After timing the contacts switch back to 15-16. A stop is not possible here.
3 – 5... Free for customized special functions
Dispaly
Function 4: Counting direction
4 – 0 upward. Timing/counting begins with zero
and ends with the preselected value. A RESET signal sets back to zero.
4 – 1 downward. Timing begins with the presel-
ected value and ends with zero. A RESET
signal sets back to the preselected value.
6 – 1 Programming disabled during timing.
The programming mode by "<" and ">" - keys is not possible during timing (i.e. the START signal is turned on). Programming only, if the START input is turned off.
Display
Function 7: Aux. contact, only version 52311x
7 – 0 Auxiliary contact is immediate contact.
Timer mode: The 2nd contact switches with applying the START signal . Counter mode: The 2nd contact switches on with the first counting pulse.
7 – 1 Auxiliary contact is progammable pre-
contact
The display shows next "Pxx ".
xx is the timer/counter value of the 2nd
contact. Set the value with <, > e.g."P52". Through this the 2nd contact switches on
52 clocks before reaching the timer/counter
preselection (1st contact). With the value
"P00 " the 2nd contact switches at the
same time as the 1st contact with reaching the preselection value.
Display
Function 8: Input frequency
8 – 0 Input frequency at start/count 50 Hz.
8 – 1 Input frequency at start/count 500 Hz.
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
L05
E61-282-00
3
8
100
45
48
55
R
PR
LOCK
Digital Timer/Counter ENS20
Maintenance
Techn. Data
The device must be checked once per month for proper function and for signs of tampering.
Operating voltage DC 24 V, AC 230V / AC 115 V, 50-60 Hz Residual ripple + / - 10% Power consumption < 2 VA LED´s 3 digits, 7 mm red, time up indication Protection IP65 front Internal data storage time 10 years Contacts 2 changeover contacts Switching capacity AC 250 V, 8 A; DC 24 V, 3 A Contact life mechanical 2x107 operations electrical 105 operations Inputs 2, 3 DC10..30 V or external contact Time base quartz-stabilized, time tolerance: < 0.1% Min. power-off time function 5-1:100 ms, function 5-0: 200 ms Input frequency / counter 50 / 500 Hz programmable Trigger closing of the contact / falling edge Time ranges 7 between 0.01 s and 999 h Temperature range 0°C - +500C Dielectric strength 4 kV DIN VDE 0110-1:1997-04 Weight approx. 200 g
The device is otherwise maintenance free, provided that it was installed properly.
Errors and technical changes reserved
English translation
Dimensions
Variants
48 mm without front frame 55 mm with front frame
Order-No. 523110 ENS20 AC230 V, 2 changeover contacts Order-No. 523111 ENS20 AC115 V, 2 changeover contacts Order-No. 523112 ENS20 ADC24 V, 2 changeover contacts Order-No. 583010 Plastic front frame 55 x 55 mm (option)
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
L05
E61-282-00
4
Digital Timer/Counter ENS20
Errors and technical changes reserved
English translation
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
L05
E61-282-00
5