Zamil PDS036, PDS048, PDS060, PDS075, PDS090 Installation, Operation & Maintenance Manual

...
INSTALLATION,
OPERATION
&
MAINTENANCE
MANUAL
DOUBLE SKIN PACKAGED AIR CONDITIONERS
'PDS' SERIES
PL-OM-PDS-05-1M-E
INDEX
Contents Page
Model decoding ........................................................................................................................................ 2
Dimensions.......................................................................................................................................... 3-10
Fresh air hood assembly ........................................................................................................................ 11
Rigging instructions ................................................................................................................................ 12
Installation .............................................................................................................................................. 13
Typical schematic wiring diagram...................................................................................................... 14-19
INSTALLATION INSTRUCTIONS
General................................................................................................................................................... 20
Location of unit ....................................................................................................................................... 20
Wiring ..................................................................................................................................................... 20
Start-up inspection & check list ......................................................................................................... 20-21
Check-out & operational start-up procedure ...................................................................................... 21-22
Belt tension testing procedure ........................................................................................................... 22-23
ELECTRICAL
Power supply .......................................................................................................................................... 24
Unbalanced voltage ................................................................................................................................ 24
Motor contactor ...................................................................................................................................... 25
Fan motor ............................................................................................................................................... 25
Crankcase heater ................................................................................................................................... 25
Lube oil protection control ................................................................................................................. 25-26
Voltage monitor ...................................................................................................................................... 26
Electronic thermostat ........................................................................................................................ 26-27
REFRIGERATION
Compressor ............................................................................................................................................ 28
High & low pressure switch .................................................................................................................... 29
Pump down control................................................................................................................................. 30
Trouble shooting chart ....................................................................................................................... 31-33
Parts list ............................................................................................................................................ 34-40
Recommended spare parts .................................................................................................................... 41
Preventive maintenance schedule.......................................................................................................... 42
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.
THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
1
14
AIR UNIT
LOW CFM & 100% FRESH
C :COPPER FIN
J :ALUMINUM FIN
K :COATED
ALUMINUM FIN
L :COPPER FIN
NOTE: The oracle system al-
lows to select 5, 6, 8, 10 or
12 rows. Please order correct
number of rows according to
the selection software.
EVAPORATOR COIL
ECONOMIZER
STANDARD UNIT &
A :ALUMINUM FIN
B :COATED
ALUMINUM FIN
****
13
UNIT
ECONOMIZER
CONFIGURATION
12
KITS
MECHANICAL OPTIONS
11
KITS
FRESH AIR UNIT
A : STANDARD UNIT &
B : LOW CFM & 100%
***
SENSOR
A : STD.
D : DISCHARGE GAS
VALVE
E : DRIP ELIMINATOR
H :HOT GAS BYPASS
DRIER, MUFFLER, BALL
VALVE & GAUGES
M :REPLACEABLE FILTER
B : M & H COMBO
***
PRESSURE SWITCHES AND
FAN CYCLING SWITCH
VALVE
ELECTRICAL OPTIONS
A : STD.
C :COMP. CIRCUIT BREAKER
K : ADJUSTABLE LOW & HIGH
ANTI-ICE
P : PUMP DOWN SOLENOID
V :VOLT FREE CONTACT &
B : K & V COMBO
10
MODEL DECODING
CONDENSER COIL
9
COMPRESSOR
A :ALUMINUM FIN
TYPE
S : SCROLL
*
8
FIN
B :COATED ALUMINUM
HERMETIC
(UP TO PDS600)
H :SEMI-
WITH ALUMINUM
D :HERESITE COATING
ING
FIN
HERMETIC
L : SEMI-
C :COPPER FIN
RECIPROCAT-
G : M & E COMBO
T : M & D COMBO
K : M, H & D COMBO
E : K & C COMBO
G : K & P COMBO
L : K, C & P COMBO
WITH COPPER FIN
H :HERESITE COATING
**
RECIPROCAT-
ING WITH
CAPACITY
CONTROL
L : M, E & D COMBO
N : H, E & D COMBO
S : M, H & E COMBO
R : M, H, D & E COMBO
M : K, V & P COMBO
N : V, C & P COMBO
T : K, V & C COMBO
R : K, V, C & P COMBO
20
INDOOR AIR QUALITY (IAQ)
19
(kW/STAGES)
HEATER OPTIONS
18
DRIVE OPTIONS
17
BLOWER MOTOR
16
&
***
MONITOR
BAG FILTER & 2" THICK ALUMINUM PRE-FILTER
2" THICK ALUMINUM FILTER
ULTRA VIOLET LAMPS
ECONOMIZER CONTROL WITH OUTSIDE AIR THERMO-
A : STD. OPTIONS
B :
D :
U :
M :
N : NO HEATER
A : 5/1
B : 6/1
A : ALT. I
B : ALT. II
C : ALT. III
A : 1 HP TEFC
B : 1.5 HP TEFC
C : 2 HP TEFC.
2
STAT (PSYCHROTROLL)
ECONOMIZER CONTROL WITH ENTHALPY SENSOR
ECONOMIZER CONTROL WITH ENTHALPY SENSOR
CO
D & U COMBO
D & M COMBO
D & L COMBO
D & H COMBO
B & U COMBO
L :
H :
K :
G :
R :
S :
T :
E : B & M COMBO
F : B & L COMBO
C : 7.5/1
D : 10/2
F : 15/2
G :20/2
H : 25/2
J : 30/2
D : 3 HP TEFC
E : 5 HP TEFC
F : 7.5 HP TEFC
G : 10 HP TEFC
H : 15 HP TEFC
I : 20 HP TEFC
J : B & H COMBO
N : D, M & U COMBO
P : D, L & U COMBO
V : D, H & U COMBO
I : B, M & U COMBO
L : 40/2
M : 50/2
P : 60/2
J : 25 HP TEFC
K : 30 HP TEFC
Y : B, L & U COMBO
Z : B, H & U COMBO
S : SINGLE
REFRIGERA-
TION CIR-
CUIT
D :DUAL
7
SUPPLY
( V-Ph-Hz )
ELECTRICAL
4, 5 & 6
NOMINAL
BASIC
1, 2 & 3
(MBH)
COOLING
CAPACITY
H :208/230-3-60
M: 380-3-60
036
048
060
075
PDS
CLASSIC
DOUBLE SKIN
(4 WIRE)
F : 460-3-60
090
100
120
UNIT
PACKAGED
150
180
220
240
300
360
420
480
540
600
660
720
780
840
SUPPLY AIRFLOW
15
AIRFLOW
RETURN & FRESH
2
T : TOP
F : FRONT
STANDARD UNIT & ECONOMIZER
T : TOP RETURN & SIDE FRESH AIR
B :BOTTOM RETURN & SIDE FRESH AIR
S : SIDE RETURN & SIDE FRESH AIR
LOW CFM & 100% FRESH AIR UNIT
(MIDDLE FAN)
R : REAR RETURN & SIDE FRESH AIR
M: TOP FRESH AIR (100% FRESH AIR)
(MIDDLE FAN)
L : SIDE FRESH AIR (100% FRESH AIR)
K : REAR FRESH AIR (100% FRESH AIR)
(MIDDLE FAN)
E : TOP RETURN & SIDE FRESH AIR
C :SIDE RETURN & SIDE FRESH AIR
N :REAR RETURN & SIDE FRESH AIR
NOTES:
– Single scroll compressors for models PDS036-PDS075 (single circuit) & single semi-hermetic compressors up to models PDS150 (single circuit). All other models are with dual compressors (dual circuit).
– Capacity control options starts from units PDS060 onwards.
– Standard options contains vibration eliminator (for semi-hermetic), fixed high/low pressure switches, fan cycling (low ambient) switches and UVM .
– To select low CFM & 100% fresh air units, follow the software selection procedure.
*
**
***
****
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 036/048/060
264 (10. 4)
302 (11.9)
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 036/048/060
266 (10. 5)
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
255 (10.0)
288 (11.4)
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
3
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 075/090
372 (14.6)
336 (13.2)
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 075/090
294 (11.6)
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
389 (15.3)
302 (11.9)
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
4
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 100/120/150
F/A
CONDENSER AIR IN
F1' F2' F3'
F4'
CONDENSER AIR IN
F1
1205 (47.4)
125 (4.9)
F2
R/A
R/A
R/A
4412 (173.7)
F3
TOP VIEW
295x1145 (11.6x45.0)
476 (18.8)
FRONT VIEW
378 (14.9)
F4
S/A
S/A
408 (16.1)
S/A
1270 (50.0)
1330 (52.4)
END VIEW
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 100/120/150
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
465 (18.5)
400 (15.7)
346 (13.6)
157.5 (6.2)1366 (53.8) 1365.5 (53.75)157.5 (6.2) 1366 (53.8)
30 (1.2) TYP
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
5
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 180/220
312 (12.3)
677 (26.7) 476 (18.7)
450(17.7)
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 180/220
476 (18.7)677 (26.7)
312 (12.3)
450(17.7)
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
6
395x1145 (15.6.6x45.0) - STD. / ECON.
CONDENSER AIR IN
F1'
F1
CONDENSER AIR IN
F/A
R/A
R/A
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 240/300
F2'
F2 F3
TOP VIEW
425x1645 (16.7x64.8) - R.A
F3'
562 (22.2)
634 (25.0)
F4'
480 (18.9)
F4
S/A
Ø40 (1.6) DRAIN OUTLET
AUXLIARY CONTROL BOX
FRESH AIR HOOD
(For economizer s ystem, hood supplied for
S/A
100% fresh air)
MAIN CONTROL BOX
Ø102 (Ø4) POW ER ENTRY
HEATER BOX (OPTIONAL)
RIGGING HOLES Ø76.2 (2 Nos. EACH S IDE)
CONDENSER ACCE SS
S/A
S/A
1480 (58.3)
150 (5.9)
R/A
4995 (196.6)
FRONT VIEW
480 (18.9)
1770 (69.7)
1830 (72.0)
END VIEW
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 240/300
480 (18.9)
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
7
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 360/420
590 (23.3)
745 (29.3)
132 (5.2)642 (25.3)
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 360/420
562 (22.2)759 (29.9)
458 (18.0)
240 (9.5)
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
8
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 480/540/600
718 (28.2)746 (29.4 )
422 (16.6)
260.6 (10.3)
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 480/540/600
640 (25.2)785 (30.9)
378 (14.9)
368 (14.5)
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
9
UNIT DIMENSIONS
STANDARD & ECONOMIZER UNIT
MODEL No.: PDS 660/720/840
806 (31.7)702 (27.6)
806 (31.7)
LOW CFM/100% FRESH AIR UNIT
MODEL No.: PDS 660/720/840
640 (25.2)785 (30.9)
640 (25.2)
404 (15.9)
128 5.1)
806 (31.7)
806 (31.7)
Notes: 1. All dimensions are in mm ( dimensions in bracket are in inches).
2. Service clearance should be 1200mm (4 feet) on all sides.
3. F1, F2.... are mounting hole locations. Please refer to page 12 for weight distribution.
10
368 (14.5)640 (25.2)
Legend: F/A = Fresh Air
R/A = Return Air S/A = Supply Air
640 (25.2)
FRESH AIR HOOD ASSEMBLY
1
5
2
3
4
9
7
VERTICAL DAMPER
(OPTIONAL)
8
10
HOOD ACCESSORIES
1. Hood panel
2. 1/4'' dia. taptite screw
3. Right hand side panel
4. Left hand side panel
5. #10 SM screw
6. Bottom panel
7. Left hand end panel
8. Right hand end panel
9. Filter
10.Middle slide bracket
6
11
ATTENTION TO RIGGERS:
Hook rigging sling thru holes in base rail, as shown below. Holes in base rail are centered around the unit center of gravity. Use spreader bar when rigging, to prevent the slings from damaging the unit.
CAUTION:
All panels should be in place when rigging. Care must be taken to avoid damage to the coils during handling.
WEIGHT DISTRIBUTION
RIGGING INSTRUCTIONS
STANDARD & ECONOMIZER UNIT
MODEL
NUMBER
PDS 036 PDS 048 PDS 060 PDS 075 PDS 090 PDS 100 PDS 120 PDS 150 PDS 180 PDS 220 PDS 240
PDS 300 PDS 360 PDS 420 PDS 480 PDS 540 PDS 600 PDS 660 PDS 720 PDS 780 PDS 840
LOAD DISTRIBUTION AT POINTS - KG
F1 F1' F2 F2' F3 F3' F4 F4' F5 F5' F6 F6'
155* 155* 135* 135* 170* 170* 140 140 N.A. N.A. N.A. N.A. 160* 160* 135* 135* 185* 185* 145 145 N.A. N.A. N.A. N.A. 165* 165* 140* 140* 195* 195* 150 150 N.A. N.A. N.A. N.A. 205* 205* 162* 162* 225* 225* 170 170 N.A. N.A. N.A. N.A. 220* 220* 165* 165* 240* 240* 175 175 N.A. N.A. N.A. N.A. 245* 245* 180* 180* 280* 280* 195 195 N.A. N.A. N.A. N.A. 255* 255* 182* 182* 290* 290* 198 198 N.A. N.A. N.A. N.A. 265* 265* 184* 184* 300* 300* 201 201 N.A. N.A. N.A. N.A. 305* 305* 209* 209* 360* 360* 226 226 N.A. N.A. N.A. N.A. 315* 315* 211* 211* 370* 370* 229 229 N.A. N.A. N.A. N.A. 350* 350* 216* 216* 410* 410* 234 234 N.A. N.A. N.A. N.A. 370* 370* 226* 226* 440* 440* 244 244 N.A. N.A. N.A. N.A.
250* 250* 250* 250* 240* 240* 475* 475* 160 160 N.A. N.A. 275* 275* 275* 275* 240* 240* 475* 475* 162 162 N.A. N.A. 350* 350* 350* 350* 275* 275* 550* 550* 230 230 N.A. N.A. 365* 365* 365* 365* 280* 280* 550* 550* 235 235 N.A. N.A. 375* 375* 375* 375* 280* 280* 570* 570* 240 240 N.A. N.A. 400* 400* 400* 400* 290* 290* 375* 375* 375* 375* 260 260 410* 410* 410* 410* 290* 290* 390* 390* 375* 375* 260 260 420* 420* 420* 420* 290* 290* 405* 405* 375* 375* 260 260 425* 425* 425* 425* 290* 290* 415* 415* 380* 380* 260 260
TOTAL
LOAD
(KG)
1200 1250 1300 1525 1600 1800 1850 1900 2200 2250 2420 2560
2750 2875 3510 3590 3680 4200 4270 4340 4400
LOW CFM & 100% FRESH AIR UNIT
MODEL
NUMBER
PDS 036 PDS 048 PDS 060 PDS 075 PDS 090 PDS 100 PDS 120 PDS 150 PDS 180 PDS 220 PDS 240
PDS 300 PDS 360 PDS 420 PDS 480 PDS 540 PDS 600 PDS 660 PDS 720 PDS 780 PDS 840
LOAD DISTRIBUTION AT POINTS - KG
F1 F1' F2 F2' F3 F3' F4 F4' F5 F5' F6 F6'
155* 155* 105* 105* 160* 160* 105 105 N.A. N.A. N.A. N.A. 160* 160* 105* 105* 175* 175* 110 110 N.A. N.A. N.A. N.A. 165* 165* 110* 110* 180* 180* 120 120 N.A. N.A. N.A. N.A. 205* 205* 125* 125* 215* 215* 130 130 N.A. N.A. N.A. N.A. 220* 220* 135* 135* 220* 220* 138 138 N.A. N.A. N.A. N.A. 245* 245* 146* 146* 269* 269* 165 165 N.A. N.A. N.A. N.A. 245* 245* 166* 166* 274* 274* 165 165 N.A. N.A. N.A. N.A. 255* 255* 166* 166* 294* 294* 173 173 N.A. N.A. N.A. N.A. 305* 305* 188* 188* 357* 357* 175 175 N.A. N.A. N.A. N.A. 315* 315* 211* 211* 348* 348* 204 204 N.A. N.A. N.A. N.A. 350* 350* 186* 186* 410* 410* 204 204 N.A. N.A. N.A. N.A. 370* 370* 198* 198* 440* 440* 218 218 N.A. N.A. N.A. N.A.
390* 390* 215* 215* 505* 505* 190 190 N.A. N.A. N.A. N.A. 400* 400* 231* 231* 515* 515* 216 216 N.A. N.A. N.A. N.A. 440* 440* 333* 333* 615* 615* 310 310 N.A. N.A. N.A. N.A. 465* 465* 337* 337* 625* 625* 310 310 N.A. N.A. N.A. N.A. 490* 490* 337* 337* 638* 638* 322 322 N.A. N.A. N.A. N.A. 400* 400* 400* 400* 350* 350* 575* 575* 325 325 N.A. N.A. 410* 410* 410* 410* 350* 350* 580* 580* 325 325 N.A. N.A. 420* 420* 420* 420* 350* 350* 585* 585* 335 335 N.A. N.A. 430* 430* 430* 430* 350* 350* 595* 595* 345 345 N.A. N.A.
NOTE: 1. Please refer to the dimensional drawings (page 3-10) for distance between points/mounting holes.
2. Multiply by 1.3 factor for copper fins coil and add to the total weight of the unit.
F1'
+
F2'
+
F3'
+
F4'
+
F5'
TOTAL
LOAD
(KG)
1050 1100 1175 1350 1425 1650 1700 1775 2050 2155 2300 2450
2600 2725 3400 3475 3550 4100 4150 4220 4300
+
F6'
+
F1
+
MODULAR DOUBLE SKIN PACKAGED UNIT
F2
+
F3
+
F4
+
12
F5
+
F6
+
INSTALLATION
1. Provide a concrete pad or another form of stand. Use 6-12 each rubber/cork pads 4" x 4" x 1" thick each (rubber-in­shear for example) at each corner and along side rails, or use 6-12 each spring isolators.
2. Service Clearance: To avoid condenser air obstructions/recirculation, and to give adequate service space, indicated clearances must be observed. See drawing below.
3. All wiring must comply with NEC (National Electrical Code) and local electrical codes. The electric supply must comply with the unit nameplate. See the typical wiring diagram for guidance.
4. All units are pre-charged with R-22 and oil, sealed and tested for leaks. Therefore do not attempt to open the system.
5. Install a flexible connection for duct work to minimize vibration transmission. Connect drain pipe (copper or PVC) to the nearest drain pit.
6.
Care should be taken in locating the roof curb & roof opening. The packaged unit should be adequately mounted on roof.
7. Install & secure ductwork to curb prior to mounting unit on the roof curb.
RECOMMENDED SERVICE CLEARANCE
E'
CONTROL BOX
S/A
CONTROL BOX
– Multiply 'A' by 1.5 if nearby low walls exist. – Multiply 'A' by 2.0 if nearby high walls exist. – FOR MULTIPLE UNIT INSTALLATION, distance between adjacent unit = 2A.
NOTE: There should not be any obstacles above condenser air discharge.
TYPICAL HIGH AND LOW VOLTAGE FIELD WIRING CONNECTIONS
APPLICABLE FOR
N
L3
L2
LEGEND:
CB ECB ETB
HVTB
NTB
POWER WIRES
CB OR FUSED
DISCONNECT SWITCH
CIRCUIT BREAKER ELECTRONIC CONTROL BOARD
EARTH TERMINAL BLOCK
HIGH VOLTAGE TERMINAL BLOCK NEUTRAL LINEN
NEUTRAL TERMINAL BLOCK
FIELD WIRING GROUNDING
L1
380V UNITS ONLY
INDOOR THERMOSTAT
W2W1Y2Y1GCR
S/A
UNIT CONTROL PANEL
R C G
LVTB
Y1
Y2 W1 W2
NTB
L1
HVTB
L2
L3
ETB
13
TYPICAL SCHEMATIC WIRING DIAGRAM
(Single compressor units)
REFER TO UNIT NAMEPLATE FOR POWER SUPPLY
THERMOSTAT CONTROLLER
BM
COOLING
HEATING ST G1
HEATING ST G2
TO FUSED
DISCONNECT SWITCH OR CB
(NOTE 4)
(NEUTRAL WIRE)
(SEE NOTE -7)
[UVM]
ATB
JP1
1 1A
R R
24V
C C
Y1
W1
W1
LPS1
P
YR1-1
CR1-1
PDSR1-1
LVTB
Y1
W1
W1
HVTB
L1 L2 L3
NTB
LUG
T1A
COMP
[NOTE:5]
CC
68
T3A
T2A
69
CONTROL CONNECTION
TO NTBTO HVTB
JP2
1B
23
ATB
15
G G
F1
(SSPS)
HPS1
2A
31A
29
30
JP4
24
P
SEE APPLICABLE FM CONTROL CONNECTION
(ABOVE RIGHT)
CB
TO ATB
15
HC1
HC2
NL1
(AI)
JP5
26
25
SR1-1
TO ATB
1
TRANS
16
18
TO FR (SEE OPTIONAL VFC INDICATION CONNECTION)
41A
28
BMC
OLR
70
(OPS)(DTS)
JP7JP6
2827
3A
4A
230V
24V
OLR-1
39A 40A
SM
AFS
NC
C
NO
SEE APPLICABLE FM POWER CONNECTION
(AT RIGHT)
SR1
CC
CR1
PDS
TO ATB
2
19
38A
SR1-2
ATB
2
RELAY SAFETIES
CONTACTOR COMPRESSOR
SOLENOID PUMP DOWN
BMC
PDSR1
YR1
WITHOUT FCS
ATB
CR1-2
1
ATB
17
CONTACTOR BLW MTR
RELAY PUMP DOWN SOLENOID
RELAY COOLING
CONTACTORS HEATER 1&2
CONDENSER FAN MOTOR CONNECTIO N - (DUAL FAN MOTOR)
L1 L2
L3 L1
FMC
37A
35A
36A
FM1
TK[FM1]
TK[FM2]
12B
12
(AS APPLICABL E)
36B
37B
35B
FM2
FMC
ATB
13B
2
[ J1 ] -- COMP. PUMP DOWN DELAY TIME
[ J2 ] -- CO MP. ANTI-RECYCLE TIMER
J1 J2
WITH FCS
ATB
1
TO HVTB
L2 L3 L2L1 L3
36A
35A
CR1-2
12
FCS
CONDENSER FAN MOTOR CONNECTION - (SINGLE F AN MOTOR)
WITHOUT FCS ATB
CR1-2
1
WITH FCS ATB
CR1-2
FCS
12
1
FMC1 FMC2
37A
TK[FM1]
TK[FM2]
12A
(AS APPLICABLE)
TO HVTB
L3L2L1
FMC
36A
35A
37A
FM
TK[FM]
12
TK[FM]
TO HVTBTO HVTB
37B
36B
35B
FM2FM1
FMC1
12B
FMC2
13B
FMC
12B
FMC
12B12A
PRESSURE SWITCH SETTINGS
NAME OPEN (PSIG) CLOSE (PSIG)
LPS
HPS
FCS 190 ± 15
PRESET TO 0 SEC. (STD. UNIT) / 30 SEC. (PD UNIT) PRESET TO 3 MIN.
25 ± 5
450 ± 10
TIMER SETTING ON SM
10 sec. 30 sec.0 sec.
FACTORY SETT ING OF J1 & J2
60 sec.
50 ± 5
360 ± 15
290 ± 10
90 sec.
CLOSE -- 3 min.OPEN -- 5 min.
ATB
2
ATB
2
ATB
2
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
14
TYPICAL SCHEMATIC WIRING DIAGRAM
(Single compressor units)
SINGLE STAGE HEATING
TO HVTB TO HVTB
CB11
73A
71A
72A
HC1 HC1
T3F
T1F
T2F
HEATER1
CRANKCASE HEATER CONNECTION
SCROLL COMP.
L1
RECIP. COMP.(Semi-Hermetic)
1
COMP. SSPS CONNECTION
24
1
OIL PRESSURE SWITCH CONN.
3A
27
CR2-1A
1
UVM CONNECTION
TO ATB
TO ATB
CR2-1B
M1/11
L1/MP/L
1A
T1G
28A
L1 L2
1
T2G
HEATER2
100A
(REMOVE JP4)
2 240
TO HVTB
L1 L2
1
T3G
C.HTR
C.HTR
SSPS
CR2
OPS-1
OPS
(REMOVE JP7)
UVM-1
8
M2/14
L2/R/N
L3
L3
(REMOVE JP1)
DUAL STAGE HEATING
L1 L3L2L2 L3L1
72A
71A
73A
T2F
T1F
T3F
HEATER1
(AS APPLICABLE)
(AS APPLICABLE)
(NOTE 5)
25
2
(AS APPLICABLE)
2
28
UVM
HEATER CONNECTION DETAILS
(OPTIONAL)
TO HVTB
L2 L3L1
CB12CB11
71B
73B
72B
HC2
T1G
T3G
T2G
HEATER2
UNIT STATUS INDICATION CONNECTION
(VOLT-FREE CON TACTS)
L2
2
2
SM-4
55
43
48
51
15
45
ANTI-ICE CONNECTION
25
DTS CONNECTI ON
26
SERVICE LAMP CONNECTION
230Vac
HEATER BOX CONNECTION TY PES
T2T1 T3
TYPE-I
41A
FR-2A
FR-2B
COMP1 ON COMP1 0FF
COMP1 TRIP
FR-1
UNIT TRIP
49
OLR-2
BM TRIP
C. UNIT ON/OFF
AR1
46
AI1
(REMOVE JP5)
DTS
(REMOVE JP6)
SW
OHT
FR
OHT
Note: Heater 2 connection is applicable only for units with 10 to 20 kw heating.
COMP. ON/OFF/TRIP & UNIT TRIP
B. BM ON,OFF & TRIP I NDICATION
BMC-1A
AR1-1A
UNIT ON
1
2
T3
FLFL
TYPE-II TYPE-III
HEATER DATA TA BLE
HTG.
5 K.W
1 1
6 K.W
7.5 K.W 1
10 K.W 10 K.W
1 OR 2 1 OR 2
12 KW
1 OR 2
15 KW 20 KW
1 OR 2
(OPTIONAL)
17
54
CCA-2A
CCA-2B
58
5756
44
BMC-1B
50
BM OFFBM ON
52
17
AR1-1B
47
UNIT OFF
(OPTIONAL)
26
(OPTIONAL)
27
(OPTIONAL)
98
LAMP
OHT
FL
HTR1STG. HTR2 5 KW
6 KW
7.5 KW 10 KW
5 KW
7.5 KW 10 KW
T2 T3T1T1 T2
----
----
----1
---­5 KW 6 KW6 KW
7.5 KW 10 KW
COMPRESSOR CKT. BREAKER
CONNECTION
(OPTIONAL)
TO HVTB
L2L1 L3
CB1
L1A
L2A
L3A
CC
T2A
T1A
T3A
COMP
LEGEND
AI ANTI ICE THERMOSTAT AFS AIR FLOW SWITCH AR AUXILIARY RELAY ATB AUXILIARY TERMINAL BLOCK BM BLOWER MOTOR BMC BLOWER MOTOR CONTACTOR CC COMPRESSOR CONTACTOR CB CIRCUIT BREAKER C. HTR CRANKCASE HEATER CR CONTROL RELAY COMP COMPRESSOR DTS DISCHARGE TEMPERATURE SENSOR FL FUSE LINK FCS FAN CYCLING SWITCH FM FAN MOTOR (CONDENSER) FMC FAN MOTOR CONTACTOR FR FAULT RELAY HC HEATER CONTACTOR HPS HIGH PRESSURE SWITCH HVTB HIGH VOLTAGE TERMINAL BLOCK H HEATER JP JUMPER L1 LINE 1 L2 LINE 2 L3 LINE 3 LPS LOW PRESSURE SWITCH LUG LUG GROUND LLS LEAD LAG JUMPER IN SM NTB NEUTRAL TERMINAL BLOCK OLR OVER LOAD RELAY OHT OVER HEAT THERMOSTAT PDSR PUMP DOWN SOLENOID RELAY SM SYSTEMIZER SR SAFETY RELAY SSPS SOLID STATE PROTECTIVE SYSTEM TK MOTOR THERMAL CONTACT TRANS TRANSFORMER T'STAT THERMOSTAT UVM UNDER VOLTAGE MONITOR YR COOLING RELAY
_ _ _
FIELD WIRING
+
DISCONNECT TAB - 1/4" SPLICE-CLOSED END
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE 90 OR ITS EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE.
4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY END USER WITH RATING AS RECOMMENDED BY ZAMIL.
5.
COMPRESSOR IS PROVIDED WITH INHERENT THERMAL OVERLOAD PROTECTION.
6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE ACROSS TERMINAL 4 & 2 OF SYSTEMIZER IS 24 VAC. ALSO COMPRESSOR LOCKOUT LIGHT IS ON.
7.
NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER SUPPLY ONLY.
0
C
15
TYPICAL SCHEMATIC WIRING DIAGRAM
(Dual compressor units)
REFER TO UNIT NAMEPLATE FOR POWER SUPPLY
[UVM]
ATB
1
JP1
K2-T1
K3-T1
K1-T1
LPS1
P
LPS2
P
TO ATB
24VAC (C) SUPPLY
1A
YR1-1[RB2]
CR1-1[RB1]
YR2-1[RB2]
CR2-1[RB1]
PDSR1-1[RB1]
PDSR2-1[RB1]
BMR-1 [RB2]
23A
23B
17
TO FUSED DISCONNECT SWITCH OR CB
(SEE NOTE-4)
NEUTRAL WIRE
(SEE NOTE -12)
CONTROL CONNECTION
TO HVTB
L1
F1
1B
JP2
SR1-1[RB1]
2A
K2-T2
SR2-1[RB1]
2B
K3-T2
18B
K1-T2
[SSPS1]
JP4
HPS1
P
HPS2
P
TO SM TO SM
5B
38B 38A
PDSR2
ATB
24A
25A
[SSPS2]
JP7
24B
25B
TO ATB
5A
220VAC (C)
SUPPLY
PDSR1
15
L1 L2 L3
[AI1] JP5
[AI2]
JP8
2
HVTB
NTB
LUG
TO NTB
N
OLR1-1
26A
OLR2-1
26B
TO ATB TO ATB
3B 3A
CR2
CB
L1
L2 L3
CC1 CC2
OLR1
T2A
T1A
T3A
COMP
1
OLR2
T3B
T2B
T1B
COMP
2
[NOTE:11]
ATB
2
SEE COMPRESSOR PWS CONNECTION IF COMP. IS STARTED IN PWS
3A
3B
4A
4B
16
CC1
C1-CONTACTOR
CR3
SEE COMPRESSOR PWS CONNECTION IF COMP. IS STARTED IN PWS
CC2
C2-CONTACTOR
CR4
PDS1
C1-PUMP DOWN SOLENOID
PDS2
C2-PUMP DOWN SOLENOID
BMC
BM CONTACTOR
27A
27B
SEE OPS / DTS CONNECTION
(NOTE - 8)
28C/29A
28D/29B
CR1
1
SR2
TRANS1
230V
24V
SR1
RB1
TO ATBTO ATB
2
17
SEE COND.FM AND
BM CONNECTION
DOL STARTING CONNECTION OF
COMPRESSOR - W/ CB [OPTIONAL]
HVTB
L1 L2 L3
L3A
L2A
L1A
L1B
CC1
OLR1
T3A
T2A
PRESSURE SW ITCH SETTINGS
NAME OPEN (PSIG)
25 ± 5LPS1 & 2
LPS3 & 4 45
HPS1 & 2 450 ± 10
190 ± 15FCS1 & 2
T1A
COMP
1
CLOSE(PSIG)
50 ± 5
55 6555LPS5 & 6 360 ± 15 290 ± 10
T1B
TIMER SETTINGS ON SM
PUMP DOWN DELAYJ1 ( ADJ.)
SEC'S
J2 ( ADJ.)
MIN
LLS ( ADJ.)
SELECTION
J1 - (PUMP DOWN DELAY TIME JUMPER) -- PRESET TO 30 SEC J2 - (ANTI-RECYCLE TIMER JUMPER) -- PRESET TO 3 MIN
LLS - (COMPRESSOR LEAD-LAG SEQUENCE JUMPER) -- PRESET TO M1 [FOR AUTOMATIC LEAD LAG OPTION UNITS, PR ESET TO 15D OR 30D]
0
ANTI-RECYCLE TIMER
0
M1
COMP1
COMP2
LEADING
LEADING
FACTORY SETTING OF J1,J2 & LLS
NOTE: FOR UNITS HAVING MORE THAN 2 COOLING STAGES, OR WITH HGS
LLS SHOULD ALWAYS BE IN M1 POSITION. - COMP1 AS LEAD COMP
3010 60
5
310
RT 15D
M2
RUN TIME
MODE
15 DAYS
CHANGE-OVER
COMP
CB2CB1
L3B
L2B
CC2
OLR2
T3B
T2B
2
90
TST
TEST MODE
30D
30 DAYS
CHANGE-OVER
DDC CONTROL PANEL
OR THERMOSTAT
(BY OTHERS)
BLW MTR
st
1 STAGE
COOLING
nd
2 STAGE COOLING
st
1 STAGE
HEATING
nd
2 STAGE HEATING
15
R
17
C
G
Y1
Y2
W1
W2
LLS
1
18
J1
POWER
J2
Y1
Y2 4B
31A
31B
29
30
SEE OPTIONAL ECONOMIZER CONNECTIONS
AFS
NC
C
NO
5A24A
LOCKOUT-C1
LOCKOUT-C2
5B
FROM FR1 RELAY
(SEE OPTIONAL VFC CONNECTIONS)
FROM PDSR1 (RB1)
SR1-2[RB1]
39A
6A
SM
SR2-2[RB1]
6B
39B
FROM PDSR2 (RB1)
FROM FR2 RELAY
(SEE OPTIONAL VFC CONNECTIONS)
(NOTE-9)
34
OLR-1
18A
40A
40B
BMR
BM-CONTACT OR
K1
YR1
STG 1 COOLING RELAY
K2
YR2
STG 2 COOLING RELAY
K3
RB2
HR1
STG 1 HEATER RELAY
K4
HR2
STG 2 HEATER RELAY
K5
28
K6
17
K7
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
16
TYPICAL SCHEMATIC WIRING DIAGRAM
(Dual compressor units)
CRANKCASE HEATER CONNECTION
SCROLL COMP.
COMP. 1:
L2
COMP. 2:
RECIP. COMP.(Semi-Hermetic)
1
1
M1/11
L1/MP/L
M1/11
L1/MP/L
CC1A-1B
CC2A-1B
SSPS1
(REMOVE JP4)
SSPS2
(REMOVE JP7)
COMP. 1:
COMP. 2:
COMP. SSPS CONNECTION
COMP. 1:
24A
1
COMP. 2:
24B
1
OIL PRESSURE SWITCH CONN.
COMP. 1:
27A
1
CR3-1
28A
2
COMP. 2:
27B
1
CR4-1
28B
2
COMPRESSOR UNLOADER CONNECTION
COMP 1
1
COMP 2
1
NOTES:
- COMP IS RUNNING AT FULL CAPACITY IF UNLOADER SOLENOID IS DE- ENEGIZED
- UL1 & UL2 SOLENOID CONNECTION IS APPLICABLE FOR COMPRESSORS WITH 50 % CAPACITY UNLOADER.
- UL3 & UL4 SOLENOID CONNECTION IS APPLICABLE FOR COMPRESSORS WITH
33% ~ 66% CAPACITY UNLOADER.
UNIT STATUS (VFC) INDICATION CONNECTION
3A
SM-4A
55
48
51
LPS3
CR3-2
5A
C
LPS5
C
LPS4
CR4-2
5B
C
LPS6
C
A. INDIVID UAL COMP. O N/OFF/TRIP & UNIT TRIP
COMP 1
FR1
41A
FR1-2A
FR1-2B
54
AR6-1A
COMP1 ON COMP1 0FF COMP1 TRIP
43
B. BM ON,OFF & TRIP INDICATION
BMC-1A B MC-1B
BM ON
OLR-2
BM TRIP
C.HTR1
C.HTR2
C.HTR1
100A
C.HTR2
101A
M2/14
L2/R/N
M2/14
L2/R/N
OPS1-1
OPS1
240
OPS2-1
OPS2
240
NO
6A
NC
P
NO
7A
NC
P
NO
6B
NC
P
NO
7B
NC
P
2 3B
17
AR6-1B
585756
FR1-1 FR2-1
UNIT TRIP
BM OFF
(AS APPLICABLE)
(AS APPLICABLE)
(NOTE 5)
(AS APPLICABLE)
SR1 (RB1)
28C
SR2 (RB1)
28D
(AS APPLICABLE)
UL1
UL3
UL2
UL4
SM-4B
60
44A
5049
52 45
L2L1
L3
2
2
25A
2
25B
2
(NOTE-8)
2
2
2
2
COMP2 ON COMP2 0FF COMP2 TRIP
C. UNIT ON/OFF
15
AR1-1A
UNIT ON UNIT OFF
UVM CONNECTION
TO HVTB
L2L1
L3
L2L1
L3
UVM-1
81
TO ATB
1
TO ATB
1A
ANTI-ICE CONNECTION
COMP. 1:
COMP. 2:
25A
25B
AI1
(REMOVE JP5)
AI2
(REMOVE JP8)
SERVICE LAMP CONNECTION
SW
1
230Vac
2
DTS CONNECTION
COMP. 1:
DTS1
28C
COMP. 2:
28D
HGS CONNECTION
Y1 [LVTB]
Y2 [LVTB]
A. FOR UNITS WIT H NO COMP. CAPACITY UNLOADERS
1
B. FOR UNITS WITH COMP. CAPACITY UNLOADERS
6A
(SEE COMP. UNLOADER CONNECTIONS)
COMP 2
AR7AR6
FR2
41B
FR2-2A
FR2-2B
59
AR7-1A
AR7-1B
44
AR1
AR1-1B
46
DTS2
(OPTIONAL)
636261
29A
29B
AR8
31A
AR9
31B
AR8-1
AR9-1
6D
AR9-1
AR8-1
6D
2
17
17
47
UVM
(REMOVE JP1)
(OPTIONAL)
TO HVTB
(IN MAIN CONTROL PA NEL)
BLOWER MOTOR POWER CONNECTION
(OPTIONAL)
26A
26B
(OPTIONAL)
98
NOTE: CB5 IS APPLICABLE ONLY FOR BM WITH 7.5HP AND ABOVE
LAMP
6C
6C
(OPTIONAL)
TO SR1 (RB1)
TO SR2 (RB1)
(OPTIONAL)
HGS
HGS
(NOTE 8)
17
17
2
2
A. CONNECTION FOR 10 TO 30KW
HEATING.
TO HVTB1
L2L1
L3
L2L1L3
CB11
72A
71A
73A
HC1
T2F
T1F
T3F
HEATER1 HEATER2
(Stg. 1 Heating)
(Stg. 2 Heating)
ATB
1
ATB
1
B. CONNECTION FOR 40 TO 60KW HEATING.
TO HVTB1TO HVTB1
L3L2L1 L2L1 L3 L2L1
HC2
K4-T1
K5-T1
HR1-1[RB2]
HR2-1[RB2]
L1
71A
T1F
K4-T2
K5-T2
L3
L2
72A
73A
T3F
T2F
(Stg. 1 Heating)
8
9
CB11CB12
HC1
L2L3L1
72B
73B
71B
T2G
T3G
T1G
PWS STARTING CONNECTION OF COMPRESSOR - W/O CB [AS APPLICABLE]
HVTB
L1 L2 L3
CC1
OLR1
T2A
T3A
T1A
3A
CC1A-2
3D
26A
81A
CC3 CC2
OLR3 OLR2
T1C
T3C
T2C
COMP
1
CC1 CC2
2
3B
CC3
2
27A 26B
OLR3-1OLR1-1
OLR2-1
CC2A-2
T3D
T2D
T3B
T1B
T1D
T2B
COMP
2
2
CC4
2
3E
27B
OLR4-1
81B
HVTB1
L1 L2 L3
(NOTE -10)
CB5
L3E
L2E
L1E
BMC
OLR
70
69
68
BM
ELECTRIC HEATER CONNECTION DETAILS
T1H
T2H
HC1
HC2
CC4
OLR4
(OPTIONAL)
TO HVTB1
L3
L3
L1
L2
CB12
73B
71B
72B
HC2
T3G
T1G
T2G
T3H
HEATER2
PWS STARTING CONNECTION OF COMPRESSOR - W/ CB [OPTIONAL]
3A
26A
HVTB
(Stg. 2 Heating)
ATB
2
ATB
2
L1 L2 L3
CC1A-2
T2I
T1I HEATER4HEATER1 HEATER3
L2A
L1A
T2A
T1A
CC1
CC3
3D
81A
T2
T3
T1
OHT
FL
UP TO 10 K.W
(TYPE-I)
HTG.
10 KW
COMP
T1C
T2C
1
15 KW 20 KW 25 KW 30 KW 15 KW 40 KW 50 KW 60 KW
NOTE: HEATER 3 & 4 IS APPLICABLE ONLY
FOR HEATING 40KW AND ABOVE
CC3CC1
OLR3
T3C
2
2
T3I
CB1
L3A
OLR1
T3A
HEATER BOX CONNECTION TYPES
T3
T1
T2
OHT
FL
10 TO 15 K.W
(TYPE-II)
HEATER DATA TABLE
STG.
I STG.
2
5 KW
7.5 KW
2 2
10 KW
2
12.5 KW 2 2
10 KW x 2
2
12.5 KW x 2
2
15 KW x 2
L2B
L1B
L3B
T2B
T1B
T3B
3B
CC2A-2
26B27A
3E
81B
CB2
CC2
OLR2
COMP
CC2
CC4
OHT
5 KW
7.5 KW 10 KW
12.5 KW
10 KW x 2
12.5 KW x 2 15 KW x 2
2
OLR4-1OLR2-1OLR1-1 OLR3-1
FL
10 TO 15 K.W
(TYPE-III)
II STG.
15 KW
T1D
T2D
T3
T2T1
CC4
OLR4
T3D
2
2
27B
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.
17
TYPICAL SCHEMATIC WIRING DIAGRAM
(Dual compressor units)
FAN LAYOUTS
[PDS100~150]
FAN2
FAN1
A. STANDARD OPTION
CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS
[PDS180~300] [PDS360~600]
FAN1 FAN2
TO HVTB
L1 L2 L3
CB6
101
102
100
FMC
35A
ATB ATB
CC1A-1
12 12A 12B
1
CC2A-1
35B
37A
36A
FM1 FM2
TK[FM2]TK[FM1]
( 4-CONDENSER FAN MOTOR CIRCUIT )
A. STANDARD OPTION
TO HVTB
CB6
101
100
102
FMC1
36C
35C
37A
FM3
TK[FM1]
12 12B
TK[FM2]
13 13B
37C
36A
35A
FM1
ATB
CR1-2[RB1]
1
ATB
CR2-2[RB1]
1
B. WITH FAN CYCLING OPTION
TO HVTB L1 L2 L3
101
102
100
FMC1
35C
37A
35A
36A
FM1
CR1-2 [RB1]
ATB
1
ATB
1
CR2-2 [RB1]
12
FCS1
13
FCS2
TO HVTB
L1 L2 L3
104
105
103
FMC3
37C
36C
12A
13A
37B
35B
36B
FM2FM3 FM4
TK[FM1]
TK[FM3]
TK[FM2]
TK[FM4]
[PDS660~840]
FAN1 FAN3 FAN2 FAN4
CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS
FAN1
FAN5
FAN3
FAN2
FAN6
FAN4
( 2-CONDENSER FAN MOTOR CIRCUIT )
B. WITH FAN CYCLING OPTION
36B
37B
ATB
FMC
2
1
CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS
A. STANDARD OPTION
TO HVTB
L2 L3L1L1 L2 L3
CB7
104
105
103
FMC2
37B
35B
36B
FM2 FM4
TK[FM3]
13C
TK[FM4]
13D
36D
37D
35D
FMC1
ATB
2
FMC2
ATB
2
TO HVTB
100
35A
FM1
ATB
1
ATB
1
101
36A
102
37A
CR2-2[RB1]
B. WITH FAN CYCLING OPTION
TO HVTB
L1
L3L2
CB7CB6
FMC2
12B
13C
13B
13D
FMC1
FMC3
FMC2
FMC4
FMC4
36D
35D
37D
ATB
2
ATB
2
CB6
100
101
102
FMC1 FMC3
36A
37A
35A
35E
FM1 FM3FM5
ATB
1
ATB
1
TO HVTB
L2
L1
101
100
35A
36A
FM1
CC1A-1
12
FCS1
CC2A-1
12A
NO
C
FCS2
NO
NC
P
C
NC
P
( 6-CONDENSER FAN MOTOR CIRCUIT )
TO HVTB
CB6
103
FMC1
35B
36E
37E
35E
37C
35C
36C
FM3 FM5
CR1-2[RB1]
36E
CR1-2 [RB1]
CR2-2 [RB1]
12 12B
13 13B
37E
TK[FM3]TK[FM1]
37C
35C
36C
TK[FM1]
12
12B
FCS1
12A
NO
C
NC
P
TK[FM2]
13
13B
FCS2
13A
NO
C
NC
P
L3
CB6
102
100
FMC1
35B
37A
TK[FM1]
12B
TK[FM2]
12C
L3L1 L2L3L2L1
CB7
105
104
FMC2
35D
37B
36B
FM2 FM4
TK[FM5]
TK[FM6]TK[FM4]TK[FM2]
TO HVTB
L3L1 L2
CB7
105
103
104
FMC2
37B
35B
36B
FM2
TK[FM5]
13E
TK[FM3]
13C
TK[FM6]
13F
TK[FM4]
13D
LEGEND
AI ANTI ICE THERMOSTAT AFS AIR FLOW SWITCH AR AUXILIARY RELAY ATB AUXILIARY TERMINAL BLOCK BM BLOWER MOTOR BMC BLOWER MOTOR CONTACTOR CC COMPRESSOR CONTACTOR CB CIRCUIT BREAKER C. HTR CRANKCASE HEATER CR CONTROL RELAY COMP COMPRESSOR DTS DISCHARGE TEMPERATURE SENSOR FL FUSE LINK
101
102
FMC2
FCS FAN CYCLING SWITCH FM FAN MOTOR (CONDENSER) FMC FAN MOTOR CONTACTOR
37B
36B
FM2
FMC1
ATB
2
FMC2
FR FAULT RELAY HC HEATER CONTACTOR HPS HIGH PRESSURE SWITCH HVTB HIGH VOLTAGE TERMINAL BLOCK H HEATER JP JUMPER L1 LINE 1 L2 LINE 2 L3 LINE 3 LPS LOW PRESSURE SWITCH LUG LUG GROUND LLS LEAD LAG JUMPER IN SM NTB NEUTRAL TERMINAL BLOCK OLR OVER LOAD RELAY OHT OVER HEAT THERMOSTAT PDSR PUMP DOWN SOLENOID RELAY PWS PART WIND START SM SYSTEMIZER SR SAFETY RELAY SSPS SOLID STATE PROTECTIVE SYSTEM
36F
35F
37D
36D
13E13C
13F13D
FMC1
FMC2
37F
FM6
ATB
2
ATB
2
TK MOTOR THERMAL CONTACT TRANS TRANSFORMER T'STAT THERMOSTAT UVM UNDER VOLTAGE MONITOR YR COOLING RELAY
_ _ _
FIELD WIRING
+
DISCONNECT TAB - 1/4" SPLICE-CLOSED END
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE 90 OR ITS EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE
FMC4
37D
36D
35D
36F
35F
37F
FM4
FM6
FMC1
ATB
2
FMC3
FMC2
ATB
2
FMC4
OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE.
4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY END USER WITH RATING AS RECOMMENDED BY ZAMIL.
5. PLEASE ALLOW 2-3 MINUTES FOR SSPS SWITCH TO CLOSE, BEFORE STARTING THE UNIT.
6. USE DISCONNECT TAB OR SPLICE ONLY WHERE­EVER REQUIRED FOR EXTENSION OF ORIGINAL WIRE.
7. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE ACROSS TERMINAL 4A/4B & 2 OF SYSTEMIZER IS 24 VAC. ALSO COMPRESSOR LOCKOUT LIGHT IS ON.
8. FOR UNIT WITH OPTIONAL OPS/DTS, FOLLOW SR COIL CONNECTION AS SHOWN IN OPS/DTS CONNECTION BLOCK.
9. IF HEATERS ARE FACTORY INSTALLED, PLEASE READ BROKEN LINES AS CONTINUOUS LINES.
10. HVTB 1 NOT REQUIRED FOR NON HEATER MODELS.
11.COMPRESSORS ARE PROVIDED WITH INTERNAL THERMAL PROTECTOR FOR OVERLOAD PROTECTION. EXTERNAL OLR IS PROVIDED FOR ADDED PROTECTION & AVAILABLE FOR PDS180 & ABOVE.
12.
NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER SUPPLY ONLY.
+
0
C
18
ECONOMIZER CONNECTION
AQS
OAT
EC
SAT
ECONOMIZER BOARD
POT2POT1LE D2LED1 POT4POT3
LED3
LED4
FCC
COUNTER
MTR3
STS
FS040
1
2
8
COM
24V
0-10V
AQS
J1
RAD
MTR2
ECON BRD
OAD
MTR1
ODS
LEGEND
SAT SUPPLY AIR THERMISTOR AQS AIR QUALITY SENSOR OAT OUTDOOR AIR THERMOSTAT FCC FREE COOLING COUNTER OAD OUTDOOR AIR DAMPER MOTOR RAD RETURN AIR DAMPER MOTOR STS SUPPLY AIR TEMPERATURE SENSOR MTR DAMPER MOTOR EC ENTHALPY CONTROLLER
NOTES
1. DAMPER MOTOR IS NOT REQUIRED FOR SINGLE DAMPER MOTOR APPLICATION.
2.
IF EC OR OAT OPTION IS FACTORY INSTALLED, PLEASE READ BROKEN LINES AS CONTINUOUS LINES.
19
INSTALLATION INSTRUCTIONS
GENERAL
The complete shipment should be inspected for damage. Any damage, visible or concealed, should be reported immedi­ately to the delivery man or driver. Any damage visible at the time of delivery should be noted on the shipment invoice. These units are shipped completely assembled and wired. These units does not require any refrigerant tube installation at the field. Units require external power, thermostat wiring, condensate drain piping and ducting as applicable. Size of unit for an installation should be based on a heat gain calculation made according to applicable standards. Units must also be installed in accordance with regulations of the "National Fire Protection Association" and local electrical codes. Where local regulations vary with instruction furnished, installer should adhere to local standards. Prepare your concrete pad or steel stand as applicable. Remove shipping protective covers and wooden crating and lift unit from base and place in position with necessary applicable vibration isolators. Equipment must be installed so as to allow for service access and air circulation in accordance with these instructions and other Zamil publications for the specific equipment being installed.
LOCATION OF UNIT
When selecting the location for the unit, the following points should be kept in mind:
1. Provisions for a concrete slab which will allow for minimum clearance from building or structures
2. That the terrain allows for drainage away from the unit.
3. If the unit is to be roof mounted, inspect the roof for load bearing capacity. The roof should have sufficient structural strength to carry the weight of the unit.
4. Availability of electric power.
5. Position the unit to provide for unrestricted air circulation and to prevent any possibility of air recirculation.
6. Check minimum clearances required for your unit, with regard to walls, or other obstructions.
7. Air cooled equipment should not be installed under low structural overhangs which can cause condenser air recircu­lation or restriction.
8. Care should be taken to prevent air from other sources from entering condenser, if this air is at a high temperature.
WIRING
All wiring must comply with the "National Electric Code" and local electrical standards. The power supply, voltage, frequency and phase must coincide with the unit nameplate. Power wiring to the equipment must be adequately sized for maximum ampacity as shown on unit name plate. The unit wiring diagram, completely illustrates the internal wiring and field connection needed for power supply and control wiring. The power supply should be run through the sized shielded cable or rigid conduit and through a separate fused discon­nect switch/circuit breaker. For control wiring, use approved thermostat wire (minimum 18 gauge). Never use telephone wire for this purpose. A sized circuit breaker/fused disconnect switch should be located adjacent to the unit for safety & servicing purposes. Wiring connection to the unit must have insulation suitable for temperatures of a minimum of 600C. Minimum circuit ampacity for each model is shown on the name plate and product catalog. Equipment wiring diagram should be examined and thoroughly understood before field wiring connections are made. Power supply should be checked to be certain that supply voltage agrees with equipment nameplate. Serious damage to compressors and motors can occur, if improper voltage is applied.
START-UP INSPECTION & CHECK LIST
After the installation is completed in all respect, the following points should be covered before the system is switched on for operation.
1. Remove or loosen shipping retainers under motor compressors. Make sure the hold down nuts on spring mounted
compressors are not touching the compressor feet.
2. Make sure all electrical fasteners/connections are tight and clean.
3. All controls are set according to manufacturer's instructions (low & high pressure switch, pump down pressure switch,
fan cycling switch, etc...)
4. Make sure all valves are open (compressor suction & discharge service valves, liquid line, etc.).
5. Follow all the instructions from the warning tags and stickers.
20
6. Compressor crankcase heater should be energized for 24 hours (special attention should be taken to disable com-
pressor contactor before energizing the unit fitted with pump down controls. If not, compressor may operate for few minutes to pumpdown the system, even the thermostat is OFF).
7. Thorough inspection on evaporator coil, condenser coil and other components for any physical damage.
8. Expansion valve bulb is strapped properly at correct location.
9. Circuit breaker/fused disconnect switch.
10. Blower fan belt is properly tightened and pulleys are properly aligned.
11. Blower fan & condenser fans are at correct rotation and their mountings are properly tightened.
12. All refrigerant service valve caps are installed.
13. All piping, piping insulation and piping supports are properly installed.
14. Thermostat is the right one and installed properly.
15. Duct work and accessories (check the following list and select whichever applicable to each jobs).
Flexible Connection
Air Filters Clean
Air Filter Access Door Gasket
Sound Attenuators (If Applicable)
Fresh Air Intake
Ductwork Caulking Inside/Outside Building
Ductwork Supports Inside/Outside Building
Duct Leakage Inside/Outside Building
Volume Dampers
Volume Damper Access Doors
Fire Dampers
Fire Damper Access Doors
Transfer Grilles/Door Grilles
Duct Insulation/Liner
Diffusers/Grilles
Duct Humidistat
Filter flag
CHECK-OUT & OPERATIONAL START-UP PROCEDURE
After the completion of inspection and check list, the following points should be covered before system is placed in operation.
1. Connect the manifold gauge to suction & discharge line service valves. Prepare recommended instruments for check-
ing Voltage, Amps, RPM, CFM, static pressure, etc.
2. Start the blower fan and condenser fan. Check the amperage against the nameplate ampere.
3. Start the compressor and observe the following points (on multiple compressor units, it is highly recommended to start
the compressors one by one to achieve careful observation for each compressor). (a) Check compressor discharge and suction pressures. If not within system design limits, determine why and take
corrective action.
(b) Check liquid line sight glass and expansion valve operation. If there are indications that more refrigerant is re-
quired, leak test all connections and system components and repair any leaks before adding refrigerant.
(c) Observe oil level in compressor crankcase sight glass (if available) and add oil as necessary to bring to recom-
mended oil level.
21
All compressors are charged with somewhat greater than the normal oil level required for adequate lubrication, in order to provide some allowance for oil which will be circulating in the system during operation. Depending on the system design, the amount of oil in the system at the time of compressor installation, oil lost due to leakage, etc., it may necessary either to add or remove oil from a system any time it is first placed in operation with a different compressor.
An abnormally low oil level may result in a loss of lubrication; while an excessively high oil level may result in oil slugging and possible damage to the compressor valves or excessive oil circulation. The oil level may vary consider­ably on initial start-up if liquid refrigerant is present in the crankcase, and the oil level should be checked with the compressor running after having reached a stabilized condition.
(d) Thermostatic expansion valves must be checked for proper superheat settings. Recommended superheat is 150F
to 200F.
(e) Using suitable instruments, carefully check line voltage and amperage at the compressor terminals. Voltage must
be within ±10% of that indicated on the compressor nameplate. If high or low voltage is indicated, notify the power company. The current normally should not exceed 110% of the nameplate rating. If amperage draw is excessive, immediately determine the cause and take corrective action. On three phase compressor motors, check to see that a balanced load is drawn by each phase.
(f) Carry out any necessary tests, recording airflow rates, entering/leaving temperatures, sound levels, outdoor tem-
peratures, supply airflow rates in occupied spaces and any other specified parameters.
BELT TENSION TESTING PROCEDURE INSTRUCTION
To determine the lbs. force required to tension a drive, you simply do the following:
1. Measure the Belt span as shown.
2. Divide belt span by 64 to get belt deflection needed to check tension.
3. Set large "0" ring on span scale at required belt deflection. This scale is in 1/16" increments.
4. Set small "0" ring at zero on the "Force Scale" (plunger).
5. Place the larger end of the tension checker squarely on one belt at the center of the belt span. Apply force on the plunger until the bottom of the large "0" ring is even with the top of the next belt or with the bottom of a straight edge laid across the sheaves.
6. Read the force scale under the small "0" ring to determine force required to give the needed deflection.
7. Compare the force scale reading with the correct value for the belt style and cross section used, as given in table on next page. The force should be between the minimum and maximum values shown.
8. If there is too little deflection force, the belts should be tightened. If there is too much defection force, the belts should be loosened.
EXAMPLE
1. Belt Span 64" (Small Sheave is 3.0 P.D. with "A" type belt.
2. 64 = 1" Deflection needed. 64
3. Set large "0" ring at 1" on span scale.
be
4. Set small "0" ring at zero plunger.
5. Check the force – lbs. required for a 1" deflection of the belt.
6. Press down on plunger until the bottom of the large "0" ring is even with top of the next belt in the set or with the bottom
of a straight edge.
7. 'A' type belts table shows an "A" belt with 3.0" P.D. Small sheave should have a deflection force between 1-1/2 lbs.
and 2-1/8 lbs.
8. Increase or decrease the tension on belts until the deflection force is between 1-1/2 lbs. 2-1/8 lbs.
NOTE:
Tension new drives at the maximum deflection force recommended. Check the tension at least two times during the first day's operation as there normally will be a rapid decrease in belt tension until belts have run in. Check the tension periodically after the first day's operation and keep tension in recommended area. The correct operating tension for a V-belt drive is the lowest tension at which the belts will not slip under the peak load conditions. Shafts must be adequate for the tensions required.
22
BELT TENSION TESTING PROCEDURE
BELT SPAN
64
BELT SPAN
SMALL
"0"
RING
LARGE
"0"
RING
DEFLECTION =
FORCE SCALE
SPAN SCALE
BELT TENSION CHECKER MEASURE THE BELT DEFLECTION FORCE
BELTS
BELT TYPE
A
B
BELT
CROSS
SECTION
3 L
4 L
5 L
PULLEY PITCH DIA. (P.D.)
SMALL
RANGE
1.25 – 1.75 2 – 2.25
2.5 – 3
2.1 – 2.8 3 – 3.5
3.7 – 5
3 – 4.2
4.5 – 5.2
DEFLECTION FORCE - LBS.
MINIMUM
1/2 5/8 3/4
1-1/8 1-1/2 1-7/8
2
2-3/8
MAXIMUM
5/8 7/8
1-1/8
1-5/8 2-1/8 2-5/8
2-7/8 3-3/8
23
ELECTRICAL
ELECTRIC POWER SUPPLY
All wiring should be in accordance with National Electric Code and local standards.
Before making an installation, check the electric power supply. The power supply must be of the same characteristics as that on the nameplate.
Normally the wire size used establishes the circuits maximum permissible load. For example a number 12 wire circuit is considered to be a 20 ampere circuit and is protected by a 20 ampere fuse. The unit amperage nameplate rating should not exceed 80% of the circuit rating, 16 amperes.
When identifying electrical trouble in any unit, check the power supply at the main disconnect switch and the unit. A high or low voltage condition may prevent the unit from starting, or if the unit is running, compressor can cut-off automatically on the motor overload. On some installations, the voltage may be entirely adequate when tested, but may drop or surge some time later due to increase or decrease of load on the power line. This condition may be repeated daily at the same hour. When this condition is suspected, make arrangements with the local power supplier to place a recording voltmeter on the line to check and correct the erratic voltage conditions.
The voltage drop should not be more or less than 10% of the units rated voltage. If the voltage at the meter is correct, but the voltage at the unit fluctuates 10% or more, the branch circuit is not adequate.
UNBALANCED VOLTAGE
Unbalanced voltage on a three phase circuit may be the source of electrical trouble. If balanced supply voltages are not always maintained, so with the three line currents will not be equal. Unbalanced voltage on a three phase compressor motor may overheat and trip the motor on external or internal current sensing motor protector, whichever one is provided.
To determine that an unbalanced voltage condition exists, the supply voltage at the main disconnect switch and at the unit disconnect switch should be measured. Voltage unbalance is calculated as follows. The percentage of voltage unbalance equals one hundred times the ratio of the Maximum Voltage Deviation from the Average Voltage, and the Average Voltage.
Voltage unbalance, % = 100 x
The percentage increase in temperature rise in a phase winding resulting from voltage unbalance will be approximately two times the square of the voltage unbalance.
Because of the unbalanced voltage condition in a three phase circuit, it is possible that one phase winding in the com­pressor motor may be over-heated while the other have a temperature within normal limits. Where unbalanced voltage on a three phase circuit exists, the power company should be notified of such unbalance to determine, if the situation can be corrected.
A common source of unbalanced voltage on a three phase circuit is a single phase load between two of the three phases. A large lighting or heating circuit connection to one phase of a three phase circuit can easily cause sufficient variations in motor currents to endanger the motor. Interchange the single phase loads to equally divide the entire loads among the three phases. Balance the supply voltage as evenly as possible.
Maximum voltage deviation from average voltage
Average voltage
Unless the unbalanced voltage condition can be corrected, the only way to insure motor safety is to be sure that the protectors are in the high current phase when using two leg protection, or to use protectors in all three legs.
24
MOTOR CONTACTOR
The motor controller (contactor) is a load current carrying device which makes and breaks to start and stop the compres­sor motor. The magnetic coil of the controller is energized to make and break the contactor contacts. Frequently, motor contactors are subjected to quick cycling due to various causes. This may cause burned and/or sticking contacts and can cause a compressor motor failure, even though the motor overload protectors trip and open the control circuit.
FAN MOTOR
The condenser fan motor is a single speed electrical motor with ball bearings, protected with an automatic reset internal overload.
CRANKCASE HEATERS
The function of the crankcase heater is to hold the compressor oil reservoir at a temperature higher than the coldest part of the system. The low wattage heaters are energize continuously and it is not necessary to have them de-energize when the compressor is operating.
Power must be supplied to crankcase heater for minimum of 12 hours prior to system start up. If power is off 6 hours or more, crankcase heater must be on for 12 hours before operating the system. Failure to follow these instructions may result in compressor damage.
Crankcase heaters are effective to retard migration of liquid refrigerant to the crankcase during off cycle. But they are not a remedy for slugging or flood back due to liquid refrigerant accumulating in a trapped suction line, improper piping practice, over feeding to the evaporator, leaking solenoid valve, etc.
In some cases where migration of refrigerant to the crankcase occurred due to long storage time, shutdown period, defective components, etc. The crankcase heater may be ineffective. Such cases may be easily observed by high oil level and cold crankcase. In these cases, it is highly recommended to front seat or close both suction and discharge service valves of the compressor and release all liquid refrigerant from the compressor.
The liquid refrigerant dilutes the oil in the crankcase and the refrigerant rich oil will be pumped to the rods and the bearings through the crankshaft. As the refrigerant boils off, there will not be enough oil for sufficient lubrication at the bearings furthest from the oil pump. The center and rear bearings may seize or may wear enough to allow the rotor to drop and drag on the stator causing it to short. Also the liquid refrigerant washes the oil off the pistons and cylinders during the suction stroke causing them to wear during the compression stroke.
When the crankcase is filled with liquid refrigerant and the compressor starts severe agitation, oil foaming etc. will cause major damage to the compressor.
Periodic checking for proper operation of crankcase heater is highly recommended.
LUBE OIL PROTECTION CONTROL
Pressure lubricated refrigeration compressors require a pressure protector in the event of an oil pressure failure. The lube oil pressure protection control is factory set to conform with compressor manufacturers specifications and should not be changed.
The control measures the net oil pressure available to circulate oil through the lubrication system. The positive displace­ment oil pump circulates the refrigerant oil through the lubrication system. Since the oil pump is connected directly to the compressor crankcase, the inlet pressure to the oil pump will always be the crankcase pressure. The oil pump outlet pressure will be the crankcase pressure plus the oil pump pressure. Therefore, net oil pump pressure will always be the pump outlet pressure minus the crankcase pressure.
The control contains a built-in time delay switch that is a trip-free expansion rod device actuated by a resistance heater. The control is factory set to cut-in at 18 PSIG and cut out at 9 PSIG. When the compressor starts the resistance heater
of the time delay becomes energized. If the net oil pressure does not build to 18 PSIG or above within 120 seconds, the time delay trips to stop the compressor. If the net oil pressure drops below 18 PSIG, but not below 9 PSIG during a running cycle, the time delay resistance heater becomes energized and unless the net oil pressure returns to 18 PSIG or above during the 120 seconds safety time period, the compressor will shut down. The compressor will shut down when­ever the net oil pressure drops below 9 PSIG, and will never run for more than the predetermined 120 seconds on abnormal oil pressure.
25
OIL PUMP
OUTLET PRESSURE
CRANKCASE
PRESSURE
NET OIL
PRESSURE
78 60 18
_
=
New series of solid state lube oil protection controls with modern pressure transducers are replacing the old type me­chanical expansion rod-resistance heater type oil protection controls.
FEATURES:
An entirely new control concept. This unique design incorporates a modern pressure transducer to monitor oil pressure.
Each control reflects improved calibration stability over the control's entire pressure range.
Controls boast truly accurate timing despite ambient temperature and voltage variations.
All electronic components are purposely "over-sized" and computer-matched to provide the greatest safety factor and
dependable service life.
Control's solid state circuitry is completely encapsulated to protect the components from the harmful effects of vibra-
tion, dirt or moisture.
Controls reset instantaneously, thanks to the precise solid state timing circuit. No annoying wait for old-fashioned timer
heater to cool down.
Control module is interchangeable with the old type conventional oil protection and with competitive brands of oil
protection controls. An exact replacement from a mounting, wiring and logic function standpoint.
Control maintains timing over the full voltage range of 102 to 264 VAC. Voltage selection is not necessary.
Unit is not position sensitive.
Users are offered a choice of controls with or without cover, a handy mounting bracket and other options.
"Logic" circuitry in the module monitors oil pressure pulses during marginal operation and integrates them resulting in
a longer span of time before lock-out occurs.
Last, but not least, it has enlarged the reset button to a new "thumb-sized" dimension. The reset button is slightly
recessed to protect it from damage.
VOLTAGE MONITOR
This device protects the motors in the unit from faults such as; under or over voltage, unbalance & phase reversal of the power supply. When the device sensed such faults, it will cut-off the supply in the control circuit thereby cutting off power to the motors. The voltage monitor will re-set automatically when power is brought back to it’s normal conditions.
LINE VOLTAGE
RANGE
190 - 480 VAC
TRIP & RE-SET VOLTAGE (% OF SET POINT)
UNDER VOLTAGE
TRIP
RE-SET
90%
93%
OVER VOLTAGE
TRIP
RE-SET
110%
107%
PHASE IMBALANCE
TRIP6%RE-SET
4.5%
ELECTRONIC THERMOSTATS General Informations: Single stage or two stage thermostats provide low voltage control of one or two stage heating
and/or cooling applications. The thermostat normally displays room temperature, mode of operation and which system is currently on.
You may select different heating and cooling setpoints for the systems to maintain (example 700F in heating and 750F in cooling). Raising or lowering the setpoints in heating or cooling is as simple as pushing a button.
The thermostat also allows you to select continuous fan operation, (useful when using an electronic air cleaner), or have the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and should not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers/ diffusers.
26
CONTROLS & SEQUENCE OF OPERATION
Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct rotation when the system is operated. Verification of correct rotation is by observing that the suction pressure drops and discharge pressure rises when compressor run. Reverse rotation results in abnormal sound, as well as, substantially low current draw and by interchanging power supply wire L1 & L3 will correct this problem.
The operation of the air conditioning unit is controlled by a 24VAC electronic control board.
Mode:
Select the desired mode of operation by continuous press­ing of the MODE button:
Controls cooling system only (the word COOL will display for 5 seconds).
Controls heating system only (the word HEAT will display for 5 seconds).
HEAT/COOL - Controls both systems automati­cally (the word AUTO will display for 5 seconds).
OFF - Systems will not operate
24 V (C)
24 V
R
Y2
Y1
L I G
G H T
W1
S
W2
Equipment Relays
2nd stage Cooling
1st stage Cooling
Fan Relay
1st stage Heating
2nd stage Heating
24VAC
Line Voltage Transformer
Cooling:
Select the temperature you want your cooling system to maintain by pressing and holding the COOLING button under the or symbols until the desired tempera­ture is displayed. The control setpoint temperature is dis­played for 5 seconds.
LED 1
LED 2
Thermostat
Field Wiring
*
Clogged Filter
Compressor Fault
Clogged filter switch not provided
*
* Clogged filter switch not provided
Heating:
Select the temperature you want your heating system to maintain by pressing and holding the HEATING button under the or symbols until the desired temperature is displayed. The control setpoint temperature is displayed for 5 seconds.
Fan:
The fan will be energized automatically when the systems are operating but no indication of this on the display. To select continuous fan operation, press the FAN button and the display will show . This is recommended for electronic air cleaners and continuous ventilation requirements.
Off
When the word OFF is displayed the heating and cooling systems will not operate. Avoid using the OFF mode during extremely cold weather to prevent damage from freezing.
Auto:
Selecting this mode of operation will control both heating and cooling systems. The thermostat will automatically switch from one to the other as determined by the selected temperatures in heating and cooling. NOTE: The thermostat always maintains a minimum 20F (10C) difference or dead band between the heating and cooling setpoints.
Celsius / Fahrenheit
Simultaneously press and to switch between Celsius and Fahrenheit temperature display.
27
REFRIGERATION
COMPRESSOR
Single scroll compressor for models PDS036 to PDS075 and dual scroll compressors for model PDS090 to PDS600 are used as standard. Optional single semi-hermetic compressor for models PDS036 to PDS150 (single circuit). All other models are dual semi-hermetic compressors (dual circuit). The compressors are equipped with internal motor protection and also provided with vibration isolators. Oil pressure control is provided on units with semi-hermetic compressor only. Each compressor has lockout devices to protect it from short cycling when tripped by safety controls. The compressor motors conform to NEMA MG-1 & MG-2. Scroll Compressors are used in some of these units. The major benefits being:
1. Low Sound Level: Quieter operation because of no dynamic suction and discharge valves action.
2. Low vibration and discharge pulses.
3. High Energy Efficiency: Because of high volumetric efficiency it minimize pressure and heat transfer losses.
4. High Capacity: Due to its high mass flow and high compression ratios.
5. High Durability: With its robust design, few moving parts, low motor strains, large internal volume for liquid handling makes this compressor highly reliable.
6. High Charge Limit: Therefore, lower applied costs as no suction accumulator required, no need for pump down system and check valve in discharge line.
Low capacity can be caused by inefficient compressor, that is, the compressor does not pump sufficient quantity of refrigerant, even though a full charge is available in the system. Electrical and mechanical tests should be performed to determine if the compressor is defective. If the compressor is found to be all right but the electrical components are defective, remove and replace the defective electrical components only. Below are some tests that should be performed on the compressor to determine, if the compressor is defective.
1. Test compressor motor winding for ground.
2. Test compressor motor windings for continuity.
3. Test that compressor motor will run both without a load and under a load.
4. Test the current or ampere drawn.
5. Observe sound level of compressor.
To establish that the compressor suction and discharge valves are operating and holding properly, attach gauges to the liquid and suction service valves. "Front seat" the liquid service valve.
Start the compressor, allowing it to operate long enough to pump down to approximately 1 PSIG. Shut the compressor off and observe the compound gauge. The gauge pressure may build rapidly. Repeat the pump down process several times observing the gauge pressure each time after the compressor stops. If the gauge pressure builds rapidly each time after the compressor stops, it indicates that the compressor discharge valves are not holding and refrigerant is leaking from the high side to the low side of the compressor.
To check the suction valves, assuming that the discharge valves are holding, allow the compressor to operate long enough to pump down the system to approximately 10 inches of vacuum. If the compressor required longer time to accomplish this, then the suction valves are not holding and the compressor should be changed out as it is defective.
MOTOR COMPRESSOR BURN OUT PROCEDURE
The extent of the contamination in a system will indicate the amount of clean-up necessary. If a compressor had burned out, the following method of clean-up is recommended:
1. Discharge the refrigerant from the system.
2. Replace the inoperative compressor.
3. Clean up the system thoroughly and remove all the contaminations.
4. Install a system cleaner or filter drier in the suction line and replace the liquid line filter drier.
5. Connect a vacuum pump to both the low and the high side of the system to remove air and other non-condensables from the system.
6. Allow the vacuum pump to operate until a pressure of 500 microns is achieved.
7. Recharge the system and allow it to operate 8 to 12 hours.
8. Take an oil sample and test for acidity.
28
If the first acidity test shows that the acid content is below the safe level, as indicated in the test kit instructions, and the oil is clean, the clean-out system can be removed. If an in-line suction filter drier was used, it can remain in the system provided the pressure drop through the filter does not exceed the manufacturers listed pressure drop. For a badly contaminated system that indicates acid in the oil after 8 to 12 hours of operation, change the suction and liquid line filter­driers and check the system after 24 hours of operation.
There are instances where contaminants are discovered in a refrigeration system with the compressor still operational. The same procedure applies, when cleaning these systems, as on a compressor burn-out.
SOURCE OF CONTAMINATION
There are many ways in which a refrigerant system can become contaminated. The most common of these are as follows:
1. Improper or inadequate dehydration.
2. Wet refrigerant.
3. Wet oil (caution: It is best to purchase oil in small containers and use as needed. Open containers will absorb mois­ture).
4. Refrigerant leaks (allowing system to operate in a vacuum).
5. Failure to remove oil and moisture after having opened the system for repair.
6. Higher than normal operating temperatures and pressures will cause a breakdown of the oil and refrigerant.
7. Using oil other than specified (Sunoco 3G is recommended).
8. Improper use of soldering or brazing flux.
HIGH PRESSURE SWITCH
A high pressure switch is located in the discharge line and senses the discharge pressure. Should the discharge pressure exceed 450 psig, the control will open turning off the compressor. The control is designed to protect against excessive discharge temperatures and pressures which can cause compressor overheating and damage to the motor windings or valves.
Should the control open, it will remain open until the pressure in the system is lowered to 360 psig. Tripping of the high pressure control is normally due to:
1. Restricted condenser coil.
2. Overcharge of refrigerant.
3. Defective fan motor or fan capacitor.
4. Incorrect fan blade.
5. Fan motor internal overload tripping due to lack of lubrication or defective bearings.
To test the high pressure control: Install a high pressure gauge to the access valve or the liquid line valve. Disconnect the condenser fan motor. Turn on the unit and observe the pressure on the gauge when the compressor trip off. The pressure should be 450 ± 10 psig. Allow the system to remain off, until the gauge pressure drop to approximately 360 ± 15 psig and reconnect the condenser fan motor. Reset the unit by putting off the thermostat and if the high pressure control has closed, the compressor will restart.
LOW PRESSURE SWITCH
To provide protection for the compressor in the event of refrigerant loss, a low pressure control is installed in the suction line.
The control is preset to open when the suction pressure is 25 psig. The contacts of the control will close when the suction pressure rises to 50 psig. To test the control for the correct pressure setting, install a compound gauge to the gauge port on the suction service valve. "Front seat" the liquid valve and start the unit. Note the gauge pressure, when the compres­sor stops.
To determine the cut-in pressure, allow the suction pressure to build slowly and observe the gauge pressure at the time when contact closes. A good functional low pressure switch must have both cut-out and cut-in pressure within ± 2 psig.
29
PUMP DOWN CONTROL
A pump down control is a solenoid type valve installed in the liquid line to prevent the flow of refrigerant into the evapo­rator during the off cycle. The valve is mounted in the liquid line refrigerant stream or at other suitable location in the liquid line, but ahead of metering device.
The thermostat and other controls are used in conjunction with the solenoid valve to control the operation. A pump down pressure switch is used to stop the compressor at pre-determine evaporator pressure.
The thermostat is wired through the controls to energize the liquid line solenoid valve when the room temperature calls for cooling, its contacts closes and through the controls it energize the solenoid valve. The opened solenoid valve allows refrigerant to flow to the evaporator coil - causing the evaporator pressure to rise, the low pressure control contacts to close and the compressor to start.
When the thermostat is satisfied, the solenoid valve closes and the compressor continues to run until a substantial portion of the refrigerant has been pumped out from the evaporator. When the pump down pressure switch cut-out setting is achieved, power to the control circuit is interrupted and the compressor stops.
A pump down control may be necessary on an installation where additional protection for the compressor is required to prevent slugging of oil or liquid refrigerant.
Below are some conditions which may exist in an installation where additional protection is required:
1. Migration of refrigerant to the compressor during the off cycle.
2. Flooding, at start-up, due to improperly trapped lines or coil.
3. Suction line in slab or beneath ground forming a large trap.
4. Suction line in cool area causing refrigerant to condense during off cycle.
5. Where condensing unit is installed using existing coils and copper lines, or on a new installation where the above said
conditions exist that cannot be avoided, which could result in compressor damage.
30
TROUBLE SHOOTING CHART
SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE
Compressor will not start – no hum.
Compressor will not start – hums but trips on overload protector.
Compressor starts and runs, but short cycles on overload protector.
1. Line disconnect switch open.
2. Fuse removed or blown.
3. Overload protector tripped.
4. Control stuck in open position.
5. Control off due to cold location.
6. Wiring improper or loose.
7. Thermostat defective or improperly installed.
8. Control circuit open.
9. Burned/open circuit motor winding.
1. Improperly wired.
2. Low voltage to unit.
3. Compressor motor has a winding open or shorted.
4. Internal mechanical trouble in com­pressor.
5. Liquid refrigerant in compressor.
6. High discharge pressure.
1. Additional current passing through overload protector.
2. Low voltage to unit (or unbalanced if three phase).
3. Overload protector defective.
4. Excessive discharge pressure.
5. Suction pressure too high.
6. Compressor too hot - return gas hot.
1. Close start or disconnect switch.
2. Replace fuse.
3. Refer to electrical section.
4. Repair or replace control.
5. Relocate control.
6. Check wiring against diagram.
7. Replace or relocate.
8. Trace control circuit with wiring dia­gram and repair.
9. Replace the compressor with all pre­cautions.
1. Check wiring against diagram.
2. Determine reason and correct.
3. Replace compressor.
4. Replace compressor.
5. Check crankcase heater.
6. Unequilized pressure in the system.
1. Check wiring diagram. Check for added fan motors, pumps, etc. con­nected to wrong side of protector.
2. Determine the reason and correct.
3. Check current, replace protector.
4. Check airflow across the condenser coil, restrictions in refrigeration system.
5. Check for possibility of misapplica­tion. Use stronger unit.
6. Check refrigerant charge (fix leak), add if necessary.
Space temperature too high. 1. Control setting too high.
2. Expansion valve too small.
3. Cooling coils too small.
4. Inadequate air circulation.
Suction line frosted or sweating.
Liquid line frosted or sweating.
1. Expansion valve passing excess re-
2. Expansion valve stuck open.
3. Evaporator fan not running.
4. Overcharge of refrigerant.
1. Restriction in dehydrator or strainer.
2. Liquid shut-off valve partially closed.
frigerant or is oversized.
31
1. Reset control.
2. Use larger valve.
3. Add surface or replace.
4. Improve air movement.
1. Re-adjust valve or replace with smaller valve.
2. Clean valve of foreign particles, re­place if necessary.
3. Determine reason and correct.
4. Correct charge.
1. Replace part.
2. Open valve fully.
TROUBLE SHOOTING CHART
SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE
Units runs OK, but short cycles on.
Unit operates long or continu­ously.
Evaporator ices up.
1. Overload protector.
2. Thermostat.
3. High pressure cut-out due to: (a) Insufficient air. (b) Overcharge. (c) Air in system.
4. Low pressure cut-out due to: (a) Undercharge. (b) Restriction in expansion device.
1. Shortage of refrigerant.
2. Control contacts stuck or frozen closed.
3. Refrigerated or air conditioned space has excessive load or poor insulation.
4. System inadequate to handle load.
5. Evaporator coil iced.
6. Restriction in refrigeration system.
7. Dirty condenser.
8. Filter dirty.
1. Restricted airflow.
2. Dirty air filter.
3. Short of refrigerant.
4. Low air volume.
5. Restricted distributor tube.
6. Restricted liquid line/low liquid line pressure.
1. Check the cause.
2. Differential set too close - widen.
3. (a) Check airflow to the condenser correct.
(b) Reduce refrigerant charge. (c) Purge.
4. (a) Fix leak, add refrigerant.
(b) Replace device.
1. Fix leak, add charge.
2. Clean contacts or replace control.
3. Determine the fault and correct.
4. Replace with larger system.
5. Defrost.
6. Determine location and remove.
7. Clean condenser.
8. Clean or replace.
1. Check for dirt or lint on coil.
2. Clean or replace. Advice customer
on periodic cleaning of filter.
3. Check system pressure. Take super-
heat reading. Add refrigerant.
4. Check for dirty air filter or loose belt.
5. Check for warm distributor tube.
6. Check for restriction in lines/improve
liquid line pressure by proper charg­ing or installing fan cycle switch, etc.
Head pressure too high.
Head pressure too low.
1. Refrigerant overcharge.
2. Air in system.
3. Dirty condenser.
4. Malfunction of condenser fan (air-
5. Excessive air temperature entering
6. Restriction in discharge line.
1.Low ambient temperatures (air-
2. Refrigerant shortage.
3. Damaged valves in compressor.
cooled).
condenser.
cooled).
1. Correct the refrigerant charge.
2. Recharge the system after a thorough
triple evacuation.
3. Clean.
4. Check and correct or replace.
5. Check for short circuiting of con-
denser discharge air, correct it.
6. Correct it.
1. Install fan cycling switch, if not pro-
vided. Check the setting and opera­tion, if provided.
2. Correct the refrigerant charge after
leak testing.
3. Repair/replace the compressor.
32
TROUBLE SHOOTING CHART
SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE
High suction pressure.
Loss of oil pressure.
1. High load on evaporator. Load in ex­cess of design conditions.
2. Unbalanced system. Oversized air han­dling unit matched with under sized condensing unit.
3. Compressor discharge valve leaking.
4. Expansion valve widely open.
5. Improper bulb location or installation.
1. Loss of oil from compressor due to: (a) Oil trapping in system. (b) Compressor short cycling. (c) Insufficient oil in system. (d) Operation at excessively low suction
pressure.
2. Excessive liquid refrigerant returning to compressor.
3. Malfunctioning oil pump.
4. Restriction in oil pump inlet screen.
1. Check the design.
2. Follow manufacturer's guide line and correct it.
3. Repair/replace compressor.
4. Check and adjust the superheat ac­cordingly.
5. Check the expansion valve bulb is properly tighten at correct location.
1. (a) Correct the system piping. (b) Trace out the wiring/defective con-
trols/components, etc. and correct it. (c) Add oil. (d) Check the superheat of expansion
valve and other possible causes
like clogged filter, low CFM, iced
evaporator etc. & correct it.
2. Check the system for correct super­heat & other possible causes like clogged filter, low CFM, iced evapo­rator, etc. and correct it.
3. Repair or replace it.
4. Clean/replace it (oil change recommended).
Relay defective or burned out.
Unit noisy. 1. Loose parts or mountings.
1. Incorrect relay.
2. Incorrect mounting angle.
3. Line voltage too high or too low.
4. Excessive short cycling.
5.
Relay being influenced by loose mounting.
2. Tubing rattle.
3. Bent fan blade causing vibration.
4. Fan motor bearings worn.
1. Check and replace.
2. Remount relay in correct position.
3. Determine reason and correct.
4. Determine reason and correct.
5. Remount rigidly.
1. Find and tighten.
2. Tighten the pipe support.
3. Replace blade.
4. Replace motor.
33
PARTS LIST (SINGLE CIRCUIT)
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
DISTRIBUTOR
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS036H PDS036M PDS036F PDS048H PDS048M PDS048F PDS060H PDS060M PDS060F
800-674-26 N.A. 800-674-28 800-674-20 800-674-21 800-674-22 800-674-13 800-674-14 800-674-15
800-098-55 N.A. 800-098-55 800-098-57 800-098-55 800-098-55 800-098-59 800-098-55 800-098-55
800-688-03 800-688-03 800-688-02 800-688-05 800-688-05 800-688-06 800-688-07 800-688-07 800-688-08
800-098-57 800-098-55 800-098-55 800-098-59 800-098-55 800-098-55 800-098-59 800-098-57 800-098-55
800-227-05 800-227-05 800-227-06 800-227-10 800-227-10 800-227-11 800-577-00 800-227-14 800-227-15
800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08
800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00
800-187-01 800-187-01 800-187-01 800-187-02 800-187-02 800-187-02 800-187-03 800-187-03 800-187-03
800-198-00 800-198-00 800-198-00 800-198-00 800-198-00 800-198-00 800-198-00 800-198-00 800-198-00
800-077-16 800-077-16 800-077-16 800-077-16 800-077-16 800-077-16 800-077-16 800-077-16 800-077-16
800-077-16 800-077-11 800-077-11 800-077-11 800-077-11 800-077-11 800-077-11 800-077-11 800-077-11
800-705-88 800-705-88 800-705-88 800-705-88 800-705-88 800-705-88 800-705-88 800-705-88 800-705-88
800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31
N.A. N.A. N.A. N.A. N.A. N.A. 800-688-16 800-688-16 800-688-17
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
DISTRIBUTOR
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS075H PDS075M PDS075F PDS090H PDS090M PDS090F PDS100H PDS100M PDS100F
800-674-23 800-674-24 800-674-25 N.A. N.A. N.A. N.A. N.A. N.A.
800-098-59 800-098-55 800-098-55 N.A. N.A. N.A. N.A. N.A. N.A.
800-688-09 800-688-09 800-688-10 800-688-11 800-688-11 800-688-12 800-688-13 800-688-14 800-688-15
800-688-18 800-688-18 800-688-19 800-688-20 800-688-20 800-688-21 800-688-22 800-688-23 800-688-24
800-098-61 800-098-57 800-098-55 800-098-61 800-098-57 800-098-57 800-098-61 800-098-57 800-098-57
800-227-14 800-227-14 800-227-15 800-226-33 800-226-33 800-226-34 800-227-14 800-227-14 800-227-15
800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
800-531-08 800-531-08 800-531-08 800-531-05 800-531-05 800-531-05 800-531-05 800-531-05 800-531-05
800-201-00 800-201-00 800-201-00 800-200-00 800-200-00 800-200-00 800-200-01 800-200-01 800-200-01
800-187-03 800-187-03 800-187-03 800-182-00 800-182-00 800-182-00 800-182-00 800-182-00 800-182-00
800-191-00 800-191-00 800-191-00 800-198-41 800-198-41 800-198-41 800-198-45 800-198-45 800-182-00
800-077-20 800-077-20 800-077-20 800-077-20 800-077-20 800-077-20 800-077-16 800-077-23 800-077-23
800-077-16 800-077-16 800-077-16 800-077-16 800-077-16 800-077-16 800-077-22 800-077-22 800-077-22
800-705-89 800-705-89 800-705-89 800-705-91 800-705-91 800-705-91 800-705-94 800-705-94 800-705-94
800-705-38 800-705-38 800-705-38 800-705-40 800-705-40 800-705-40 800-705-41 800-705-41 800-705-41
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31
34
PARTS LIST (SINGLE CIRCUIT)
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
CAPACITY UNLOADER KITS
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS120H PDS120M PDS120F PDS150H PDS150M PDS150F
N.A. N.A. N.A. N.A. N.A. N.A.
N.A. N.A. N.A. N.A. N.A. N.A.
800-690-01 800-690-02 800-690-03 800-677-04 800-677-05 800-677-06
800-690-01 800-690-02 800-690-03 800-677-44 800-677-45 800-677-46
800-098-65 800-098-59 800-098-59 800-098-65 800-098-59 800-098-59
800-577-02 800-577-02 800-577-02 800-577-00 800-577-00 800-577-00
800-227-14 800-227-14 800-227-15 800-227-14 800-227-14 800-227-15
800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
800-531-05 800-531-05 800-531-05 800-531-05 800-531-05 800-531-05
800-200-00 800-200-00 800-200-00 800-200-00 800-200-00 800-200-00
800-185-00 800-185-00 800-185-00 800-186-00 800-186-00 800-186-00
800-077-23 800-077-23 800-077-23 800-077-23 800-077-23 800-077-23
800-077-22 800-077-22 800-077-22 800-077-22 800-077-22 800-077-22
800-705-94 800-705-94 800-705-94 800-705-20 800-705-20 800-705-20
800-705-40 800-705-40 800-705-40 800-705-40 800-705-40 800-705-40
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
CAPACITY UNLOADER KITS
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS090H PDS090M PDS090F PDS100H PDS100M PDS100F PDS120H PDS120M PDS120F
800-674-73 N.A. 800-674-75 800-674-20 800-674-21 800-674-22 800-674-13 800-674-14 800-674-15
800-098-57 N/A 800-098-55 800-098-57 800-098-55 800-098-55 800-098-59 800-098-55 800-098-55
800-226-33 800-226-33 800-226-34 800-227-14 800-227-14 800-227-15 800-227-14 800-227-14 800-227-15
800-093-11 800-093-11 800-093-11 800-093-11 800-093-11 800-093-11 800-093-11 800-093-11 800-093-11
800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08 800-531-08
800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00 800-201-00
800-187-02 800-187-02 800-187-02 800-187-02 800-187-02 800-187-02 800-187-03 800-187-03 800-187-03
800-077-16 800-077-20 800-077-20 800-077-23 800-077-23 800-077-23 800-077-23 800-077-23 800-077-23
800-077-16 800-077-16 800-077-16 800-077-22 800-077-22 800-077-22 800-077-22 800-077-22 800-077-22
800-705-89 800-705-89 800-705-89 800-705-91 800-705-91 800-705-91 800-705-91 800-705-91 800-705-91
800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38 800-705-38
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31
DUAL CIRCUIT
N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
N.A. N.A. N.A. N.A. N.A. N.A. 800-577-00 N.A. N.A.
35
PARTS LIST (DUAL CIRCUIT)
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
CAPACITY UNLOADER KITS
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS150H PDS150M PDS150F PDS180H PDS180M PDS180F PDS220H PDS220M PDS220F
800-674-23 800-674-24 800-674-25 800-674-79 800-674-80 800-674-81 800-674-01 800-674-02 800-674-03
800-098-59 800-098-55 800-098-55 800-098-63 800-098-57 800-098-57 800-098-61 800-098-57 800-098-57
800-227-14 800-227-14 800-227-15 800-226-33 800-226-33 800-226-34 800-226-33 800-226-33 800-226-34
800-093-11 800-093-11 800-093-11 800-093-12 800-093-12 800-093-12 800-098-51 800-098-51 800-098-51
800-531-08 800-531-08 800-531-08 800-531-05 800-531-05 800-531-05 800-531-05 800-531-05 800-531-05
800-201-00 800-201-00 800-201-00 800-200-00 800-200-00 800-200-00 800-200-00 800-200-00 800-200-00
800-186-00 800-186-00 800-186-00 800-182-00 800-182-00 800-182-00 800-182-00 800-182-00 800-182-00
800-077-23 800-077-23 800-077-23 800-077-24 800-077-24 800-077-24 800-077-16 800-077-24 800-077-24
800-077-22 800-077-22 800-077-22 800-077-24 800-077-24 800-077-24 800-077-24 800-077-24 800-077-24
800-705-91 800-705-91 800-705-91 800-705-94 800-705-94 800-705-94 800-705-94 800-705-94 800-705-94
800-705-38 800-705-38 800-705-38 800-705-40 800-705-40 800-705-40 800-705-40 800-705-40 800-705-40
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31
N.A. N.A. N.A. 800-688-11 800-688-11 800-688-12 800-688-13 800-688-14 800-688-15
N.A. N.A. N.A. 800-688-20 800-688-20 800-688-21 800-688-22 800-688-23 800-688-24
N.A. N.A. N.A. 800-098-61 800-098-57 800-098-57 800-098-61 800-098-57 800-098-57
N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
CAPACITY UNLOADER KITS
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS240H PDS240M PDS240F PDS300H PDS300M PDS300F PDS360H PDS360M PDS360F
800-674-36 800-674-37 800-674-38 800-674-17 800-674-18 800-674-19 800-674-70 800-674-71 800-674-72
800-098-65 800-098-61 800-098-59 800-098-65 800-098-61 800-098-61 800-098-65 800-098-63 800-098-61
800-690-01 800-690-02 800-690-03 800-690-04 800-690-05 800-690-06 800-690-07 800-690-08 800-690-09
800-690-01 800-690-02 800-690-03 800-690-04 800-690-05 800-690-06 800-690-07 800-690-08 800-690-09
800-098-65 800-098-59 800-098-59 800-098-67 800-098-63 800-098-61 800-098-68 800-098-63 800-098-61
800-577-02 800-577-02 800-577-02 800-577-00 800-577-02 800-577-02 800-577-02 800-577-02 800-577-02
800-226-03 800-226-04 800-226-01 800-226-03 800-226-04 800-226-01 800-226-33 800-226-33 800-226-34
800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
800-531-41 800-531-41 800-531-41 800-531-41 800-531-41 800-531-41 800-531-42 800-531-42 800-531-42
800-200-00 800-200-00 800-200-00 800-200-00 800-200-00 800-200-00 800-200-01 800-200-01 800-200-01
800-184-70 800-184-70 800-184-70 800-184-71 800-184-71 800-184-71 800-184-71 800-184-71 800-184-71
800-077-26 800-077-26 800-077-26 800-077-26 800-077-26 800-077-26 800-077-28 800-077-28 800-077-28
800-077-26 800-077-26 800-077-26 800-077-26 800-077-26 800-077-26 800-077-26 800-077-26 800-077-26
800-705-20 800-705-20 800-705-20 800-705-20 800-705-20 800-705-20 800-705-21 800-705-21 800-705-21
800-705-40 800-705-40 800-705-40 800-705-40 800-705-40 800-705-40 800-705-41 800-705-41 800-705-41
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-30 800-557-30 800-557-30
36
PARTS LIST (DUAL CIRCUIT)
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
CAPACITY UNLOADER KITS
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS420H PDS420M PDS420F PDS480H PDS480M PDS480F PDS540H PDS540M PDS540F
800-674-82 & 70 800-674-83 & 71 800-674-84 & 72 800-674-82 800-674-83 800-674-84 800-674-85 & 82 800-674-86 & 83 800-674-87 & 84
800-677-13 800-677-14 800-677-15 800-690-10 800-690-11 800-690-12 800-690-22 &10 800-690-23 & 11 800-690-24 & 12
800-677-53 800-677-54 800-677-55 800-690-10 800-690-11 800-690-12 800-690-22&10 800-690-23&11 800-690-24&12
800-098-67 800-098-63 800-098-61 800-098-68 800-098-65 800-098-63 800-098-65 & 65 800-098-65 & 63
800-577-00 800-577-00 800-577-00 800-577-02 800-577-02 800-577-02 800-577-02 800-577-02 800-577-02
800-226-33 800-226-33 800-226-34 800-226-03 800-226-04 800-226-01 800-226-03 800-226-04 800-226-01
800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
800-531-42 800-531-42 800-531-42 800-531-17 800-531-17 800-531-17 800-531-17 800-531-17 800-531-17
800-200-01 800-200-01 800-200-01 800-200-04 800-200-04 800-200-04 800-200-04 800-200-04 800-200-04
800-184-72 800-184-72 800-184-72 800-184-73 800-184-73 800-184-73 800-184-73 800-184-73 800-184-73
800-077-28 800-077-28 800-077-28 800-077-16 800-077-32 800-077-32 800-077-32 800-077-32 800-077-32
800-077-26 800-077-26 800-077-26 800-077-29 800-077-29 800-077-29 800-077-29 800-077-29 800-077-29
800-705-21 800-705-21 800-705-21 800-705-08 800-705-08 800-705-08 800-705-08 800-705-08 800-705-08
800-705-41 800-705-41 800-705-41 800-705-42 800-705-42 800-705-42 800-705-42 800-705-42 800-705-42
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-30 800-557-30 800-557-30
800-093-41 800-098-65
800-098-65 & 63 800-098-63 & 61
800-093-41 800-098-65 800-098-63 800-098-67 & 65 800-098-65 & 63
800-097-54 800-093-41
800-098-63/61 800-098-67/61
MODEL NUMBER
COMPRESSOR (SCROLL)
CONTACTOR (SCROLL)
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
CAPACITY UNLOADER KITS
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS600H PDS600M PDS600F PDS660H PDS660M PDS660F PDS720H PDS720M PDS720F
800-674-85 800-674-86 800-674-87 N.A. N.A. N.A. N.A. N.A. N.A.
800-097-54 800-098-67 800-098-65 N.A. N.A. N.A. N.A. N.A. N.A.
800-690-22 800-690-23 800-690-24 800-677-25 800-677-26 800-677-27 800-690-25 800-690-26 800-690-27
800-690-22 800-690-23 800-690-24 800-677-65 800-677-66 800-677-67 800-690-25 800-690-26 800-690-27
800-098-68/63 800-098-65 800-098-65 800-098-65/65 800-098-67 800-098-65 800-098-68 800-098-67
800-577-00 800-577-02 800-577-02 800-577-00 800-577-00 800-577-00 800-577-02 800-577-02 800-577-02
800-226-03 800-226-04 800-226-01 800-226-03 800-226-04 800-226-01 800-226-03 800-226-04 800-226-01
800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
800-531-17 800-531-17 800-531-17 800-531-17 800-531-17 800-531-17 800-531-17 800-531-17 800-531-17
800-200-04 800-200-04 800-200-04 800-200-04 800-200-04 800-200-04 800-200-04 800-200-04 800-200-04
800-184-74 800-184-74 800-184-74 800-184-75 800-184-75 800-184-75 800-184-75 800-184-75 800-184-75
800-077-32 800-077-32 800-077-32 800-077-35 800-077-35 800-077-35 800-077-35 800-077-35 800-077-35
800-077-29 800-077-29 800-077-29 800-077-29 800-077-29 800-077-29 800-077-29 800-077-29 800-077-29
800-705-08 800-705-08 800-705-08 800-705-08 800-705-08 800-705-08 800-705-08 800-705-08 800-705-08
800-705-42 800-705-42 800-705-42 800-705-42 800-705-42 800-705-42 800-705-42 800-705-42 800-705-42
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-30 800-557-30 800-557-30
800-097-51 800-098-65
37
PARTS LIST (DUAL CIRCUIT)
MODEL NUMBER
COMPRESSOR (SEMI-HERMATIC RECIP.)
COMPRESSOR (SEMI-HERM. W/-UNLOADER)
CONTACTOR (SEMI-HERMATIC RECIP.)
CAPACITY UNLOADER KITS
COND. FAN ASS’Y (FAN, MOTOR WITH GRILLE)
CONTACTOR
FILTER DRYER
SIGHT GLASS
EXPANSION VALVE
BLOWER WHEEL (STD. & ECONOMIZER)
BLOWER WHEEL (100% FRESH AIR)
PUMP DOWN SOLENOID VALVE
MECHANICAL SHUT OFF VALVE
ACCESS VALVE
LOW PRESSURE GAUGE (LIQUID FILLED)
HIGH PRESSURE GAUGE (LIQUID FILLED)
ADJUSTABLE
ADJUSTABLE
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH LOW PRESSURE SWITCH
PDS780H PDS780M PDS780F PDS840H PDS840M PDS840F
800-690-28&25 800-690-29&26 800-690-30&27 800-690-28 800-690-29 800-690-30
800-690-28&25 800-690-29&26 800-690-30&27 800-690-28 800-690-29 800-690-30
800-097-54/098-65
& 097-51/098-65
800-577-02 800-577-02 800-577-02 800-577-02 800-577-02 800-577-02
800-226-03 800-226-04 800-226-01 800-226-03 800-226-04 800-226-01
800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
800-531-17 800-531-17 800-531-17 800-531-17 800-531-17 800-531-17
800-200-04 800-200-04 800-200-04 800-200-04 800-200-04 800-200-04
800-184-75 800-184-75 800-184-75 800-184-76 800-184-76 800-184-76
800-077-35 800-077-35 800-077-35 800-077-35 800-077-35 800-077-35
800-077-29 800-077-29 800-077-29 800-077-29 800-077-29 800-077-29
800-077-16 800-705-08 800-705-08 800-705-08 800-705-08 800-705-08
800-705-42 800-705-42 800-705-42 800-705-42 800-705-42 800-705-42
800-207-08 800-207-08 800-207-08 800-207-08 800-207-08 800-207-08
800-706-30 800-706-30 800-706-30 800-706-30 800-706-30 800-706-30
800-706-31 800-706-31 800-706-31 800-706-31 800-706-31 800-706-31
800-557-29 800-557-29 800-557-29 800-557-29 800-557-29 800-557-29
800-557-30 800-557-30 800-557-30 800-557-30 800-557-30 800-557-30
800-557-31 800-557-31 800-557-31 800-557-31 800-557-31 800-557-31
800-098-65/61 & 65/59
800-098-68&67 800-097-54/098-65 800-098-65/61 800-098-68
38
PARTS LIST: BLOWER MOTOR GROUP
HP (TEFC) VOLTAGE (V-Ph-Hz) MOTOR (RPM) CONTACTOR OVER LOAD RELAY
208/230-3-60 800-879-43(3600) 800-098-50 800-098-85
460-3-60 800-879-43(3600) 800-098-50 800-098-84
1 380-3-60 800-879-63(3600) 800-098-50 800-098-84
208/230-3-60 800-879-19(1800) 800-098-50 800-098-85
460-3-60 800-879-19(1800) 800-098-50 800-098-84 380-3-60 800-879-55(1800) 800-098-50 800-098-84
208/230-3-60 800-882-43(3600) 800-098-50 800-098-87
460-3-60 800-882-43(3600) 800-098-50 800-098-84
1.5 380-3-60 800-882-63(3600) 800-098-50 800-098-85 208/230-3-60 800-882-19(1800) 800-098-50 800-098-87
460-3-60 800-882-19(1800) 800-098-50 800-098-84 380-3-60 800-882-55(1800) 800-098-50 800-098-85
208/230-3-60 800-828-43(3600) 800-098-50 800-098-87
460-3-60 800-828-43(3600) 800-098-50 800-098-85
2 380-3-60 800-828-63(3600) 800-098-50 800-098-85
208/230-3-60 800-828-19(1800) 800-098-50 800-098-87
460-3-60 800-828-19(1800) 800-098-50 800-098-85 380-3-60 800-828-54(1800) 800-098-50 800-098-85
208/230-3-60 800-770-43(3600) 800-098-54 800-098-88
460-3-60 800-770-43(3600) 800-098-50 800-098-85
3 380-3-60 800-770-61(3600) 800-098-50 800-098-87
208/230-3-60 800-770-19(1800) 800-098-54 800-098-88
460-3-60 800-770-19(1800) 800-098-50 800-098-85 380-3-60 800-770-63(1800) 800-098-50 800-098-87
208/230-3-60 800-771-19(1800) 800-098-57 800-098-89
5 460-3-60 800-771-19(1800) 800-098-50 800-098-87
380-3-60 800-876-05(1450) 800-098-55 800-098-88
208/230-3-60 800-772-19(1800) 800-098-57 800-098-91
7.5 460-3-60 800-772-19(1800) 800-098-55 800-098-88
380-3-60 800-876-09(1800) 800-098-55 800-098-89
208/230-3-60 800-773-19(1800) 800-098-59 800-098-91
10 460-3-60 800-773-19(1800) 800-098-55 800-098-89
380-3-60 800-876-13(1800) 800-098-57 800-098-89
208/230-3-60 800-774-19(1800) 800-098-63 800-098-93
15 460-3-60 800-774-19(1800) 800-098-57 800-098-89
380-3-60 800-876-17(1800) 800-098-59 800-098-91
208/230-3-60 800-775-19(1800) 800-098-65 800-098-94
20 460-3-60 800-775-19(1800) 800-098-59 800-098-91
380-3-60 800-876-21(1800) 800-098-61 800-098-91
208/230-3-60 800-776-19(1800) 800-098-67 800-098-95
25 460-3-60 800-776-19(1800) 800-098-61 800-098-91
380-3-60 800-876-25(1800) 800-098-63 800-098-93
208/230-3-60 800-777-19(1800) 800-098-68 800-098-95
30 460-3-60 800-777-19(1800) 800-098-63 800-098-93
380-3-60 800-876-29(1800) 800-098-65 800-098-94
39
PARTS LIST: HEATER GROUP
KILOWATTS VOLTAGE (V-Ph-Hz) CONTACTOR HEATER
208/230-3-60 800-098-51/800-098-50* 80032030
5 460-3-60 800-098-51/800-098-50* 80032042
380-3-60 800-098-51/800-098-50* 80032036
208/230-3-60 800-098-51/800-098-50* 80032031
6 460-3-60 800-098-51/800-098-50* 80032043
380-3-60 800-098-51/800-098-50* 80032037
208/230-3-60 800-098-51 80032003
7.5 460-3-60 800-098-51 80032023
380-3-60 800-098-51 80032013
208/230-3-60 800-098-51 80032004
10 460-3-60 800-098-51 80032024
380-3-60 800-098-51 80032014
208/230-3-60 800-098-51 80032006
15 460-3-60 800-098-51 80032026
380-3-60 800-098-51 80032016
208/230-3-60 800-098-55/800-098-54*
20 460-3-60 800-098-51
380-3-60 800-098-51
208/230-3-60 800-098-57/800-098-54* 80032005 (12.5 kW)
25 460-3-60 800-098-51 80032025 (12.5 kW)
380-3-60 800-098-51 80032015 (12.5 kW)
208/230-3-60 800-098-57/800-098-56*
30 460-3-60 800-098-51/800-098-50*
380-3-60 800-098-55/800-098-54*
208/230-3-60 800-098-55
40 460-3-60 800-098-55
380-3-60 800-098-57
208/230-3-60 800-098-57
50 460-3-60 800-098-57
380-3-60 800-098-57
208/230-3-60 800-098-57
60 460-3-60 800-098-59
380-3-60 800-098-57
NOTE: Heater contactor part number with 230 & 24V control volts, please refer to units diagram for the specific contactor control voltage. Contactor part number with * mark is 24V.
40
RECOMMENDED SPARE PARTS
PERCENTAGE OF SPARE PARTS
ITEM
Compressor 2% 1% 3% 2%
Capacitor 3 2 5 4
Condenser fan motor 2 1 3 2
Evaporator blower motor 1 0.5 2 1
Belt 2 1 4 3
Contactor compressor 2 1 3 2
Contactor heater 2 1 3 2
Contactor fan motors 2 1 3 2
HPS/LPS/other controls 2 1 3 2
Expansion valve 1 0.5 2 1
Filter drier 2 1 3 2
Electric heater 1 0.5 2 1
Fuse link, heater 3 1 4 3
ONE YEAR SUPPLY TWO YEAR SUPPLY
100 UNITS 1000 UNITS 100 UNITS 1000 UNITS
Transformer (24V secondary) 1 0.5 2 1
Propeller fan 1 0.5 2 1
Blower Wheel 0.5 0.25 1 0.5
Bearing-blower 2 1 4 2
Thermostat (Wall) 1 1 2 1
Heater-crankcase 3 1 4 2
Filter 2 1 4 4
NOTE : When ordering spare parts, please quote the complete model number on the unit nameplate.
41
PREVENTIVE MAINTENANCE SCHEDULE
I T E M
Clean air filters & replace if required.
Clean evaporator coil, drain pan & drain line.
Clean condenser coil.
Check blower belt/tension/wear/crack and replace it, if required.
Lubricate blower motor/condenser motor.
Check alignment of pulleys.
Check/clean electrical connections, controls & control box.
Check motors, blower bearings & lubricate it.
Check all electrical control components, wiring terminals etc. for spark, overheating & loose connections. Replace/correct as necessary.
Check all damper operation. Repair/replace as required.
Check insulation flanking. Repair/replace as required.
FREQUENCY OF MAINTENANCE, MONTHS
1
X
X
X
X
3
X
X
X
X
X
6
X
12
X
Check loose bolts/screws & tight as necessary.
Check for rusted/dented/damaged body parts & repair/repaint as necessary.
Check mountings (spring isolator/rubber pads). Repair/replace as necessary.
Check flexible canvas connections & duct work. Repair/replace as required.
Run test all motors and check the amperage, abnormality etc. Run test compressors and check the amperage, noise, oil level, pressure
etc. and correct them accordingly. Check the thermostat/control devices for correct operation, calibrate/
re-adjust as required. Apply corrosion inhibitor/contact cleaner as required.
Check all pressures/temperatures as applicable and satisfy the operation & performance.
NOTE: Always observe for abnormal noise or vibration.
X
X
X
X
X
X
X
X
X
MAINTENANCE TOOLS/EQUIPMENT REQUIRED
STANDARD : Screw drivers (Slot & Phillips), adjustable wrenches, pliers, refrigeration wrenches & socket set wrenches,
pulley puller, etc.
SPECIAL : Manifold gauge set, R-22 charging cylinder, belt tension checker, leak detector, vacuum pump with elec-
tronic gauges, thermometer & hook type ammeter/voltmeter/ohmmeter.
42
Loading...