YZ WM1-DIN Technical data

Energy Management Power Analyzers Type WM1-DIN
3-dgt multi-range µP-based meter
Scrolling of power, energy, power factor (cos ϕ), current and voltage
Automatic selection of k (kilo) or M (mega) scale
Automatic measurement of peak value
Double measuring input: Up to 5 A or up to 27 A
Degree of protection (front): IP 40
- Pulse output for connection to remote display or PLC
- Serial RS 485 output for connection to a personal computer
Product Description
3-dgt µP-based meter for measuring power, energy, power factor (cos ϕ), current and voltage with automatic selection of scale. A pro­grammable alarm setpoint
output is available on request. The housing is easy to mount on DIN-rail and offers a degree of protection (front) of IP 40.
Type Selection
Range code
27A: 5 AAC or 27 AAC
selectable
1)
on request
Power Supply
C: 115 VAC, -15% +10%,
50/60 Hz
D: 230 VAC, -15% +10%,
50/60 Hz (standard)
Set-points
0: no alarm 1: one alarm
1)
Input Specifications
Accuracy
(@ 25°C ± 5°C, R.H. 60%) ± 2 % f.s., ± 2 dgt
Temperature drift ± 250 ppm/°C, Display 7-segment LED, h 14.2 mm,
Decimal point position Automatic selection and
Max. and min. indication Max.: 999, Min.: 0 Overflow indication “oF” Input
Current 27 AAC permanent, direct
Voltage (48 to 62 Hz) 400 VAC (1-phase conn.)
3 digits
indication of ”k” or “M” range.
conn. max. 32 AAC for 2 minutes. 5 AAC permanent, CT conn. max. 6 AAC for 2 minutes
500 VAC (3-phase conn.)
Ordering Key
Model Range code Measurement Power supply Setpoints Option
Options
XX: None (1-phase/
3-phase system with neutral, balanced load)
TX: Measurement on
3-phase system with­out neutral (balanced load)
PX: Pulse output (available
only without alarm)
Input (cont.)
Type 1-phase/3-phase with neu-
Wave form Undistorted sine wave
Impedance
Voltmeter input: 1 M Ammeter input: 1 m(27 A)
Key-pad enable input By means of external, volta-
WM1-DIN27A A D0XX
RX: RS 485 serial interface
(1-phase/3-phase system, with neutral and balanced load)
SX: RS 485 serial interface
(3-phase system, with­out neutral and with balanced load)
tral, balanced load (standard) 3-phase without neutral, balanced load (on request)
(form factor 1.11)
6 m(5 A)
ge free NC contact. The in­put is not insulated from the measuring inputs. Can be used to avoid un­wanted programming modifi­cations, resets and totalized energy.
1
WM1-DIN
Input Specifications (cont.)
Measurements
Voltage, current,
, or V
instantaneous power V
L-N
, I, W, VA, VAR
L-L
(max. display: 999M-)
Peak value Accessible by means of the
key-pad in run mode.
Energy Wh, VAh VARh
(max. display: 999 M-)
Power factor - cos ϕ Accuracy: ± 4 dgt @ 25˚C,
voltage 3% f.s. current 10% f.s. Display: L.10/1.00/C.10; In case of voltage and/or current lower than 3% f.s., the display flashes “1.00”
Reset date updating Month and day of the last
reset manually programmed by key-pad
Primary range Transformer ratio program-
mable from 1 to 999 (max. 5000/5A).
Output Specifications
General Specifications
Operating temperature 0° to 50°C (32° to 122°F)
(R.H. < 90% non-condensing)
Storage temperature -10° to 60°C (14° to 140°F)
Insulation reference voltage 300 V Dielectric strength 4000 V EMC EN 50081-1, EN 50082-1 Safety standards EN 61010-1, IEC 61010-1,
Connector Screw-type Housing
Dimensions 89 x 71.5 x 58.5 mm
Material ABS,
Degree of protection IP 40 (front) Weight Approx 320 g Approvals CE
(R.H. < 90% non-condensing)
to ground
rms
rms
for 1 minute
VDE 0411
(4 DIN-modules)
self-extinguishing: UL 94 V-0
Alarms (on request)
Number of setpoints 0 standard (1 on request). Setpoint adjustment From 0 to 999 MW/MVA/
MVAR/instantaneous power, MWh/MVAh/MVARh energy and from L/C. 10 to
1.00 cos ϕ key-pad program-
mable Accuracy ± 2% Hysteresis 0 to 100% f.s.
key-pad programable Time delay adjustment 0 to 255 s
key-pad programable Alarm type Low or high
key-pad programable Output type Static by TRIAC. (24 VAC to
250 VAC/max. 50 mA). Insulation 2 kV between alarm output
and all inputs and serial out -
put (if available)
Pulse output (on request)
Type
Insulated, open collector: V
= 0.6 VDC/max. 4 mA
ON
max. 20 VDC
V
OFF
Pulse: ON status 200 ms
OFF status 800 ms min.-
NPN output Pulse number From 1 to 999 pulses for
kWh, kVAh or kVARh Insulation 2 kV between output and
all inputs and serial output if
available
Serial output (on request)
Type One-way multidrop RS 485
(double direction: only for standard static TRIAC output)
Addresses 256 adresses
key-pad selectable.
Data W, VA, VAR, Wh, VAh, VARh,
V, I, cos ϕ and setpoint status where present
Data format 1 start bit - 7 data bit -
even parity - 1 stop bit. 1 start bit - 7 data bit ­odd parity - 1 stop bit. 1 start bit - 8 data bit ­no parity - 1 stop bit
Baud-rate 1200, 2400, 4800 and 9600
bauds, key-pad selectable
Connections 2 wires (max. length: 1200 m)
+ shield. Bias and/or line termination (selectable by DIP-switch).
Power supply Separate 5 VDC, power
consumption 70 mA (PSU­DIN module).
Insulation By means of optocouplers,
2 kV between serial output and measuring inputs. 2 kV between 5 VDC power supply input and measuring inputs.