The System 182 is a modular, multiparameter measuring system. The
control and operation unit of the system is the DIQ/S 182-MOD
Universal Transmitter with integrated power pack. Is has three relay
outputs and a Modbus output for the connection to existing process
control systems.
SensorsOne or two digital YSI single sensors (one sensor for one main
measured parameter) or a double sensor (one sensor for two main
measured parameters) can be connected to the DIQ/S 182-MOD
Universal Transmitter. I. e. up to two main measured parameters (e.g.
pH, D. O. content, turbidity value...) and additionally up to two
secondary measured parameters (e.g. temperature) can be displayed
and administrated. Each sensor is automatically recognized after being
connected and immediately starts measuring.
The sensors can be directly connected to the DIQ/S 182-MOD
Universal Transmitter.
ba76025e0102/2012
Fig. 1-1Simple systems with one and two sensors
1 - 1
OverviewSystem 182
Relay outputsThe relay outputs can be linked to sensors. Linked outputs can be used
to monitor sensors and for the output of measured values.
A relay output is programmable as:
Alarm contact (event monitoring)
Limit monitor
Proportional output of measured values (pulse width or frequency
output)
Control unit of a compressed air-driven sensor cleaning system.
For quick orientation, the states of all relay outputs are clearly indicated
on the display.
Modbus outputThe Modbus output enables a connection to a Modbus master (Modbus
RTU/RS 485) and thus a connection to a superordinate process
control.
Compressed air-driven
cleaning system
The DIQ/S 182-MOD Universal Transmitter is prepared for the
compressed air-driven, time-controlled sensor cleaning function. For
this, a DIQ/CHV valve module and if necessary a CH cleaning head is
required per sensor (both available as accessories). The cleaning
procedure is controlled by the Universal Transmitter. The Universal
Transmitter provides the supply voltage and control relay for the
compressed air valve in the DIQ/CHV valve module. This enables a
simple setup and uncomplicated wiring.
Alternatively, the MIQ/CHV PLUS valve module can be installed in the
system. It combines the relay, valve and valve power supply in one MIQ
enclosure. Thus, no additional wiring is required, which makes
installation easier especially if the distance between the Universal
Transmitter and sensor is great.
Further system optionsIf necessary, an additional power pack can be added to supply sensors
with high power consumption (e.g. UV/VIS sensor).
1 - 2
ba76025e0102/2012
System 182Overview
1.2Behavior of the system in the case of power failure
The system configuration remains stored permanently. It consists of
the following settings:
– Sensor settings
– Settings and links of relay outputs
– Modbus settings
– System settings (display language, air pressure/location altitude,
passwords, etc.)
Linked relay outputs switch to the non-active condition (open).
When the power is restored the system is automatically restarted.
The system continues to work with the settings at the time of the
power failure (except for the time).
ba76025e0102/2012
1 - 3
OverviewSystem 182
1 - 4
ba76025e0102/2012
System 182Safety instructions
2Safety instructions
This operating manual contains essential instructions that must be
followed during the commissioning, operation and maintenance of the
System 182. Thus, it is essential for the operator to read this
component operating manual before carrying out any work with the
system.
General safety
instructions
Other labels
Safety instructions in this operating manual are indicated by the
warning symbol (triangle) in the left column. The signal word (e.g.
"Caution") indicates the danger level:
Warning
indicates instructions that must be followed precisely in order to
prevent serious dangers to personnel.
Caution
indicates instructions that must be followed precisely in order to
avoid slight injuries to personnel or damage to the instrument or
the environment.
Note
indicates notes that draw your attention to special features.
Note
indicates cross-references to other documents, e.g. component
operating manuals.
Target groupThe System 182 was developed for online analysis. Some
ba76025e0102/2012
2.1User qualification
maintenance activities, e.g. changing the membrane caps in D.O.
sensors, require the safe handling of chemicals. Thus, we assume that
the maintenance personnel is familiar with the necessary precautions
to take when dealing with chemicals as a result of their professional
training and experience.
2 - 1
Safety instructionsSystem 182
Special user
qualifications
The following installation activities may only be performed by a
qualified electrician:
Connecting the DIQ/S 182-MOD Universal Transmitter or an
additional MIQ power supply module to the power supply.
Connecting external, line voltage-carrying circuits to relay contacts.
2.2Authorized use
The authorized use of the System 182 consists only of its use in online
analysis. Please observe the technical specifications according to
chapter 10 T
ECHNICALDATA. Only operation and running according to
the instructions in this component operating manual is authorized.
Any other use is considered to be unauthorized. Unauthorized use
invalidates any claims with regard to the guarantee.
2.3General safety instructions
All components of the System 182 are constructed and inspected in
accordance with the relevant guidelines and norms for electronic
instruments (see chapter 10 T
safe and secure technical condition.
ECHNICALDATA). They left the factory in a
Function and
operational safety
The failure-free function and operational safety of the System 182
components are only guaranteed if the generally applicable safety
measures and the special safety instructions in this operating manual
are followed during their use.
The failure-free function and operational safety of the System 182
components are only guaranteed under the environmental conditions
that are specified in chapter 10 T
ECHNICALDATA.
If System 182 components are transported from a cold environment
into a warm environment, this can cause a malfunction through the
formation of condensation. In this case, wait for the components to
adjust to room temperature before recommissioning.
2 - 2
ba76025e0102/2012
System 182Safety instructions
Safe operationIf safe operation is no longer possible, the System 182 must be taken
out of operation and secured against inadvertent operation.
Safe operation is no longer possible if components:
have been damaged in transport
have been stored under adverse conditions for a lengthy period of
time
are visibly damaged
no longer operate as described in this manual.
If you are in any doubt, contact the supplier of your System 182.
Obligations of the
operator
The operator of the System 182 must ensure that the regulations and
guidelines listed below are followed when dealing with dangerous
substances:
EEC guidelines relating to safety at work
National laws relating to safety at work
Accident prevention regulations
Safety datasheets of the chemicals manufacturers.
Warning
A circuit (except for power supply connections and relay circuits),
that is connected to the System 182, must not feed any voltages
or currents that are not allowed. It has to be made sure that the
circuit at any time meets all requirements of a Limited circuit or Limited Power as well as of SELV (Safety Extra Low Voltage).
These include the following limiting value specifications:
AC voltage: max. 30 V effective / 42.4 V peak
DC voltage: max. 60 V
Current limit: max. 8 A
Power output limitation: max. 150 VA
ba76025e0102/2012
2 - 3
Safety instructionsSystem 182
2 - 4
ba76025e0102/2012
System 182Installation
3Installation
Note
How to connect the DIQ/S 182-MOD to the Modbus master is
described in detail in the chapter 7 M
3.1Scope of delivery
The following parts are included in the scope of delivery of the DIQ/
S 182-MOD:
DIQ/S 182-MOD Universal Transmitter
Accessory kit with:
– Contact carrier with screws
– ISO cap nuts with screws and ring washers
– Cable glands with sealing gaskets
ODBUSCONNECTION.
Operating manual.
3.2Requirements of the measurement location
The measurement location must meet the environmental conditions
specified in section 10.1 DIQ/S 182-MOD.
3.3Installation guidelines for lightning protection
When using the IQ SENSOR NET instrumentation, particularly in outdoor
areas, adequate protection against (electrical) surges must be
provided. A surge is a summation phenomenon of surge voltage and
surge current. It is generated through the indirect effect of a lightning
event or switching operation in the mains, in the grounding system and
in information technology lines.
To be adequately protected against the damaging effects of surges, an
integrated concept of the following protective measures is required:
internal device-related protective measures and
ba76025e0102/2012
external protective measures of the installation environment.
The internal device-related protective measures are already integrated
in the YSI online measuring technology as so-called 'lightning
protection' (see chapter 10 T
ECHNICALDATA).
3 - 1
InstallationSystem 182
The external protective measures of the installation environment can
be carried out with respect to the following guidelines:
1 All lines of the IQ S
ENSOR NET system must be
a) installed inside (or else close to) the grounded metallic mounting
constructions, e.g. handrails, pipes and posts if possible
b) or, particularly in the case of longer lines, laid in the ground.
Background: The formation of highly lightning hazardous inductive
loops between the cables and ground is avoided through the low
clearance of the grounded metal construction or by installation in the
ground.
2 Only the SNCIQ or SNCIQ-UG cable material must be used. This
cable material, particularly the high line cross section of the cable
shielding (1.5 mm²), is an important prerequisite for the hazard-free
discharging of the surge without inadmissibly high overvoltages
developing along the line at the same time that could have a
damaging effect on the individual IQ S
ENSOR NET components. It is
not recommended to use cables from other manufacturers with
usually appreciably lower shielding conductor cross sections.
3 All metallic mounting constructions, handrails, pipes, posts etc. on
which MIQ modules are installed must be connected to the local
potential equalization system and the grounding system or must be
individually sufficiently grounded locally according to the codes of
practice.
For the individual grounding of the measuring point the mounting
construction must be solidly connected by means of a large-area
auxiliary electrode with the measuring medium.
Metallic control shafts/pipes and other large-area metallic bodies
that reach into the measuring medium are, for example, ideal for use
in the grounding of the mounting construction.
This creates a set path for the main surge. As a result it is possible
to avoid the surge being discharged via the IQ S
ENSOR NET cable
and via the valuable sensors in the measuring medium.
3 - 2
4 The contacts of the MIQ modules must always be protected by the
associated contact covers if they are not in use. The contact cover
provides improved insulation against the electric fields of a
thunderstorm event through the extension of the air and creepage
paths.
5 It is recommended to attach a metallic or nonmetallic sun shield to
each outside location of the MIQ modules. Sun shields protect the
electric field lines in the area of the MIQ module through an
advantageous development of the electrical field lines in the area of
the MIQ module and promote the dissipation of the surge via the
mounting construction.
6 The mains voltage for supplying the measuring system must comply
ba76025e0102/2012
System 182Installation
with overvoltage category II. Generally this is ensured through the
public operator of the power supply networks. In company-owned
networks, e.g. in all power supply systems owned by wastewater
treatment plants, this must be kept separate by a potential
equalization and a surge protection system for the plant.
7 One part of the IQ S
ENSOR NET safety and lightning protection
concept is based on high-grade protective insulation of the network
components and of the entire system. It does not have or require
any protective ground (PG) conductor or earth terminal. Avoid any
direct connection of the IQ S
ENSOR NET connections or the metallic
sensor enclosures with the local grounding or potential equalization
system and with metallic construction elements (see point 9).
8 Additional external lightning protection measures directly on the
IQ S
ENSOR NET system or its components, e.g. the use of
overvoltage surge arresters, are not necessary for protection
against the indirect effects of lightning and could possibly result in
malfunctions.
9 For the realization of the internal lightning protection of the system
(e.g. wastewater treatment plant control stands) and for the
protection of IQ S
into buildings or distributions coming from the IQ S
ENSOR NET external resources, cable entry points
ENSOR NET must
be carried out as follows:
– The shield of SNCIQ or SNCIQ-UG cables can be connected to
the local potential equalization with a gas overvoltage surge
arrester. Shielding terminals (e. g. of the Modbus system) have
to be used to contact the shield. The shield of the cable must not
be opened under any circumstances.
– 0/4-20 mA interfaces must be realized with shielded cables. The
cable shield must be connected directly to the potential
equalization(s) provided. If plant potential equalization systems
are provided on both sides, the shield must also be connected on
both sides. The inner conductors must have no contact with the
potential equalization.
– The Modbus cables have to be installed according to the rules of
the relevant bus system.
– Relay lines should be connected to the local potential
equalization in order to provide general and consistent protection
via gas overvoltage surge arresters.
ba76025e0102/2012
3 - 3
InstallationSystem 182
MIQ Module
MIQ Module
DIQ/S 182-MOD
MIQ Module
MIQ Module
MIQ Module
DIQ/S 182-MOD
MIQ Module
3.4Connecting system components
3.4.1Connecting MIQ modules: General information
You can connect the Universal Transmitter to MIQ modules without
connection cable (stack mounting).
Mounting direction
Variant 1 - stack expansion
forwards.
The back of the Universal
Transmitter or an MIQ module is
attached to the lid of an
MIQ module
(page 3-6).
Select this variant if an
MIQ module is already
permanently installed, e.g. to a
wall.
Variant 2: - stack expansion
backwards.
The lid of an MIQ module is
attached to the back of the
Universal Transmitter or another
MIQ module (page 3-9).
3 - 4
Select this variant if the
Universal Transmitter or other
MIQ module is already
permanently installed, e.g. in a
panel.
ba76025e0102/2012
System 182Installation
Caution
For optimum stability, a maximum of two MIQ modules may be
connected to the Universal Transmitter. One MIQ power supply
module only may be mounted per stack in addition to the
Universal Transmitter.
Note
In the case of panel mounting, the front module must be installed
individually in the switch cabinet aperture first. Only then can any
MIQ modules be added (variant 2).
Note
The terminator switch on the terminal strip of all MIQ modules in the
System 182 must be set to "Off".
Materials required 2 x ISO blind nuts (M4)
2 x cheese-head screws (M4x16) with plastic washer
1 x contact base with two plastic tapping screws (scope of delivery
of the MIQ module).
Tools Phillips screwdriver.
Below, both installation variants of attaching an MIQ module to the
Universal Transmitter are described. The assembly of further MIQ
modules is carried out analogously. To dismantle a stack, proceed in
the reverse order to mounting.
ba76025e0102/2012
3 - 5
InstallationSystem 182
13
24
For stack mounting remove label
and install contact carrier
MIQ module
DIQ/S 182-MOD
7
5
6
DIQ/S 182-MOD
3.4.2Variant 1: Stack expansion forwards
Preparing the stack
mounting
Mounting the contact
Fig. 3-1Preparing MIQ modules for stack mounting (variant 1)
1Remove the covers from the drilled mounting holes (pos. 1 and
3 in Fig. 3-1).
2Remove the contact cover (pos. 2).
3Pull off the adhesive label (pos. 4).
base
Fig. 3-2Mounting the contact base (variant 1)
Note
Only use the plastic tapping screws supplied for attaching the contact
base. They ensure the correct fit.
3 - 6
ba76025e0102/2012
System 182Installation
9
8
DIQ/S 182-MOD
4Attach the contact base (pos. 5 in Fig. 3-2) on the Universal
Transmitter with the two plastic tapping screws (pos. 6).
5On the Universal Transmitter, remove the two countersunk
screws (pos. 7 in Fig. 3-2) and swing open the lid.
Premounting the ISO
blind nuts
Fig. 3-3Premounting the ISO blind nuts (variant 1)
6Insert the cheese-head screws (pos. 8 in Fig. 3-3) with the
plastic washers in the drilled mounting holes in the enclosure
and loosely screw in the ISO blind nuts (pos. 9).
ba76025e0102/2012
3 - 7
InstallationSystem 182
MIQ module
DIQ/S 182-MOD
7
MIQ module
DIQ/S 182-MOD
Stacking the
MIQ modules
Fig. 3-4Stacking the MIQ modules (variant 1)
Fig. 3-5Closing the enclosure (variant 1)
7Attach the prepared Universal Transmitter to the lid of the
MIQ module. At the same time, ensure that the two clips on the
Universal Transmitter click into place in the lid of the
MIQ module. Subsequently, tighten the two screws (pos. 8 in
Fig. 3-3).
3 - 8
8Close the lid of the Universal Transmitter and fix it with the two
countersunk screws (pos. 7 in Fig. 3-5).
ba76025e0102/2012
System 182Installation
5
13
24
For stack mounting remove label
and install contact carrier
3
4
MIQ module
DIQ/S 182-MOD
6
7
DIQ/S 182-MOD
3.4.3Variant 2: stack expansion backwards
Preparing the stack
mounting
Fig. 3-6Preparing the MIQ modules for stack mounting (variant 2)
1Remove the covers from the drilled mounting holes (pos. 1 and
3 in Fig. 3-6).
2Remove the contact cover (pos. 2).
3Pull off the adhesive label (pos. 4).
4On the MIQ module, remove the two countersunk screws (pos.
5) and swing open the module lid.
Mounting the contact
base
Fig. 3-7Mounting the contact base (variant 2)
ba76025e0102/2012
3 - 9
InstallationSystem 182
8
9
MIQ module
Note
Only use the plastic tapping screws supplied for attaching the contact
base. They ensure the correct fit.
5Attach the contact base (pos. 6 in Fig. 3-7) on the Universal
Transmitter with the two plastic tapping screws (pos. 7).
Premounting the ISO
blind nuts
Fig. 3-8Premounting the ISO blind nuts (variant 2)
6Insert the cheese-head screws (pos. 8 in Fig. 3-8) with the
plastic washers in the drilled mounting holes in the module lid
and loosely screw in the ISO blind nuts (pos. 9).
3 - 10
ba76025e0102/2012
System 182Installation
MIQ module
DIQ/S 182-MOD
5
MIQ module
DIQ/S 182-MOD
Stacking the
MIQ modules
Fig. 3-9Stacking the MIQ modules (variant 2)
Fig. 3-10 Closing the enclosure (variant 2)
ba76025e0102/2012
7Attach the prepared MIQ module to the back of the Universal
Transmitter. At the same time, ensure that the two clips on the
Universal Transmitter click into place in the lid of the
MIQ module. Subsequently, tighten the two screws (pos. 8 in
Fig. 3-8).
8Close the MIQ module and fix it with the two countersunk
screws (pos. 5 in Fig. 3-10).
3 - 11
InstallationSystem 182
3.4.4Distributed mounting
General informationFor the locally separated connection between Universal Transmitter
and MIQ modules and between MIQ modules the following cables can
be used:
SNCIQ cable
SNCIQ/UG earth cable - suitable for underground laying in
accordance with VDE 01816, Part 2 and DIN/VDE 0891, Part 6.
The cables are delivered as piece goods (please specify length when
ordering!).
Note
For distances under 2 m, e.g. to connect the Universal Transmitter and
DIQ/JB when installing two sensors in the immediate vicinity of the
Universal Transmitter, any two-wire screened cable can also be used
(wire cross-section > 0.5 mm²)
Caution
The IQ Sensor Net cable may be connected to the SENSORNET
connections only. No wires of the cable may be connected with an
external electrical potential. Otherwise, malfunctions could occur.
General installation
instructions
Materials required 1 x SNCIQ or SNCIQ/UG connection cable (see
Pay attention to the following points when connecting components via
IQ S
ENSOR NET lines:
The sum of all IQ S
ENSOR NET line lengths (SNCIQ, SNCIQ/UG and
SACIQ) in the system may be up to a maximum of 250.
IQ S
ENSOR NET lines must always be installed separately at a
minimum distance of 20 cm from any other lines carrying a voltage
greater than 60 V.
The terminator switch on the terminal strip of all MIQ modules in the
System 182 must be set to "Off".
chapter 12 A
CCESSORIESANDOPTIONS)
Wire end sleeves for 0.75 mm2 wire cross-section with matching
crimping tool
1 x cable gland with seal (scope of delivery of MIQ module).
3 - 12
Tools Cable stripping knife
Wire stripper
Phillips screwdriver
Small screwdriver.
ba76025e0102/2012
System 182Installation
SNCIQ
SNCIQ/UG
approx. 35 mmapprox. 45 mm
approx. 45 mm
Preparing the cable
ends
1Cut off the cable to the required length.
2Remove approx. 45 mm of cable insulation (in the case of the
SNCIQ/UG earth cable, remove both the inner and
outer
insulation).
3Only for the SNCIQ/UG earth cable:
strip the outer insulation for a further 35 mm.
4Shorten the exposed shielding braid up to the cable sheath.
5Shorten the two fillers (plastic inlays) up to the cable sheath.
6Bare the red and green wires and fit them with wire end
sleeves.
7Fit the filler stranded wire with a wire end sleeve.
Connecting the cablesThe SNCIQ and SNCIQ/UG cables are connected to the terminal strip
ba76025e0102/2012
Fig. 3-11 Prepared cable end
in the same way as the SACIQ sensor connection cable (see
section 3.4.5):
1Open the enclosure of the Universal Transmitter or
MIQ module.
2Select a free SENSORNET connection. At the same time, look
out for the SENSORNET designation on the label on the
bottom of the enclosure.
3 - 13
InstallationSystem 182
SACIQSNCIQ
SNCIQ/UG
1
3
2
SENSORNET 2
SENSORNET 1
Fig. 3-12 Connecting cables (example of Universal Transmitter)
3Screw a cable gland (pos. 1 in Fig. 3-12) with the sealing ring
(pos. 2) into the enclosure.
4Loosen the coupling ring (pos. 3 in Fig. 3-12).
5Feed the cable through the cable gland into the enclosure.
3 - 14
ba76025e0102/2012
System 182Installation
SNCIQ(/UG)
or SACIQ
redgreen
X3X2X1
SENSORNET 1
RED
SHIELD
GREEN
Terminal
designation:
Filler stranded wire (SNCIQ...)
or black (SACIQ)
Fig. 3-13 Example: SENSORNET connection
6Connect the cable ends to the terminal strip. At the same time,
look out for the designations of the terminals (red / shield /
green).
7Tighten the coupling ring (pos. 3 in Fig. 3-12).
8Close the enclosure.
Note
The complete assignment of the terminal strip is shown in section 3.12.
ba76025e0102/2012
3 - 15
InstallationSystem 182
3.4.5Connecting IQ sensors
Sensors can be connected to all free SENSORNET connectors in the
182 system. The Universal Transmitter
DIQ/S 182-MOD has two SENSORNET connections.
General installation
instructions
Observe the following points when attaching sensors to the system:
The sum of all IQ S
ENSOR NET line lengths (SNCIQ, SNCIQ/UG and
SACIQ) in the system may be up to a maximum of 250.
IQ S
ENSOR NET lines must always be installed separately at a
minimum distance of 20 cm from other lines that carry a voltage
greater than 60 V.
Materials required 1 x SACIQ connection cable (see chapter 12 A
OPTIONS)
1 x cable gland with seal
The free end of the connection cable already has the sheath removed
in the factory and all the wires are fitted with wire end sleeves.
Tools Phillips screwdriver
Small screwdriver.
Connecting the SACIQ
cable to the Universal
The connection of the SACIQ cable to the terminal strip is described in
section 3.4.4 (see C
ONNECTINGTHECABLES, Seite 13).
Transmitter or
MIQ module
CCESSORIESAND
Connecting the sensor
to the connection cable
Caution
The SACIQ sensor connection cable may only be connected to the
SENSORNET connections. No wires of the cable may be
connected with an external electrical potential. Otherwise,
malfunctions could occur.
1Remove the protective caps from the plug connections of the
IQ sensor and SACIQ sensor connection cable and keep them
safe.
2Plug the socket of the SACIQ sensor connection cable onto the
plug head connector of the IQ sensor. At the same time, rotate
the socket so that the pin in the plug head connector (1) clicks
into one of the two holes in the socket.
3Then, screw the coupling ring (2) of the IQ sensor connection
cable on the IQ sensor up to the stop.
3 - 16
ba76025e0102/2012
Loading...
+ 124 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.