YZ WM4-96 Technical data

Energy Management Modular Universal Utility Meter and Power Analyzer Type WM4-96
Class 0.5 (current/voltage)
Universal meter: energy, water and gas
32-bit µP-based multifunction power analyzer
Back-lighted graph display (128x64 dots)
Front size: 96x96 mm
Measurement of single phase and system instantaneous
Measured energies: kWh and kvarh on 4 quadrants
Graphic display of the load profile (daily, weekly,
monthly display)
Current and voltage inputs with autoranging capability
4x4 dgt instantaneous variable read-out
4x9 dgt total energies read-out
4x6 dgt partial energies read-out
, var, var
dmd
, VA, VA
dmd
dmd
, PF, PF
avg
, V, AL,
An,
Optional RS 422/485 serial output
Optional RS232 + real time clock function and 2Mb
data logging of alarms, MIN/MAX events and up to 8 variables with programmable time interval.
MODBUS RTU, JBUS protocol
ransmission and reception of SMS messages (vari-
T
ables and alarm status)
Data transmission and reception by means of analogue modem
Up to 4 optional pulse outputs
Up to 4 optional alarm outputs
Universal power supply
Front degree protection: IP 65
: 18-60VAC/VDC, 90-260 VAC/VDC
Product Description
Universal utility meter and power analyzer which can be used in 3 different operating modes:
- direct measurements for the power quality analysis (LV or MV/HV connection);
- indirect energy and power measurements by means of watt-hour meters (LV or MV/HV connection);
direct measurements for the
­instantaneous variables (LV connection) and indirect
measurements for the ener­gy variables (LV or MV/HV). It’s possible to add the management of gas and water metering to all of these working modes. Automatic transmission of SMS alarm messages. Remote read-out from GSM mobile phones of all the instantaneous variables, the last variables available in the data logging and the energy meters.
48 independent energy meters to be used as single,
dual, multi-time energy management
Interface with watt-hour meters by means of digital
inputs (+kWh, +kvarh, -kWh, -kvarh)
Interface with gas and water meters by means of digi-
tal inputs (one water meter, two gas meters to be used as single or dual time management)
Display refresh rate: 10 samples/s
Harmonic distortion analys (FFT) up to the 50th harmonic with graphic and numeric indication (current and voltage)
Harmonics source detection
How to order
Model Range code System Power supply Slot A Slot B Slot C Slot D Options
How to order
Wm4Soft Network: programm to download memory data and to manage a modem. Wm4Soft Remote: programm to set all the programming parameters.
WM4-96 A V53H XX XX XX XX X
Wm4Soft Network Wm4Soft Remote
Type selection
Range code (on r
XXX: None AV5:
240/415 VAC­1/5 AAC (max. 300 V (L-N)/ 520 V (L-L) - 6 A)
AV7: 400/690VAC -
1/5 AAC (max. 480V (L-N) / 830 V (L-L) / 6 A
Power supply
L:
18 to 60V
H: 90 to 260VAC/VDC
equest)
AC/VDC
Slot A (interfacing)
XX:
None 3 universal digital inputs
D2:
+ excitation output (16-24VDC)
(alarm or pulse)
Slot D
XX:
None
R2: Dual r O2: Dual open collector O4:
elay output,
(AC1-8AAC, 250V
(30V/100mADC)
output Four open collector out­put (30V/100mADC)
AC)
Slot B (communication)
XX:
None
S1: Serial output,
RS485 multidr bidirectional
Options
X: None M: Serial port
RS232+RTC+ 2Mb or Data memory to store all events and contin-
ecor
uous r variables
E1: WEB-server option
op,
d up to 8
Slot C (alarm or pulse)
XX:
None
R1:
Single relay output (AC1-8AAC, 250VAC)
R2: Dual relay output,
(AC1-8AAC, 250VAC)
O1:
Single open collector output (30V/100mADC)
O2:
Dual open collector out
(30V/100mADC)
put
D1:
3 digital inputs for volt-
ee contacts
age-fr
D2:
3 universal digital inputs + excitation output (16-24VDC)
-
1
M4-96
W
Input specifications
umber of analogue inputs
N
Current 1 (1-phase; system code: 3) Voltage 1 (1-phase; system code: 3)
Digital inputs
AQ1038 No. of inputs: 3 (voltage-free)
Purpose W
Contact measuring current
AQ1042
Purpose W
Excitation output 16V<+Aux<24VDC Max 15mA Contact measuring current
Common characteristics
Input frequency Max 20 Hz, dutycycle 50% Close contact resistance Max 1k Open contact resistance Min 100k Insulation 4000VRMS
Max. input number 6 in the configuration:
Accuracy
(display,RS232, RS485) In: 5A, If.s.: 6A
Current (AL1, AL2, AL3) ±0.5% RDG (0.2 to 1.2 In)
(@25°C ±5°C, R.H. 60%) ±5mA (0.02 to 0.2 In)
Current (A
) ±1% RDG (0.2 to 1.2 In)
n
Voltage AV5 range: ±0.5% RDG (48 to 300 V
±5°C, R.H. 60%) ±1% RDG (84 to 519 V
C
°
(@25
AV7 range: ±0.5% RDG (80 to 480 V
Frequency ±0.1% RDG (40 to 440 Hz) Active power
°C ± 5°C, R.H. 60%) ±0.5% (RDG + FS) (PF 0.5 L/C,
(@ 25
Reactive power
(@ 25°C ± 5°C, R.H. 60%) ±0.5% (RDG + FS) (PF 0.5 L/C,
Apparent power
(@ 25°C ± 5°C, R.H. 60%) ±0.5% (RDG+ FS)
Energies
(@ 25°C ± 5°C, R.H. 60%) Active: class 1 according to
3 (3-phase; system code: 3) 4 (3-phase; system code: 3)
measurement synchro-
md
d
nization + var
md
d
and PF
Interfacing with watt-hour meters
+kWh, +kvarh)
(
. Tariff selection: energy. <8mA/ 17.5 to 25VDC Number of inputs: 3 + excitation
nization + var
output
measurement synchro-
dmd
dmd
and PF Interfacing with watt-hour meters (-kWh, -kvarh) or/and measurements of gas /water m3. T arif f selection: energy or GAS.
15mA
AQ1038+AQ1042 or 2*AQ1042
Vn: 240VL-N, Vf.s.: 300VL-N
@ 40 to 100 Hz
L-L
±1% RDG (139 to 830 V Includes also: frequency , power supply and output load influences
0.1 to 1.2 In, range AV5) or
(PF 0.5 L/C,
RDG
1%
±
0.1 to 1.2 In, range AV5)
0.1 to 1.2 In, range AV5) or ±1% RDG (PF 0.5 L/C,
1.2 In, range A
0.1 to
to
(0.1
1.2 In, range A
V5)
V5) or ±1% RDG (0.1 to 1.2 In, range AV5)
EN61036 Reactive: class 2 accor
ding
to EN61268
Ib: 5A, Imax: 6A
0.1Ib: 500mA, tart-up current: 20mA
S Un: 240V (AV5), 400V (A V7)
Harmonic distortion 1% FS (FS: 100%)
(@ 25°C ± 5°C, R.H. 60%)
phase: ±2°; Imin: 0.1Arms; Imax: 15Ap; Umin: 50V Umax: 500Vp
.
md
d
Sampling frequency: 6400
samples/s
Additional errors
0.3%
Humidity
RDG Input frequency 0.4% RDG, 62 to 400 Hz Magnetic field 0.5% RDG @ 400 A/m
NOTE: all accuracies are
dmd
.
referred to measurements carried out with the analogue input module
Temperature drift
200ppm/°C
Sampling rate 6400 samples/s @ 50Hz Display Graph LCD backlighted
(128x64 dots). Read-out for the instantaneous variables: 4x4 digit or 4x3 Total energies: 4x9 digit; Partial energies: 4x6 digit
Max. and min. indication Max. 9999 (999,999,999),
Min. -9999 (–999,999,999)
Measurements Current, voltage, power,
energy ,power factor,frequen­cy, harmonic distortion(see “Display Pages”). TRMS measurement of a distorted
)
L-N
Coupling type Direct.
)
)
est factor
Cr
L-N
)
L-L
wave (voltage/curr
3, max. 15Ap/500Vp “A
(L-N), 15Ap/800Vp “AV7” (L-N)
Ranges (impedances)
AV5 58/100 V (> 500 kΩ) -
1 AAC ( 58/100 V (> 500 k 5 AAC (
0.3 VA) 240 V/415 V (> 500 k) ­1 AAC (0.3 VA) 240 V/415 V (> 500 k) ­5 AAC (0.3 VA)
AV7 100/170 V (> 500 k) -
1 AAC (0.3 VA) 100/170 V (> 500 k
0.3 VA)
5 AAC ( 400/690 V (> 500 k) ­1 AAC (0.3 VA) 400/690 V (> 500 k) ­5 AAC (
Frequency 40 to 440 Hz Overload protection
Continuous: voltage/current: AV5: 300V
V7: 480V
A
For 1s: voltage/current: AV5: 600V
AV7: 960V
@ 50Hz
, 60% to90% R.H.
1
/2digit
ent) .
0.3 VA) ) -
) -
0.3 VA)
L-N L-N
/1040V
L-N
/1660V
L-N
/ 500V / 830V
L-L L-L
L-L L-L
/ 6A
/ 6A /120A /120A
RMS
V5
;
2
WM4-96
Output specifications
RS422/RS485 (on request) Multidrop
idirectional (static and
b dynamic variables)
onnections 2 or 4 wires, max. distance
C
1200m, termination directly on the module
Addresses
from 1 to 255, key-pad selectable Protocol MODBUS RTU/JBUS Data (bidirectional)
Dynamic (reading only) All display variables, see
lso the table, “List of the
a
onnected variables”.
tatic (writing only) All configuration parameters
S
c
energy reset, activation of digital outputs.
Data format 1 start bit, 8 data bit, no
parity/even parity/ odd parity, 1 stop bit
Baud rate 1200, 2400, 4800 and 9600
bit/s selectable
Insulation By means of optocouplers,
4000 V
output to
RMS
measuring inputs
4000 V
output to
RMS
power supply input
RS232
((oonn rreeqquueesstt)
)
Bidirectional (static and
dynamic variables) Connections 3 wires, max. distance15m Data format 1 start bit, 8 data bit,
no parity, 1 stop bit Baud rate 2400, 4800, 9600,
38400 bit/s Protocol MODBUS RTU (JBUS) Other features As per RS422/485
Communication by modem
Analogue modem For the remote communica-
tion of all the data measured and managed by WM4. External communication Modem. Recommended type: US Robotics
GSM Modem For the transmission of
SMS messages: alarms, instantaneous variables, last available variables of data logging and energy meters. The alarms can also be transmitted automatically, while the variables can be
ecalled by means of special
r SMS question codes
GSM kit type-tested for WM4 Siemens kit (external)
model “TC35 TERMINAL” included GSM module, antenna and 230V power supply.
Digital outputs (on request)
To be used as alarms and/or retransmission of the energy, gas, water metering and/or
outputs remotely
olled
contr
by the serial
communication port.
The outputs are completely programmable independently of the type of module being used.
Pulse outputs (on request)
Number of outputs Up t o 4 Type
From 1 to 1000 pulses programmable for k-M-G Wh, k-M-G varh, open collector (NPN transistor) V
1.2 VDC/ max. 100 mA
ON
0 VDC max.
3
V
OFF
Outputs connectable to total and/or partial energy meters
Pulse duration
220 ms (ON), 220 ms (OFF) According to DIN43864
Insulation By means of optocouplers,
4000 V
RMS
output to
measuring inputs,
RMS
output to
4000 V power supply input.
Notes
The outputs can be either open collector type or relay type (for the relay output refer to the specifications described in the “alarm outputs” section).
Alarm outputs (on request)
Number of set-points Up to 4, independent Alarm type Up alarm, down alarm
with or without latch , phase asymmetry, phase loss, neutral loss.
Monitoring of the variable All the variables listed at
the paragraph “List of the connectable variables”.
Set-point adjustment 0 to 100% of the electrical
scale
Hysteresis 0 to 100% of the electrical
scale On-time delay 0 to 255 s Relay status Selectable: normally
de-energized or normally
gized
ener Output type
Relay, SPDT
AC 1-8A, 250V
AC DC 12-5A, 24VDC AC 15-2.5A, 250VAC DC 13-2.5A, 24VDC
Min. response time 150 ms, filters excluded,
FFT excluded, setpoint on-time delay: ”0s”
Insulation 4000 V
RMS
output to
measuring input,
RMS
output to
4000 V power supply input.
Notes The outputs can be either
relay type or open collector type (for this latter one, see the specifications mentioned in the pulse outputs)
3
M4-96
W
Software functions
Password Numeric code of max 3
digits; 2 protection levels of the programming data
1st level Password “0”: no protection
nd level Password from 1 to 499:
2
ll data are protected
a Note: by entering in the programming mode by means of password, the measurement is inhibited.
perating mode selection - Direct measurements for
O
the power quality analysis (L V or MV/HV connection);
- Indirect energy and power measurements by means of watt-hour meters (LV or MV/HV connection);
- Direct measurements for the instantaneous variables (LV connection) and indirect measurements for the ener­gy variables (LV or MV/HV). It’s possible to add the management of gas and water metering to all of these working modes.
Pulse weight Water/gas meter inputs:
selectable from 1 to 10000 pulses/m
3
, energy from 1 to 10000.00 imp/kWh/kvarh
Transformer ratio CT up to 30000A (6000)
VT up to 600 kV (6000)
Filters
Filter operating range 0 to 99.9% of the input
electrical scale.
Filtering coefficient 1 to 255 Filter action
Display, alarms, serial outputs (fundamental variables:
V,A,W and their derived ones).
Event logging Only with RS232+RTC
module+ Data memory
T ype of data Alarms and max./min. (max.
480 events) stor
ed with date (dd:mm:yy) and hour (hh:mm:ss) reference, data logger and load pr
ofile
Sampling management Only for data logger and load
profile. The sample stored within the selected time inter­val results from the continu­ous average of the measur values. The average is calcu lated (min. sample) with an interval within two following
easurements of approx.
m
200 ms. Data management type: FIFO Memory size 2 Mbyte Battery life 10 years
Data logger function The data are stored at time
intervals from 1 to 60 min.; up
to 8 instantaneous variables
can be selected. Historical data storing time See the “Historical data
storing time table”. Data format Date: day, month
ime: hours, minutes, seconds,
t
type of stored variable:
variable value.
Load profile Storage at time intervals of
5-10-15-20-30 min of Wdmd. Historical data storing time 30 weeks: with recording
interval of 5min.
90 weeks: with storing
interval of 15min. Data format Wdmd variable value, min-
utes, seconds, day, month.
Displaying 4 variables per page
1 page that can be layed out
by the user
30 fixed pages Energy meters Up to 12 pages depending on
the selected tariff mode. Dis-
playing of the consumed
energy up to two months pre-
ceding the current one by
means of password (depend-
ing on the selected tariff mode). Water and gas meters 1 page with two displaying
modes depending on the
selected one:
water and gas m
day-time and night gas m Stored events 240 pages.
Display of the data by means
of password. Data logger
Display of the data by means
of password with reset func-
tion of the relevant memory
section. Load profile 3 pages, daily, weekly and
monthly graphic display.
Reset function of the r
memory section by means of
password.
ed
Display language Selectable:
-
Italian, English, French, Ger
man, Spanish
3
or
3
.
elevant
-
Wm4Soft software: parameter programming and memory data transfer
Wm4Soft Network English language softwar
to transfer memory data and write messages to be coupled to the SMS alarms, plus modem communication
4
e
management. The p rog r a m
runs under Windows
/95/98/98SE/2000/NT/XP Working mode Three differ ent working
modes can be selected:
- management of a local
.
WM4-96
Wm4Soft software: memory data transfer (cont.)
S485 network;
R
- management of modem ommunication from a single
c instrument to PC (data down­load);
- management of modem
communication from local networks (RS485 communi­cation) to a common PC
data download).
ata Storing In pre-formatted XLS files
D
Data T ransfer Manual or automatic at
(
Excel data base).
( The instantaneous and the energy , gas, water variables are stored into two separated files.
programmable timings.
Modem communication Phone book management
m4Soft Remote
W
Data access By means of RS232 serial
General Specifications
(save up to 100 numbers). Each number is associated to a modem that corresponds
ither to the single instrument
e or to a network of instruments. Each network can manage up to 10 local instruments.
nglish language software
E
o program the working
t parameters of the instrument The program runs under Windows 95/98/98SE/2000/ NT/XP.
port to be coupled to a GSM or analogue modem or RS485 port (also multi-drop availability.).
Operating 0 to +50°C (32 to 122°F) Temperature
Storage -10 to +60°C (14 to 140°F) temperature
Insulation reference voltage 300 V
Insulation 4000 V
Dielectric strength 4000 V Noise Rejection
CMRR
EMC IE C EN 61000-6-2,
(R.H. < 90% non-condensing)
(R.H. < 90% non-condensing)
RMS
to ground (AV5 input)
RMSbetween all inputs/
outputs to ground
RMS
for 1 minute
100 dB, 48 to 62 Hz
IEC EN 61000-6-3
Other standards
Safety IEC 61010-1, EN 61010-1 Product Energy measurements:
Pulse output DIN43864
Approvals CE, UL and CSA Connector Screw-type
Housing
Dimensions 96x96x140 mm Material ABS,
Protection degree Front: IP65,
Weight Approx. 600 g
Load profile display
Installed power
Example: the consumed power inte­grated in 15 minutes exceeds the installed power
Graph of consumptions
By means of the “F” key you can display the single integration time periods and the details r power programmed for that time period, the storing time of the Wdmd sample and the relevant value.
Time of the last integration
Wdmd of the last integration period
Profile of the installed power divided into time periods
elating to the value of the installed
EN61036, EN61268.
max. 2.5 mm2 wires (2x 1.5mm2)
self-extinguishing: UL 94 V-0 NEMA4x, NEMA12
(packing included)
Daily graph: resolution of 15 minutes, total time of 24 hours.
Weekly graph: resolution of 2 hours, total time of 7 days.
Monthly graph: resolution of 12 hours, maximum total time of 31 days.
5