SensorsUp to four main measured variables (e.g. pH, oxygen content, turbidity
value...) together with their associated auxiliary measured variable
(e.g. temperature) can be displayed and administrated with this
measuring system. According to the number of available main
measured variables, individual sensors (one physical sensor for each
main measured variable) and multiple sensors (one physical sensor for
several main measured variables) from the selection of digital
IQ S
ENSOR NET sensors can be combined and connected.
Each sensor is automatically recognized after being connected and
immediately starts measuring.
Up to four physical sensors can be connected directly to the DIQ/
S 182 XT-4-PR.
Note
Installation examples are given in section 3.13 I
NSTALLATIONEXAMPLES.
ba76027e0102/2012
1 - 1
OverviewSystem 182 XT-4
Relay outputsThe relay outputs can be linked to sensors. Linked outputs can be used
to monitor sensors and for the output of measured values.
A relay output can be programmed as:
a monitoring relay
a limit monitor
a proportional output of measured values (pulse width or frequency
output)
the control unit of a sensor cleaning system driven by compressed
air.
For quick orientation, the states of all relay outputs are clearly indicated
on the display.
PROFIBUS DP outputThe PROFIBUS output enables a connection to a PROFIBUS master
(PROFIBUS-DP) and thus a connection to a superordinate process
control.
Cleaning system driven
by compressed air
The DIQ/S 182 XT-4-PR is prepared for the time-controlled sensor
cleaning function driven by compressed air. The cleaning process is
controlled from the operating unit. The operating unit provides the
supply voltage and control relay for the compressed air valve in the
DIQ/CHV valve module. This enables simple setup and uncomplicated
wiring.
Alternatively, the MIQ/CHV PLUS valve module can be installed in the
system. It combines the relay, valve and valve power supply in one MIQ
enclosure. Thus, no additional wiring is required, which makes
installation easier especially if there is a greater distance between the
DIQ/S 182 XT-4-PR and sensor.
Further system optionsIn case of increased energy demand, an additional power supply unit
can be installed for the power supply if necessary.
1 - 2
ba76027e0102/2012
System 182 XT-4Overview
1.2Behavior of the system to a power failure
The system configuration is non volatile and is permanently
retained. It consists of the following settings:
– Sensor settings
– Settings and links of the relay outputs
– PROFIBUS settings
– System settings (display language, air pressure/altitude,
passwords etc.)
Linked relay outputs switch to the non active condition (open).
A restart is carried out automatically when the power returns. The
system continues to work with the settings at the time of the power
failure (except for the time).
ba76027e0102/2012
1 - 3
OverviewSystem 182 XT-4
1 - 4
ba76027e0102/2012
System 182 XT-4Safety instructions
2Safety instructions
This operating manual contains essential instructions that must be
followed during the commissioning, operation and maintenance of the
System 182 XT-4. Thus, it is essential for the operator to read this
component operating manual before carrying out any work with the
system.
General safety
instructions
Other labels
Safety instructions in this operating manual are indicated by the
warning symbol (triangle) in the left column. The signal word (e.g.
"Caution") indicates the level of danger:
Warning
indicates instructions that must be followed precisely in order to
prevent serious danger to personnel.
Caution
indicates instructions that must be followed precisely in order to
avoid slight injury to personnel or damage to the instrument or the
environment.
Note
indicates notes that draw your attention to special features.
Note
indicates cross-references to other documents, e.g. component
operating manuals.
Target groupThe System 182 XT-4 was developed for online analysis. Some
ba76027e0102/2012
2.1User qualification
maintenance activities, e.g. changing the membrane caps in D.O.
sensors, require the safe handling of chemicals. Thus, we assume that
the maintenance personnel is familiar with the necessary precautions
to take when dealing with chemicals as a result of their professional
training and experience.
2 - 1
Safety instructionsSystem 182 XT-4
Special user
qualifications
The following installation activities may only be performed by a
qualified electrician:
Connection of the DIQ/S 182 XT-4-PR or an additional MIQ power
supply module to the power supply.
Connection of external, line voltage-carrying circuits to relay
contacts.
2.2Authorized use
The authorized use of the System 182 XT-4 consists only of its use in
online analysis.
Please observe the technical specifications according to chapter 10
T
ECHNICALDATA. Only operation and running according to the
instructions in this component operating manual is authorized.
Any other use is considered to be unauthorized. Unauthorized use
invalidates any claims with regard to the guarantee.
2.3General safety instructions
All components of the System 182 XT-4 are constructed and inspected
in accordance with the relevant guidelines and norms for electronic
instruments (see chapter 10 T
They left the factory in a safe and secure technical condition.
ECHNICALDATA).
Function and
operational safety
The fault-free functioning and operational safety of the System 182 XT4 components are only guaranteed if the generally applicable safety
measures and the special safety instructions in this operating manual
are followed during their use.
The fault-free functioning and operational safety of the System 182 XT4 components are only guaranteed under the environmental conditions
specified in chapter 10 T
ECHNICALDATA.
If components of the System 182 XT-4 are transported from a cold
environment into a warm environment, this can cause a malfunction
through the formation of condensation. In this case, wait for the
components to adjust to room temperature before recommissioning.
2 - 2
ba76027e0102/2012
System 182 XT-4Safety instructions
Safe operationIf safe operation is no longer possible, the System 182 XT-4 must be
taken out of operation and secured against inadvertent operation.
Safe operation is no longer possible if components:
have been damaged in transport
have been stored under adverse conditions for a prolonged period
of time
are visibly damaged
no longer operate as described in this manual.
If you are in any doubt, contact the supplier of your System 182 XT-4.
Obligations of the
operator
The operator of the System 182 XT-4 must ensure that the regulations
and guidelines listed below are followed when dealing with dangerous
substances:
EEC guidelines relating to safety at work
National laws relating to safety at work
Accident prevention regulations
Safety datasheets of the chemicals manufacturers.
Warning
A circuit (except for the power supply connections) that is
connected to the System 182 XT-4 must not feed any voltages or
currents that are not allowed. It has to be made sure that the
circuit at any time meets all requirements of a Limited circuit or Limited Power as well as of SELV (Safety Extra Low Voltage).
These include the following limiting value specifications:
AC voltage: max. 30 V effective / 42.4 V peak
DC voltage: max. 60 V
Current limit: max. 8 A
Power output limitation: max. 150 VA
ba76027e0102/2012
2 - 3
Safety instructionsSystem 182 XT-4
2 - 4
ba76027e0102/2012
System 182 XT-4Installation
3Installation
Note
How to connect the DIQ/S 182 XT-4-PR to the PROFIBUS master is
described in detail in the chapter 7 PROFIBUS
3.1Scope of delivery
The following parts are included in the scope of delivery of the DIQ/
S 182 XT-4-PR:
DIQ/S 182 XT-4-PR with attached MIQ/JB branching module
Accessory kit with:
– Contact carrier with screws
– ISO cap nuts with screws and ring washers
– Cable glands with sealing gaskets
CONNECTION.
Operating manual.
3.2Requirements of the measurement location
The measurement location must meet the environmental conditions
specified in section 10.1.
ba76027e0102/2012
3 - 1
InstallationSystem 182 XT-4
- Position power supply modules near
main consumers (e. g. MIQ/VIS)
Power requirement= SP of all consumers
(take into account the relative
switching on time of valves)
- Number and types of required sensors
- Measuring locations to be designed
- Distances
- Infrastructure, process environment etc.
Rough planning
Determination of power requirement
Rating
Fine adjustment
IQtopology + layoutS
ENSORNET
Power requirement of components
Determination of rating
of power supply modules
Fundamentals of planning
Start
End
Arrangement of
power supply modules
- Sum of all line lengths max. 250 m
3.3System planning
Overview of planning
steps
Fig. 3-1System planning
3 - 2
ba76027e0102/2012
System 182 XT-4Installation
3.4Basic requirements for optimum installation
3.4.1General information
The System IQ S
ENSOR NET supplies all components with low voltage
as well as digital communication via a shielded 2-wire line.
Because of this characteristic the energy consumption of all
components must be taken into account (power rating) when planning
an IQ S
ENSOR NET system. The energy consumption determines
whether an additional power module is necessary (section 3.4.2).
3.4.2Drawing up the power rating
Power rating - why?All components in the system require a specific level of electrical power
for operation. Thus, it is necessary to draw up a power rating after
selecting the desired components. At the same time a determination is
made of whether the entire power requirement of all components
(consumers) is covered by the existing power supply in the DIQ/
S 182 XT-4-PR. If this is not the case, the power available in the system
must be increased by an additional MIQ power supply module.
ba76027e0102/2012
3 - 3
InstallationSystem 182 XT-4
Power requirement of
ENSOR NET
IQ S
components
ComponentPower requirement [W]
IQ sensors
®
SensoLyt
TriOxmatic
TriOxmatic
TriOxmatic
FDO
TetraCon
VisoTurb
ViSolid
AmmoLyt
NitraLyt
VARiON
NitraVis
CarboVis
NiCaVis
700 IQ (SW)0.2
®
700 IQ (SW)0.2
®
701 IQ0.2
®
702 IQ0.2
®
700 IQ (SW)0.7
®
700 IQ (SW)0.2
®
700 IQ1.5
®
700 IQ1.5
® Plus
700 IQ0.2
® Plus
700 IQ0.2
® Plus
700 IQ0.2
®
70x IQ (TS)7.0
®
70x IQ (TS)7.0
®
70x IQ7.0
MIQ modules
MIQ/JB0
MIQ/JBR0
MIQ/CR33.0
MIQ/C63.0
MIQ/R61.5
MIQ/IC20.2
+ 2.2 W per connected
WG 20 A2 power supply/isolator
MIQ/CHV PLUS1.0 x rel. turn-on duration *
DIQ/CHV0.8 x rel. turn-on duration *
MIQ/Blue PS0.6
Additional digital interfaces
MIQ/IF232 (+ MIQ/T2020 PC) **0.2
* In order to take the relative on-time into account, see following text
** Only for safeguarding the system configuration by means of ConfigSaveLoad
3 - 4
ba76027e0102/2012
System 182 XT-4Installation
Allowing for the relative
on-time in valves
Determining the number
of MIQ power supply
modules
Valves usually switch on periodically for a limited time and then require
the nominal power. Crucial for the load on the power unit of the DIQ/
S 182 XT-4-PR is the time averaged (effective) power requirement that
depends on the relative on-time, ED:
Relative on-time ED = t
/ (tOn + t
On
Off
)
The effective power requirement is the product of the nominal power of
the valve component and the relative on-time:
P = P
nominal
* ED
Since ED is always < 1, the effective power requirement is always
smaller than the nominal power of the valve component.
Note
For the control of sensor cleaning systems operated by compressed
air, a relative on-time of max. 0.1 has been adopted in practice.
From the value determined for the power requirement, determine the
number of the MIQ power supply modules as follows:
Total power requirement PNumber of additional
MIQ power supply modules
≤ 4.5 W0
P
> 4.5 W1
P
Calculation example:
Example configuration 1Power
requirement [W]
(component)
®
+ 1 VisoTurb
+ 1 ViSolid
+ 1 FDO
+ VARiON
700 IQ1.51.5
®
700 IQ+ 1.53.0
®
700 IQ+ 0.73.7
® Plus
700 IQ+ 0.23.9
requirement P [W] (sum
Total power
of the components)
+ 1 DIQ/CHV (ED = 0.1)(0.8 x 0.1 =) 0.083.98
+ 1 DIQ/CHV (ED = 0.05)(0.8 x 0.05 =) 0.044.02
Result: Total power requirement P < 4.5 W, hence no additional power
supply module is required.
ba76027e0102/2012
3 - 5
InstallationSystem 182 XT-4
Example configuration 2Power
+ 1 FDO
+ NitraVis
+ MIQ/CHV PLUS (ED = 0.1)(1.0 x 0.1 =) 0.18.8
Power supply with the
aid of the
MIQ/Blue PS radio
module
Total power
requirement [W]
(component)
®
700 IQ0.70.7
®
705 IQ8.08.7
requirement P [W] (sum
of the components)
Result: Total power requirement P > 4.5 W, hence an additional power
supply module is required.
The MIQ/Blue PS radio module can also supply power to components
with a total of up to 7 W power consumption on an IQ S
ENSOR NET
island. Details of this are given in the operating manual of the MIQ/
Blue PS.
3.4.3Optimum installation of the additional MIQ power supply
module
Basic ruleIt is preferable to install the MIQ power supply module in the vicinity of
the IQ S
ENSOR NET component with the highest power consumption
(example UV/VIS sensor).
3 - 6
ba76027e0102/2012
System 182 XT-4Installation
3.5Installation guidelines for lightning protection
When using the IQ SENSOR NET instrumentation, particularly in outdoor
areas, adequate protection against (electrical) surges must be
provided. A surge is a summation phenomenon of surge voltage and
surge current. It is generated through the indirect effect of a lightning
event or switching operation in the mains, in the grounding system and
in information technology lines.
To be adequately protected against the damaging effects of surges, an
integrated concept of the following protective measures is required:
internal device-related protective measures and
external protective measures of the installation environment.
The internal device-related protective measures are already integrated
in the YSI online measuring technology as so-called 'lightning
protection' (see chapter 10 T
ECHNICALDATA).
The external protective measures of the installation environment can
be carried out with respect to the following guidelines:
1 All lines of IQ S
ENSOR NET systems must be
a) installed inside (or else close to) the grounded metallic mounting
constructions, e.g. handrails, pipes and posts if possible
b) or, particularly in the case of longer lines, laid in the ground.
Background: The formation of highly lightning hazardous inductive
loops between the cables and ground is avoided through the low
clearance of the grounded metal construction or by installation in the
ground.
2 Only the SNCIQ or SNCIQ-UG cable material must be used. This
cable material, particularly the high line cross section of the cable
shielding (1.5 mm²), is an important prerequisite for the hazard-free
discharging of the surge without inadmissibly high overvoltages
developing along the line at the same time that could have a
damaging effect on the individual IQ S
ENSOR NET components. It is
not recommended to use cables from other manufacturers with
usually appreciably lower shielding conductor cross sections.
3 All metallic mounting constructions, handrails, pipes, posts etc. on
which MIQ modules are installed must be connected to the local
potential equalization system and the grounding system or must be
individually sufficiently grounded locally according to the codes of
practice.
For the individual grounding of the measuring point the mounting
construction must be solidly connected by means of a large-area
auxiliary electrode with the measuring medium.
Metallic control shafts/pipes and other large-area metallic bodies
that reach into the measuring medium are, for example, ideal for use
ba76027e0102/2012
3 - 7
InstallationSystem 182 XT-4
in the grounding of the mounting construction.
This creates a set path for the main surge. As a result it is possible
to avoid the surge being discharged via the IQ S
ENSOR NET cable
and via the valuable sensors in the measuring medium.
4 The contacts of the MIQ modules must always be protected by the
associated contact covers if they are not in use. The contact cover
provides improved insulation against the electric fields of a
thunderstorm event through the extension of the air and creepage
paths.
5 It is recommended to attach a metallic or nonmetallic sun shield to
each outside location of the MIQ modules. Sun shields protect the
electric field lines in the area of the MIQ module through an
advantageous development of the electrical field lines in the area of
the MIQ module and promote the dissipation of the surge via the
mounting construction.
6 The mains voltage for supplying the measuring system must comply
with overvoltage category II. Generally this is ensured through the
public operator of the power supply networks. In company-owned
networks, e.g. in all power supply systems owned by wastewater
treatment plants, this must be kept separate by a potential
equalization and a surge protection system for the plant.
7 One part of the IQ S
ENSOR NET safety and lightning protection
concept is based on high-grade protective insulation of the network
components and of the entire system. It does not have or require
any protective ground (PG) conductor or earth terminal. Avoid any
direct connection of the IQ S
ENSOR NET connections or the metallic
sensor enclosures with the local grounding or potential equalization
system and with metallic construction elements (see point 9).
8 Additional external lightning protection measures directly on the
ENSOR NET system or its components, e.g. the use of
IQ S
overvoltage surge arresters, are not necessary for protection
against the indirect effects of lightning and could possibly result in
malfunctions.
9 For the realization of the internal lightning protection of the system
(e.g. wastewater treatment plant control stands) and for the
protection of IQ S
into buildings or distributions coming from the IQ S
ENSOR NET external resources, cable entry points
ENSOR NET must
be carried out as follows:
– The shield of SNCIQ or SNCIQ-UG cables can be connected to
the local potential equalization with a gas overvoltage surge
arrester. Shielding terminals (e. g. of the PROFIBUS system)
have to be used to contact the shield. The shield of the cable
must not be opened under any circumstances.
3 - 8
– 0/4-20 mA interfaces must be realized with shielded cables. The
cable shield must be connected directly to the potential
ba76027e0102/2012
System 182 XT-4Installation
equalization(s) provided. If plant potential equalization systems
are provided on both sides, the shield must also be connected on
both sides. The inner conductors must have no contact with the
potential equalization.
– The PROFIBUS cables have to be installed according to the rules
of the relevant bus system.
– Relay lines should be connected to the local potential
equalization in order to provide general and consistent protection
via gas overvoltage surge arresters.
ba76027e0102/2012
3 - 9
InstallationSystem 182 XT-4
MIQ Module
MIQ Module
DIQ/S 184 XT-4-PR
MIQ Module
MIQ Module
MIQ Module
DIQ/S 184 XT-4-PR
MIQ Module
3.6Connecting system components
3.6.1Connecting MIQ modules: General information
You can connect the DIQ/S 182 XT-4 with MIQ modules without
connecting cable (stacking). According to the same principle
MIQ modules can also be connected with one another.
Mounting direction
Variant 1 - stack expansion
forwards.
The DIQ/S 182 XT-4-PR or an
MIQ module is attached by its
back to the lid of an MIQ module
(from page 3-12).
Select this variant if an
MIQ module is already
permanently installed, e.g. to a
wall.
Variant 2: - stack expansion
backwards.
An MIQ module is attached with
its lid to the back of the DIQ/
S 182 XT-4-PR or another
MIQ module (page 3-15).
3 - 10
Select this variant if the DIQ/
S 182 XT-4-PR or the front
MIQ module is already
permanently installed, e.g. in a
panel.
ba76027e0102/2012
System 182 XT-4Installation
Caution
For optimum stability only one MIQ module may be attached to
the DIQ/S 182 XT-4-PR.
Note
In all MIQ modules in the System 182 XT-4 the terminator switch on the
terminal strip must be set to "Off".
Materials required 2 x ISO blind nuts (M4)
2 x cheese-head screws (M4x16) with plastic washer
1 x contact base with two plastic tapping screws (scope of delivery
of the MIQ module).
Tools Phillips screwdriver.
Both installation variants of the attachment of an MIQ module on the
DIQ/S 182 XT-4 is described in the following. The assembly of further
MIQ modules is carried out analogously. To dismantle a stack, proceed
in the reverse order to mounting.
ba76027e0102/2012
3 - 11
InstallationSystem 182 XT-4
For stack mounting remove label
and install contact carrier
13
24
MIQ module
DIQ/S 182 XT-4_PR
7
5
6
DIQ/S 182 XT-4-PR
3.6.2Variant 1: Stack expansion forwards
Preparing the stack
mounting
Mounting the contact
Fig. 3-2Preparing components for stack mounting (variant 1)
1Remove the covers from the drilled mounting holes (pos. 1 and
3 in Fig. 3-2).
2Remove the contact cover (pos. 2).
3Pull off the adhesive label (pos. 4).
base
Fig. 3-3Mounting the contact base (variant 1)
3 - 12
ba76027e0102/2012
System 182 XT-4Installation
9
8
DIQ/S 182 XT-4-PR
Note
Only use the plastic tapping screws supplied for attaching the contact
base. They ensure the correct fit.
4Fix the contact base (pos. 5 in Fig. 3-3) onto the DIQ/S 182 XT-
4-PR with the two plastic self-tapping screws (pos. 6).
5Remove the two countersunk screws (pos. 7 in Fig. 3-3) of the
DIQ/S 182 XT-4-PR and swing open the lid.
Premounting the ISO
blind nuts
Fig. 3-4Premounting the ISO blind nuts (variant 1)
6Insert the cheese-head screws (pos. 8 in Fig. 3-4) with the
plastic washers in the drilled mounting holes in the enclosure
and loosely screw in the ISO blind nuts (pos. 9).
ba76027e0102/2012
3 - 13
InstallationSystem 182 XT-4
MIQ module
DIQ/S 182 XT-4-PR
7
MIQ module
DIQ/S 182 XT-4-PR
Stacking the
MIQ modules
Fig. 3-5Stacking the MIQ modules (variant 1)
Fig. 3-6Closing the enclosure (variant 1)
7Attach the prepared DIQ/S 182 XT-4-PR to the cover of the
MIQ module. At the same time, ensure that the two clips on the
DIQ/S 182 XT-4-PR click into place in the lid of the
MIQ module. Subsequently, tighten the two screws (pos. 8 in
Fig. 3-4).
3 - 14
8Close the cover of the DIQ/S 182 XT-4-PR and fix it in place
with the two countersunk bolts (pos. 7 in Fig. 3-6).
ba76027e0102/2012
System 182 XT-4Installation
5
1
2
For stack mounting remove label
and install contact carrier
4
3
MIQ module
DIQ/S 182 XT-4-PR
6
7
DIQ/S 182 XT-4-PR
3.6.3Variant 2: stack expansion backwards
Preparing the stack
mounting
Mounting the contact
base
Fig. 3-7Preparing the MIQ modules for stack mounting (variant 2)
1Remove the covers from the drilled mounting holes (pos. 1 and
3 in Fig. 3-7).
2Remove the contact cover (pos. 2).
3Pull off the adhesive label (pos. 4).
4On the MIQ module, remove the two countersunk screws (pos.
5) and swing open the module lid.
Fig. 3-8Mounting the contact base (variant 2)
ba76027e0102/2012
3 - 15
InstallationSystem 182 XT-4
8
9
MIQ module
Note
Only use the plastic tapping screws supplied for attaching the contact
base. They ensure the correct fit.
5Fix the contact base (pos. 6 in Fig. 3-8) onto the DIQ/S 182 XT-
4-PR with the two plastic self-tapping screws (pos. 7).
Premounting the ISO
blind nuts
Fig. 3-9Premounting the ISO blind nuts (variant 2)
6Insert the cheese-head screws (pos. 8 in Fig. 3-9) with the
plastic washers in the drilled mounting holes in the module lid
and loosely screw in the ISO blind nuts (pos. 9).
3 - 16
ba76027e0102/2012
Loading...
+ 128 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.