1
Product Description Ordering Key
DHA52 is a fully programmable timer to allow
execution of self-designed
timing functions. The function can be prepared using
the free PC software BHF
and connecting the unit to a
PC. The user can decide to
leave to the front knob for
final setting the adjustment
of one of the time steps.
For mounting on DIN-rail.
17.5 mm wide housing suitable both for back and front
panel mounting.
• Fully programmable timing unit
• The function is designed with the BHF PC software
• Waveform design capability:
up to 16 status changes
each status time range 0.1 s to 100 h
programable trigger input event
time steps can be set from the front knob
• Full reprogrammability of the timing functions
• Repeatability: ≤ 0.2%
• Output: 5 A SPDT relay
•
For mounting on DIN-rail in accordance with DIN/EN 50 022
• 17.5 mm DIN-rail housing
• Combined AC and DC power supply
• LED indication for relay status and power supply ON
Output SPDT relay
Rated insulation voltage 250 VAC (rms)
Contact Ratings (AgSnO
2
)µ
Resistive loads AC 1 5 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life ≥ 30 x 106operations
Electrical life ≥ 10
5
operations
(at 5 A, 250 V, cos ϕ = 1)
Operating frequency < 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand
voltage 2.5 kV (1.2/50 µs)
Output Specifications
Type Selection
Housing
Function
Type
Item number
Output
Power supply
Time steps
Mounting Output Housing Supply: 24 VDC and 24 to 240 VAC
DIN-rail SPDT Mini-D DHA 52 C M24 S16
Time Specifications
Time ranges each step
0.1 to 1 s
1 to 100 s
6 to 600 s
60 to 6000 s
0.1 to 10 h
1 to 100 h
Setting accuracy
(fixed steps) ≤ 0.1% +/- 10 ms of the set
value for each step
(knob step) ≤ 5%
Repeatability ≤ 0.2%
Time variation
Within rated power supply ≤ 0.05%/V
Within ambient temperature ≤ 0.2%/°C
Reset
Manual reset of time Close the trigger contact
and/or relay between pins A1 and Y1
Pulse duration ≥ 100 ms
Power supply interruption ≥ 200 ms
Timers
Fully programmable
Type DHA52
DHA 52 C M24 S16
Power supply Overvoltage cat. II
Rated operational voltage (IEC 60664, IEC 60038)
through terminals A1, A2 24 VDC ± 15% and
24 to 240 VAC + 10% -15%,
45 to 65 Hz
Voltage interruption ≤ 10 ms
Rated operational power 1.5 W
Supply Specifications